Chiller PQ Issues - EPRImydocs.epri.com/.../E232227_Chiller_PQ_Issues.pdf · · 2009-12-18Chiller...
Transcript of Chiller PQ Issues - EPRImydocs.epri.com/.../E232227_Chiller_PQ_Issues.pdf · · 2009-12-18Chiller...
1
Chiller PQ Issues
Mark Stephens, PESenior Project ManagerIndustrial Studies Electric Power Research Institute 942 Corridor Park Blvd Knoxville, Tennessee 37932 Phone 865.218.8022
2 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
HVAC and Chiller Basics: Commercial Office Building Example
3. Refrigeration Loop
2. Chilled Water Loop
1. Airsideloop
4. Heat RejectionLoop
5. Building AutomationSystem (Optional)
3 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
HVAC and Chiller Basics: Industrial Process Cooling Water Example
BAS(Optional)
HeatExchanger
HeatExchanger
Evap
o rat
orEv
apo r
ator
SecondaryPCW
Loop toProcessLoads
FromProcessLoads
Capacity ControlValve
(2 or 3 Way)
ChilledWater
Pump(s)
Con
dens
e rC
onde
nse r
CompressorCompressor
ExpansionValve
ExpansionValve
Cooling Tower Pump(s)
Cooling Tower Pump(s)
3WayModulating
Valve
3WayModulating
Valve
3WayModulating
Valve
CoolingTower
CoolingTower
Chiller System
PrimaryChilled WaterLoop
Refrigeration Loop
HeatRejection
Loop
95°
85°85°
95°120°
100°38°
50°80°
55°55°
80°
BTU Flow
4 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Susceptibility Concerns for Chiller Systems
• Voltage Sag Induced Shutdowns:– Weak Control Relay in Chiller Control Cabinet (pilot relay)– Chiller controls or micro settings do not allow for voltage sag
induced deviations– Interlock with Chilled Water Supply (CWS) Flow Switch or with
Chilled Water Pump contactors– Shutdown due to Over-current– ASD Shutdown due to DC Bus Trip Level
• Shutdown due to Voltage/Current Unbalance– Chiller controls or micro settings too tight for typical unbalance
conditions– Phase-Monitoring Relay in MCC or control panel
5 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Survey/Case Study Breakdown
46%
40%
7% 7%Voltage Sag/MomentaryInterruptionVoltage Unbalance
Harmonics
Flicker
Based on Survey/Case Study Responses
6 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
What happens to Customer’s HVAC/Chiller System during a Voltage Sag?
Any one or more of these equipment may tripdepending on the sensitivity of the equipment/control:
• Chiller Control Panel
• Chiller Starter
• Chilled Water Supply (CWS) Pump
• Condenser Cooling Water Pump
• Air Handling Unit Motor Controls
7 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Trane Centravac Chiller
Evaporator
Condenser
Chiller ControlPanel
CompressorCompressorMotor StarterPanel
8 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
McQuay Chiller
9 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
York Chillers
OM SeriesTurbomaster
MaxESeries with SoftStart
MillenniumYK Series
10 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
York Chiller With Solid State Starter
11 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
York Chiller With Electro Mechanical Starter
12 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
York Chiller With ASD
13
Control Panel PQ Issues
14 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Control Panel PQ Issues
• AC Input Board – Inputs subject to misinterpretation/device chatter from Voltage Sag Events can lead to shutdown
• Relay Output Board – Control of vane and orifice valves, chiller compressor starter/pilot relay
Control Voltage 120Vac 50/60Hz fromControl Power Transformer (2-3kVA Typical)
AC Input Board
Stop Compressor
Start Compressor
CWS Flow Switch
CWP Running
Relay Output Board
Open
CloseVaneMotor
Open
Close
OrificeValveMotor
Run Oil Pump OilPumpStarter
Run Compressor* PilotRelay
Multiple Solenoid Valves(oil return, liquid line, vent line, etc.)
L1 N
Compressor Running
Warm Oil OilHeaterRelay
Oil Heater Relay Contact
Oil Pump Heater
5Amp
20Amp
*Note: Some Manufacturers utilize a data Link toseperate microprocessor based Starter Panel wherePilot Relay and starter contactors are located. Thispanel also contains another control powertransformer.
15 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Control Panel PQ Issues
• Linear/Switch Mode Power Supply for Instrumentation
• Microprocessor for control decisions
• DC Input board for instrumentation measurements (Pressure/Temp)
• Motor Protection Board: Measures Phase Current and Voltage
Compressor Current Ph. B
Power Supply Board
Control Voltage 120Vac50/60Hz (continued)
L1 NVdc Return
Microprocessor
DC Input Board
Compressor Current Ph. A
Compressor Current Ph. C
CT1
CT2
CT3
PT
TT
Various PressureTransmitters
Various TemperatureTransmitters
Compressor Motor ProtectionMonitoring Board/Relay
Compressor Voltage Ph. B
Compressor Voltage Ph. A
Compressor Voltage Ph. C
Va
Vb
Vc
Interlock withMicroprocessor
16 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Control Power Schemes
Notes:1.An external control power transformer
may be used to feed both the microprocessor panel and the compressor starter panel. In this case, applying voltage conditioning from this power source can lead to a must more robust chiller control system.
2.Some vendors mount the control power transformer in the starter panel. This transformer can be used to supply control voltage to the starter internal to the panel as well as for the microprocessor control panel.
3.The control signals between the two panels will either consist of hardwired control signals between the starter elements in the panels or a datalink to a separate starter microprocessor that is located in the starter panel.
CompressorMotor
Starter Panel
CompressorMotor
Starter Panelwith Control
PowerTransformer 2
MicroprocessorControl Paneland Display
MicroprocessorControl Paneland Display
External Control Power Transformer 1
ControlSignals 3
ControlSignals 3
Control PowerControl Power
Control Power
CompressorMotor
Starter Panelwith Control
PowerTransformer 2
MicroprocessorControl Paneland Display
ControlSignals 3
Control Power
PowerDistribution
Panel
Configuration "1"
Configuration "2"
Configuration "3"
17 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Control Power Schemes Evaluated by EPRI
Micro to starter panel
Unit ConfigurationStarter Type Control Signal Reason for Susceptibility
A 2 wye-delta Datalink Motor Starter, Voltage Unbalance setting
B 2 wye-delta Hardwired Motor Starter
C 2 soft starter Datalink Contactors used in running mode
D 2 wye-delta Datalink Pilot Relay and Motor Starter
E 1/3 across line Hardwired Pilot Relay
F 1/3 soft starter Hardwired Pilot Relay
18 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Chiller Voltage Sag Susceptibility – Unit A
SingleSingle--Phase Voltage SagsPhase Voltage Sags PhasePhase--toto--Phase Voltage SagsPhase Voltage Sags
Background Background -- Control Power Transformer Connected acrossControl Power Transformer Connected acrossPhases A and B. Tested in EPRI Lab.Phases A and B. Tested in EPRI Lab.Reason for susceptibility Reason for susceptibility –– Control Relays and Surge DeltaControl Relays and Surge DeltaAmp SettingsAmp Settings
19 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Chiller Voltage Sag Susceptibility – Unit B
0
1020
3040
5060
7080
90
0 10 20 30 40 50 60
Cycles
%V
nom
inal
Motor Controls Trip
Motor ControlsChatter/DropoutChiller Controls Only
CBEMA/ITIC
PhasePhase--toto--Phase Voltage SagsPhase Voltage Sags
Background Background -- Control Power Transformer Connected acrossControl Power Transformer Connected acrossPhases A and B. Tested at site where unit is installed. Phases A and B. Tested at site where unit is installed. Reason for susceptibility Reason for susceptibility –– Control Relay in Control Relay in WyeWye--Delta Starter.Delta Starter.
20 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Chiller Voltage Sag Susceptibility – Unit C
PhasePhase--toto--Phase Voltage SagsPhase Voltage Sags
Background Background -- Control Power Transformer ConnectedControl Power Transformer Connectedphasephase--toto--phase. Chiller utilized 480Vac soft starter, tested at EPRI phase. Chiller utilized 480Vac soft starter, tested at EPRI lab.lab.Reason for susceptibility Reason for susceptibility –– Compressor Motor Contactor Chatter afterCompressor Motor Contactor Chatter afterSoft starter is out of circuit (normal running operation).Soft starter is out of circuit (normal running operation).
Voltage Sag Ridethrough Curve
0%20%40%60%80%
100%
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1Duration (in seconds)
Volta
ge (%
of N
omin
al)
DUT SEMI F47
21 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Chiller Voltage Sag Susceptibility – Unit D
PhasePhase--toto--Phase Voltage SagsPhase Voltage Sags
Background Background -- Control Power Transformer ConnectedControl Power Transformer Connectedphasephase--toto--phase. Chiller utilized phase. Chiller utilized wyewye--delta 480Vac starter. Tested at EPRI .delta 480Vac starter. Tested at EPRI .Reason for susceptibility Reason for susceptibility –– Compressor Motor Contactor Chatter.Compressor Motor Contactor Chatter.““Momentary Power LossMomentary Power Loss”” warning shows up for Phase C sags only and results in warning shows up for Phase C sags only and results in Shutdown.The chiller Micro only monitors that phase for power loShutdown.The chiller Micro only monitors that phase for power loss.ss.““Transition Complete Input OpenTransition Complete Input Open”” message displayed on phase A and B sags whenmessage displayed on phase A and B sags whenMotor contactors and relays cause the chiller to trip.Motor contactors and relays cause the chiller to trip.
0
10
20
30
40
50
60
70
80
0 5 10 15 20 25 30
Cycles
%Vn
omin
al Phase C-NPhase B-NPhase A-NSEMI F47
SingleSingle--Phase Voltage SagsPhase Voltage Sags
0
10
20
30
40
50
60
70
80
0 5 10 15 20 25 30
Cycles
%Vn
omin
al
Phase A-BSEMI F47
22 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Chiller Voltage Sag Susceptibility – Unit E
Component Voltage Sag SummaryComponent Voltage Sag Summary
Background Background –– 120Vac Test of control panel. Chiller utilized line starter. T120Vac Test of control panel. Chiller utilized line starter. Tested atested atChiller Manufacturer Lab.Chiller Manufacturer Lab.Reason for susceptibility Reason for susceptibility –– Compressor Motor Pilot Relay. Chiller required 2 minutesCompressor Motor Pilot Relay. Chiller required 2 minutesTo reset and allow a restart (typical for most chillers to allowTo reset and allow a restart (typical for most chillers to allow for the compressor tofor the compressor toSpin down).Spin down).
SingleSingle--Phase Voltage SagsPhase Voltage Sags
6965
60
00
10
20
30
40
50
60
70
80
1R Relay* CompressorStarter
Oil PumpStarter
24Vdc P/S**
%Vn
omin
al
23 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Chiller Voltage Sag Susceptibility – Unit F
Soft Starter Susceptibility to SingleSoft Starter Susceptibility to Single--Phase SagsPhase Sags
Background Background –– 120Vac Test of control panel with solid state starter electroni120Vac Test of control panel with solid state starter electronic starter. c starter. Tested at Chiller Manufacturer Lab.Tested at Chiller Manufacturer Lab.Reason for susceptibility Reason for susceptibility –– Compressor Motor Pilot Relay. Chiller required 2 minutesCompressor Motor Pilot Relay. Chiller required 2 minutesTo reset and allow a restart (typical for most chillers to allowTo reset and allow a restart (typical for most chillers to allow for the compressor tofor the compressor toSpin down). Soft Starter electronics robust since powered by DCSpin down). Soft Starter electronics robust since powered by DC power supply.power supply.
SingleSingle--Phase Voltage Sags Phase Voltage Sags
24
Chilled Water Loop Considerations
25 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Chilled Water LoopsPrimary and Secondary
PLC ASDs Pumps
26 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Chilled Water LoopsTypical PLC Interface
Loop Number Description Source Voltage Note QI-191 P-191 Run
Status 120Vac Control Relay (Model # AB/700-HC24A1) CR7 coil voltage from drive control power transformer (CPT)
Signal Susceptible to voltage sags due to sensitive “ice cube” relay.
QA-191 P-191 Fault 120Vac Control Relay (Model # AB/700-HC24A1) CR6 coil voltage from drive control power transformer (CPT)
Signal Susceptible to voltage sags due to sensitive “ice cube” relay.
HS-191-2 P-191 Start/Stop Control RelayCR9 fed from PLC control power
PLC control power on UPS. Signal not expected to be susceptible to voltage sags.
HY-191 P-191 in Auto 120Vac control relay CR8 fed from drive CPT.
Signal Susceptible to voltage sags due to sensitive “ice cube” relay.
HIC-191 Pump P-191 Pump Speed Control Signal
4-20ma Signal fed through power supply in PLC cabinet.
PLC control power on UPS. Signal not expected to be susceptible to voltage sags.
PLC ASDs
27 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Example PCW Pump PLC-Drive Hardwired Interface
Fab Quadrant A/B PCW Pumps 610,611,612
Two-Relay PLC Interface Scheme and
Control Power Transformer
(Estimated at 0.25kVA)
Fab Quadrant C/D PCW Pumps 614,615,616 Four-Relay PLC Interface
Scheme and Control Power Transformer
(0.2 kVA)
Fab Quadrant E PCW Pumps 617,618,619
Four-Relay PLC Interface Scheme and
Control Power Transformer (0.38 kVA)
28 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
A Satisfactory Response for One Application May Not Be for Another
• For HVAC application an automatic restart or a manual restart after time delay may be the best option - in that case the tripping of the chiller unit does not have significant impact oncustomer.
• However, for process chilled water application, the loss of the chiller or the CWP may have significant financial impact.
29
Chiller Voltage Unbalance Issues
30 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Voltage Unbalance and Chillers
• Shutdown occurs when the chiller's current sensing relay/micro processor detects an imbalance or over current condition in excess of the preset limits.
• Chiller shutdown is influenced by the single phase loading conditions internal and external to the building electrical system.
• The American National Standards Institute (ANSI) std. C84.1-1989 recommends that voltage imbalance on power lines should not exceed 3%.
• Some factory preset imbalance protection limits cause chillers to shutdown or operate at reduced capacity when the chiller is experiencing an amperage imbalance. Example Chiller setpoint range 5% to 40%.
Rule of Thumb:1% Voltage Unbalance
Leads to 6 to 10%Current Unbalance
%Voltage %Current ImbalanceUnbalance Min Max
0.25% 1.50% 2.50%0.50% 3.00% 5.00%0.75% 4.50% 7.50%1.00% 6.00% 10.00%1.25% 7.50% 12.50%1.50% 9.00% 15.00%1.75% 10.50% 17.50%2.00% 12.00% 20.00%2.25% 13.50% 22.50%2.50% 15.00% 25.00%2.75% 16.50% 27.50%3.00% 18.00% 30.00%
31 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Voltage Unbalance And HP Derating
• If voltage imbalance present, may have to derate chiller cooling capacity (maximum amp) to protect motor.
• For Motors with Service Factors of 1.5, allowable %Current Imbalance to 30%.
Application Note 12 – Matching Utilization Voltage to Motor Nameplate
32 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Motor Service Factor
Motor Service Factor (SF) is a factor that when multiplied by Motor Service Factor (SF) is a factor that when multiplied by horsepower, gives us the allowable horsepower loading, which mayhorsepower, gives us the allowable horsepower loading, which maybe carried under the conditions specified for the service factorbe carried under the conditions specified for the service factor at at rated voltage and frequency. This is practical as it gives you srated voltage and frequency. This is practical as it gives you some ome 'fudge' in estimating horsepower needs and actual running 'fudge' in estimating horsepower needs and actual running horsepower requirements. It also allows for cooler winding horsepower requirements. It also allows for cooler winding temperatures at rated load, protects against intermittent heat rtemperatures at rated load, protects against intermittent heat rises, ises, and helps to offset low or unbalanced line voltages.and helps to offset low or unbalanced line voltages.
Click Here for More on Motor Nameplate Data
33 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Chiller Voltage Unbalance and Current Imbalance Parameters
34 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Recommended Chiller Micro/Motor Protection Settings
Parameter Function Recommended Setting for best
PQ performance
Note
Voltage Unbalance
Measure of allowable phase Voltage
Unbalance
>3% From ANSI C84.1, 98% percent of the electric
supply systems surveyed are within the 0-3.0 percent
voltage unbalance range
Voltage UnbalanceTime (sec)
Delay Time in which Unbalanced Voltage
Must be Present Before Chiller Trips
5 Second Minimum
Instantaneous Settings not recommended
Current Imbalance
Measure of allowable phase current
Imbalance
20%-30% For motors with Service Factors of 1.15 or greater
Current Imbalance Time (Sec)
Delay Time in which Imbalanced Current
Must be Present Before Chiller Trips
5 seconds Minimum
Instantaneous Settings not recommended
35 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Recommended Chiller Micro/Motor Protection Settings
Parameter Function Recommended Setting for best PQ performance
Note
Auto Restart Option
Restarts chiller after shutdown
Enable Always consider auto start features or auto start up of
an adjacent chiller upon the fault of the unit that is
running.Single Cycle
DropoutDetects Loss of Power
for a Single CycleDisable Parameter Not available on
all chiller systems
PB (Time) Phase Balance Relay 5 Seconds Instantaneous Settings not recommended
For IQ500 Motor
Protection relay:
DIP Switches 5 & 6
To prevent chiller from tripping 6 seconds after a steady state current
imbalance of 50%
Set 5 and 6 to 1 and 1
Set other protection relays for same general function
For IQ 1000II Motor
Protection Relay:
Set point 32
Trip/Delay Phase Unbalance Function
I2T Trip Set other protection relays for same general function
36
Example Case Studies
37 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Case Study MatrixCase No.
Customer Type Utility Chiller Manufacturer
Power Quality Issue(s)
1 Government Building(Nation Archives)
PEPCO Confidential Voltage SagsMomentary Interruptions
2 Bank City Public Service
Trane Voltage SagsMomentary Interruptions
3 Semiconductor Manufacturer
South East Asian Utilty
Confidential Voltage SagsMomentary Interruptions
4 General Manufacturing Iberdrola(Spain)
McQuay Voltage SagsMomentary Interruptions
5 General Manufacturing Lincoln Electric
McQuay Voltage Unbalance
6 General Manufacturing Louisville Gas and Electric
Carrier Voltage SagsMomentary InterruptionsVoltage Unbalance
7 Cosmetics Manufacturing
SRP York Voltage SagsMomentary InterruptionsVoltage UnbalanceHarmonics
8 General Manufacturing PSE&G Not disclosed Voltage SagsMomentary Interruptions
9 Commercial High Rise FPL Trane Voltage Unbalance10 Television Station FPL Trane Voltage Unbalance11 Community College FPL Trane Voltage Unbalance12 Church Memphis
Light, Gas and Water
Not disclosed Induced Flicker
38 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Case Study Number 1: Chiller Voltage Sag/Momentary Outage Problems at Government Building Threatens Document Storage(summarized)
• Upgraded to new state of the art microprocessor controlled chillers
• Chillers found to trip off line 10 seconds after voltage sag event had cleared
• EPRI Worked with PEPCO to diagnose problem
39 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Shutdown Sequence
2K2X “Ice Cube”
Relay
Interface toMicroprocessor
40 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Shutdown Sequence
2K2X “Ice Cube”
Relay
41 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Recommendations
•Add Voltage Conditioner, such a a Constant Voltage Transformer (CVT) on Control Power Circuit
42 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Case Study #2: Chiller Control Panel Causes Shutdowns at Industrial Plant
• EPRI has Conducted Tests on Chillers at Suppliers Cooperate Engineering
• Tests Revealed Sensitive Relay in Compressor Starter Circuit
• Dropping out for deep sags and interruptions is typically preferred by customers to lower the likelyhood of mechanical damage
Single 2kVA Control Power Transformer Feeds Control Power and Oil Heater
43 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Vulnerable Board Mounted “Ice Cube”relay, 1R drops out at about 69% of nominal, 1 cycle.
The Sensitive Component
44 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
• Move Heater Load Above Control Power Transformer and Install a CVT (as Shown).
• Hold in down to 40% Vnominal if sized properly
Recommendations: Option 1 CVT
CVT
45 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Recommendation Option 2: VDC
• Option 2:Utilize a VDC to compensate down to 37% of nominal, but drop out for low voltages or interruptions.– 6T model holds in down
to 37% of nominal
VDC
46 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Voltage Unbalance Case Studies
• Background For Voltage Unbalance Case Studies. All involved Trane chiller systems and have been provided by Florida Power and Light.
• Trane worked with FPL to implement to solve voltage unbalance incompatibilities between the utility system and the chiller control system.
47 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Trane Control Panel Review
Panel Name Unbalance Tolerance
Black Classic 15% Current
UCP1 Dip Switch Selectable:- 15% Current if Enabled and chiller loaded >= 80%- Ignored if disabled (uses temperature sensors)
UCP2 Originally: Two settings,Factory Default: 15 % Current or 25% Current if selectedCurrently: 30 % non-defeatable Current
48 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Case Study Number 3: Commercial high rise.
• Utilized Trane Chiller with early version of UCP2 control panel• Tripped at 10 to 15 % Current Unbalance• Trane adjusted trip calibration to 25%• No Customer Complaints of False Trips Since Change was
implemented.
49 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Case Study Number 4:Television Station.
• Utilized early version of UCP2 control panel. • Measurements showed that chiller tripped at 2% voltage
unbalance, 13 to 16 percent current unbalance• Trane installed new control panel to change unbalance trip to
30%.
50 Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved. PQIG 2009
Review of Recommendations
• Protect Chiller Control Circuits from Voltage Sags– Relays, Motor Starter
Contactors• Make sure that Micro settings/or
hardwired controls have appropriate delays for detecting loss of voltage, current, and voltage unbalance
• Make sure that Micro settings are adjusted to allow for voltage unbalances of up to 3% and current imbalance from 18% to 30%.
• Set Chiller for Autorestart option if allowable.
• Remember to consider other loops such as chilled water, heat rejection, and airside in solution.
L1
L2
L3N
415/230Vor 6.6kV3 Phase
FU
M
CPT1
MSMS
ChillerController Motor
ProtectorRelay
M1
MC1
MC1
FU
M2
MC2
MC2
FU
M3
MC3
MC3
FU FU
FU
PLC
CPT2
CPT3 CPT4 CPT5
Chiller C
ompresser
Motor and Controls
Process Cooling
Water System
Controller
Chilled
Water Pumps
Condenser Water
Pumps Cooling
Tower Fans
CPT3Power
Conditioner
CPT4Power
Conditioner
CPT5Power
Conditioner
CPT2Power
Conditioner
CPT1Power
Conditioner
HOA HOA HOA
CR1
CR1