2.0 kW - 3,7 kW FM GB TECHNICAL MANUAL HIGH WALL-MOUNTED FAN COIL UNITS WITH BLDC MOTOR AND INCORPORATED VALVE

Transcript of Manuale tecnico FM Rev02 - wolf-klimatechnik.ch

Page 1: Manuale tecnico FM Rev02 - wolf-klimatechnik.ch

2.0 kW - 3,7 kW

FM

GB TECHNICAL MANUAL

HIGH WALL-MOUNTED FAN COIL UNITS WITH BLDC MOTOR AND INCORPORATED VALVE

Page 2: Manuale tecnico FM Rev02 - wolf-klimatechnik.ch

2

FM

All copying, even partial, of this manual is strictly forbidden FC66003740 - Rev 01

TABLE OF CONTENTS

1 GENERALITIES ..................................................................... 3

2 CONSTRUCTIVE FEATURES ................................................. 3

3 ACCESSORIES ..................................................................... 4

4 RATED TECHNICAL DATA ..................................................... 5

5 PERFORMANCES ................................................................. 6

5.1 Cooling .................................................................................6

5.2 Heating..................................................................................7

5.3 Valve information ...................................................................8

5.4 Sound levels ..........................................................................9

6 OVERALL DIMENSIONS ...................................................... 10

6.1 Mounting plate dimensions ..................................................10

7 WIRING DIAGRAMS ............................................................ 11

8 MASTER/SLAVE NETWORKS .............................................. 11

9 WALLPAD ........................................................................... 13

10 INSTALLATION REqUIREMENTS ......................................... 14

11 ROUTINE MAINTENANCE .................................................... 15

12 MODBUS ............................................................................ 16

The technical and dimensional data provided herein may undergo changes in connection with product improvements.

OPERATING LIMITSMinimum inlet water temperature = 5°CMaximum Inlet water temperature = 70°CMinimum air intake temperature = 5°CMaximum air intake temperature = 35°C Maximum wet bulb air intake temperature = 24°CSupply voltage = 230 Vac

- For any further information, contact the manufacturer: [email protected] To get the weight of the unit, refer to the User Manual, Rated technical data table.

Page 3: Manuale tecnico FM Rev02 - wolf-klimatechnik.ch

3

FM

All copying, even partial, of this manual is strictly forbiddenFC66003740 - Rev 01

1 GENERALITIES

High wall-mounted FM fan coil units are available in 3 models with cooling capacities ranging from 2.1 to 4.4 kW, complete with electronically controlled inverter motor (BLDC, 2 or 3-way ON/OFF solenoid valve and infrared remote control.

The performance features of FM fan coil units are certified by EUROVENT which guarantees the reliability of the data shown on this documentation.

2 CONSTRUCTIVE FEATURES

CABINET

The ABS cabinet features attractive design, rounded shape, for every type of environment.The integrated air outlet is equipped with a motor driven flap that can sweep automatically or be positioned manually, and adjustable fins for a uniform distribution of air in the room.

The front panel is complete with display to show all the functions of the unit and the room temperature.

HEAT EXCHANGERUprated heat exchanger made with copper piping and high efficiency alumi-nium fins with hydrophilic surface treatment, complete with air vent valve and facilitated emptying valve.

ON/OFF SOLENOID VALVE ASSEMBLYAll units are equipped with 2 or 3-way solenoid valve with electrothermal ON/OFF actuator (230 V) directly installed on the heat exchanger inside the unit and controlled by the microprocessor controller. Hoses for the connection to the system facilitate the installation operations.

DECLARATION OF CONFORMITY

Galletti S.p.A. hereby declares, under its sole responsibility, that the high wall-mounted fan coil units belonging to the FM series, have been designed, built and tested in conformity with the specifications of European Directives: 2006/42/CE, 2004/108/CE, 2006/95/CE

Bentivoglio, 08/01/2014Galletti S.p.A.Luca Galletti

FM high wall-mounted

1 2 3 4 5 6 7 8 9 10 11

S K A F M 0 3 2 T 0 0

Revision Name of series Size No. of valves Control included Motor Other

Page 4: Manuale tecnico FM Rev02 - wolf-klimatechnik.ch

4

FM

All copying, even partial, of this manual is strictly forbidden FC66003740 - Rev 01

2 CONSTRUCTIVE FEATURES

FAN-DRIVE ASSEMBLYTangential fan directly coupled to an electronically controlled electric motor of synchronous brushless type (BLDC) controlled by inverter.The great advantage of brushless motors is the significant reduction in power consumption, which reaches up to a 2/3 of that of asynchronous motors with the corresponding reduction in CO2 emissions. The DC Inverter technology allows to continuously adjust the air flow and heating capacity to the actual needs of the environment by considerably reducing the fluctuations in room temperature that are typical of step-by-step adjustments.

The direct consequence is the reduction in the noise emission of the fan coil, which is proportional to the demands of the environment.

CONTROL SYSTEMThe microprocessor control system with infrared user interface enables the automatic control of the fan coil unit.The main control specifications are:- Selection of the cooling, heating, dehumidification mode or the automatic

mode.- PID control algorithm to regulate the BLDC fan: the control logic adapts

the fan rpm to the difference between measured temperature and set temperature, integrate over time the deviation measured and adapt the rpm accordingly. The derivative logic analyzes the change speed thus assuring little variations.

- Water temperature reading and definition of minimum working temperatures - Auxiliary contacts for signalling of heating or cooling mode- Inlet contact for remote on/off operation ( (for instance signalling of room

occupied)- Serial port for the implementation of master/slave networks - Autorestart after power cut.

REMOTE CONTROL

Infrared remote control with LCD display, to set all the functions of the fan coil:- Switching on and off- Temperature Set point- Operating mode (cooling-dehumidification-ventilation-heating-automatic)- Ventilation (automatic-maximum-medium-minimum)- Switching on and off via Timer- Air outlet flap sweep- ClockWhen, in a maser/slave system, the fan coil with remote control is the master unit, the settings are automatically sent to the slave units.The flap sweep function is not applicable.

AIR FILTERThe filter is washable and can be easily removed for cleaning operations, by lifting the front panel of the cabinet.

3 ACCESSORIES

available as an option is a wired wallpad with a large display, which can be used to control and set all the functions of each individual fan coil unit in master/slave systems. WALLPAD supplied with cable for the connection to the fan coil unit.

Temperature pattern with 3-speed motor and brushless motor

3-speed motor

Noise pattern with 3-speed motor and brushless motor

3-speed motor

Page 5: Manuale tecnico FM Rev02 - wolf-klimatechnik.ch

5

FM

All copying, even partial, of this manual is strictly forbiddenFC66003740 - Rev 01

4 RATED TECHNICAL DATA

1 Water temperature 7-12°C, air temperature D.B. 27°C, W.B. 19°C (47% relative humidity)2 Water temperature 50°C, water flow rate same as in cooling mode, air inlet temperature 20°C3Sound power measured according to standards ISO3741 and ISO37444Sound pressure level measured at a distance of 1 m with a directivity factor of 4

RATED TECHNICAL DATA OF FM FAN COIL UNITS

Model 22 / 23 32 / 33 42 / 43

Supply voltage V - ph - Hz 230-1-50 / 220-1-60

Speeds 1 2 3 1 2 3 1 2 3

Total cooling capacity (1) kW 1,37 1,64 2,07 1,94 2,40 3,02 2,68 3,28 3,74

Sensible cooling capacity (1) kW 0,99 1,20 1,52 1,40 1,47 2,22 1,95 2,40 2,74

Water flow rate (1) l/h 234 281 356 335 414 518 457 565 641

Pressure drop (1) kPa 11 15 22 18 26 38 25 36 45

FCEER - nominal value 168 187 183

FCEER - Class B A B

Heating capacity (2) kW 1,75 2,12 2,70 2,48 2,61 3,93 3,45 4,20 4,87

Pressure drop (2) kPa 9 12 18 15 22 32 20 29 36

FCCOP - nominal value 216 230 238

FCCOP - Class B

Air flow rate m3/h 290 370 500 370 445 645 570 740 876

Power input W 8 10 13 10 13 20 13 20 30

Sound power level (3) dB/A 35 40 48 38 43 53 45 52 57

Sound pressure level (4) dB/A 27 32 40 30 35 45 37 44 49

Water content dm3 0,43 0,86

Water connections (female gas) inches 1/2

Condensate drainage connection inches (mm) 5/8 (16)

Dimensions H x L x P mm 876/228/300

Net weight kg 12,00 13,00 14,00

Page 6: Manuale tecnico FM Rev02 - wolf-klimatechnik.ch

6

FM

Tbs1 / Tbu1 (UR1) 25°C (51%) Tw1 / Tw2 6°C / 11°C 7°C / 12°C

Vr PFT PFS qw Dpw PFT PFS qw DpwW W l/h kPa W W l/h kPa

FM 22 / FM 231 1290 910 223 10 1010 810 173 62 1560 1110 266 14 1270 1000 220 103 1980 1410 338 21 1650 1290 284 15

FM 32 / FM 331 1830 1290 313 16 1390 1120 238 102 2290 1370 392 24 1850 1200 317 163 2890 2060 497 36 2390 1870 410 26

FM 42 / FM 431 2570 1820 439 24 2190 1670 374 182 3160 2240 544 34 2720 2070 464 263 3600 2550 619 43 3110 2360 533 33

Tbs1 / Tbu1 (UR1) 25°C (51%) Tw1 / Tw2 8°C / 13°C 9°C / 14°C

Vr PFT PFS qw Dpw PFT PFS qw DpwW W l/h kPa W W l/h kPa

FM 22 / FM 231 820 740 140 4 810 810 140 42 1040 1040 180 7 940 940 162 63 1260 1140 216 9 1200 1200 205 9

FM 32 / FM 331 1190 1050 205 8 1180 1180 202 72 1310 1000 223 9 1080 920 187 63 1760 1640 302 15 1760 1760 302 15

FM 42 / FM 431 1750 1510 302 12 1500 1500 259 92 2230 1890 382 18 1860 1860 320 133 2570 2170 439 23 2130 2130 367 17

Tbs1 / Tbu1 (UR1) 27°C (47%) Tw1 / Tw2 6°C / 11°C 7°C / 12°C

Vr PFT PFS qw Dpw PFT PFS qw DpwW W l/h kPa W W l/h kPa

FM 22 / FM 231 1590 1080 274 14 1370 990 234 112 1890 1300 324 19 1640 1200 281 153 2370 1630 407 29 2070 1520 356 22

FM 32 / FM 331 2270 1530 389 24 1940 1400 335 182 2770 1620 475 33 2400 1470 414 263 3470 2400 594 49 3020 2220 518 38

FM 42 / FM 431 3030 2090 518 32 2680 1950 457 252 3700 2560 634 45 3280 2400 565 363 4210 2910 724 56 3740 2740 640 45

Tbs1 / Tbu1 (UR1) 27°C (47%) Tw1 / Tw2 8°C / 13°C 9°C / 14°C

Vr PFT PFS qw Dpw PFT PFS qw DpwW W l/h kPa W W l/h kPa

FM 22 / FM 231 1100 890 187 7 970 970 166 62 1350 1100 234 11 1160 1160 198 83 1740 1400 299 16 1350 1260 230 11

FM 32 / FM 331 1520 1240 263 12 1210 1130 209 82 1970 1310 338 18 1320 1080 227 93 2520 2040 432 28 2140 2140 367 21

FM 42 / FM 431 2290 1810 392 19 1860 1660 320 132 2830 2240 486 28 2330 2060 400 203 3240 2560 554 35 2690 2360 461 25All copying, even partial, of this manual is strictly forbidden FC66003740 - Rev 01

5 PERFORMANCES

5.1 COOLING

Tbs1 Air inlet temperature (dry bulb)Tbu1 Air inlet temperature (wet bulb)Ur Relative humidityTw1 Water inlet temperatureTw2 Water outlet temperature

PFT Total cooling capacityPFS Sensible cooling capacityqw Water flow rate∆pw2-∆pw3 Pressure drop water side, unit without valveVr Fan speed

Page 7: Manuale tecnico FM Rev02 - wolf-klimatechnik.ch

7

FM

Tbs1 20°C Tw1 / Tw2 45 / 40°C 50°C / 40°C

VrPH qw Dpw PH qw DpwW l/h kPa W l/h kPa

FM 22 / FM 231 1470 256 10 1530 133 32 1790 310 14 1870 162 53 2280 396 22 2400 209 7

FM 32 / FM 331 2080 364 18 2170 187 62 2130 371 18 2200 191 63 3320 576 40 3490 302 13

FM 42 / FM 431 2900 504 24 3100 270 82 3530 612 34 3770 328 113 4110 713 45 4410 385 15

Tbs1 20°C Tw1 / Tw2 60°C / 50°C 70°C / 60°C

VrPH qw Dpw PH qw DpwW l/h kPa W l/h kPa

FM 22 / FM 231 2290 202 6 3000 263 102 2780 245 9 3640 320 143 3550 310 13 4640 407 21

FM 32 / FM 331 3240 284 11 4260 374 172 3310 288 11 4360 382 183 5160 450 24 6740 590 38

FM 42 / FM 431 4520 396 15 5880 515 232 5490 479 21 7140 626 333 6390 558 28 8330 731 42

Tbs1 22°C Tw1 / Tw2 45 / 40°C 50°C / 40°C

VrPH qw Dpw PH qw DpwW l/h kPa W l/h kPa

FM 22 / FM 231 1330 230 8 1380 119 32 1620 281 12 1690 148 43 2070 360 18 2170 187 6

FM 32 / FM 331 1880 328 15 1950 169 52 1920 335 15 1970 173 53 3000 522 33 3150 274 11

FM 42 / FM 431 2630 457 20 2810 245 72 3200 554 29 3420 299 103 3720 648 38 4000 349 13

Tbs1 22°C Tw1 / Tw2 60°C / 50°C 70°C / 60°C

VrPH qw Dpw PH qw DpwW l/h kPa W l/h kPa

FM 22 / FM 231 2140 187 6 2860 252 92 2600 227 8 3460 302 133 3330 292 12 4420 389 19

FM 32 / FM 331 3040 266 10 4060 356 162 3090 270 10 4150 364 163 4840 421 22 6410 562 35

FM 42 / FM 431 4240 371 13 5600 490 212 5150 450 19 6800 598 303 6000 526 25 7930 695 39

All copying, even partial, of this manual is strictly forbiddenFC66003740 - Rev 01

5 PERFORMANCES

5.2 HEATING

Tbs1 Air inlet temperature (dry bulb)Tw1 Water inlet temperatureTw2 Water outlet temperature

PT Heating capacityqw Water flow rate∆pw2-∆pw3 Pressure drop water side, unit without valveVr Fan speed

Page 8: Manuale tecnico FM Rev02 - wolf-klimatechnik.ch

8

FM

M30x1.5

Ø28

A

C

DN

DN

B D

All copying, even partial, of this manual is strictly forbidden FC66003740 - Rev 01

2 Way Valve Body

3 Way / 4 Outlet

Differential pressure Chart

Differential pressure Chart

Valve Dimensions (mm)

DN A B C D

D15(G1/2”)

52 47 19.5 63

Valve Dimensions (mm)

Valve Model DN A B C D

DFPS-HWS-007b D15(G1/2”)

52 70 35 86

5 PERFORMANCES

3.5 VALVE INFORMATION

Page 9: Manuale tecnico FM Rev02 - wolf-klimatechnik.ch

9

FM

Lw

FM Vr125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz LwA LpA

dB dB dB dB dB dB dB dB/A dB/A

FM 22 / FM 23

1 43,8 46,1 45,2 42,3 33,9 23,1 17,0 46 38

2 36,9 38,9 37,5 32,4 23,6 16,4 17,4 38 30

3 36,3 36,7 34,0 28,4 21,7 17,3 19,2 35 27

FM 32 / FM 33

1 51,2 52,9 50,5 48,4 41,3 32,0 21,5 52 44

2 41,6 44,0 42,5 37,5 28,7 20,4 19,1 43 35

3 37,7 39,2 37,9 32,9 24,3 17,8 17,5 38 30

FM 42 / FM 43

1 54,8 55,8 53,7 54,3 47,5 38,1 26,8 57 49

2 48,6 50,0 49,4 48,1 40,5 30,3 20,3 51 43

3 43,0 44,4 44,1 41,3 32,5 21,8 18,6 45 37

All copying, even partial, of this manual is strictly forbiddenFC66003740 - Rev 01

6 OVERALL DIMENSIONS

5 PERFORMANCES

5.4 SOUND LEVELS

LpA Total sound pressure level, weighted A, measured at a distance of 1 m, with a directivity factor of 2.

Lw Sound power level by octave band, not weightedLwA Total sound power level, weighted AVr Fan speed

Model Unit dimensions (mm)

A B C D E F G H

FM 22 / 23 / 32 / 33 / 42 / 43

40 105 875 55 105 R20 60 74

Unit dimensions (mm)

1 2 3 4

665 170 710 125

Unit dimensions (mm)

a b c d e f g h

200 55 30 30 220 229 10 300

Page 10: Manuale tecnico FM Rev02 - wolf-klimatechnik.ch

10

FM

All copying, even partial, of this manual is strictly forbidden FC66003740 - Rev 01

6 OVERALL DIMENSIONS 6.1 MOUNTING PLATE DIMENSIONS

Hot w

ater

4-p

ipe

conv

ecto

r se

nsor

Hot

/chi

lled

wat

er

2-pi

pe

conv

ecto

r sen

sor

Retu

rn a

ir se

nsor

ON/OFF electric control board (20/24).

Conn

ectio

n to

ste

pper

mot

or o

f air

outle

t fla

p

Connect

LED

Disp

lay/

IR re

ceiv

erW

all-m

ount

ed c

able

con

trol

Yellow/green

Auxiliary heating contact

Auxiliary cooling contact

7 WIRING DIAGRAMS

Make the electrical connections with the power supply disconnected, in accordance with current safety regulations.Check that the mains electricity supply is compatible with the voltage shown on the unit rating plate.Each fan coil requires an individual electric socket and a switch with a suitable safety fuse.--------- Factory wiring - - - - - Field wiring Each fan coil requires an omnipolar main switch classified as overvoltage category III to be mounted on the power supply line.

Page 11: Manuale tecnico FM Rev02 - wolf-klimatechnik.ch

11

FM

All copying, even partial, of this manual is strictly forbiddenFC66003740 - Rev 01

7 WIRING DIAGRAMS

ABBREVIATIONS Ts = set temperatureTr = Room temperatureTi1 = convector chilled water temperature Ti2 = convector hot water temperature AUX1 = hot water free contactAUX2 = chilled water free contactMTV1 = cooled motor driven valve

--------- Factory wiring - - - - - Field wiring

DIPA-S1 SW1-5: unit address setting. SW6: unit type setting: Master or slave.

Mode Configuration:

SW7=0; SW8=0; unit working in cooling/heating mode. SW7=1; SW8=0; unit working in cooling mode only.

DIPB-S2 SW1: Occupation contact settingSW2: Unit configuration setting: 0= 2-pipe systemSW3: On/Off valve configuration0=w/o valve1=with valve SW4: Pre-heating setting:0=36 °C 1=28 °C SW5, SW6, S3 (by-pass jumper): Fan speed configuration.

I/O contacts: L/N: Power supply: 230 Vac Valve 1: Valve output On/Off -230 Vac. (2 pipes: cooling/heating) Valve 2: Valve output On/Off -230 Vac. (4 pipes: heating only) HEATING: Electric heater input/output - 230 Vac. AI1: Return air temperature sensor - 1 (Tr). AI2: Internal convector temperature sensor - 1 (Ti1). AI3: Internal convector temperature sensor - 2 (Ti2). AUX1: No-voltage contacts; ON: unit in heating mode. AUX2: No-voltage contacts; ON: unit in cooling mode. ON/OFF: Occupation contact CN1~2: Stepper motor rate. CN3: Serial BUS contacts. CN4: Fan speed output - 230 Vac. KEY: On/Off switch. The 20/24 type uses an electric control board MTV2 = motor driven hot valve

8 MASTER / SLAVE NETWORKS

The FM fan coil units are equipped with a PCB suitable for the implementation of master/slave networks with up to 32 units. Depending on the control panel used on the master unit it is possible to implement two different types of master/slave control.

Global control communicationMaster unit with IR remote control or a wired WALLPAD.The master unit will transmit the settings to all slave units. During normal operation the slave units can receive data from the wireless remote control or the wall-mounted control. After receiving the global commands from the master unit, all slave unit settings will be replaced by the master settings. In case of global control communication it is not possible to set different settings on slave units, which will all work in the same manner.

Addressable communicationsThe master controller must be a wired wallpad. The slave unit parameters are set as usual. After receiving the control commands from the master unit, the addressed slave unit settings will be replaced by the master settingsIn that case using the WALLPAD it is possible to send customized instructions to each of the units connected to the network.

Master unit function The master unit sends the data referring to its settings to the slave unit. The settings of the Master unit are: Unit On / Off, Mode, Fan Speed , Timer, Clock, Temperature selection, sweep function and sleep function for use from remote control. The settings of the Master unit are: Unit On / Off, Mode, Fan Speed , Timer, Clock, Temperature selection, sweep function and sleep function for use from wall-mounted control.

Page 12: Manuale tecnico FM Rev02 - wolf-klimatechnik.ch

12

FM

All copying, even partial, of this manual is strictly forbidden FC66003740 - Rev 01

8 MASTER / SLAVE NETWORKS

Slave unit function The slave unit receives data referring to its settings from the master unit. The slave unit can be set locally on a desired setting by means of the local controller, provided there are no subsequent changes to the settings of the master unit. The slave units can be set individually for switching on and off via the timer using the remote control or the wall-mounted control. The remote control cannot change the clock and timer settings set via the wall-mounted control.

Page 13: Manuale tecnico FM Rev02 - wolf-klimatechnik.ch

13

FM

All copying, even partial, of this manual is strictly forbiddenFC66003740 - Rev 01

9 WALLPAD

Wall-mounted cable control equipped with a large display to show all the functions and to control each fan coil unit of a master/slave system. WALLPAD is supplied with cable for the connection to the fan coil unit.

2323 23 23

°C

°FCOOL

SUN

FANAUTO

DRY HEAT SLEEP SWING%Z

ZZ

MON TUE WED

IR

ONOFF

TIMER

CANCELMODE

FAN

SLEEP FRESHNET

SWINGDAY

THU FRI SAT HEATER

ERRUNIT:

TIME PARAMETERS

Area of day displayDisplay of the day of the week

Keypad lock

IR receiptTo receive the signal of the portable wireless control

Area of timer displayDisplay of timer switching on and off or real-time clock, RTCSwitch on timerSwitch off timerGlobal control by the master in network mode

Day buttonTo select the day of the week, from Sunday to SaturdayOr used for programming the weekly switching on and off via the timer, to select the day of the week

Network button for the network controlClock setting buttonTo adjust RTC setting or the timer settings in the switching on and off timer programming

Timer cancelling buttonTo cancel the switching on and off settings in timer programming mode

Timer buttonPress to enable the programming mode of switching on and off timer

Fan speed buttonPress to select low, medium or high speed

Sleep buttonPush the button once to select the Sleep modePress again to cancel the sleep function

Use SWING and FRESH buttons to set the global control mode

Use + and - parameter buttons to see the various parameters

Pushbutton for selecting the room temperature

Area of unit displayDisplay of unit addressDisplay of ERR errorDisplay of UNIT address

Display of Fan speedDisplay of operationArea of temperature displayDisplay of room or selected temperature

Page 14: Manuale tecnico FM Rev02 - wolf-klimatechnik.ch

14

FM

All copying, even partial, of this manual is strictly forbidden FC66003740 - Rev 01

9 WALLPAD

THE OVERALL DIMENSIONS ARE SHOWN BELOW

10 INSTALLATION REqUIREMENTS

Select the position of the high wall-mounted unit based on the following considerations: The air inlet and outlet front part must be free of obstructions. The air should flow freely. The wall the unit is mounted on must be sufficiently rigid so as not to resonate and produce noise. The position should permit easy access for installing the connecting water pipes and in a convenient place for drainage. Make sure that the opening on both sides of the fan coil unit is as shown in the following drawing. The position above the floor should be higher than eye level. Avoid positions directly exposed to sunlight.

Higher than eye level.

Page 15: Manuale tecnico FM Rev02 - wolf-klimatechnik.ch

15

FM

All copying, even partial, of this manual is strictly forbiddenFC66003740 - Rev 01

10 INSTALLATION REqUIREMENTS

Clearance for maintenance and repairing is shown above ** All dimensions are in mm. The signal receiver on the unit must be kept as far away as possible from any source of high frequency emissions. Keep the unit away from fluorescent lamps which can affect the control system. To avoid electric or magnetic interference of the control system, make sure that the control cables are installed separately from 220-240 Vac electric cables. Where electromagnetic waves are present, use shielded cables for the sensors. Install a filter if harmful interferences are present in the power supply.

Filter

11 ROUTINE MAINTENANCE

The material must undergo maintenance in order to retain its characteristics over time. Lack of maintenance may have the effect of voiding the product warranty. We recommend cleaning it once a month, but the frequency depends on operating conditions. To remove the filter Open the grill by lifting it from the lower position indicated by the arrow. Remove the filter from the grille.Use a vacuum cleaner to remove dust. If dust is glued to the filter, remove it with clean or soapy water, rinse the filter with clean water and dry it. Put the filter back into its housing in the grill. Close the liftable grill by pressing both sides down, into the position indicated by the arrow.

Page 16: Manuale tecnico FM Rev02 - wolf-klimatechnik.ch

16

FM

All copying, even partial, of this manual is strictly forbidden FC66003740 - Rev 01

12 MODBUS

The protocol implemented on the fan coil is Modbus RTU (9600,N,8,1) on RS485.

IMPLEMENTED FUNCTIONS

Function Code Function Description

01(01H) Read Coils Status

02(02H) Read Input Status

03(03H) Read Holding Registers

04(04H) Read Input Registers

05(05H) Write Single Coil

06(06H) Write Single Register

15(0FH) Write Multiple Coils

16(10H) Write Multiple Registers

255(FFH) Extended Commands which is used to test

IMPLEMENTED EXCEPTIONS

Error code Description Definition

01 (01H) Invalid commands Received commands beyond valid commands

02 (02H) Invalid data address Data addresses beyond valid data address

03 (03H) Invalid data Data beyond definition range

04 (04H) Write data not succeed Write data not succeed

INPUT COILS

Description Address Type

Unit ON/OFF 100000 R/W

Sleep mode 100001 R/W

Louver swing 100002 R/W

STATUS COILS

Description Address Type Remark

MTV1 200000 R

MTV2 200001 R

AUX1 200002 R

AUX2 200003 R

Condensate pump 200004 R

Electrical Heater 200005 R

Wired wall pad 200006 R

PRO 200007 R

Float switch 200008 R

Reserved 200009 R

EH protection switch 2000010 R

Internal actually running and unit ON/OFF 2000011 R Testing purpose only.

Page 17: Manuale tecnico FM Rev02 - wolf-klimatechnik.ch

17

FM

All copying, even partial, of this manual is strictly forbiddenFC66003740 - Rev 01

12 MODBUS

HOLDING REGISTERS

Description Address Type Remark

Mode setting 300000 R/W

Cooling mode= 01(H)Humidify mode= 02(H)Fan mode= 04(H)Heating mode= 08(H)Auto mode= 10(H)

Fan speed setting 300001 R/W

Low speed= 04(H)Medium speed= 02(H)High speed= 01(H)Auto fan speed= 07(H)

Louver swing setting 300002 R/W

Position 1= 01(H)Position 2= 02(H)Position 3= 03(H)Position 4= 04(H)Auto= 0F(H)Stop= 00(H)

Setting temperature 300003 R/W 16~30 degree C (actual*10 format)

Address setting 300004 R Set by dip-switch, reading only

Reset 300005 W = 0x33 reset error

Week 300006 W Calibration wired wall pad and set timer function

Hour 300007 W Calibration wired wall pad and set timer function

Minute 300008 W Calibration wired wall pad and set timer function

Second 300009 W Calibration wired wall pad and set timer function

Hours in Timer on 300010 R/W Timer ON

Minute in Timer on 300011 R/W Timer ON

Hours in Timer on 300012 R/W Timer OFF

Minute in Timer on 300013 R/W Timer OFF

Icon of Timer ON or OFF 300014 R/W

BIT0= Icon of Timer ONBIT1= Icon of Timer OFF1= enable0= disable

Super low speed rpm 310000 R/W 200~1500

Low speed rpm 310001 R/W 200~1500

Medium speed rpm 310002 R/W 200~1500

High speed rpm 310003 R/W 200~1500

RPM setting 310004 R/W 200~2000 (used to test, 0=disable)

Temperature sampling time 310005 R/W 2~100, default:5S

Factor of auto fan speed 310006 R/W 2~150, default:20

Factor of modulating valve 310007 R/W 2~250, default:150

Page 18: Manuale tecnico FM Rev02 - wolf-klimatechnik.ch

18

FM

All copying, even partial, of this manual is strictly forbidden FC66003740 - Rev 01

12 MODBUS

INPUT REGISTERS

Description Address Type Remark

Dip switch 1 status 400000 R

Dip switch 2 status 400001 R

Room temperature sensor 400002 R

Ti1 temperature sensor 400003 R

Ti2 temperature sensor 400004 R

Error code 400005 R

Bit0= Room temperature sensor errorBit1= Ti1 temperature sensor errorBit2= Ti2 temperature sensor errorBit3= Float switch errorBit4= Indoor coil low temperature protectionBit5= Indoor coil over heat protectionBit6= ReservedBit7= Electrical heater failureBit8= Motor1 errorBit9= Motor2 errorBit10= System parameters errorBit11= ReservedBit12= ReservedBit13= ReservedBit14= ReservedBit15= Reserved

Fan speed status 400006 RLow=04(H)Medium= 02(H)High= 01(H)

Mode status 400007 R

Cooling mode= 01(H)Dehumidify mode= 02(H)Fan mode= 04(H)Heating= 08(H)

Setting temperature status 400008 R Testing only

Room temperature in wall pad status 400009 R

Room temperature in main PCB status 400010 R

Unit type 400011 R4-pipe= 03, 2-pipe= 02This setting is configured by dip switch

EC motor 1#RPM 400012 R

EC motor 2#RPM 400013 R

Page 19: Manuale tecnico FM Rev02 - wolf-klimatechnik.ch

19

FM

All copying, even partial, of this manual is strictly forbiddenFC66003740 - Rev 01

Page 20: Manuale tecnico FM Rev02 - wolf-klimatechnik.ch

Wolf (Schweiz) AGDorfstrasse 147CH-8802 KilchbergTelefon +41 43 500 48 00Fax +41 43 500 48 [email protected]