MSC ENGINEERING PACKAGE
EP No: ECR-19-000982 Rev 00
EP Title: 609J Breathing Air Facility Mechanical HVAC Upgrade
Document Action Only Physical Modification
1.0 PACKAGE DESCRIPTION RELEASE Radiological Record
Request and Justification:
Upgrade HVAC system in 609J Air Compressor Room to accommodate additional heat load.
Two existing air compressors (40 HP and 75 HP) will be removed from 609J Air Compressor Room and replaced with two new 75 HP water cooled air compressor. Because one of the air compressors is larger than the original design, there will be additional heat generated. The existing HVAC system is not capable to meet the new cooling demand requirements for the compressor room, therefore the upgrade of the HVAC system is required.
CACN: 408625
Work Package No/Project No:
Z-283
Area:200E
Facility:Fire station 92
Building:609J
System ID:N/A
Release
Work Complete Field Work Complete
Design Authority
Change Description and Scope:
This FMP upgrades the HVAC system for 609J Air Compressor Room.
Mechanical work:
Remove the existing HVAC unit, concrete pad, all exterior and interior ductwork, and thermostat as shown in INFO-01.
Pour a new concrete pad in the approximate location shown in DWG-04 - DWG-05. Field verify the exact location of the concrete pad and HVAC unit. Concrete pad shall be in accordance with sections "25 ton HVAC Unit Concrete Pad", and "Section D" found in DWG-04. Install new Trane 25-ton HVAC unit (model # TSH300G4R0AA3L) onto the new concrete pad and label as "AC-1". Install a new thermostat for the new HVAC unit in the approximate location the previous thermostat was located.
Install new rectangular exterior and interior ductwork as shown in DWG-02 through DWG-04. New rectangular ductwork must be 22 gauge Aluminum with 2-inch internal duct liner in accordance with ASTM C1071 and NFPA 90B. Maximum spacing of ductwork support is 5 ft. for horizontal and 10 ft. for vertical ductwork. Install new supply air grilles as shown in DWG-02 and DWG-03. Supply and return air grilles are to be Titus or engineering approved equivalent.
Exterior supply ductwork shall enter the building through the existing wall penetration. Existing wall penetration must be modified to compensate the size of the new ductwork.
Electrical Work
In panel "MP-609J" remove the existing 50A circuit breaker located in circuits 2, 4, 6, and replace with a new 70 Amp breaker. Remove the existing 60 Amps disconnect servicing the existing 17.5 ton HVAC unit and all the associated conduit and conductors up to the pull box. Pull box shall be reused in the new installation.
Note: wire to the 3-ton heat pump is also in the same conduit as the 17.5 ton. In new installation, reuse this wiring as no changes are made in the 3 ton unit.
Install a Square D safety disconnect model number HU363RB or engineering approved equivalent 100A non-fusible disconnect
ECR-19-000982 00 1 of 15
N/A
y/d n/k per telecon 8/21/19
DATE:
Aug 21, 2019
0 49
0
44E❑ ❑
on the outside wall of building 609J near the new HVAC Unit "AC-1" (Approximate location of disconnect shown in DWG-06). Label the new disconnect as "DS-AC-1 fed from Panelboard MP-609J circuit 2, 4, 6".
Field route one new 1 1/2" minimum conduit and run 3#4 THHN copper conductors and 1#8 copper ground from "MP-609J" circuit 2, 4, 6, to safety disconnect "DS-AC-1". Field position safety disconnect as needed. Field route one new 1 1/2" minimum flex conduit running 3#4 THHN copper conductors and 1#8 copper ground from "DS-AC-1" to the new HVAC unit "AC-1" mounted on the concrete pad. See DWG-06 and DWG-07 for more detail on the conduit/conductors.
Install permanent labeling to all new equipment and its associates components.
2.0 PACKAGE INDEX
Action Document No. Rev. No. E/S/R Section Description Page No. Release to Work?
I INFO-01 - - INFO-01 - HVAC Demo Plan Yes
RWC H-6-15620 01 1 S DWG-01 - DWG-03 - 609J Mechanical HVAC Plan Yes
NWC H-6-15620 02 0 - DWG-04 - 609J Mechanical HVAC Equipment Details Yes
NWC H-6-15620 03 0 - DWG-05 - 609J Construction and Concrete Notes Yes
RWC H-6-15622 01 2 S DWG-06 - Electrical Details Yes
RWC H-6-15623 01 1 R DWG-07 - Conduit and Feeder Schedule Yes
RWC H-6-18185 01 1 E DWG-08 - DWG-09 - Electrical Panel Schedule Yes
RWC h-6-15095 01 4 E DWG-10 - Electrical One-Line Diagram Yes
3.0 DESIGN REQUIREMENTS
Electrical modifications shall be in compliance with NFPA 70, National Electrical Code, 2017 Edition. All electrical components shall be approved by a National Recognized Testing Laboratory (NRTL).
New HVAC unit installation shall be in compliance with manufacturers' recommendations, authority having jurisdiction, and current codes and standards including:
-SMACNA Standard for ductwork installation, 2016 Edition-International Mechanical Code, 2015 Edition-ASHRAE 62.2, 2016 Edition-NFPA 90A, 2015 Edition
Air balancing per current SMACNA HVAC system, testing, adjusting and balancing.
MSC-PRO-ENG-709, Rev. 2 - CAD and Drawing Development and control process for Engineering.
4.0 ACCEPTANCE CRITERIA and METHODS
Acceptance Criteria Acceptance Method
Acceptable NEC inspection is required before energizing any new or modified circuits. Inspection Testing
Test wiring for continuity and unintentional grounds prior to energization. Inspection Testing
Verify that all new equipment is labeled to identify panel and circuit. Inspection Testing
Verify that the panel schedules have been physically updated at the panel location. Inspection Testing
Perform thermostat functional check to verify heating and cooling modes. Inspection Testing
Air balance to be within +/- 10% of design per SMACNA standards. Inspection Testing
5.0 OTHER AFFECTED DOCUMENTS
ECR-19-000982 00 2 of 15
5
6,7,89
1011
1213,14
15
❑ ❑
❑ ❑
❑ ❑
❑ ❑
❑ ❑
❑ ❑
Verification by: Peer Review Formal Design Review Alternate Calculations Qualification Testing
Document Type Document No. Rev. No. Owning Organization Technical Authority
Procedure RES0001 2 MSA K Tran
6.0 DESIGN VERIFICATION
Design Verification Checklist:
a. Are the Functional Requirements and Design Criteria appropriately selected for the modification? Yes No NA
b. Does the design meet the specified Functional Requirements and Design Criteria? Yes No NA
c. Were the design inputs correctly incorporated into the design? Yes No NA
d. Is the design output reasonable compared to the design inputs? Yes No NA
e. Have suitable materials, parts, and processes been specified? Yes No NA
f. Have suitable acceptance, inspection, and operability been adequately addressed in the change? Yes No NA
g. Have constructability, maintenance, and operability been adequately addressed in the design? Yes No NA
h. Are all affected design documents identified and appropriately changed? Yes No NA
Additional Design Verification Documents Prepared? Yes No
NOTE: Identify additional Design Verification Documentation in Section 2.0 Package Index.
A review of the design has been performed. The selected Functional Requirements and Design Criteria meet the stated Engineering Request. Design Verification performed by the method(s) identified has confirmed that the design documented by this FMP is adequate and meets the stated Functional Requirements and Design Criteria.
H2945424 - SEAN LEISTRITZ 8/19/2019 7:52:40 AM
Design Verifier: Print Name Signature Date
7.0 REVIEWS
USQ: USQ GCX
No: Not Required
H8439758 - KHOI N TRAN 8/19/2019 8:03:28 AM
Reviewer Print Name Signature Date
Environmental: Screened Ref: Not Required
ECO Print Name Signature Date
8.0 APPROVALS and DISTRIBUTION
Approvals
H5046101 - YURIY V DUBINETS 8/19/2019 8:42:38 AM
ECR Author: Print Name Signature Date
H8439758 - KHOI N TRAN 8/19/2019 8:14:28 AM
Design Authority: Print Name Signature Date
H7518890 - DREW A THOMAS 8/20/2019 10:09:48 AM
Engineering Manager: Print Name Signature Date
ECR-19-000982 00 3 of 15
00000000
000000000
®®
®0
®®
®®0
H3510488 - DANIEL (DAN) C PARR 8/20/2019 12:30:07 PM
Title:Project Manager Print Name Signature Date
H0098833 - KEVIN F HANLON 8/20/2019 12:54:32 PM
Title:Engineer Print Name Signature Date
H3842891 - GERARDO CRUZ 8/19/2019 9:56:21 AM
Title:Drafting Print Name Signature Date
H0321425 - MARK BERKENBILE 8/19/2019 2:02:56 PM
Title:Construction Manager Print Name Signature Date
H7343523 - SEAN M SUNDAY 8/19/2019 2:16:15 PM
Title:QA Review Print Name Signature Date
Distribution
HID Name
H2945424 SM Leistritz
H0098833 KF Hanlon
H7518890 DA Thomas
H3510488 DC Parr
H5439758 KN Tran
H3842891 G Cruz
H0321425 MP Berkenbile
H7343523 SM Sunday
ECR-19-000982 00 4 of 15
ECR-19-000982 00 5 of 15
Facility IV odification Package Continuation PageReference Drawing
N/A
Sheet Number
N/A
Revision Number
N/A
Section Title
INFO-01
LD \G 60.9 VAC Dh
0
VO PLA\
I II II III11.EF_i
./1.4.1rW
REMOVE EXISTINGTHERMOSTAT OF AC-1 UNIT.
L___
-
rir1
tr,
11,I,MI
z0
0w
0000000000000000
AIRCOMPRESSOR
C2
24x14E 1000(TYP 7PL)
AIL
CONDENSATE TANKS
AIRCOMPRESSOR
Cl
AEL
COMPRESSORROOM
1011111
00000000
8888
-I •I-••
—36x20 UPBOD = FF+9'-0-7/8"
36x36 At0
II
111
IIII
OEF-1
CONTROLLER
O
36x36BOD = FF-F1'-0"
48x48EI(lYP 2PL)
DEMOLISH AND REMOVEEXISTING AC-1 UNIT,CONCRETE PAD, ANDASSOCIATED EXTERIOR ANDINTERIOR DUCTWORK. FORNEW AC-1 UNIT PLANSEE DWG-02 OF THIS ECR.
ECR-19-000982 00 6 of 15
Facility IV odification Package Continuation PageReference Drawing
H-6-15620
Sheet Number
01
Revision Number
01
Section Title
DWG-01
WAS.. I I I I I I I I II I L_ _ _J__ _ _J__ _ _J__ _ _J__ _ _J__ _ __I1 II I
36x20 UPBOD FF+9'-0-7/8"©
HE ' t E I E I C I C I C 1 E 1=1.- -E.: ± '-..E=E". t•-• j'' '-t -1- r'-' ̀"-EI = E2' -'[= E. =-1 -I=
I
I III
0 AC-1 d
I I
II CONDENSATE TANKS- IIII `L i- It " "HO II A%V P
AMEF-1
7 7 'L II
I, /I \X/
,, , ...._
A---A36x20 — — — FLAG NOTESmw 20x16 11 , \ ,6,,,c1, \
t t i io I
-4 9- 17.5 TONS 111110" PROVIDE TURNING VANES AT ALL SQUARE 90''S.0000 AIR -II 10-HU AIR
o _— °°°° COMPRESSOR COMPRESSOR 0000 -II p- 1110- INSULATE OUTSIDE DUCTS WITH 2" FIBERGLASS
11=-1 —
C2 Cl 0000°°°°-II ID- INSULATION COVER WITH MASTIC BOARD.
24x14 A 1000 CAEL AIL 36x36 1 PIO- SHOP PRIME FRAMES WITH INORGANIC ZINC PRIMER.
(TYP 7PL)(f)
--I
w W -11. - A,- --
L-LJ
Z COMPRESSOR -4.0- li'''a_ ROOM It
Itla -I= - 1 36x36
0 101 W-...-
BOD = FF+1'-0"
Lu I 1 I I I
I
I 48x48 B(-Pa' 2PL)0 0 0
EF-1CONTROLLER
REGISTER, GRILLE, DIFFUSER SCHEDULE
SYMBOL TYPE SERVICE STYLE INSTALLATION MATERIAL COLOR DAMPER MAX NC MFR/MODEL ACCESSORIES/REMARKS
A GRILLE SUPPLY SINGLE DEFLECTION DUCT ALUMINUM WHITE YES 29 TITUS / 301 FL SINGLE DEFLECTION, 3/4" SPACING, BLADES PARALLEL TO LONG DIMENSION WITHOPTIONAL DAMPER, MOUNT DIRECTLY TO EXPOSED DUCT
B LOUVER INTAKE COMBINATION INTEGRAL FLANGE ALUMINUM RUSKIN/ELC6375D CLEAR ANODIZE FINISH. RUSKIN MODEL NO. GCA226, 120V, 2—POSITION ACTUATOR.
C GRILLE RETURN ZERO DEFLECTION SURFACE MOUNT ALUMINUM WHITE NO 35 TITUS / 350ZFL ZERO DEFLECTION, 3/4" SPACING, BLADES PARALLEL TO LONG DIMENSION
ECR-19-000982 00 7 of 15
Facility IV odification Package Continuation PageReference Drawing
H-6-15620
Sheet Number
01
Revision Number
01
Section Title
DWG-02
SeI I I I I I I I I-I I L__ __L___ __L_ _ __L_ _ _J__ _ _J__ _ _JI I
FOR HVAC GENERAL NOTES, SEE DWG-03
0 0 0 ANCHORS7'—O"ID....4 L I --ct
I I
ELELELLELED_-_----- F_-E=„E.,i_iAC-1 COMPRESSOR
P. 6 PLACESSEE it
II -00 II 7 n . H-6-15620-2II I
II NOTE TO DRAFTER:II --oil- , 101 -11 11- " 401 0
- DO NOTAM
110 EF-1z 44x20 -I
11—
D- II%17 %r 25 TON HVAC
CONCRETE PAD INCORPORATEI - II FLAG NOTES
77 7 -11 11- SEE AM
W 24x20 e u_i_ _____ AC
,..,,,,,,,„------
0 H-6-15620-2
IEt t iii - 1 110110" PROVIDE TURNING VANES AT ALL SQUARE 90°'S.
i- --.AL AIL
0t W
P" 2" INTERNAL FIBROUS GLASS DUCT LINER IN
Al I- ACCORDANCE WITH ASTM C1071, NFPA 90B.
il,...0 - - - - - . 3'-0"0
= 0 „00000000 HH 3 SHOP PRIME FRAMES WITH INORGANIC ZINC PRIMER.0. _
FL1 24x14 A 1270 CFM - 4-„;,,,\ BOLLARD, SPACED
(11P 7PL) - - li.vI
EQUALLY 60" MAX,9 PLACES
1:00110- 44"x20" EXTERIOR SUPPLY DUCTWORK ENTERBUILDING THROUGH EXISTING WALL PENETRATION.
a.
‘Mk > I
0 c)I0TYP.
SEE EXISTING WALL PENETRATE MUST BE MODIFIED TOIl0 CONDENSATE TANKS )=' I 36x36 C 9900 CFM '
ink COMPENSATE THE SIZE OF NEW DUCTWORK. MAXIMUMW H-6-15620-2Iw I— I 48x48 B 2PL)DUCT SUPPORT HANGER SPACING IS 5' FOR
(TYP t HORIZONTAL DUCTWORK AND 10' FOR VERTICAL
0
AIR COMPRESSOR'SCHANGED PER
O 0
LIH-6-15620-2
DUCTWORK, SEE DRAWING H-6-15620 SHEET 2 FORDUCTWORK MOUNTING DETAIL.
EH-6-15620-2 SCALE IN FEET
NOTE TO DRAFTER:
ECR - 1 9-000493 EF-1DO NOT
CONTROLLER 3 Q 3 9 feet INCORPORATE
REGISTER, GRILLE, DIFFUSER SCHEDULE
SYMBOL TYPE SERVICE STYLE INSTALLATION MATERIAL COLOR DAMPER MAX NC MFR/MODEL ACCESSORIES/REMARKS
A GRILLE SUPPLY SINGLE DEFLECTION DUCT ALUMINUM WHITE YES 29 TITUS / 301 FL SINGLE DEFLECTION, 3/4" SPACING, BLADES PARALLEL TO LONG DIMENSION WITHOPTIONAL DAMPER, MOUNT DIRECTLY TO EXPOSED DUCT
B LOUVER INTAKE COMBINATION INTEGRAL FLANGE ALUMINUM RUSKIN/ELC6375D CLEAR ANODIZE FINISH. RUSKIN MODEL NO. GCA226, 120V, 2— POSITION ACTUATOR.
C GRILLE RETURN ZERO DEFLECTION SURFACE MOUNT ALUMINUM WHITE NO 35 TITUS 350ZFL ZERO DEFLECTION, 3 4" SPACING, BLADES PARALLEL TO LONG DIMENSION
D GRILLE SUPPLY SINGLE DEFLECTION DUCT ALUMINUM WHITE YES 29 TITUS / 301 RLSINGLE DEFLECTION, 3/4" SPACING, BLADES PARALLEL TO LONG DIMENSION WITHOPTIONAL DAMPER, MOUNT DIRECTLY TO EXPOSED DUCT
AIR CONDITIONING SCHEDULENOMINAL TOTAL TOTAL SENSIBLE ELECTRICAL CHARACTERISTICS AMBIENT TEMP. (F)
FANUNIT DIMENSIONS (IN.)
SYMBOL MFG. MODEL AIR FLOWCFM
STATICPRESSUREIN W.C.
CAPACITY(MBH)
CAPACITY(MBH) VOLTAGE PHASE HERTZ MCA (A) DRY BULB WET BULB
EER IEER/SEER MOTORTPE
MOTOR(HP) CONFIGURATION
PLEATEDFILTER
REFRIGERANTCHARGE
WEIGHT(LBS) HEIGHT WIDTH LENGTH
AC-1 TRANE TSH300G4ROA3L 9990 0.75 286.97 286.12 460 3 60 55 80 67 10.0 12.40 BELTDRIVE 7.5 HORIZONTAL MERV-8 R-410A 3026 56 85 122
ECR-19-000982 00 8 of 15
Facility IV odification Package Continuation PageReference Drawing
H-6-15620
Sheet Number
01
Revision Number
01
Section Title
DWG-03
WAS:
NOTES
5:
NOTES HVAC GENERAL NOTES:
1. COORDINATE ALL WORK WITH THE RESPECTIVE CRAFTS INVOLVED. 1. COORDINATE ALL WORK WITH THE RESPECTIVE CRAFTS INVOLVED. 1. PROVIDE ALL MATERIAL, EQUIPMENT, AND INSTALL THE NEW HVAC SYSTEMAS INDICATED ON THE DRAWINGS. ALL INSTALLATIONS SHALL BE IN
2. ALL WORK TO BE PERFORMED IN A NEAT AND WORKMAN LIKE 2. ALL WORK TO BE PERFORMED IN A NEAT AND WORKMAN LIKE ACCORDANCE WITH ALL APPLICABLE CODES.MANNER. MANNER.
2. ALL DUCTWORK DIMENSIONS, ARE INTERNALLY CLEAR DIMENSION, AND DUCT3. ALL DUCTWORK SHALL BE FABRICATED AND INSTALLED IN 3. VERIFY EXISTING SPACE LIMITATIONS BEFORE FABRICATING SIZE'S SHALL BE INCREASED TO COMPENSATE FOR DUCT LINING THICKNESS.
COMPLIANCE WITH SMACNA STANDARD 15D FOR 1" W.C. DESIGN DUCTWORK.PRESSURE CLASS. 3. COMPLY WITH SMACNA "HVAC DUCT CONSTRUCTION STANDARDS — METAL
4. MAKE INCREASE IN DUCT WIDTH OR DEPTH NO MORE ABRUPT AND FLEXIBLE" BASED ON 2—INCH PRESSURE CLASS. USE 22 GAUGE4. VERIFY EXISTING SPACE LIMITATIONS BEFORE FABRICATING
DUCTWORK.THAT 1 TO 7 UNLESS GUIDE VANES ARE USED, EXCEPT WHENOTHERWISE NOTED.
ALUMINUM SUPPLY AND RETURN DUCTWORK. DUCT SUPPORT'S SHALL BEPER SMACNA.
5. MAKE INCREASE IN DUCT WIDTH OR DEPTH NO MORE ABRUPT 5. COORDINATE ALL ELECTRICAL REQUIREMENTS WITH ELECTRICALTHAT 1 TO 7 UNLESS GUIDE VANES ARE USED, EXCEPT WHENOTHERWISE NOTED.
CONTRACTOR. ALL ELECTRICAL AND CONTROLS WIRING ANDCONDUIT BY ELECTRICAL CONTRACTOR.
4. INSTALL DUCT INSULATION LINER ON EXTERIOR DUCT IN ACCORDANCE WITHSMACNA, DUCT INSULATION SHALL BE A MINIMUM R-8 INSULATION. FIBROUSGLASS DUCT LINER IN ACCORDANCE WITH ASTM C1071, NFPA 90B.
6. VERIFY SPACE LIMITATIONS BEFORE FABRICATING AND INSTALLINGDUCTWORK. 5. ROUTE AND SUPPORT DUCTWORK IN APPROXIMATE LOCATION AS SHOWN.
FIELD ADJUSTMENT SHALL BE MADE AS DEEMED NECESSARY TO7. SEAL DUCTWORK WITH DUCT SEALING COMPOUND EQUAL TO BIDDLE ACCOMMODATE INSTALLATION, AS LONG AS THERE IS NO DEVIATION FROM
"AGUA—CRYLIC" SILCONIZED ACRYLIC SEALANT. SIZE AND FUNCTION. ATTACH HANGERS/SUPPORT TO PRIMARY BUILDING
8. COORDINATE ALL ELECTRICAL REQUIREMENTS WITH ELECTRICALSTRUCTURE.
CONTRACTOR. ALL ELECTRICAL AND CONTROLS WIRING ANDCONDUIT BY ELECTRICAL CONTRACTOR.
6. LOCATE THE THERMOSTAT AT LEAST 4'—O" (CENTER OF LINE) AFF.
9. HP-1 AND AC-1 FURNISHED BY OWNER. CONTRACTORRESPONSIBLE FOR LOCATING AND WIRING UNITS AND INSTALLING
7. PROVIDE ALL 90 DEGREE SQUARE ELBOW WITH TURNING VANES ASINDICATED ON THE DRAWINGS.
DUCTWORK. 8. ALL TRANSVERSE JOINT, LONGITUDINAL SEAM AND OUTDOOR DUCTWORK MUST
10. AIR COMPRESSORS, CONDENSATE TANKS, FILL STATIONS ANDBE SEALED PER ASHRAE DUCTWORK SEAL CLASS B.
STORAGE VESSELS FURNISHED BY OWNER AND SET IN PLACE BYCONTRACTOR.
9. CONDENSATE DRAIN PIPING SHALL BE FULL SIZE AS THE UNIT DRAINOUTLET.
NOTE TO DRAFTER:PLACE NOTE UNDERAIR CONDITIONING SCHEDULE
REMARKS
ENTERING DRYBULB TEMPERATURE: 80FENTERING WETBULB TEMPERATURE: 67FAMBIENT TEMPERATURE: 95FECONOMIZER & POWER EXHAUST COMBINATION PACKAGE,ULTRA LOW LEAK HORIZONTAL WITH RELIATEL CONTROLLERDIFFERENTIAL ENTHALPY SENSOR.ELECTRICAL JUNCTION BOX.FACTORY INSTALLED VARIABLE FREQUENCY DRIVESTANDARD CONDENSER COIL WITH HAIL GUARDFACTORY INSTALLED SMOKE DETECTORHIGH/LOW STATIC DRIVE KITS
10. THE LOCATION OF ALL THE ITEMS SHOWN ON THE DRAWINGS ARE NOTDEFINITE. ALL DIMENSIONS ARE APPROXIMATE. THE EXACT LOCATIONNECESSARY TO SECURE THE BEST CONDITIONS AND RESULTS MUST BEDETERMINED BY SITE CONDITIONS AND SHALL BE APPROVED BY ENGINEERBEFORE INSTALLATION.
11. TESTING, ADJUSTING AND BALANCING SHALL BE IN ACCORDANCE WITHSMACNA STANDARD.
HVAC UNIT AC-1 SEQUENCE OF OPERATIONS:
HVAC UNIT CONTROL IS BY MANUFACTURER'S MICROPROCESSOR CONTROL.HVAC UNIT OPERATES WITH A SINGLE STAND—ALONE 7—DAY PROGRAMMABLETHERMOSTAT PROVIDING START/STOP, COOLING, AND FAN CONTROL. THERMOSTATIS TO BE A HONEYWELL T7350 OR ENGINEERING APPROVED EQUIVALENT.
HVAC UNIT SUPPLY FAN OPERATES CONTINUOUSLY TO MAINTAIN A TEMPERATURESET POINT OF 75F.
ECONOMIZER CONTROLLER TO CONTROL OUTSIDE AIR AND RETURN AIR MOTORIZEDDAMPER. OUTSIDE AIR IS PROVIDED TO MAINTAIN COOLING SET POINT WHENOUTSIDE AIR IS 60F OR LESS.
NOTE TO DRAFTER:DO NOTINCORPORATE
ECR-19-000982 00 9 of 15
Facility IV odification Package Continuation PageReference Drawing
H-6-15620
Sheet Number
02
Revision Number
NEW
Section Title
DWG-04
- W:
0 ®
12x12
14x14E1 550 CFM A
44x20
A
Co0
SECTIONH-6-15620-1 SCALE: NTS
STEEL ANGLE
0
12x12
14x14E1 550 CFM
24x20
A A
9'-0" BOD
SEE DETAIL
STEEL THREAD ROD
SEE DETAILS
NUT&WASHER ON BOTH SIDES(NON - CORROSIVE)
3/8"95 STEEL THREAD ROD
3/8"95 WASHERDIA/THREAD 3/8"-16 NUT
2"x2"x1/4" STEEL ANGLE
DETAIL(. B2
NOTE:
ALL STEEL SUPPORTS SHALL BE PAINTED WITH2 COATS OF ANTI-RUST PAINT AND 1 COATOF FINISHED COAT (WHITE) OR AS SPECIFIED.
SECTIONH-6-15620-1 SCALE: NTS
EXPANSION BOLT3/8" LENGTH 2"
3/8"0 STEEL THREAD ROD
DUCTWORK MOUNTING DETAIL SCALE: NTS
CO
Co
Co
Co
0GRADE
Co
13'-2 3/8"
0
Al
Co
FILL PIPE WITHGROUT, CROWN TOP
4" SCH 40 STEEL PIPEPAINTED SAFETY YELLOWOR BOLLARD PLASTICCOVER YELLOW, HDPE,MIN 1/8" THICK
COMPACTEDSUBGRADE
12" SONOTUBE FILLEDWITH 3000 PSICONCRETE
TYPICAL BOLLARDH-6-15620-1
#4 L-SHAPE REBAR24" X 24" TYP.AT ALL CORNERS
8" x 2'-0"FROST WALL ALLAROUND
8" CONC. SLAB
#4 REBAR© 12" O.C. E.W
25 TON HVAC UNIT0 CONCRETE PAD
H-6-15620-1 SCALE: NTS
SCALE: NTS
GRADE
#4 REBAR© 9" 0.C. E.W
9 5/8"
UNDISTURBEDSOIL
NOTES
1. FOR NOTES AND SCHEDULES, SEE SHEET 1.
2. FOR GENERAL AND CONSTRUCTION NOTES, SEE SHEET 3.
L3"x3"X3/8"x4"STEEL ANGLE
25 TONHVAC UNIT
GRADE
CONCRETEPAD
3/16TYP. 2PLACES
1/2"x5 1/2" KB-TZ SS304ANCHOR WITH 4" EMBEDMENT
ANCHOR DETAILH-6-15620-1 SCALE: NTS
8'-071 1 '-0"
6" STABILIZATIONMATERIAL
POLYETHYLENE VAPORBARRIER EXTENDED UNDERGRADE BEAM
CO
Co
co
LU
Co
CLR. COVE
Co
Co
(7)
ECR-19-000982 00 10 of 15
Facility IV odification Package Continuation PageReference Drawing
H-6-15620
Sheet Number
03
Revision Number
NEW
Section Title
DWG-05
\- W: GENERAL NOTES 1. ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE 2012 EDITION OF THE INTERNATIONAL BUILDING CODE
(IBC), LOCAL RULES AND STANDARDS OF GOVERNING AGENCIES HAVING JURISDICTION.
2. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF SITE CONDITIONS, INSTALLATION STANDARDS ANDCONSTRUCTION CONDITIONS. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS PRIOR TO SHOP FABRICATIONAND/OR FIELD ERECTION. DISCREPANCIES BETWEEN SITE CONDITIONS AND THE CONSTRUCTION DRAWINGS SHALL BECALLED TO THE ATTENTION OF THE ENGINEER. WORK DONE WITHOUT THE ENGINEERS APPROVAL IS THERESPONSIBILITY OF THE CONTRACTOR.
3.
4.
CONTRACTOR IS TO PROVIDE A METHOD OF CONSTRUCTION WHICH WILL ALLOW FOR OWNER TO REMAINOPERATIONAL THROUGHOUT CONSTRUCTION WITH AS LITTLE DISRUPTION AS POSSIBLE.
ALL SPECIAL INSPECTION AND TESTING SHALL BE PERFORMED BY AN INDEPENDENT INSPECTION. CONTRACTOR TOCOORDINATE WITH INSPECTION AND TESTING AGENCY FOR REQUIRED CONSTRUCTION INSPECTIONS AND MATERIALTESTING.
5. THE DIMENSIONS, LOCATIONS, AND ELEVATIONS OF ANY EXISTING STRUCTURES WHICH RELATE TO OR INFLUENCESNEW CONSTRUCTION SHALL BE VERIFIED BY FIELD MEASUREMENT BY THE CONTRACTOR PRIOR TO PREPARATIONAND SUBMISSION OF CHECKED SHOP DRAWINGS TO THE ENGINEER OF RECORD FOR REVIEW.
6. PROTECTION OF EXISTING STRUCTURES DURING THE COURSE OF THE CONSTRUCTION SHALL BE THERESPONSIBILITY OF THE GENERAL CONTRACTOR.
7. PRIOR TO DIGGING VERIFY LOCATION AND DEPTH OF UTILITIES AND OTHER UNDERGROUND INTERFERENCES.
8. DESIGN CRITERIA
BUILDING CODEBASIC WIND LOAD (3 SEC GUST)RISK CATEGORYSsS1SDSSD1BASE SHEAR, VWEIGHT OF HVACALLOWABLE BARING CAPACITY
CONSTRUCTION NOTES:
EARTH WORK:
IBC 2012115 MPHIII0.460.150.440.150.198 W3100 LBS1500 PSF
1. BACKFILL AND FILL MATERIAL: WELL GRADED AND UNIFORMLY MIXED SOIL WITHLARGEST PARTICLE BEING 3" IN GREATEST DIM & CONSISTING NOT MORE THAN 20%VOLUME.
2. STABILIZATION MATERIAL: CLEAN WASHED CRUSHED ROCK OF 5/8" MINUS.
3. EXCAVATION: UNLESS INSTRUCTED OTHERWISE BY OWNER REPRESENTATIVE PERFORMUNDERGROUND SCAN FOR BURIED UTILITIES IN THE AREA OF EXCAVATION. NOTIFYOWNER REPRESENTATIVE PRIOR TO BEGINNING OF EXCAVATION.
4. PREPARATION FOR BACKFILL AND FILL: ALLOW CONC TO CURE 72 HOURS (MIN)BEFORE BACKFILLING. DO NOT BACKFILL BY SLUICING OR FLOODING, & KEEP AREAFREE OF STANDING WATER.
5. BACKFILL AND FILL: PLACE AND COMPACT FILL, BACKFILL, AND STABILIZATION MATERIALTO 95% OF MAXIMUM DRY DENSITY AS DETERMINED BY ASTM D-1557.
6. FINISH GRADE: AFTER BACKFILLING IS COMPACTED, RESTORE SURFACE IN AREASDISTURBED BY WORK BY PLACING UNCOMPACTED 3 INCH COURSE OF STABILIZATIONMATERIAL.
CONSTRUCTION NOTES:
CONCRETE:
1. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 4000 PSI AT 28 DAYS.
2. CAST IN PLACE CONCRETE SHALL MEET THE FOLLOWING REQUIREMENTS:ACI 117 - STANDARD SPECIFICATIONS FOR TOLERANCES FOR CONCRETE CONSTRUCTION AND
MATERIALS.ACI 301 - SPECIFICATIONS FOR STRUCTURAL CONCRETE.ACI 302 - GUIDE FOR CONCRETE FLOOR AND SLAB CONSTRUCTION.ACI 305 - HOT WEATHER CONCRETING.ACI 306 - COLD WEATHER CONCRETING.
3. UNLESS NOTED OTHERWISE, ALL CONCRETE FLAT WORK SHALL CONFORM TO THE FOLLOWINGFINISHING TOLERANCES 1/8" GAP UNDER A 1C-0" STRAIGHT EDGE MEASURED AS PER ASTM E1155:
OVERALL FLATNESS NUMBER, Ff >20MINIMUM LOCAL FLATNESS NUMBER, Ff>15OVERALL LEVELNESS NUMBER, Fl > 15MINIMUM LOCAL LEVELNESS NUMBER, Fl>10
4. ALL CONCRETE FLOORS ARE TO BE WET CURED FOR 7 DAYS IMMEDIATELY AFTER PLACEMENT, ASPER THE RECOMMENDATIONS OF ACI 302 OR SPRAY WITH CURING COMPOUND.
5. ALL REINFORCING STEEL SHALL BE GRADE 60 DEFORMED BARS COMPLYING WITH ASTM SECTIONA615.
6. ALL DETAILING, FABRICATION AND PLACEMENT OF REINFORCING STEEL SHALL COMPLY WITH THEREQUIREMENTS OF THE ACI MANUAL OF STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETESTRUCTURES (ACI-SP - 66).
7. REINFORCEMENT LAP LENGTHS AND HOOK DIMENSIONS SHALL BE PER THE REINFORCEMENT TABLEUNLESS NOTED OTHERWISE.
8. THE FOLLOWING MINIMUM CONCRETE COVER SHALL BE PROVIDED FOR REINFORCEMENT: (MIN. COVERLISTED U.N .0.).(A) CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3"(B) CONCRETE EXPOSED TO EARTH OR WEATHER:
#6 THROUGH #18 BARS: 2"#5 BAR, W31 OR D31 WIRE AND SMALLER: 1 1/2"
(C) CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND:SLABS, WALLS, JOISTS #14 AND 18 BARS: 1 1/2"#11 BAR AND SMALLER: 3/4"BEAMS, COLUMNS PRIMARY REINFORCEMENT, TIES, STIRRUPS, SPIRALS: 1 1/2"SHELLS. FOLDED PLATE MEMBERS #6 BAR AND LARGER: 3/4"#5 BAR, W31 OR D31 WIRE, AND SMALLER: 1/2"
9. ALL EXPOSED CORNERS OF CONCRETE SHALL BE ROUNDED WITH A 1/2" DIAMETER EDGER.
10. CLEAN REINFORCING OF LOOSE RUST, MILL SCALE, DIRT, OR ANY OTHER FOREIGN MATERIAL.ACCURATELY POSITION, SUPPORT AND SECURE REINFORCEMENT.
11. PROPORTION AND DESIGN MIXES TO RESULT IN MAXIMUM CONCRETE SLUMP OF 5" AT POINT OFPLACEMENT AND NOT MORE THAN 8" WITH USE OF SUPERPLASTICIZER.
12. DEPOSIT CONCRETE IN A CONTINUOUS OPERATION UNTIL THE PLACING OF CONCRETE IS COMPLETE.IF THE POUR IS TO BE DISCONTINUOUS, CONTRACTOR SHALL USE CONSTRUCTION JOINTS, ASAPPROVED BY THE ENGINEER.
13. REPAIR ALL SURFACE DEFECTS INCLUDING TIE HOLES, MINOR HONEYCOMBING AND OTHER VISUALIRREGULARITIES WITH CEMENT MORTAR. MORTAR FOR PATCHING SHALL BE THE SAME COMPOSITIONAS THAT USED IN THE CONCRETE. PATCHING SHALL BE DONE AS SOON AS THE FORMS AREREMOVED.
14. CONCRETE SLAB FINISH: BROOM FINISH
15. CONCRETE TESTING: 5 TEST CYLINDERS AND TEST THEM FOR COMPRESSION AT 2 © 3-DAY AND 2CD 7-DAY AND 1 CD 28-DAYS.
ECR-19-000982 00 11 of 15
Facility IV odification Package Continuation PageSection Title
DWG-06Reference Drawing
H-6-15622
Sheet Number
01
Revision Number
02
WAS:
5KW UNITHEATER
1/2"0 CONDUIT
5KW UNITHEATER
1/2"0 CONDUIT
)-
LP-15
AA AA -'1,-°- AA
II II I I II
II II I I II
LP-13
)
LOUVRE
1
/ TO17.5 TON
AC17.5 TON
AC DISCONNECTRATED 60A
LP-15
-eAA -11-,,-EL
II II II I
II II I I II
LOUVRE
'Er' lirj lirj ̀ Er' ̀ 11j ̀ Er'LP-13
J )
LOUVRE TO25 TON
AC25 TON
AC DISCONNECTRATED 100A
LOUVRE
ECR-19-000982 00 12 of 15
Facility lvodification Package Continuation PageReference Drawing
H-6-15623
Sheet Number
01
Revision Number
01
Section Title
DWG-07
WAS:
Se
WIRE RUN LISTWIRE RUN
NO.NC. OFWIRES
SIZE OFWIRE
TYPE OFWIRE
FROM VIA TO WIRE NUMBERS
100 4 600KCMIL 1 WAV HOUR CT ENCLOSURE P100 MP-609J (MAIN) T3-A, -B, -C, -N
101 3--------:16 0 2 MP-6093 (CKT-2/4/6) P104, PE 17.5 TON AC DISCONNECT MP-609J-A1, -51, -Cl. -GND
102 3 1 2/ 6 2 MP-609J (04T-19121/23) NIPPLE OR FMC *MR T4 MP-609J-A2, -62, -02, -GND
103 3 1 1 4 2 MP-6C9J (CKT-20/22/74) P101 75 HP AIR COMPRESSOR MP-609J -A3, -B3 -C3, -GNI)
104 3 18__-------16 2 MP-609J (CKT-11315) P104, PB, P105 3 TON HEAT PUMP DISCONNECT MP-609J-A4, -B4, -C4, -GND
105 4 600KCMIL 2 XFMR Td NIPPLE OR FMC LP-509J (MAIN) T4-A, -B, -C, -N
106 4 10 2 UP-609J (CKT-1,3,5) P113, JB, P111 COMPRESSOR ROOM HEATER LP-6C9J-A 1 , -B1, -C1, -OND
107 3,----------:(14----------' 4 2 LP-609J (CKT-19,21,23) MTS, P102 40 HP COMPRESSOR LP-609J-A2, -132, -C2, -GND
108 3 8 2 LP-609J (CKT-2.4) P112 COMPRESSOR ROOM EMAUST FAN LP-60911-110, -N10, -GNU
109 3 12 3 LP-509J (CKT-7) P113, JB, P114 ANNUNCIATOR LP-809J-H7, -N7, -GND
110 6 16 4 40 HP COMPRESSOR P106, JB, P110 ANNUNCIATOR 401-IP-LOA , -2, 40HP-HT-1, -2, 2SP
111 6 16 4 75 HP COMPRESSOR p109, .1113, P110 ANNUNCIATOR 75HP-L0-1, -2, 7.51-1P-HT- , -2, 23P
112 a 12 3 LP-609J (C KT-8) P107 LIGHTS, BOTTLE FILL ROOM WEST LP-60SJ-1-18, -Nd. -GNI)
113 3 12 3 LP-509J (CKT-9) P106 LIGHTS, COMPRESSOR ROOM SOUTH LP-6C9J-H9, -NO, -GND
114 3 12 3 LP-609J (CKT-15) P106 LIGHTS, COMPRESSOR ROOM NORTH LP-609J-H15, -N15, -GND
115 3 12 3 LP-509J (CKT-16) P107 LIGHTS, BOTTLE FILL ROOM EAST LP-609J-1-116, -N16, -GND
116 3,-------- 1 >_----- 4 1 LP-609J (CKT-19,21,23; MIS, P103 40 HP MOBILE AIR COMPRESSOR RCPT LP-609J-A2, -132.. -C2, -GND
117 3 12 3 LP-509J (CKT-17) P 115 LOADING DOCK LIGHTS LP-6C9J-1-117, -N17, -OND
WIRE RUN LISTWIRE RUN
NO.NO. OFWIRES
SIZE OFWIRE
TYPE OFWIRE
FROM VIA TO WIRE NUMBERS
100 4 904rail, 1 WATT HOUR CT ENCLOSURE P100 M13,6081A.MEAN T3-A, -B, -C, -N
101 3/1( 4, 80 ) 2 MP-6091 (CRT-21416) P104, PB 1(--z-I25 TON AC DISCONNECT "C15-AC-1' MP-609J-A1,1,-C1,-GND'/ 4
102 3/1'--2. 0, r 2 MP-6091 (CKT-19/21123) NIPPLE OR EMC XF-MTht-re- MP-609J-A2,-R2,-C2,-.GNID
103 3/1 1, 40 2 MP-5091 (CKT-20/22/24) P101 75 H P AIR COMPRESSOR MP-639J-A3,-B3,-C3, GND
104 3/1 8, 10G 2 MP-6091 (CKT-1/3/5) P104, PB, P105 3 TON HEAT PUMP DISCONNECT MP-609J-A4,-R4,-C4,-GND
105 4 600KCMIL 2 XFMR T4 NIPPLE OR FMC LP-6091 (MAIN) T4-A, -B, -C, -N
106 4 10 2 LP-609J (CKT-1,3,5I P113,113, P111 COMPRESSOR ROOM HEATER EP-609J-A1,-B1,-C1,-GND
107 3/1 110, 40 2 LP-609J (CKT-19,21,23) MTS, P102 40 HP AIR COMPRESSOR 113-6093-A2, -B2, -C2, -GND
108 3 8. 2 LP-609J (ICKT-2,41 P112 COMPRESSOR ROOM EXHAUST FAN 1.13-609.1-H10,-N10,-GND
109 3 12 3 LP-609J (CXT-7) P113,113, P114 ANNUNCIATOR LP-6091-H7,-N7, -GNU
110 6 16. 4 75 HP COMPRESSOR P108,16, P110 ANNUNCIATOR 40H P-10-1, -2, 40HP-FIT-1, -2, 2SP
111 6 16. 4 75 HP COMPRESSOR P109, JR, P110 ANNUNCIATOR 70HP.-10-1, -2, 751-1P-HT-1, -2, 21P
112 3 12 3 LP-609J (CKT-8) P1097 LIGHTS, BOTTLE FILL ROOM WEST 1P-6091-H8,-N8, -GND
113 3 12 3 LP-609J (CKT-91 P106 LIGHTS, COMPRESSOR ROOM SOUTH EP-609J-H9,-N9, -GND
114 3 12 3 LP-609J (CXT-15) P106 LIGHTS, COMPRESSOR ROOM NORTH EP-609.1-H15,-N15, -GND
115 3 12 3 LP-609J (CXT-16) P107 LIGHTS, BOTTLE FILL ROOM EAST LP-6091-H16,-N16, -GND
116 3/1 110, 4G 1 LP-609J (CXT-19,21,23) MTS, P103 40 HP MOBILE AIR COMPRESSOR RCPT LP-6091-A2, -B2, -C2, -GNU
117 3 12 3 LP-609J (CXT-17) P115 LOADING DOCK LIGHTS 1.13-6091-H 1.7,- 817, -0 ND
CONDUIT SCHEDULECONOLI7
NO
CONDUITSIZE
WIRE RUN NUMBERS
P100 4'' 100
P101 1.6" 103
P102 1.6" 147
P103 1.5" 116
P104 1' 101,104
P105 314" 104P106 314" 113,114
P107 314" 112, 115
P105 314" 110
P109 3/4' 111
P110 314" 110, 111
P111 314" 106
P112 314" 108
P113 , 106, 109P114 314' 109
P115 314" 117
CONDUIT SCHEDULECONDUIT
NO
CONDUIT
SIZEWIRE RUN NUMBERS
P100 4' 100
P101 1.5' 103
P102 1.5" 137
P103 1 '' 116
P104 1.5"
c.....
101, 104
P105 134
P106 314' 113, 114
P107 3/4" 112, 115
P108 3/4' 110
P109 314' 111
P1 1 0 3/4' 110, 111
P111 3/4' 106
P112 314" 106
P113 1" 106, 109
P114 314" 109
P1 1 5 314' 117
ECR-19-000982 00 13 of 15
Facility Ivodification Package Continuation PageReference Drawing
H-6-18185
Sheet Number
01
Revision Number
01
Section Title
DWG-08
WAS:
REMOVE INCORRECT PANELSCHEDULE DUE TO ERROR INECR-18-001925 INCORPORATION
PANEL MFG: SEIMENS P4C60JX400ATS
PANEL TYPE (MODEL): P2
MAIN BRKR TYPE: SERIES KD
PANELBOARD: LP-609J LOCATION: 609J VOLTAGE: 208Y/120VAC, 3PH 4WFED FROM: MP-609J VIA XFMR T4 ONE LINE DWG NO: H-6-15095
FEEDER BRKR TYPE: KD
MAIN BRKR RATING (AIC): 35 KA
FEEDER BRKR RATING (AIC): 35 KANEMA TYPE: 1 [Z] MAIN BREAKEREl SURFACE MOUNT n LUGS ONLYIII FLUSH MOUNT El TOP III BOTTOM FEED
400 AMP BUS III PANELBOARD GROUNDAMP NEUT FAULT PROTECTION
BUS III OTHER400
I GROUND
REMARKS SCHEMENUMBER
WATTS/HPLOAD DESCRIPTION
SYSNO.
CKTNO.
25400
AI
---)
CI
30
CKTNO.
SYSNO. LOAD DESCRIPTION
WATTS/HP SCHEMENUMBER
REMARKSPH A PH B PH C PH A PH B PH C
COMPRESSORROOM
1,667 1,667 1,667 UNIT HEATER5KW
1
2
4
EXHAUST FAN #13 HP
1,118 1,119A AI
A ,----\•
6 BLANK20
n(---
• 20
SPARE 7 8LIGHTS AND EMERGENCYLTG RCPT BOTTLE ROOM 395 BOTTLE FILL ROOM
WEST20
n(---
20
COMPRESSOR ROOMSOUTH
360 LIGHTS COMPRESSOR ROOM 9 10 SPARE20
nnBOTTLE
20
COMPRESSOR ROOMSOUTH 540 RCPTS COMPRESSOR ROOM 11 12 RCPTS/LIGHTS BOTTLE ROOM 840 FILL ROOM
WEST20I---\
15I---\COMPRESSOR ROOM
NORTH 875 RCPTS/LIGHTS COMPRESSOR ROOM 13 14 RCPTS BOTTLE ROOM 720 BOTTLE FILL ROOMEAST15
I---\
20
I---\COMPRESSOR ROOMNORTH 240 LIGHTS AND EMERGENCY
LTG RCPT COMPRESSOR ROOM 15 16 LIGHTS BOTTLE ROOM 480 BOTTLE FILL ROOMEAST20
(---
•
LOADING DOCK 200 LIGHTS CANOPY NORTH 17 18 BLANK---306--•
I---\— •—•
SUB FEEDERCKT BRK 9,943 9,943 9,943 40 HP
AIR COMPRESSOR
19
21
23
I---\— —110
(---
SUBTOTAL12,350 12,210 12,485 TOTAL WATTS PHASE A:
TOTAL WATTS PHASE B:TOTAL WATTS PHASE C:
TOTAL:
14,308 SUBTOTAL
* See Panel Breaker Layout Detail.
1,958 1,599 1,115
13,80913,600
41,717
ECR-19-000982 00 14 of 15
Facility Ivodification Package Continuation PageReference Drawing
H-6-18185
Sheet Number
01
Revision Number
01
Section Title
DWG-09
Se
REPLACE WITH CORRECT PANEL SCHEDULE,PREVIOUSLY REMOVED DUE TO ERROR INECR-18-001925 INCORPORATION
PANEL MFG: SIEMEN P2E18JX400ATS
PANEL TYPE (MODEL): P4
MAIN BRKR TYPE: SERIES KD
PANELBOARD: MP-609J LOCATION: 609J
FED FRO12:25KVA XFMR T3VOLTAGE: 480Y/277VAC 3PH 4WONE LINE DWG NO: H-6-15095
FEEDER BRKR TYPE: N/A
MAIN BRKR RATING (AIC): 35 KA
FEEDER BRKR RATING (AIC): N/ANEMA TYPE: 1El SURFACE MOUNT0 FLUSH MOUNT
[Z] MAIN BREAKER0 LUGS ONLYEl TOP 0 BOTTOM FEED
400 AMP BUS 0 PANELBOARD GROUNDAMP NEUT FAULT PROTECTION
BUS 0 OTHER400
l GROUND
REMARKS SCHEMENUMBER
PHA
WATTS/HP
PH B PH CLOAD DESCRIPTION
SYSNO.
CKTNO.
400
30
AI)---
BI
--)
CI
70
CKTNO.
SYSNO. LOAD DESCRIPTION
WATTS/HP
PHA PH B PH C
SCHEMENUMBER
REMARKS
3 TONRATED 4,000 4,000 4,000 HEAT PUMP
1
3
5
2
4
6
AIR CONDITIONERAC-1 14,690 14,690 14,690 25 TON
RATED
I 8 I
IA IA
175
•
225
7
9
11
8
10
12
13
15
17
14
16
18
FEED TOLTG PNLBDLP-609J
13,190 14,927 13,592480/208-120
TRANSFORMER T4112.5KVACOMPRESSOR
19 11--\
21
23
20
22
24
75 HPAIR
C1
18,643 18,643 18,643SUB FEEDERCKT BRK
1 • 1AII • II
SUBTOTAL17,190 18,927 17,592 TOTAL WATTS
TOTAL WATTSTOTAL WATTS
PHASE A:PHASE B:PHASE C:
TOTAL:
50,514
*
SUBTOTAL
See Panel Breaker Layout Detail.
33,324 33,324 33,324
52,25150,916
153,681
ECR-19-000982 00 15 of 15
Facility N odification Package Continuation PageSection Title
DWG-10Reference Drawing
H-6-15095
Sheet Number
01
Revision Number
04
WAS:WIREWAY
25 KVA,120 VAC,60 HZ
WIREWAY
-J
12PNLBD, MP-609J
3P )
400 AF 400 AT
1 480/277
3P 100 AF
3P 100 AF
) 30 AT ,) 50 AT
....*----' 3-#8 AWG, ...„.„„--- 3-#6 AWG,1-#10 AWG GND 1-#10 AWG CND
13P I 1100A SW I3P
1
1 100A SWI1 I I 1L_ _ __I L_ _ _ _J
3 TONHEAT PUMP
17.5 TONAC
3P400 AF225 AT
75 HPCOMPRESSOR
10
3P
3—#1 AWG,1—#4 AWG GND
I
12
3P )
100 AF 3P
30 AT
3—#8 AWG,1—#10 AWG GND
r-
?25 KVA, I3P120 VAC,60 HZ
100A SW
3 TONHEAT PUMP
r-
113P 100A SWI I 75 HPL_ _ _J COMPRESSOR
3P )
400 AF400 AT
PNLBD, MP-609J 480/277
3—#4 AWG,1—#8 AWG GND
400 AF225 AT
10
3P
3—#1 AWG,1—#4 AWG GND