Wall-Hung On-Demand VICTORIA 20/20F Combination Water Heater Radiant Heating Technologies, Inc. PO Box 13217, Burton, WA 98013 253-238-1706 / 866-682-3078 / fax 253-238-0650 www.radiantheattech.com

description

Libretto tecnico della caldaia ROCA Victoria 20

Transcript of ROCA Victoria - manuale Tecnico

Page 1: ROCA Victoria - manuale Tecnico

Wall-Hung On-Demand

VICTORIA 20/20FCombination Water Heater

Radiant Heating Technologies, Inc.PO Box 13217, Burton, WA 98013

253-238-1706 / 866-682-3078 / fax 253-238-0650www.radiantheattech.com

Page 2: ROCA Victoria - manuale Tecnico

Victoria wall-hung boilers Heating training centres

Table of contents

Table of contents Nomenclature and services Overall view Overall dimensionsPre-plumbing jig and Wall Spacing FrameHydraulic test Installation recommendations Start-up recommendations (I)Start-up recommendations (II) Start-up recommendations (III)Start-up recommendations (IV) Automatic air vent KitPressures of gasElectronic PCB Electrical wiring Room thermostat connection Fuse change Connection of Victoria 20 + V3V kitMain components (l)Main components (ll)Control panel Overall view of Hydroblock Hydroblock components Hydroblock operation Hydroblock and pump Water loop Central Heating mode operation DHW mode operation Outlines hydraulic Victoria 20 (Heating) 3-Way Valve Outlines hydraulic Victoria 20/20 (Heating)Outlines hydraulic Victoria 20/20 (Sanitary)

Outlines hydraulic Victoria 20/20 F (Heating)Outlines hydraulic Victoria 20/20 F (Sanitary)Outlines hydraulic Victoria 20/20 T (Heating) Outlines hydraulic Victoria 20/20 T (Sanitary)Stored DHW service Overheat thermostat Flame safeguard rectification system (l)Flame safeguard rectification system (ll)Chimney “pull” safety :20/20 Chimney “pull” safety :20/20F and TBurnerCombustion chamber Kit valve G20 and G25Cross-section of gas valve Gas changeover Kit Components of the boilers F and TFlue duct kit (l)Flue duct kit (ll)Flue duct kit (III)Flue duct kit (IV)Flue duct kit (V)Flue duct kit (VI)Flue duct kit (VII)Timer connectionsProgramming instructions (l)Programming instructions (ll)Programming instructions (lll)Control DIP switches MaintenaceFactory settings Fault codes

1 2 3 4 5 6 7 8 91011121314151617181920212223242526272829303132

33343536373839404142434445464748495051525354555657585960616263

1

Page 3: ROCA Victoria - manuale Tecnico

Victoria wall-hung waterheaters

CE marked. These waterheaters comply with the requirements of the Electromagnetic Compatibility Directive 89/336/EEC, the Gas Appliance Directive 90/396/EEC, the Low Voltage Directive 73/23/EEC, and the Efficiency Directive 92/42/EEC .

Victoria 20/20 F

Overall view

2Heating training centres

Victoria wall-hung boilers

CSA CERTIFIED FOR USA and CANADA.

Page 4: ROCA Victoria - manuale Tecnico

Victoria wall-hung waterheaters

8.4" / 213mm

12.6

" / 3

20m

m

26.8

" / 6

80m

m

17.7" / 450mm13.2" / 335mm

3.9" / 100mm

Victoria 20/20 F

42" / 1066mm

3Heating training centres

Overall dimensions

Page 5: ROCA Victoria - manuale Tecnico

Victoria wall-hung waterheaters

Pre-plumbing jig and wall Spacing Frame

Wall-mounting bracket, supplied with the pre-plumbing jig

Distance from the wall: 5.5" / 140 mm

Gap between connections: 2.36" / 60mm

PMI with no cocks PMI with cocks PMCA with cocks Wall Spacing Frame (1.38"/35 mm)

4Heating training centres

Page 6: ROCA Victoria - manuale Tecnico

Victoria wall-hung waterheaters

Hydraulic test

The PMCA is supplied with the 3/4” cap nut.The PMI could do without the pump; in thiscase, the mains pressure and connection should be used for filling the system. Monitor the operation through the necessarycontrols: Pressure gauge and safety valve.

5

Mains water

Pump

3/4” cap nut

Pump

Heating training centres

Page 7: ROCA Victoria - manuale Tecnico

Victoria wall-hung waterheaters

Installation recommendations

Observe current regulations and minimum distance from flammable materials.

Please refer to the Instructions delivered with the waterheater

6Heating training centres

15.7" /

59" /

Page 8: ROCA Victoria - manuale Tecnico

Victoria wall-hung waterheaters

Start-up recommendations (l)

Please refer to the instructions which are delivered with the waterheater.Power supply 230V Live/Neutral. (Do not reverse polarity).Room thermostat connection.Work on the pump motor shaft to unlock it if it were jammed.Manually vent the boiler.Fill the primary loop (if no DHW cylinder has been installed) slowly until the pressure reaches 14.5 - 29 PSI / 1-2 bar. (If a DHW cylinder has been installed, then fill the secondary loop first). Open the DHW circuit for it to fill up and vent With the gas inlet cock still closed, program the Heating mode. The boiler will perform a lighting cycle and will then lock out under code 60-70-90. Leave it like that for five minutes so that the pump, which is still running, can help vent the circuit. Next, check the pressure level and top up if it has dropped to 14.5 PSI / 1 bar. Open the gas inlet cock, reset the system (code 60-70-90) and the boiler will start operating. Allow the waterheater to operate in the Heating mode for ten minutes, during which check that all radiators warm up. Should one radiator fail to warm up, bleed the air in it. But if it still does not warm up, then the flow rates in all radiators should be balanced, always optimizing the pump performance curve (flow rate/pressure) through its speed selector control.Open the DHW tap with the highest flow rate in the house. The waterheater will operate for ten minutes continuously at full output (79,366 Btu / 20,000 kcal/h). If the flue spillage detection thermostat does not trip, that means that the removal of flue gases is correct. If a gas meter is available, check the gas input rate, as indicated in the waterheater Instructions

7Heating training centres

Page 9: ROCA Victoria - manuale Tecnico

Victoria wall-hung waterheaters

Where a water column is available, connect it to the gas valve pressure test point and check the working pressure with the waterheater operating at full output (79,366 Btu / 20,000 kcal/h).Program the Heating mode again. Program the DHW mode again. For a higher level of comfort, particular ly where substantial pressure variations in the water supply occur, set the program close to the draw-off temperature.Remove the water column, replace the plug and washer, start the system, and using soapy water check the whole circuit for gas tightness.Ensure that the waterheater room has a proper ventilation and air renewal system.

Instruct the user on the following points:Recommend him/her to read the User’s Instructions.Instruct him/her on how to program the Heating and DHW temperature and the room thermostat (if any).Instruct him/her on how to fill and/or top up the Heating system.Demonstrate how the fault codes work for insufficient gas (60-70-90 and 40-80-90) and how to reset (R) after opening the gas inlet cock or changing the gas cylinder.Recommend him/her to turn the selector switch to the “R” position whenever a red fault lamp lights up.If the red light appears two or three consecutive times, tell the user to write down the number of the temperature LEDs which light up and then to notify the nearest Service Center or Installer.Train him/her on the various safety devices, recommendations and maintenance operations specified in the waterheater Instructions.

8Heating training centres

Start-up recommendations (lI)

Page 10: ROCA Victoria - manuale Tecnico

Victoria wall-hung waterheaters

It should be ON

It should be between 14.5 and 29 PSI / 1 and 2 bar Fill and/or top up if pressure is less than 14.5 PSI / 1 bar

9Heating training centres

Start-up recommendations (lII)

Page 11: ROCA Victoria - manuale Tecnico

Victoria wall-hung waterheaters

Set the minimum speed possible to reduce system rumbling as muchas possible. See the pump performancegraph (flow rate/pressure).

Bleed air and/or drain

Turn

10Heating training centres

Start-up recommendations (lV)

Page 12: ROCA Victoria - manuale Tecnico

Victoria wall-hung waterheaters

Automatic air vent Kit

11Heating training centres

Page 13: ROCA Victoria - manuale Tecnico

Victoria wall-hung waterheaters

Pressures of gas

Gas Inlet Pressure:G20(GN): 20 mbarG30(GB): 28 ÷ 30 mbar G31(GP): 37 mbar

12Heating training centres

Gas input rates and pressures with Natural Gas (G20) are for 3a L.H.O. = 9,200kcal/m , density = 0.62, 15 °C and 1,013mbar.

(*) measured under standard conditions (15°C and 1013mbar) (**) burner setting pressure

2.391.460.87

853614

0.830.570.31

1.030.710.38

270140 47

341158 52

Heat Output 79,366 Btu/20,000 Kcal/h 47,620 Btu/12,000 Kcal/h

27,778 But/7,000 Kcal/h

3Gas Input Rate (m /h)(*)G20 G30 G31

Pressure (mmwg) (**)G20 G30 G31

Page 14: ROCA Victoria - manuale Tecnico

Victoria wall-hung waterheaters

Electronic PCB

RH electrode LH electrode

TimerTransformer(230V/12V)

Azu

l

Azu

l

Azu

l

Azu

l

Azu

l

Azu

l

Mar

rón

Mar

rón

Gri

s

Gri

sN

aran

ja

Roj

o

220Vca Bla

nco

Gri

s

Tie

rra

amar

illo

Gri

s

Nar

anja

Roj

o

FlowSwitch

To the mains

Ignition transformer (18,000V)

Earth conn.(to chassis)

Room Stat(option) Low Voltage Wiring

Conexión relojprogramador, en laplaca electrónica

5 Vcc

Clixon Cortatiros: 5 VccClixon intercambiador: 12V

Sondas: 5 Presostato: 5

12 Vcc220 Vca

220VcaV Am

arill

oM

arró

n

Azu

l

220Vca

Flame rod

230Vca

Fuse3.15 A

Neutral

Live Earth conn.(to mains)

Pump and Fan Wiring

Timer connection onthe electronic PCB

5Vcc

Flue Spillage Limit Thermostat: 5VdcOverheat Thermostat: 12V

Sensors: 5Vdc Pressure switch: 5Vdc

12Vcc230Vca

230Vca

230Vca

13Heating training centres

Blu

eYe

llow

Bro

wn

Whi

te

Blu

e

Blu

e

Bro

wn

Gre

y

Bro

wn

Gre

yO

rang

eB

lue

Red

Blu

e Gre

y

Ora

nge

Red

Blu

elE

arth

- y

ello

w

Blu

e

Gre

y

20 T

h so

leno

id v

alve

Kit

pow

er s

uppl

y

3-w

ay v

alve

Neu

tral

- F

an (

F/T

)

Neu

tral

- P

ump

Live

- P

ump

Live

- F

an (

F/T

)

Com

mon

- S

olen

oidV

12 T

h so

leno

id v

alve

Saf

ety

sole

noid

val

ve

DH

W s

enso

r

Ove

rhea

t the

rmos

tat

CH

sen

sor

Flu

e sp

ill.d

etec

t. th

. Or

Pre

ssur

e sw

itch

in F

&T

O

verh

eat t

herm

osta

t E

arth

con

nect

ion

Pow

er s

uppl

y

Ear

thS

igna

l

Gre

en

7 T

h so

leno

id v

alve

Page 15: ROCA Victoria - manuale Tecnico

Victoria wall-hung waterheaters

Electrical wiring

Low Voltage Wiring

15.79" / 400 mm

Earth connection to chassis

Solenoid valves connector

Indicator lights, sensors, and pressure switch connector

21.65" / 550 mm

4.72"/120 mm

5.9"/150 mm

9" / 230 mm

7 Th Solenoid valve 12 Th 20 Th Safety

Flue spillage detection thermostat or pressure switch (F and T) DHW sensor

Overheatthermostat

CH Sensor

Note:The exhaust fan, the pump and the flow switch are fed by other connectors (see “Electronic PCB” sections)

3.94" / 100 mm

7.09"/180 mm

7.09"/180 mm

3.15"/80 mm

14Heating training centres

Page 16: ROCA Victoria - manuale Tecnico

Victoria wall-hung waterheaters

Room thermostat connection

Thermostat with anticipatory resistor Thermostat without anticipatory resistor

15

Fuse Fuse

Main power supply

Neutral (N)Room thermostat with anticipatory resistor

Remove jumper

N T1 T2 T1 T2

Heating training centres

Page 17: ROCA Victoria - manuale Tecnico

Victoria wall-hung waterheaters

Fuse change

Room thermostatconnection

Mains powersupply

Neutral

Live

Earth connection(to the mains)

Earth connection (to chassis)

Thermostat jumper is obligatory when no room thermostat has been fitted (it is supplied with it)

Fuse of 3.15 Amps Roca genuine spare only. The only fuse in the boiler.

It can be accessed after removing the lower LH cover in the waterheater and then pulling out the cover holding it.

16Heating training centres

Page 18: ROCA Victoria - manuale Tecnico

3-way valve

Supplied

Supplied

Cables to be supplied by others

R 33kW

Magnetic detector

DHW Sensor

Connection of Victoria 20 + V3V kit

c2

B1

A3

877

62

B2

B3

B4

A1

1

230V

Victoria 20

12

34

56

78

910

11

12

13

14

15

1 2 3 4 5 6

Victoria wall-hung waterheaters

V3V

17Heating training centres

N F

Stored

Page 19: ROCA Victoria - manuale Tecnico

Victoria wall-hung waterheaters

Compact casingTop fixing: Locating pins Bottom fixing: Screws Removable decor. lid “Spring-effect” flanges

Color of casing WHITE - RAL 9016Stages of Output:27,778 Btu / 7,000 kcal/h 47,620 Btu / 12,000 kcal/h 79,366 Btu / 20,000 kcal/hAdjustable for Heating

Net efficiency: 91.7% , as per Efficiency Directive 92/42/CEE

Main components (I)

18Heating training centres

CSA CERTIFIED EFFICIENCY: 87%

18

Page 20: ROCA Victoria - manuale Tecnico

Victoria wall-hung waterheaters

Expansion Vessel Fill pressure: 10.88 PSI / 0.75 bar Butyl diaphragm and nitrogen charge Total/useful capacity: 2.1 gal/1.2 gal - 8 litres/4.5 litres

Draught Diverter Flue socket collar Ø 5" / 127 ID Flue duct Ø 4.9" / 125 OD

Burner Stainless steel. 13 “becks” “Clover-like” flame on the ends for interlighting

Ignition electrodes and flame rod Burner Centred

Control panel Direct access to the boiler wiring and fuse (3.15A). Fault codes in Heating temperature leds.Ignition transformer on electronic board (18,000V)

Flue Spillage Limit Thermostat Set at: 149°F / 65°C

Heat Exchanger Bithermal. 6 steps in DHW and Heating. Made of copper and high-temperature aluminium paint

Combustion Chamber Compact. Side fixing rods

Main components (II)

19Heating training centres

Page 21: ROCA Victoria - manuale Tecnico

Victoria wall-hung waterheaters

DHW Temp. Selector Temperature range: 104°F/40°C ÷ 140°F/60°C

CH Temp. Selector Temperature range: 104°F/40 °C ÷ 194°F/90 °C

Service Changeover Selector Heating and DHW / DHW only / Reset / Off

TimerPlanned position in the supplied kit. Digital

Access cover forexternal connection Supply Voltage: 230V Input fuse: 3.15 Amps Room Thermostat Power Supply (optional): 230V

Casing Fixing Screws Bottom only. Top - locating pins

Access Cover to Internal Wiring All boiler’s internal wiring

Indicator leds for: Service, Voltage, Faults

Pump3-speed type 2.6µF, 450V Capacitor

Central Heating Temp. Leds Fault codes

Pump Speed Selector (I, II and III)

Mechanical Pressure Gauge Recommended

Fill Pressure: 21.8 PSI/1.5 bar

Pressure Relief Valve Set at 43.5 PSI/3 bar. Removable

Control panel

20Heating training centres

Page 22: ROCA Victoria - manuale Tecnico

Victoria wall-hung waterheaters

Overall view of Hydroblock

21

Set in the Hydroblok serviceable if captive pin is removed

Flow Regulator

Mains Water Inlet Filter Use Allen 4 key or Screwdriver to open

By - pass

Mains Water Inlet

Mains Water Inlet (3/4”)

CH Return (3/4”)

Pressure ReliefValve Discharge (1/2”). Route to a drain

2 Chassis Fixing Screws Allen 4

Outlet to the Heat Exchanger

Connection to the pump

Pressure ReliefValveSet at 3 bar Serviceable and rotary

Magnetic Detector

By - pass, Vent and Drain Cock Tight: Fixed by - passLoose: Air vent or drain

Fill Point Valve

Limitation: 3.7gal/14 l/min.

4

Mains water

By - pass pipe Inlet

60 mm

Heating training centres

Page 23: ROCA Victoria - manuale Tecnico

Victoria wall-hung waterheaters

Hydroblock components

22

Magnetic Detector

M4 x 12

Ø 8 ID x Ø 1.9

Ø 23 ID x Ø 3.6

Fill Point Valve Pin Ø 2 x 16 mm long

Fill Point Valve O-rings

Mains Water Inlet Filter Use Allen 4 key to open

Water Filter O-ring Ø 13 ID x Ø 2

Ø 7.2 ID x Ø1.9 and Ø 2.6 ID x Ø1.9

Mains Water Inlet

Magnetic Float Magnet material: Nd powder Maximum Temperature: 302°F/150°CMin. DHW Collection: 2.9 PSI/0.2 bar and 0.79gal/3 litres/min.

Flow Regulator Limitation: 3.7gal/14 l/min

By-pass O-ring. Ø 4.2 ID x Ø 1.9

Anti-friction Washer for Pressure Relief Valve Ø 25,5 ID x Ø 28,6 OD x 1

Pressure Relief Valve Set at 3 bar Serviceable and rotary

Pressure Relief Set Pin Ø 3 x 16 mm long

Detector O-ring

By - pass, Vent and Drain Cock

Allen 4 Bolts

Pump O-ring

Heating training centres

Page 24: ROCA Victoria - manuale Tecnico

Victoria wall-hung waterheaters

Magnetic Detector CH Return To pump volute and heat exchanger

CH Circuit Fill Point

Mains Water Inlet

By - pass Circuit Inlet

Discharge to a drain

Drain and Vent

To the DHW Heat Exchanger

Hydroblock operation

23Heating training centres

Page 25: ROCA Victoria - manuale Tecnico

Hydroblock and pump

160014.0012.001100800600

Victoria wall-hung waterheaters24

0,40,2

6

5

4

3

2

1

Pressure Gauge Connection to Pump Volute

O-ring for fixing the Pressure Gauge. Ø 9.52 ID x Ø 1.78

Mechanical Pressure Gauge Fixing

To Heat Exchanger

Fixing the body to the volute Allen 5 M6 x 20

Fixing the Pump to the Hydroblok

O-ring Ø 23 ID x Ø 3.6

Return to radiators

Mains Water Inlet

Mechanical Pressure Gauge

Unblocks of the pump

PRIMARY HEAD

0,6 0,8 1,0 1,2 1,4 1,63V (m /h)

H (m.w.g.)

Heating training centres

Page 26: ROCA Victoria - manuale Tecnico

Victoria wall-hung waterheaters

Water loop

Expansion VesselFill pressure: 10.88PSI/0.75 barButyl diaphragm and nitrogen charge

Total/useful Capacity: 2.11gal/1.2 gal - 8 litres/4.5 litres

Heat Exchanger 6 steps in Heating:3 for flow and 3 for return Primary capacity: 0.08 gal/300 cm³ Secondary capacity: 0.71 gal/270 cm³

Domestic Cold Water Inlet Pipe OD 0.55"/14 mm

DHW Sensor Contact-type.

DHW Outlet Pipe OD 0.55"/14 mm

Hydroblok

Air vent Kit

CH Sensor Contact-type

Overheat Thermostat Manual reset. Set at 221°F/105°C

CH Return Pipe Ø OD 0.71"/18 mm

CH Flow Pipe Ø OD 0.71"/18 mm

Mechanical Pressure Gauge

Pump 3-speed type.

25Heating training centres

Page 27: ROCA Victoria - manuale Tecnico

Victoria wall-hung waterheaters

Expansion Vessel Fill pressure: 10.88PSI/0.75 barButyl diaphragm and nitrogen charge Total/useful Capacity: 2.11gal/1.2 gal - 8 litres/4.5 litres

Heat Exchanger 6 steps in Heating: 3 for flow and 3 for return Primary capacity: 0.08 gal/300 cm³ Secondary capacity: 0.71 gal/270 cm³

Air vent Kit

CH Sensor

CH Flow Pipe Ø OD 0.71"/18 mm

To radiators Maximum Operating Pressure: 43.5 PSI/3 bar

Central Heating mode operation

26

Temp. Res. kW 104°F/40°C 5.330 122°F/50°C 3.605 140°F/60°C 2.490 158°F/70°C 1.753 176°F/80°C 1.256 194°F/90°C 0.915

Heating training centres

Page 28: ROCA Victoria - manuale Tecnico

DHW mode operation

Heat Exchanger 6 Steps in DHWPrimary capacity: 0.08 gal/300 cm³ Secondary capacity: 0.71 gal/270 cm³

Expansion Vessel Fill pressure: 10.88PSI/0.75 barButyl diaphragm and nitrogen charge Total/useful Capacity: 2.11gal/1.2 gal - 8 litres/4.5 litres

Temp. Res. kW 104°F/40°C 5.330 122°F/50°C 3.605 140°F/60°C 2.490

DHW Sensor

Mains Water Inlet Pipe OD 0.55"/14 mm

Outlet to draw-off points OD 0.55"/14 mm

Mains Water Inlet

Maximum operating pressure: 7 bar

Victoria wall-hung waterheaters27Heating training centres

Page 29: ROCA Victoria - manuale Tecnico

3-way valve Victoria wall-hung waterheaters

Sanitary way

Heating training centres

HeatingWay

28

Page 30: ROCA Victoria - manuale Tecnico

Outlines hydraulic Victoria 20/20 FVictoria wall-hung waterheaters

Stopped way

29Heating training centres

HeatingWay

Page 31: ROCA Victoria - manuale Tecnico

Outlines hydraulic Victoria 20/20 FVictoria wall-hung waterheaters

Sanitary way

30Heating training centres

Page 32: ROCA Victoria - manuale Tecnico

Stored DHW service

Energized relay.Signal to PCB and

pump stops(1 minute)

De-energized relayEnd of signal toPCB and pumpstop (1 minute)

3-way valve.Shuts off CH and

opens cylinderreturn (35 seconds)

3-way valve Shuts offcylinder return andopens CH return

(35 seconds)

Pump starts up Heating YesPermanent pump

start-up

No HeatingPump start-up

(2 minutes)

Burner ignition

Burner ignitionPump shutdown

Call for DHW from cylinder End of call for DHW from cylinder

Thermostat closes Thermostat opens

Victoria wall-hung waterheaters31Heating training centres

Page 33: ROCA Victoria - manuale Tecnico

Overheat Thermostat

Open during service Open before light-up

Display of fault code50, 60, 70, 90, and red Led

Display of faultcode 50, 60, 90,

and red Led

Gas supply cuts off Gas supply cuts offLockout

Fault corrected

Fault corrected

Thermostat Reset Thermostat Reset

Boiler Reset

Press red reset button Press red reset button

Control knob in R position

Yes Yes

No No

Operation of the Overheat Thermostat

Service restored

Victoria wall-hung waterheaters32Heating training centres

Page 34: ROCA Victoria - manuale Tecnico

Flame safeguard rectification system (I)

Yes

Yes

Yes

No

No No

No

Light-up

Boiler Reset

Lockout

• End of spark ignition• Service available

Control knob in “R” position

• End of spark ignition• Safety solenoid valve closes• Display of fault code 60, 70, 90, and red Led

Call for service (Light-up)

Spark ignitionIgnition

electrodes

Sadety solenoidvalve opens(gas inlet)

1st solenoid valve opens

(7 Th)

2nd solenoidvalve opens

(12 Th)

Attempt to light up

Light up in less than

4 secs

Light upin less than

1 sec

Fault corrected

Lights upin less than

2 secs.

Service now restored

1st solenoid valve opens (7 Th)

Yes

Victoria wall-hung waterheaters33Heating training centres

Page 35: ROCA Victoria - manuale Tecnico

Yes

Yes

Yes

No

No No

No

Light-up

Boiler Reset

• End of spark ignition• Service available

Control knob in “R” position

• End of spark ignition• Safety solenoid valve closes• Display of fault code 40, 80, 90 and red Led

Interruption of service

Spark ignitionIgnition

electrodes

Safety solenoidvalve opens(gas inlet)

1st solenoidvalve opens

(7 Th)

2nd solenoid valve opnes

(12 Th)

Light-up process

Lights upin less than

4 secs

Lights upin less than

1 secFault

corrected

Light upin less than

2 secs.

Service now restored

1st solenoid valve opens (7 Th)

Yes

Note: If fault code 40-80-90 lights up for any of the following reasons:

• Sensor lead splits• Sensor rubbing against earth connection• Bad earth connection contact

Then the process would be as follows:The flame does not blow out. Sparking begins for 7 seconds.

Boiler operation switches from 20 Th to 12Th and 7 Th until it goes into complete lockout.

Victoria wall-hung waterheaters

Lockout

34

Flame safeguard rectification system (II)

Attempt to relight

Heating training centres

Page 36: ROCA Victoria - manuale Tecnico

Chimney “pull” safety 20/20 F Victoria wall-hung waterheaters

Si

Yes

No

No

Lockout

Light-up

Stop

Display of fault code40,50,80,90 and red Led

Service now restored

Waiting for service call

Interruption of flue gas removal

(insufficient chimney “pull”)

Pressure in flue pipe lower

than (1)

Automatic pressure switch resetting

Pressure in flue pipe is higher than (2)

Fault corrected

in less than 3 minutes

Call service

Si

Si

Yes

Yes

Yes

No

No

Pressureswitch closed

Pressure switch open

Fault corrected

Si

Si

Locked out againPre-purge

Exhaust fan starts

Display of fault code60, 80, 90

and red Led

Exhaust fanwill run for30 seconds

Boiler DIP switch checking whether the

pressure switch is closed(pressure in flue pipe > (2)

No

Boiler DIP switch checking whether the pressure switch

is open (pressure in flue pipe < (1)

Exhaust fan stops for1 second

35Heating training centres

(1) 12 mbar in VICTORIA 20/20 T 17 mbar in VICTORIA 20/20 F(2) 15 mbar in VICTORIA 20/20 T 19,5 mbar in VICTORIA 20/20F

Page 37: ROCA Victoria - manuale Tecnico

Burner

Ignition Sequence:2 seconds at 7 Th.4 seconds at 12 Th.1 seconds at 7 Th

Burner Fixing to the Gas Valve. Allen 4 x 15

Ignition Electrodes Centered on the middle burner 5mm higher and a 4mm electrode gap

Gas Valve Pressure Test Point Bracket

Baffle plate

Flame Sensing Rod Average current: Mín: 3µA, Med: 3,6 µA, Máx: 4,1µA13 becks

Material: Stainless Steel

Victoria wall-hung waterheaters36Heating training centres

Page 38: ROCA Victoria - manuale Tecnico

Combustion chamber

Do not start the waterheater until the insulation panels have been properly assembled. For optimum operation it is essential that these insulation panels be in good condition.

Victoria wall-hung waterheaters37

Side Insulation Panels. Material: Ceramic Fibre

CompactCombustion Chamber

Threaded Rods for Chassis Fixing8.58"/218 mm long x Ø 0.24"/6mm

M5 Set NutsFor fixing the burner baffle plate

Front Insulation Panels. Material: Ceramic Fibre

Side Tabs. Fold them after fitting Side Insulation Panels

Heating training centres

Page 39: ROCA Victoria - manuale Tecnico

Kit valve G20 and G25Victoria wall-hung waterheaters

38

Chassis FixingBracket.

27,778 Btu/7,000 kcal/h

Solenoid Valve.

47,620 Btu/12,000 kcal/h

Solenoid Valve.

27,778 Btu/20,000 kcal/h

Solenoid Valve.

Safety Solenoid Valve.

Aluminum Profile for Burner Injector Holder

Solenoid Valve Assembly

Gas Governor Natural Gas only

Control Range: 0.25 ÷ 0.36 PSI / 17 ÷ 25 mbar

Burner Setting Pressure Device

Gas Supply Pressure Test Point G20(GN): 0.29 PSI/20 mbar. G30(GB): 0.41÷ 0.44PSI/28 ÷ 30 mbar. G31(GP): 0.54PSI/37 mbar

Heating training centres

Page 40: ROCA Victoria - manuale Tecnico

Cross-section of gas valveVictoria wall-hung waterheaters

39

Stages of Output Bore Size

27,778 Btu/7,000 kcal/h

Solenoid Valve.

47,620 Btu/12,000 kcal/h

Solenoid Valve.

79,366 Btu/20,000 kcal/h

Solenoid Valve.

Aluminum Profile for Burner Injector Holder

Burner Fixing.

To PressureTest Point

Valve GasketMaterial: Cork + Nitrile

Gas Valve Body Material: Aluminium

Solenoid Assembly Gasket Material: Cork + Nitrile

Solenoid Valve Assembly

Heating training centres

Page 41: ROCA Victoria - manuale Tecnico

Gas changeover kit

Any adjustments and/or settings must be carried out by a qualified technician

Victoria wall-hung waterheaters

Kit G30 / G31Kit G20 / G25

40

Natural Gas Kit (To convert a Propane/Butane Gas waterheater into Natural Gas)

Propane/Butane Gas Kit (To convert a Natural Gas waterheater

into Propane/Butane Gas)

Heating training centres

Page 42: ROCA Victoria - manuale Tecnico

Components of the waterheaters F Victoria wall-hung waterheaters

41

Pressure Switch Setting Range for VICTORIA 20/20F: 17 ÷ 19.5 mm.w.g.

Socket for connection to specific flue duct Outlet Ø 2.36"/60mm

Pressure Switch Connecting Pipes

Exhaust Fan r.p.m.: 2720Average current : 0.41A

Heating training centres

Page 43: ROCA Victoria - manuale Tecnico

42

Kit 140040030-03 for F waterheaters (supplied as standard)

Flue duct kit (I)Victoria wall-hung waterheatersHeating training centres

Page 44: ROCA Victoria - manuale Tecnico

Flue duct kit (II)Victoria wall-hung waterheaters

43

Configuration C12: Room-sealed waterheater. Horizontal concentric flue pipe. Flue gases discharged directly into the atmosphere. Exhaust fan located above the combustion chamber.

Heating training centres

Victoria 20/20 F (C - 12)

L

Ø 4

.92"

/125

L £ 19.69ft/6 m

Ø 3.94"/100mm

Ø 1

00 m

m

L

M

L + M £ 9.84ft/3 m

Page 45: ROCA Victoria - manuale Tecnico

Flue duct kit (III)Victoria wall-hung waterheaters

44

Configuration C42: Room-sealed waterheater. Horizontal concentric flue pipe connected to a twin common shunt or stack. Exhaust fan located above the combustion chamber.

140040030-03 Configurations C12 / C42: Directional, concentric horizontal flue pipe kit with Ø 60/100 damper. Quick connect coupling. 1m horizontal flue length. SUPPLIED AS STANDARD. 140040061-01 Configurations C12 / C42: Directional, concentric horizontal flue pipe kit with Ø 60/100 damper. Quick connect coupling. 1m horizontal flue length and 0.2m vertical flue length. 140040084-00 Configurations C12 / C42: Directional, concentric horizontal flue pipe kit with Ø 80/125 damper. Quick connect coupling. 1m horizontal flue length.

Heating training centres

Victoria 20/20 F (C - 42)

7.87"/0.2 m < L £ 9.84ft/3 m

Ø 3

.94"

/100

mm

L

Page 46: ROCA Victoria - manuale Tecnico

Flue duct kit (IV)Victoria wall-hung waterheaters

45

Configuration C82: Room-sealed waterheater. Single, horizontal flue pipes. Fresh air intake. Flue gas outlet to a standard common shunt. Exhaust fan located above the combustion chamber.

140040039-02 Configuration C82. Directional, twin-pipe horizontal flue kit with Ø 80 damper. Quick connect coupling. 1m horizontal flue length for both runs.

Heating training centres

Victoria 20/20 F (C - 82)

With no diaphragm: 13.12 ft/4 m < L + P £ 32.8 ft/10 mWith diaphragm Ø 1.8"/46 mm: L + P £ 13.12 ft/4 m

Ø 3

.15"

/80

L P

Ø 3

.15"

/80

Diaphragm Ø 1.8"/46 mm

Page 47: ROCA Victoria - manuale Tecnico

Flue duct kit (V)Victoria wall-hung waterheaters

46

Configuration C32: Room-sealed waterheater. Vertical concentric flue pipe. Flue gases discharged directly into the atmosphere. Exhaust fan located above the combustion chamber.

140040034-03 Configuration C32. Directional, concentric vertical flue pipe kit with Ø 60/100 damper. Quick connect coupling. 1m vertical flue length. 140040059-00 Optional vertical concentric accessory in the C32 configuration for vertical outlet to the roof.

Heating training centres

With no diaphragm: 7.87ft/2.4 m < L £ 36.1"/11 m

With diaphragm Ø 1.77"/45 mm: 1.4 m < L £ 7.87ft/2.4 m

Ø 3.94"/100mm

Ø 4.9" /125mm

L

Ø 3.94"/100mm

Ø 4.65" / 118mm

L

4.6ft/1.4 m < L £ 23ft/7 m

Victoria 20/20 F (C - 32)

Diaphragm Ø 1.77" / 45 mm

Page 48: ROCA Victoria - manuale Tecnico

Flue duct kit (VII)Victoria wall-hung waterheaters

47Heating training centres

Each 90° concentric elbow Ø 100 reduces allowed length 2.3ft/0.7mEach single 90° elbow Ø 80 reduces allowed length 1.64ft/0.5mThe first waterheater outlet elbow should not be taken into account.No reduction is necessary when using 45° elbows.

M

Ø 3.94"/100mm / Ø 4.9"/125mm

Ø 3.94"/100mm / Ø 4.9"/125mm

M

L

L

P

P

Page 49: ROCA Victoria - manuale Tecnico

Timer connections

Location of the timer connection on the electronic PCB.

Victoria wall-hung waterheaters48

Timer connection

(Earth)Black (Signal)

Green

(Power)Red

Heating training centres

Page 50: ROCA Victoria - manuale Tecnico

Programming instructions (I)

1 2 3 4 5 6 7

1 2 3 4 5 6 7

1 2 4 5 6 7 3 1 2 3 4 5 6 7

Day h m

Prog.

Programmed operating information

Day & time

Program mode

Set day

RES1hTo switch from summer to winter time

Weekdays Time and minutes

Denotes boiler operating or stopped

Set Time

Set minutes

Manual mode

Reset

Start-up First of all, delete all stored data.To do that, press the “RES” key for 3 seconds. Release key and the following display will appear:

The days of the week are flashing

Finally, release the key. The colon will be flashing.

Setting the time

1h 1h

Victoria wall-hung waterheaters49Heating training centres

Page 51: ROCA Victoria - manuale Tecnico

Finally, after entering the last switching status required, close the programming mode by pressing the key.The standard screen in the operating mode will be similar to the one shown here.Manual OperationPress the key. The screen will be similar to the one shown in this figure.

1 2 3 4 5 6 7

1 2 3 4 5 6 7

Press the key and the following screen will be displayed.

Enter the status of the day’sfirst command by pressing and taking into account that this symbol indicates that the “Waterheater is operating”. With no centre black dot, it means that the waterheater is OFF.

Enter the day’s first switching command. To do that, press the keys.

1 2 3 4 5 6 7

1 2 3 4 5 6 7 1 2 3 4 5 6 7

Enter the required switching day(s) by pressing the key. See “Possible Day Combinations” table. The screen displayed will be similar to the one in this figure.

To continue programming, press the key and repeat steps 2 to 4 as many times as necessary to complete the whole week.

Victoria wall-hung waterheaters

Possible Day Combinations are:

Or each individual day of the week.

1 2 3 4 5 6 7 1 2 3 4 5 61 2 3 4 5 6 7

= Mo, Tu, We, Th, Fr, Sa, Su = Mo, Tu, We, Th, Fr, Sa, = Mo, Tu, We, Th, Fr, = Sa, Su

50

Programming instructions (II)

Heating training centres

Page 52: ROCA Victoria - manuale Tecnico

In the manual mode, stored data will not be altered. In addition, there are specific functions to this operating mode, which are as follows:

Switching Times Display Press the key repeatedly. The stored switching times will be displayed in sequence.To exit the display mode, press the key.

Once all programmed status have been displayed, the following screen will appear again.

Changing:Press the key several times until reaching the program to be changed. Alter the settings by following steps 2 to 6 in the “Programming” section.Deleting:Press the key several times until reaching the program to be deleted. Press the keys until the “--“ symbol is displayed on the screen. Keep the key pressed for 3 seconds. This will delete all stored data. Press the key to exit the deleting mode.

1 2 3 4 5 6 7

1 2 3 4 5 6 7

Victoria wall-hung waterheaters

The following switching output status are possible:After the last occupied memory block, the number of free memory blocks are displayed on the screenFr 00 = indicates that all memory blocks are occupied.

Above two manually altered switching commands will be cancelled by the next automatic switching time.

= Advance OFF (if current switching status is =ON

=OFF

=Permanently OFF=Permanently ON

Return automatic mode is only possible by pressingthe “ “ key.

= Advance ON (if current switching status is

51

Programming instructions (III)

Heating training centres

Page 53: ROCA Victoria - manuale Tecnico

Control DIP switches

Access to DIP Switches Remove the control panel fascia

Location of DIP switches on the electronic board.

DIP SWITCHES 1 & 2: Central Heating Output Adjustment DIP SWITCH 3: CH pump operation DIP SWITCH 4: Time-delay between ON and OFFDIP SWITCHES 5 & 6: Hysteresis Selection

Output Adjustment SW1 SW2

47,620 Btu/12.000 kcal/h ON OFF27,778 Btu/7,000 kcal/h OFF OFF

79,366 Btu/20,000 kcal/h ON ON

Hysteresis SW5 SW671.6°F/22°C OFF OFF

53.6°F/12°C ON OFF46.4°F/8°C ON ON

62.6°F/17°C OFF ON

Circulating Pump Operation SW3Continuous operation OFF30 seconds after Room Thermostat stops ON

Time-delay SW4Enabled (6 minutes running) OFFDisabled ON

The factory-set configuration is shown in red.

Victoria wall-hung waterheaters52Heating training centres

Page 54: ROCA Victoria - manuale Tecnico

Maintenance

Carry out the following maintenance operations at least once a year, and preferably at the beginning of the Heating season:DHWClean the cold water filterCheck the DHW temperature Heating Check the system pressureCheck the waterheater water temperatureCheck the pump operationBleed the air in the radiators and boilerCheck the room thermostatCheck the safety valveGasCheck the burner setting pressureCheck the input rateCheck the circuit for gas tightnessClean the burner VenturisCombustion and Ventilation Check the flue duct tightnessCheck the effectiveness of ventilation and air renewal system. Ensure there are no obstructions.Conduct a flue gas analysis.

Victoria wall-hung waterheaters53Heating training centres

Page 55: ROCA Victoria - manuale Tecnico

Factory settings

Output to Central Heating

Victoria 20/20 FFeature

The following parameters are factory-set as shown:

(*) It is governed by the Room Thermostat. If no Room Thermostat has been installed, it will operate continuously.

Victoria wall-hung waterheaters54Heating training centres

79,366 Btu/20,000 kcal/h SW1 (ON) SW2 (ON)

79,366 Btu/20,000 kcal/h

30 secs following stoppage of Room StatSW3 (ON)

De-energizedSW4 (ON)

62.6°F/17°CSW5 (OFF) SW6 (ON)

Output to Domestic Hot Water System

Pump Speed Position

Pump Operation Time (*)

6-minute Time Delay

CH Hysteresis

Page 56: ROCA Victoria - manuale Tecnico

Fault codes

DHW Sensor interruptedCH Sensor interruptedFaulty Flame Relay: StuckFaulty Safety Circuit (*)Overheat Thermostat open during ignitionFlue Spillage Limit Thermostat open before ignitionFaulty Safety Relay (energized)Faulty Safety Relay (will not close following demand) (*)Burner off. Ignition time-delay too shortBurner off for lack of gas at lighting up (*)Safety Relay. Ignition Time-delay too longOverheat Thermostat open during operation (*)Flue Gas Spillage during operation (*)Safety Fuse open during operation (*)Faulty Safety Relay. Lack of gas or electrical fault (*)Pressure Switch Opening Time-delay

Victoria wall-hung waterheaters55Heating training centres

(*)Whenever these fault codes appear, reset the waterheater by turning the selector knob to the “R” position. For other codes, the waterheater will reset automatically once the fault is cleared.

40-9050-9060-9040-60-9050-60-9040-50-60-9040-70-9050-70-9040-50-70-9060-70-9040-60-70-9050-60-70-9040-50-60-70-9040-80-9040-50-80-9060-80-90