Report run on: March 25, 2010 10:19 AM RECAPP Facility Evaluation Report St. Vincent De Paul Elementary / Jr. High School B2829A Calgary Calgary RCSSD #1

Transcript of RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area...

Page 1: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM

RECAPP Facility Evaluation Report

St. Vincent De Paul Elementary / Jr. High SchoolB2829ACalgary

Calgary RCSSD #1

Page 2: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 2 of 61

B2829ABuilding Id:

St. Vincent De Paul ElementaBuilding Name:

CalgaryLocation:4525 - 49 Street N. W. Address:

4,400.33Gross Area (sq. m): $13,839,932Replacement Cost:1967Construction Year:

Evaluation Date: July 14 2009

Asset Evolution Inc.Evaluation Company:

Mario PlastinaEvaluator Name:

St. Vincent De Paul Elementary - Jr High School , originally a single storey structure, constructed in 1967 with an area of 2334 square meters. In 1975, an addition of 2066 square meters was added to the west end of the original school. The total area of the school is 4400 square meters (excluding portables). The school includes 6 classroom portables with a separate entrance and storage section. The main entrance vestibule, including the offices are currently under construction- Summer 2009. The school includes 16 classrooms, a gymnasium with a stage, an industrial art shop, home economics/sewing room, 2 science labs, computer lab, a library, a music room, conference room and administrative offices. The school includes 6 classroom portables with a separate entrance and storage section. The portables are attached to the south-west corner of the school. The 2009 student enrollment - 579 Students

General Summary:

Structural Summary:The foundations consist of cast-in-place concrete grade beams and spread footings. The building has cast-in-place concrete slabs-on-grade with conventional steel reinforcement. The lower section of the mechanical room has a concrete block wall assembly. A steel grate floor is located on the upper section of the mechanical room. The stage is constructed with a conventional wood frame assembly. Structural reinforced concrete load bearing block partitions are located throughout the building.The original roof has a wood roof deck with steel and/or wood OWSJ's supported by concrete masonry block interior and exterior walls. The 1975 roof addition has a steel roof deck with OWSJ's supported by concrete masonry block interior and exterior walls. The structure of the building appears to be in acceptable condition

Envelope Summary:The majority of the exterior envelope has a brick cladding assembly. The upper portion of the 1967 Original building has a precast aggregate concrete panel assembly. The north wall opposite the main entrance has a natural stone finish. Pre-finished horizontal metal siding are located on the upper portion of the gymnasium's exterior wall assembly. Expansion/control joints are located throughout the precast concrete cladding assembly and at the addition connection. Sealant is located around all window, door and exterior cladding assemblies. Exterior metal louvres are located on the upper portion of the exterior walls opposite the mechanical rooms. The concrete structure at the main entrance to the original school has a textured paint finish. The windows comprise of aluminum frame double glazed fixed & operable awning units. A framed spandrel panel below the glazing is included in the assembly. The main entrance doors in the original 1967 school comprise of painted steel doors & frames with GWG transoms & sidelites. The majority of the exterior doors are painted insulated hollow metal doors in a painted steel frame assembly. The roofsections have a flat modified bituminous membrane roofing assembly (SBS). A roof hatch is located in room 164 complete with metal ladder. Overall, the envelope of the building is in acceptable condition. Recommendations: - Replace sealant around all exterior windows & doors - All Section

Interior Summary:Interior partitions in the gymnasium, corridors, washrooms and vestibules typically consist of painted masonry block

25.54%5 year Facility Condition Index (FCI):

Facility Details Evaluation Details

Total Maintenance Events Next 5 years: $3,535,000

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Page 3: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 3 of 61

walls. Interior partitions located between some of the classrooms typically consist of painted gypsum board with metal stud framing. A demountable partition is located in the office area. A movable folding panel divider is located in the gymnasium, stage area and library. Steel framed glazing wall in west corridor at science rooms, home economics room, several classrooms, library and computer room. The interior doors are solid core wood doors complete with pressed steel frames. The doors have GWG inserts. The doors in the corridors are either wood and/or hollow metal doors complete with pressed steel frames. The doors & frames are rated and have GWG inserts. Chalkboards and tackboards are located in the teaching areas. Prefinished metal washroom stall partitions are located in each boy's & girls washroom & change rooms. Prefinished metal lockers are located throughout the original school corridors. Metal storage shelving throughout the vestibules, custodial utility rooms and staff supply rooms. The washrooms are equipped with typical washroom accessories: Paper towel dispensers, toilet paper dispensers, hand-soap dispensers, waste bins and mirrors. Cast in place concrete stairs are located in the mechanical room. The music room and gymnasium stage stairs are wood framed. The wood stairs to the stage are in the gym are stained.The handrails are constructed of steel with a paint finish. Vertical stained wood panels are located throughout the music room and abovethe stage wall. The interior gypsum board & concrete block wall partitions throughout the school have a paint finish. Painted/sealed concrete floors are located in the mechanical rooms, industrial arts room and storage rooms. The mainvestibules, washrooms and change rooms including showers have a ceramic tile floor finish. The stage area has a hardwood floor. Rubber flooring is located in the gymnasium. Sheet vinyl flooring is located throughout the majority of the corridors and 12 classrooms. Original VAT flooring is located in the home economics/sewing room, science rooms,storage areas, caretakers room, corridors and printing room. Carpeting is located in 5 classrooms, music room, library & in the administration areas. The carpet in the library was replaced in the Summer of 2009. The majority of the ceilinghas either a 600 x 1200 and/or 600 x 600 acoustic tile and T-bar grid ceilings throughout the corridors, classrooms, administration area and washrooms. The Gymnasium has 300 x 300 acoustic tiles laminated to the underside of deck.All the interior gypsum board ceilings in the showers, change rooms and washrooms have a paint finish. The exposed wood & steel structure in the gymnasium and mechanical room have a paint finish. The interior finishes are in good condition. Recommendations: - Replace hardwood floor on the stage area - Replace original VAT flooring - Provided power operators for barrier free access at the main north-east entrance - Provide a unisex washroom

Mechanical Summary:MECHANICAL SUMMARY (July 2009) In the c.1967 original building, primary building space heating is provided by a natural gas fired hot water boiler which provides hot water for the air handling unit heating coils and for the building heating terminal units (force flow convectors and finned tube radiation cabinets). Ventilation for the c.1967 original building is provided by two air handling units, one main unit for the school and one smaller unit for the gymnasium. The air handling systems are mixed air systems and the main air handling unit has an associated return air fan. The air handling units are equippedwith hot water heating coils. The fresh air supplied to the original building by the air handling units is balanced by the exhaust air flow from the air handling units and from the original building exhaust fans. The original building HVAC controls are primarily pneumatic, although there are some electric controls. In the c.1976 building addition, primary building space heating is provided by six natural gas fired hot water boilers which provide hot water for the air handling unit heating coil and for the building heating terminal units (force flow convectors, finned tube radiation cabinets, and a unit heater). Ventilation for the building addition is provided by one air handling unit. The air handling system is a mixed air system. The air handling unit is equipped with a hot water heating coil. The fresh air supplied to the building addition by the air handling unit is balanced by the exhaust air flow from the air handling unit and from the building addition exhaust fans. The building addition HVAC controls are primarily pneumatic, although there are some electric controls. There is a building management and control system (BMCS) which provides control and monitoring functions for someof the HVAC equipment (air handling units) as well as for other building equipment (bells, carplugs, emergency lights, etc.). The BMCS is a Johnson Controls Metasys system. Washroom plumbing fixtures include toilets, lavatories and urinals. There are 22 toilets, nine urinals, and 18 lavatoriesin the building. Other plumbing fixtures in the building include drinking fountains, various sinks, a wash fountain, eyewash stations, and shower stalls. Two natural gas fired domestic hot water heaters provide domestic hot water for

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Page 4: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 4 of 61

the building lavatories, sinks and showers. Fire protection for the building includes a standpipe system feeding standard fire hose cabinets in the original building, and cabinet and wall mounted fire extinguishers. Overall, the building mechanical equipment and systems are in acceptable condition. Items requiring attention include the replacement of some of the plumbing fixtures and replacement of the original building control air supply system.

Electrical Summary:St. Vincent De Paul Elementary School is fed from a padmounted transformer. The main distribution consists of an 800A main disconnect switch and splitter rated 800A, 120/208V, 3-phase, 4-wire. The mechanical loads within the building are fed from individual motor starters. The wiring in the building is typically standard wiring in conduit. The majority of the interior fluorescent lighting fixtures have T-12 lamps and magnetic ballasts. The classrooms in the original building have been provided with T8 fixtures. The exit lighting in the building is typically metal units with LED lamps. The emergency lighting is fed from emergency lighting battery packs and remote lighting heads. The exterior lighting consists of wall mounted HPS fixtures and recessed incandescent lighting. The building is equipped with an Edwards 6500 fire alarm system. Detection and end devices include, smoke and heat detectors, bells and pull stations. The communications systems within the building include structured wiring systems for the Nortel telephone system and the data systems. The school has a Dukane P.A. system and a Silent Knight security system. It is recommended, as routine maintenance, that a program for annual examination of major electrical components be instituted. Maintenance should include thermographic scans for hot spots and power shut down to allow examination of interior components for accumulated debris and signs of corrosion. The main concerns for the school are: - the main service is aged and consists of fusible disconnect switches - the 1967panels are aged - mechanical starters and accessories are aged - some emergency lighting battery units are aged - the incandescent exterior lighting is inefficient - the fire alarm system is aged - P.A. System sound quality is poor An Energy efficiency upgrade is recommended for the T12 fluorescent lighting. Overall the electrical systems for St. Vincent De Paul Elementary School are in marginal condition.

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Condition Rating Performance1 - Critical Unsafe, high risk of injury or critical system failure.2 - Poor Does not meet requirements, has significant deficiencies. May have high operating/maintenance costs.

3 - Marginal Meets minimum requirements, has significant deficiencies. May have above average operating maintenance costs.4 - Acceptable Meets present requirements, minor deficiencies. Average operating/maintenance costs.

Rating Guide

5 - Good Meets all present requirements. No deficiencies.6 - Excellent As new/state of the art, meets present and foreseeable requirements.

Page 5: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 5 of 61

A1010 Standard Foundations* - All Sections

A1030 Slab on Grade* - All Sections

A2020 Basement Walls (& Crawl Space)* - All Sections

B1010.01 Floor Structural Frame (Building Frame)* - All Sections

B1010.02 Structural Interior Walls Supporting Floors (or Roof)* - All Sections

B1010.09 Floor Construction Fireproofing* - All Sections

B1010.10 Floor Construction Firestopping* - All Sections

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

Rating

Rating

1967

1967

1967

1967

1967

1967

1967

Installed

Installed

Installed

Installed

Installed

Installed

Installed

100

100

100

100

100

50

50

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

MAR-10

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Updated

Updated

Updated

Updated

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)S1 STRUCTURAL

The foundations consist of cast-in-place concrete grade beams and spread footings.

The building has cast-in-place concrete slabs-on-grade with conventional steel reinforcement.

The lower section of the mechanical room has a concrete block wall assembly.

A steel grate floor is located on the upper section of the mechanical room. The stage is constructed with a conventional wood frame assembly.

Structural reinforced concrete load bearing block partitions are located throughout the building.

In visible areas, fire-stopping appeared to have been provided in the original construction.

Page 6: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 6 of 61

B1020.01 Roof Structural Frame* - 1967 Section

B1020.01 Roof Structural Frame* - 1975 Section

B1020.06 Roof Construction Fireproofing* - All Sections

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

1967

1975

1967

Installed

Installed

Installed

100

100

50

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

The original roof has a wood roof deck with steel and/or wood OWSJ's supported by concrete masonry block interior and exterior walls.

The 1975 roof addition has a steel roof deck with OWSJ's supported by concrete masonry block interior and exterior walls.

Page 7: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 7 of 61

B2010.01.01 Precast Concrete: Exterior Wall Skin*

B2010.01.02.01 Brick Masonry: Ext. Wall Skin*

B2010.01.03 Stone Assemblies: Exterior Wall Skin*

B2010.01.06.03 Metal Siding** - 1967 Section

B2010.01.06.03 Metal Siding** - 1975 Section

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

1967

1967

1967

1967

1975

Installed

Installed

Installed

Installed

Installed

75

75

75

40

40

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Updated

Updated

Replace Metal Siding - Gymnasium 1967 Section

Replace Metal Siding - Gymnasium 1975 Section

Lifecycle Replacement

Lifecycle Replacement

2013

2015

$80,000

$80,000

Unassigned

Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)S2 ENVELOPE

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-10

MAR-10

The upper portion of the 1967 Original building has a precast aggregate concrete panel assembly.

The majority of the exterior envelope has a brick cladding assembly.

The north wall opposite the main entrance has a natural stone finish.

Pre-finished horizontal metal siding are located on the upper portion of the gymnasium's exterior wall assembly.

Pre-finished horizontal metal siding are located on the upper portion of the gymnasium's exterior wall assembly.

Page 8: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 8 of 61

B2010.01.09 Expansion Control: Exterior Wall Skin*

B2010.01.11 Joint Sealers (caulking): Ext. Wall ** - All sections

B2010.01.13 Paints (& Stains): Exterior Wall**

B2010.02.03 Masonry Units: Ext. Wall Const.*

4 - Acceptable

3 - Marginal

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

1967

1967

1967

1967

Installed

Installed

Installed

Installed

75

20

15

100

Design Life

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Updated

Replace sealant around all exterior windows & doors - All Section

Repaint exterior precast panels

Failure Replacement

Lifecycle Replacement

2010

2013

$60,000

$30,000

Low

Unassigned

The sealant around the exterior windows and doors is brittle and deteriorated.

Concern:

Replace sealant around all exterior windows & doors - All Section

Recommendation:

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-10

MAR-10

Expansion/control joints are located throughout the precast concrete cladding assembly and at the addition connection.

Sealant is located around all window, door and exterior cladding assemblies.

The exterior precast panels have a paint finish.

The exterior walls have concrete block construction on the inside face of the exterior wall assembly.

Page 9: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 9 of 61

B2010.03 Exterior Wall Vapor Retarders, Air Barriers, and Insulation*

B2010.06 Exterior Louvers, Grilles, and Screens*

B2010.09 Exterior Soffits*

B2020.01.01.02 Aluminum Windows (Glass & Frame)** - 1967 Section

B2020.01.01.02 Aluminum Windows (Glass & Frame)** - 1975 Section

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

1967

1967

1967

1967

1975

Installed

Installed

Installed

Installed

Installed

100

50

50

35

40

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Updated

Updated

Replace Aluminum Framed Windows - 1967 Section - 22 units

Replace Aluminum Framed Windows - 1976 Section - 6 units

Lifecycle Replacement

Lifecycle Replacement

2013

2015

$140,000

$36,000

Unassigned

Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-10

MAR-10

Not visible.

Exterior metal louvres are located on the upper portion of the exterior walls opposite the mechanical rooms.

The concrete structure at the main entrance to the original school has a textured paint finish.

The windows comprise of aluminum frame double glazed fixed & operable awning units. A framed spandrel panel below the glazing is included in the assembly.

The windows comprise of aluminum frame double glazed fixed & operable awning units. A framed spandrel panel below the glazing is included in the assembly.

Page 10: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 10 of 61

B2030.01.02 Steel-Framed Storefronts: Doors** - 1967 Section

B2030.01.02 Steel-Framed Storefronts: Doors** - 1975 Section

B2030.02 Exterior Utility Doors** - 1967 Section

B3010.01 Deck Vapor Retarder and Insulation*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

1967

1975

1967

2004

Installed

Installed

Installed

Installed

30

30

40

25

Design Life

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

APR-09

Updated

Updated

Updated

Updated

Replace Steel-Framed Storefronts Doors - 1967 Section -6 doors & assembly

Replace Steel-Framed Storefronts Doors - 1976 Section - 2 doors & assembly

Replace Exterior Utility Doors - 1967 & 1976 Sections - 8 doors

Lifecycle Replacement

Lifecycle Replacement

Lifecycle Replacement

2013

2013

2013

$60,000

$20,000

$32,000

Unassigned

Unassigned

Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Event:

Type

Type

Type

Year

Year

Year

Cost

Cost

Cost

Priority

Priority

Priority

Updated:

Updated:

Updated:

MAR-10

MAR-10

MAR-10

The main entrance doors in the original 1967 school comprise of painted steel doors & frames with GWG transoms & sidelites.

The main entrance doors in the 1975 Addition comprise of painted steel doors & frames with GWG transoms & sidelites.

The majority of the exterior doors are painted insulated hollow metal doors in a painted steel frame assembly.

2004 - Unknown

Page 11: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 11 of 61

B3010.04.04 Modified Bituminous Membrane Roofing (SBS)** - 1967 Section

B3010.04.04 Modified Bituminous Membrane Roofing (SBS)** - 1975 Section

B3020.02 Other Roofing Openings (Hatch,Vent, etc)*

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

2004

2004

1967

Installed

Installed

Installed

25

25

25

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Replace Modified Bituminous Membrane Roofing (SBS) - Area - 2300m2

Replace Modified Bituminous Membrane Roofing (SBS) - Area - 2067m2

Lifecycle Replacement

Lifecycle Replacement

2029

2029

$375,000

$350,000

Unassigned

Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-10

MAR-10

The roof sections above the original 1967 building have a flat modified bituminous membrane roofing assembly (SBS).

The roof sections above the 1975 Addition have a flat modified bituminous membrane roofing assembly (SBS).

A roof hatch is located in room 164 complete with metal ladder.

Page 12: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 12 of 61

C1010.01 Interior Fixed Partitions*

C1010.02 Interior Demountable Partitions*

C1010.03 Interior Operable Folding Panel Partitions**

C1010.05 Interior Windows*

C1010.06 Interior Glazed Partitions and Storefronts*

C1010.07 Interior Partition Firestopping*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

Rating

1967

1967

1967

1967

1967

1967

Installed

Installed

Installed

Installed

Installed

Installed

100

50

30

80

80

50

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Updated

Updated

Updated

Replace Interior Operable Folding Panel Partitions - (3) - Library,Gym, Stage Area

Lifecycle Replacement 2013 $60,000 Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)S3 INTERIOR

Event:

Type Year Cost Priority

Updated: MAR-10

Interior partitions in the gymnasium, corridors, washrooms and vestibules typically consist of painted masonry block walls. Interior partitions located between some of the classrooms typically consist of painted gypsum board with metal stud framing.

A demountable partition is located in the office area.

A movable folding panel divider is located in the gymnasium, stage area and library.

Steel framed glazing wall in west corridor at science rooms, home economics room, several classrooms, library and computer room.

A fixed interior glazed wall with GWG is located opposite the general office area.

In visible areas, fire-stopping appeared to have been provided in the original construction.

Page 13: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 13 of 61

C1020.01 Interior Swinging Doors (& Hardware)*

C1020.03 Interior Fire Doors*

C1030.01 Visual Display Boards** - All Section

C1030.02 Fabricated Compartments(Toilets/Showers)**

C1030.08 Interior Identifying Devices*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

1967

1967

1967

1967

1967

Installed

Installed

Installed

Installed

Installed

40

50

20

30

20

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Updated

Updated

Replace Visual Display Boards - All Sections

Replace toilet partitions in girls & boys washrooms& change rooms

Lifecycle Replacement

Lifecycle Replacement

2013

2013

$50,000

$25,000

Unassigned

Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-10

MAR-10

The interior doors are solid core wood doors complete with pressed steel frames. The doors have GWG inserts.

The doors in the corridors are either wood and/or hollow metal doors complete with pressed steel frames. The doors & frames are rated and have GWG inserts.

Whiteboards, chalkboards and tackboards are located in the teaching areas.

Prefinished metal washroom stall partitions are located in each boy's & girls washroom & change rooms

The room number or room name is mounted on or above the interior doors.

Page 14: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 14 of 61

C1030.10 Lockers** - All Section

C1030.12 Storage Shelving*

C1030.14 Toilet, Bath, and Laundry Accessories*

C2010 Stair Construction*

C2020.08 Stair Railings and Balustrades*

C2020.11 Other Stair Finishes*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

Rating

1967

1967

1967

1967

1967

1967

Installed

Installed

Installed

Installed

Installed

Installed

30

30

20

100

40

0

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Updated

Updated

Updated

Replace Lockers throughout the corridors

Lifecycle Replacement 2013 $90,000 Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Type Year Cost Priority

Updated: MAR-10

Prefinished metal lockers are located throughout the original school corridors.

Metal storage shelving throughout the vestibules, custodial utility rooms and staff supply rooms.

The washrooms are equipped with typical washroom accessories: Paper towel dispensers, toilet paper dispensers, hand-soap dispensers, waste bins and mirrors.

Cast in place concrete stairs are located in the mechanical room. The music room and gymnasium stage stairs are wood framed.

The handrails are constructed of steel with a paint finish.

The wood stairs to the stage are in the gym are stained.

Page 15: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 15 of 61

C3010.02 Wall Paneling**

C3010.06 Tile Wall Finishes**

C3010.11 Interior Wall Painting*

C3020.01.02 Paint Concrete Floor Finishes*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

1967

1967

1967

1967

Installed

Installed

Installed

Installed

30

40

10

10

Design Life

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Updated

Replace Wall Paneling in The Music Room & Stage Area

Replace ceramic wall tile (washrooms & change rooms)

Lifecycle Replacement

Lifecycle Replacement

2013

2013

$50,000

$30,000

Unassigned

Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-10

MAR-10

Vertical stained wood panels are located throughout the music room and above the stage wall.

A ceramic tile wall finish is located behind the urinals of the boy's washooms and showers in the change rooms.

The interior gypsum board & concrete block wall partitions throughout the school have a paint finish.

Painted/sealed concrete floors are located in the mechanical rooms, industrial arts room and storage rooms.

Page 16: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 16 of 61

C3020.02 Tile Floor Finishes** - All Section

C3020.04 Wood Flooring** - Stage floor

C3020.07 Resilient Flooring** - Rubber (GYM)

4 - Acceptable

3 - Marginal

5 - Good

Rating

Rating

Rating

1967

1967

2006

Installed

Installed

Installed

50

30

20

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Replace ceramic tile flooring (Area - 350m2)

Replace stage floor. (Approx Area - 60m2)

Replace Rubber flooring in the Gym ( Approx. Area- 450m2)

Lifecycle Replacement

Failure Replacement

Lifecycle Replacement

2017

2010

2026

$45,000

$10,000

$55,000

Unassigned

Low

Unassigned

Finish has deteriorated and joints on hardwood floor beginning to open up.

Concern:

Replace stage floor. (Approx Area - 60m2)Recommendation:

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Event:

Type

Type

Type

Year

Year

Year

Cost

Cost

Cost

Priority

Priority

Priority

Updated:

Updated:

Updated:

MAR-10

MAR-10

MAR-10

The main vestibules, washrooms and change rooms including showers have a ceramic tile floor finish.

The stage area has a hardwood floor.

The gymnasium has a rubber floor finish.

Deteriorated hardwood floor on Stage Area.

Page 17: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 17 of 61

C3020.07 Resilient Flooring** - Sheet Vinyl

C3020.07 Resilient Flooring** - VAT

C3020.08 Carpet Flooring** - 2000 Section

4 - Acceptable

3 - Marginal

5 - Good

Rating

Rating

Rating

1967

1967

2000

Installed

Installed

Installed

20

20

15

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Replace Sheet Vinyl flooring - (Approx Area - 1500m2)

Replace VAT Flooring in the 1975 Addition - Approx Area - 800m2

Replace Carpet Flooring (Approx. Area - 750m2)

Lifecycle Replacement

Failure Replacement

Lifecycle Replacement

2013

2011

2015

$200,000

$150,000

$80,000

Unassigned

Medium

Unassigned

The tiles are loose and worn throughout the science rooms and isolated storage areas.

Concern:

Replace all VAT flooring. The cost for the removal of the VAT tile is included.

Recommendation:

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Event:

Type

Type

Type

Year

Year

Year

Cost

Cost

Cost

Priority

Priority

Priority

Updated:

Updated:

Updated:

MAR-10

MAR-10

MAR-10

Sheet vinyl flooring is located throughout the majority of the corridors, original washrooms and 12 classrooms.

Original VAT flooring is located in the home economics/sewing room, science rooms, storage areas, caretakers room, corridors and printing room. All areas are in the 1975 Addition. A portion of the north-west corridor was being replaced in the Summer of 2009. The cost for the removal of the VAT tile is included.

Carpeting is located in 5 classrooms, library & in the administration areas.

Worn VAT floor finish.

Page 18: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 18 of 61

C3020.08 Carpet Flooring** - Music room

C3030.06 Acoustic Ceiling Treatment (Susp.T-Bar)** - All Section

C3030.07 Interior Ceiling Painting*

C3030.09 Other Ceiling Finishes* - Gymnasium

5 - Good

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

2009

1967

1967

1967

Installed

Installed

Installed

Installed

15

25

20

0

Design Life

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Updated

Replace carpeting in the Music Room ( Appeox. Area - 150m2)

Replace Acoustic Ceiling Treatment (Susp.T-Bar) - Approx. Area - 4000m2

Lifecycle Replacement

Lifecycle Replacement

2024

2013

$18,000

$350,000

Unassigned

Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-10

MAR-10

Carpeting is located in the music room. The carpet in the music room was replaced in the Summer of 2009.

The majority of the ceiling has either a 600 x 1200 and/or 600 x 600 acoustic tile and T-bar grid ceilings throughout the corridors, classrooms, administration area and washrooms.

All the interior gypsum board ceilings in the showers, change rooms and washrooms have a paint finish. The exposed wood & steel structure in the gymnasium and mechanical room have a paint finish.

The Gymnasium has 300 x 300 acoustic tiles laminated to the underside of deck.

Page 19: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 19 of 61

D2010.04 Sinks** - c.1967

D2010.04 Sinks** - c.1976

4 - Acceptable

4 - Acceptable

Rating

Rating

1967

1976

Installed

Installed

30

30

Design Life

Design Life

MAR-10

MAR-10

Updated

Updated

Replace the three general purpose single and double bowl stainless steel sinks in the c.1967 original building (one in the staff room and two in the art room)

Replace the two general purpose enameled steel sinks in classroom 2 (room 111) and in classroom 8 (room 124 or the library)

Replace the sinks in the c.1976 building addition (23)

Lifecycle Replacement

Failure Replacement

Lifecycle Replacement

2013

2012

2013

$4,500

$3,000

$35,000

Unassigned

Low

Unassigned

The two general purpose enameled steel sinks are in marginal condition due to chipping of the enameled surface and wear of the chrome plated trim.

Concern:

Replace the two general purpose enameled steel sinks in classroom 2 (room 111) and in classroom 8 (room 124 or the library).

Recommendation:

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)S4 MECHANICAL

Event:

Event:

Event:

Type

Type

Type

Year

Year

Year

Cost

Cost

Cost

Priority

Priority

Priority

Updated:

Updated:

Updated:

MAR-10

MAR-10

MAR-10

There are five sinks in the c.1967 original building including three general purpose single and double bowl stainless steel sinks and two general purpose enameled steel sinks.

There are 23 sinks in the c.1976 building addition including 19 general purpose single and double bowl stainless steel sinks, one fabricated sheet metal sink, one vitreous china sink, one enameled steel laundry tub, and one enameled steel custodial service sink.

Page 20: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 20 of 61

D2010.05 Showers** - c.1967

D2010.05 Showers** - c.1976

D2010.08 Drinking Fountains / Coolers** - c.1967

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

1967

1976

1967

Installed

Installed

Installed

30

30

35

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Replace the shower head and shower control for the shower (room 163) in the physical education office (room 162)

Replace the shower heads and controls for the 17 shower stations in the c.1976 building addition

Replace the six drinking fountains in the c.1967 original building

Lifecycle Replacement

Lifecycle Replacement

Lifecycle Replacement

2013

2013

2013

$1,500

$20,000

$9,000

Unassigned

Unassigned

Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Event:

Type

Type

Type

Year

Year

Year

Cost

Cost

Cost

Priority

Priority

Priority

Updated:

Updated:

Updated:

MAR-10

MAR-10

MAR-10

In the c.1967 original building, there is a shower stall (room 163) located in the physical education instructor's office (room162). The shower stall has ceramic tiled floors and walls. This element covers only the shower head and shower control for this shower.

In the c.1976 building addition, there are showers located in the boy's and girl's change rooms (rooms 157 and 155 respectively), as well as an individual shower in the physical education office (room 159). The girl's change room showers include a communal shower containing eight shower stations, and the boy's change room showers include a communal shower containing seven shower stations in addition to one individual shower stall. The shower stalls have ceramic tiled floors and walls. This element covers only the shower heads and shower controls for these showers.

In the c.1967 original building, there are six wall mounted non-refrigerated drinking fountains (three vitreous china and three fiberglass).

Page 21: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 21 of 61

D2010.08 Drinking Fountains / Coolers** - c.1976

D2010.09 Other Plumbing Fixtures* - Eyewash Fountains - c.2007

D2010.09 Other Plumbing Fixtures* - Wash Fountain - c.1976

4 - Acceptable

5 - Good

4 - Acceptable

Rating

Rating

Rating

1976

2007

1976

Installed

Installed

Installed

35

0

0

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Replace the drinking fountain in the c.1976 building addition

Lifecycle Replacement 2013 $1,500 Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Type Year Cost Priority

Updated: MAR-10

In the c.1976 building addition, there is one wall mounted non-refrigerated vitreous china drinking fountain.

There are three emergency eyewash stations located in the building, including one in science room 13 (classroom 13 or room 130), one in science room 18 (classroom 18 or room 131), and one in the industrial arts area (classroom 17 or room 139).

There is a stainless steel half Bradley type wash fountain located in the industrial arts area (classroom 17 or room 139).

Page 22: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 22 of 61

D2010.10 Washroom Fixtures (WC, Lav, Urnl)** - c.1967

D2010.10 Washroom Fixtures (WC, Lav, Urnl)** - c.1976

4 - Acceptable

4 - Acceptable

Rating

Rating

1967

1976

Installed

Installed

35

35

Design Life

Design Life

MAR-10

MAR-10

Updated

Updated

Replace the washroom plumbing fixtures in the c.1967 original building (14 toilets, 13 lavatories and seven urinals)

Replace two lavatories in the girl's washroom in the c.1967 original building (room 166)

Replace the washroom plumbing fixtures in the c.1976 building addition (eight toilets, five lavatories and two urinals)

Lifecycle Replacement

Repair

Lifecycle Replacement

2013

2010

2013

$59,000

$3,000

$26,000

Unassigned

Low

Unassigned

Two of the five counter mount enameled steel lavatories in thegirl's washroom in the c.1967 original building (room 166) are in marginal condition due to chipping of the enamel.

Concern:

Replace two lavatories in the girl's washroom in the c.1967 original building (room 166).

Recommendation:

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Event:

Type

Type

Type

Year

Year

Year

Cost

Cost

Cost

Priority

Priority

Priority

Updated:

Updated:

Updated:

MAR-10

MAR-10

MAR-10

Washroom plumbing fixtures in the c.1967 original building include 14 toilets (13 floor mount vitreous china flush valve type toilets and one floor mount vitreous china tank type toilet), 13 lavatories (two counter mount vitreous china lavatories,one wall mount vitreous china lavatory and ten counter mount enameled steel lavatories), and seven floor mount vitreous china tank type urinals.

Washroom plumbing fixtures in the c.1976 building addition include eight toilets (eight floor mount vitreous china flush valve type toilets), five lavatories (one wall mount vitreous china lavatory and four counter mount enameled steel lavatories), and two floor mount vitreous china tank type urinals.

Page 23: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 23 of 61

D2020.01.01 Pipes and Tubes: Domestic Water*

D2020.01.02 Valves: Domestic Water** - c.1967

D2020.01.02 Valves: Domestic Water** - c.1976

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

1967

1967

1976

Installed

Installed

Installed

40

40

40

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Replace the domestic water distribution system isolation valves in the c.1967 original building

Replace the domestic water distribution system isolation valves in the c.1976 building addition

Lifecycle Replacement

Lifecycle Replacement

2013

2016

$18,000

$20,000

Unassigned

Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-10

MAR-10

There is one domestic water supply to the building located in the west mechanical (room 150). The 100 mm diameter domestic water supply to the building feeds the building domestic water distribution system and the building fire protectionsystem (standpipe system). There is a water meter for the building domestic water supply (75 mm diameter). The domestic water supply piping is steel and domestic water distribution piping in the building is copper.

Domestic water system valves in the c.1967 original building include the domestic water distribution system zone isolatingvalves, and fixture isolating valves. The domestic water system valves include gate and ball type valves.

Domestic water system valves in the c.1976 building addition include the domestic water supply system main isolation valves, the domestic water distribution system zone isolating valves, and fixture isolating valves. The domestic water system valves include gate and ball type valves.

Page 24: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 24 of 61

D2020.01.03 Piping Specialties (Backflow Preventors)**

D2020.02.02 Plumbing Pumps: Domestic Water** - 1976 Section

D2020.02.02 Plumbing Pumps: Domestic Water** - c.1990

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

1991

2003

1990

Installed

Installed

Installed

20

20

20

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Replace the backflow prevention devices in the mechanical rooms (rooms 150 and 151) including two at 75 mm diameter, one at 25 mm diameter andone at 19 mm diameter

Replace the domestic hot water system circulation pump for the c.1976 building addition

Replace the domestic hot water system circulation pump for the c.1967 original building

Lifecycle Replacement

Lifecycle Replacement

Lifecycle Replacement

2013

2023

2013

$11,000

$2,000

$2,000

Unassigned

Unassigned

Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Event:

Type

Type

Type

Year

Year

Year

Cost

Cost

Cost

Priority

Priority

Priority

Updated:

Updated:

Updated:

MAR-10

MAR-10

MAR-10

There are four backflow prevention devices located in the mechanical rooms (rooms 150 and 151) including a 75 mm diameter device for the fire protection system (standpipe system), a 75 mm diameter device for the domestic water distribution system, a 25 mm diameter device for the make-up to the c.1967 original building hot water heating system, and a 19 mm diameter device for the make-up to the c.1976 building addition hot water heating system.

There is a domestic hot water system circulation pump for the c.1976 building addition which maintains the domestic hot water circulation loop at temperature.

There is a domestic hot water system circulation pump for the c.1967 original building which maintains the domestic hot water circulation loop at temperature.

Page 25: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 25 of 61

D2020.02.06 Domestic Water Heaters** - c.2000

D2020.02.06 Domestic Water Heaters** - c.2004

D2020.03 Water Supply Insulation: Domestic*

D2030.01 Waste and Vent Piping*

4 - Acceptable

5 - Good

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

2000

2004

1967

1967

Installed

Installed

Installed

Installed

20

20

40

50

Design Life

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Updated

Replace the domestic hot water heater in the east mechanical room serving the c.1967 original building

Replace the domestic hot water heater in the west mechanical room serving the c.1976 building addition

Lifecycle Replacement

Lifecycle Replacement

2020

2024

$3,000

$4,000

Unassigned

Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-10

MAR-10

There is a gas fired domestic hot water heater in the east mechanical room (room 151) serving the c.1967 original building. The DHW heater is a Rheem model PRO-50-45M with a volume of 50.0 USG (189 L) and an input heating capacity of 45,000 Btu/h (13.19 kW).

There is a gas fired domestic hot water heater in the west mechanical room (room 150) serving the c.1976 building addition. The DHW heater is a Bradford-White Corporation model D65T3993N with a volume of 65.0 USG (246 L) and an input heating capacity of 399,999 Btu/h (117.23 kW).

Where visible, the domestic water piping is insulated to prevent heat loss and condensation. The piping insulation assembly includes insulation with a fabric cover.

Visible waste and vent piping is generally copper in smaller diameters and cast iron in larger diameters. The below gradesanitary sewer piping is probably cast iron.

Page 26: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 26 of 61

D2030.02.04 Floor Drains*

D2040.01 Rain Water Drainage Piping Systems*

D2040.02.04 Roof Drains*

D3010.02 Gas Supply Systems*

D3020.02.01 Heating Boilers and Accessories: H.W.** - c.1967

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

1967

1967

1967

1967

1967

Installed

Installed

Installed

Installed

Installed

50

50

40

60

35

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Updated

Updated

Replace the hot water heating boiler in the east mechanical room serving the c.1967 original building

Lifecycle Replacement 2013 $125,000 Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Type Year Cost Priority

Updated: MAR-10

Floor drains are used at various locations in the building including the washrooms, change rooms and some entrance vestibules.

The flat roof levels of the building are drained using standard roof drains which discharge to interior rain water leaders which discharge to the municipal storm sewer system. The storm water drainage piping is generally cast iron.

Standard roof drains with metal strainers are used to collect storm water from the building flat roof areas.

The natural gas supply to the building is to the meter room (room 167) on the south side of the building adjacent to the mechanical rooms. The gas service is underground to the meter room where the gas supply line comes above grade andenters the meter room through the wall. The gas meter and pressure reducing station are located in the meter room. Natural gas is used for the building hot water heating boilers, domestic hot water heaters, for the science room bench outlets, and for the furnaces in the portable classrooms. The natural gas piping is generally steel.

The east mechanical room (room 151) contains a Cleaver Brooks model CB700-125 packaged hot water boiler serving the c.1967 original building. The boiler has an input heating capacity of 5,230,000 Btu/h (1,532.91 kW).

Page 27: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 27 of 61

D3020.02.01 Heating Boilers and Accessories: H.W.** - c.1976

D3020.02.02 Chimneys (&Comb. Air): H.W. Boiler** - c.1967

D3020.02.02 Chimneys (&Comb. Air): H.W. Boiler** - c.1976

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

1976

1967

1976

Installed

Installed

Installed

35

30

30

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Replace the six hot water heating boilers in the west mechanical room serving the c.1976 building addition

Replace the boiler breeching in the east mechanical room including the replacement of the combustion air supply

Replace the boiler breeching in the west mechanical room including the replacement of the combustion air supply

Lifecycle Replacement

Lifecycle Replacement

Lifecycle Replacement

2013

2013

2013

$60,000

$8,000

$9,000

Unassigned

Unassigned

Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Event:

Type

Type

Type

Year

Year

Year

Cost

Cost

Cost

Priority

Priority

Priority

Updated:

Updated:

Updated:

MAR-10

MAR-10

MAR-10

The west mechanical room (room 150) contains six Slant/Fin Limited model G300-S hot water boilers serving the c.1976 building addition. The boilers have an input heating capacity of 270,000 Btu/h (79.14 kW) each.

The boiler in the east mechanical room serving the c.1967 original building has insulated breeching for the discharge of combustion gases to a stack which penetrates the roof above the east mechanical room. There is an insulated combustion air supply to the east mechanical room located on the east mechanical room mezzanine.

The boilers in the west mechanical room serving the c.1976 building addition have insulated breeching for the discharge of combustion gases to a common stack which penetrates the roof above the west mechanical room. There is an insulated combustion air supply to the west mechanical room located on the west wall.

Page 28: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 28 of 61

D3020.02.03 Water Treatment: H. W. Boiler*

D3040.01.01 Air Handling Units: Air Distribution** - c.1967

D3040.01.01 Air Handling Units: Air Distribution** - c.1976

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

0

1967

1976

Installed

Installed

Installed

30

30

30

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Replace the central air handling unit and the gymnasium air handling unit serving the c.1967 original building (located on the east mechanical room mezzanine)

Replace the air handling unit serving the c.1976 building addition (located in the west mechanical room)

Lifecycle Replacement

Lifecycle Replacement

2013

2013

$180,000

$120,000

Unassigned

Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-10

MAR-10

Water treatment for the two closed loop hot water heating systems serving the c.1967 original building and the c.1976 building addition consist of manual chemical addition via chemical pot feeders and sidestream filters in parallel with the hot water circulation pumps. The chemical pot feeders and sidestream filters are located in the east and west mechanical rooms.

There are two air handling units providing ventilation for the c.1967 original building, including the main or central air handling unit and the gymnasium air handling unit, both located on the east mechanical room mezzanine. The main air handling unit (American Standard model FA2V20 with a flow capacity of 13,465 CFM or 6,355 L/s) is a mixed air unit and includes filters, dampers, a supply fan, a mixing section, and a hot water heating coil with a circulation pump. The gymnasium air handling unit (American Standard model FA2V18 with a flow capacity of 7,450 CFM or 3,516 L/s) is a mixed air unit and includes filters, dampers, a supply fan, a mixing section and two hot water heating coils with circulation pumps.

There is one air handling unit providing ventilation for the c.1976 building addition. The air handling unit is located in the west mechanical room. The air handling unit (Mark Hot model WC-603-R1) is a mixed air unit and includes filters, dampers, a supply fan, a mixing section, and a hot water heating coil with a circulation pump.

Page 29: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 29 of 61

D3040.01.02 Fans: Air Distribution (Remote from AHU)*

D3040.01.04 Ducts: Air Distribution*

D3040.01.07 Air Outlets & Inlets:Air Distribution*

D3040.03.01 Hot Water Distribution Systems** - c.1967

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

1967

1967

1967

1967

Installed

Installed

Installed

Installed

30

50

30

40

Design Life

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Updated

Replace the c.1967 hot water distribution system

Lifecycle Replacement 2013 $225,000 Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Type Year Cost Priority

Updated: MAR-10

Air distribution fans remote from the air handling units include the return air fan for the central air handling unit serving thec.1967 original building. The return air fan is located in the east mechanical room.

The air distribution ducts include the supply air, return air, exhaust air and fresh air duct systems for the three air handlingunits (two serving the c.1967 original building and one serving the c.1976 building addition). The duct systems include associated components not specifically listed elsewhere, including duct insulation, turning vanes, dampers, mixing boxes,etc. The air distribution systems are constant volume type systems.

Air outlets and inlets include supply air diffusers and return air grilles. Supply air diffusers include square diffusers in the T-bar ceiling grid and floor registers in the gymnasium. The return air grilles in the c.1976 building addition are generally egg crate type grilles in the T-bar ceiling grid and in the c.1967 original building transfer grilles above the doors provide return flow into the corridors.

The hot water heating system for the c.1967 original building provides hot water for the air handling unit heating coils and for the original building hydronic terminal units (including force flow convectors and finned tube radiation cabinets). Thereare two main hot water circulation pumps (pump A and pump B) and three coil circulation pumps located on the east mechanical room mezzanine, and the hot water system expansion tank is also located on the east mechanical room mezzanine. The hot water distribution system includes all components of the closed loop hot water heating system including piping, valves, piping insulation, piping specialties, circulation pumps, and the expansion tank.

Page 30: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 30 of 61

D3040.03.01 Hot Water Distribution Systems** - c.1976

D3040.04.01 Fans: Exhaust** - c.1967

D3040.04.01 Fans: Exhaust** - c.1976

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

1976

1967

1976

Installed

Installed

Installed

40

30

30

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Replace the c.1976 hot water distribution system

Replace the three exhaust fans serving the c.1967 original building

Replace the nine exhaust fans serving the c.1976 building addition

Lifecycle Replacement

Lifecycle Replacement

Lifecycle Replacement

2016

2013

2013

$200,000

$11,000

$27,000

Unassigned

Unassigned

Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Event:

Type

Type

Type

Year

Year

Year

Cost

Cost

Cost

Priority

Priority

Priority

Updated:

Updated:

Updated:

MAR-10

MAR-10

MAR-10

The hot water heating system for the c.1976 building addition provides hot water for the air handling unit heating coil and for the building addition hydronic terminal units (including force flow convectors, finned tube radiation cabinets and a unit heater). There are two main hot water circulation pumps (pumps P1and P2) and one coil circulation pump located in the west mechanical room, and the hot water system expansion tank is also located in the west mechanical room. The hot water distribution system includes all components of the closed loop hot water heating system including piping, valves, piping insulation, piping specialties, circulation pumps, and the expansion tank.

Exhaust fans for the c.1967 original building include two rooftop sanitary exhaust fans and one general exhaust fan located on the east mechanical room mezzanine.

Exhaust fans for the c.1976 building addition include two rooftop sanitary exhaust fans for the washrooms and change rooms, three rooftop exhaust fans for the industrial arts area (including welding booth exhausts and a paint booth exhaust), one rooftop exhaust fan for the mechanical room, and three small exhaust fans for the kiln hood, the flammablestorage cabinet and the acid storage cabinet.

Page 31: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 31 of 61

D3040.04.02 Air Cleaning Devices: Exhaust* - Dust Collection System

D3040.04.03 Ducts: Exhaust*

D3040.04.05 Air Outlets and Inlets: Exhaust*

D3050.05.01 Convectors** - c.1967

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

1976

1967

1967

1967

Installed

Installed

Installed

Installed

0

50

30

30

Design Life

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Updated

Replace the four force flow convection cabinets in the c.1967 original building

Lifecycle Replacement 2013 $16,000 Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Type Year Cost Priority

Updated: MAR-10

In the industrial arts woodworking area there is a dust collection system. The dust collector is an Apsco unit with an automatic shaker motor. The exhaust from the dust collection system discharges back to the building (100% recirculation). This element includes the collection and discharge duct systems associated with the dust collector.

Exhaust duct systems include the collection ducts associated with the building exhaust fans and the discharge ducts associated with the interior exhaust fans. Most of the exhaust ducts are constructed of zinc coated steel and the flammable storage cabinet exhaust duct is stainless steel.

Exhaust air inlets include the inlet grilles associated with the exhaust system collection ducts, including the various hoods used in the industrial arts area. Most of the exhaust air inlets are framed ceiling grilles. Exhaust air outlets include the exhaust fan discharge vents, louvres and goosenecks, where applicable (does not apply to the roof mounted exhaust fans).

Force flow convection cabinets (or cabinet unit heaters) are used at high heat load locations (entrance vestibules). Thereare four ceiling mounted force flow convection cabinets in the c.1967 original building.

Page 32: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 32 of 61

D3050.05.01 Convectors** - c.1976

D3050.05.03 Finned Tube Radiation** - c.1967

D3050.05.03 Finned Tube Radiation** - c.1976

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

1976

1967

1976

Installed

Installed

Installed

30

40

40

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Replace the five force flow convection cabinets in the c.1976 building addition

Replace the finned tube radiation cabinets in the c.1967 original building

Replace the finned tube radiation cabinets in the c.1976 building addition

Lifecycle Replacement

Lifecycle Replacement

Lifecycle Replacement

2013

2013

2016

$20,000

$90,000

$80,000

Unassigned

Unassigned

Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Event:

Type

Type

Type

Year

Year

Year

Cost

Cost

Cost

Priority

Priority

Priority

Updated:

Updated:

Updated:

MAR-10

MAR-10

MAR-10

Force flow convection cabinets (or cabinet unit heaters) are used at high heat load locations (entrance vestibules). Thereare five ceiling mounted force flow convection cabinets in the c.1976 building addition.

Finned tube radiation cabinets are used to provide perimeter heating in the c.1967 original building.

Finned tube radiation cabinets are used to provide perimeter heating in the c.1976 building addition.

Page 33: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 33 of 61

D3050.05.06 Unit Heaters** - c.1976

D3060.02.02 Pneumatic Controls** - c.1967

4 - Acceptable

4 - Acceptable

Rating

Rating

1976

1967

Installed

Installed

30

40

Design Life

Design Life

MAR-10

MAR-10

Updated

Updated

Replace the unit heater in the west mechanical room

Replace the control air compressor for the c.1967 original building (located on the east mechanical room mezzanine)

Replace the pneumatic controls in the c.1967 original building excluding the control air supply system in the east mechanical room

Lifecycle Replacement

Failure Replacement

Lifecycle Replacement

2013

2011

2013

$4,000

$4,000

$16,000

Unassigned

Low

Unassigned

The control air compressor for the c.1967 original building is in marginal condition due to wear.

Concern:

Replace the control air compressor for the c.1967 original building (located on the east mechanical room mezzanine).

Recommendation:

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Event:

Type

Type

Type

Year

Year

Year

Cost

Cost

Cost

Priority

Priority

Priority

Updated:

Updated:

Updated:

MAR-10

MAR-10

MAR-10

A unit heater provides heating in the west mechanical room (room 150).

The HVAC system controls and actuators for the c.1967 original building are generally pneumatic (some electric controls are also used). Pneumatic controls include thermostats, valve actuators and damper actuators. The control air supply system is located on the east mechanical room mezzanine. The control air supply system consists of an air compressor mounted on an air receiver tank with a separate refrigerated air dryer. This element includes the control air distribution system.

Page 34: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 34 of 61

D3060.02.02 Pneumatic Controls** - c.1976

D3060.02.05 Building Systems Controls (BMCS, EMCS)**

D4020 Standpipes*

D4030.01 Fire Extinguisher, Cabinets and Accessories*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

1976

2004

1967

1967

Installed

Installed

Installed

Installed

40

25

60

30

Design Life

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Updated

Replace the pneumatic controls in the c.1976 building addition including the two control air supply systems in the west mechanical room

Replace the Johnson Controls Metasys Building Management and Control system in the west mechanical room (room 150)

Lifecycle Replacement

Lifecycle Replacement

2016

2029

$18,000

$60,000

Unassigned

Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-10

MAR-10

The HVAC system controls and actuators for the c.1976 building addition are generally pneumatic (some electric controls are also used). Pneumatic controls include thermostats, valve actuators and damper actuators. The control air supply systems are located in the west mechanical room. The two control air supply systems each consist of an air compressor mounted on an air receiver tank, and there is one shared refrigerated air dryer (the air dryer was replaced in c.2006). This element includes the control air distribution system.

In the west mechanical room (room 150), there is a Johnson Controls Metasys Building Management and Control Systemwhich monitors and controls the air handling units and other equipment in the building (including bells, carplugs, emergency lights, etc.).

The c.1967 original building is equipped with a standpipe system feeding standard fire hose cabinets located throughout the original building. The c.1976 building addition is not equipped with a standpipe system.

Fire extinguishers are located throughout the building in the fire hose cabinets (c.1967 original building only), in recessed wall cabinets (c.1976 building addition only), and on wall mount brackets.

Page 35: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 35 of 61

D5010.03 Main Electrical Switchboards (Main Distribution)**

D5010.05 Electrical Branch Circuit Panelboards (Secondary Distribution)** - 1967

3 - Marginal

3 - Marginal

Rating

Rating

1976

1967

Installed

Installed

40

30

Design Life

Design Life

MAR-10

MAR-10

Updated

Updated

Replace Main Service

Replace Panels Installed in 1967

Failure Replacement

Failure Replacement

2010

2010

$30,000

$27,500

High

Medium

Service is near end of life cycle. No surge protection has been provided.

The lighting panels (1967) are at the end of their life expectancy. Over the life of the panel, breaker contacts become worn and the breakers will no longer operate correctly and may trip unnecessarily. Older panels do not readily accept newer style breakers.

Concern:

Concern:

Replace main disconnect and splitter distribution with a new 800A service entrance switchboard c/w surge protection.

Replace aged panelboards with larger circuit capacity panels.

Recommendation:

Recommendation:

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)S5 ELECTRICAL

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-10

MAR-10

The incoming hydro service to St. Vincent De Paul School is a 120/208V, 3-phase, 4-wire service from an Enmax padmounted transformer, located on the South side of the school. The Enmax meter is located in the main electrical/mechanical room (Rm. 151). The main electrical service consists of a CEB main disconnect switch rated 800A, 120/208V, 3-phase, 4-wire and an 800A splitter. The splitter has fusible disconnect switches feeding six branch circuit panels and the original 1967 Westinghouse 400A, CDP panel.

The original Westinghouse CDP panel is rated 400A, 120/208V, 3-phase, 4-wire. The CDP panel feeds five Westinghouse branch circuit panels, the portables, dust collector and mechanical equipment splitters in boiler room 150 and mechanical room 151. The Westinghouse panels have bolt-on breakers and copper bussing.

Consequences of Deferral:

Consequences of Deferral:

Equipment failure could leve the building without power for prolonged period of time

Deferring replacement could lead to partial power outages and intermittent tripping of breakers as well as increased maintenance costs.

800A, 120/208V main service disconnect and splitter.

Aged 400A Westinghouse CDP panel.

Page 36: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 36 of 61

D5010.05 Electrical Branch Circuit Panelboards (Secondary Distribution)** - 1976

D5010.07.02 Motor Starters and Accessories** - 1967

4 - Acceptable

3 - Marginal

Rating

Rating

1976

1967

Installed

Installed

30

30

Design Life

Design Life

MAR-10

MAR-10

Updated

Updated

Replace Panels Installed in 1976

Replace Motor Starters (1967)

Lifecycle Replacement

Failure Replacement

2013

2010

$21,000

$7,500

Unassigned

Medium

The original motor starters are aged. Replacement parts are not available.

Concern:

Replace aged starters with new combination type starters.Recommendation:

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-10

MAR-10

There are six Federal Pioneer, 120/208V, 3-phase, 4-wire branch circuit panels fed from the 800A main splitter. The Federal Pioneer panels have bolt-on breakers and copper bussing.

Westinghouse type FVNR starters have been installed in the main mechanical room (Rm. 151).

Consequences of Deferral:If the starter fails, the associated mechanical equipment will be inoperative while repairs are being made.

Aged starters (1967).

Page 37: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 37 of 61

D5010.07.02 Motor Starters and Accessories** - 1976

D5020.01 Electrical Branch Wiring*

D5020.02.01 Lighting Accessories (Lighting Controls)*

3 - Marginal

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

1976

1967

1967

Installed

Installed

Installed

30

50

30

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Replace Motor Starters (1976)

Failure Replacement 2010 $7,500 Medium

The original motor starters are aged. Replacement parts are not available.

Concern:

Replace aged starters with new combination type starters.Recommendation:

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Type Year Cost Priority

Updated: MAR-10

Westinghouse type FVNR starters have been installed in boiler room 150. There are manual motor rated starter switchesfor fractional horsepower motor loads. An Allen Bradley starter has been provided for the main supply fan.

The majority of the cabling is standard building wire in EMT conduit. Armoured cable has been provided, in selected locations, for final connections to mechanical and miscellaneous equipment.

The lighting within the school is typically controlled by 120V line voltage switches or by low voltage switches. The relays for the low voltage lighting switches are located in the ceiling space.

Consequences of Deferral:If the starter fails, the associated mechanical equipment will be inoperative while repairs are being made.

Aged starters (1976).

Page 38: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 38 of 61

D5020.02.02.02 Interior Florescent Fixtures** - T12

D5020.02.02.02 Interior Florescent Fixtures** - T8

4 - Acceptable

5 - Good

Rating

Rating

1976

2005

Installed

Installed

30

30

Design Life

Design Life

MAR-10

MAR-10

Updated

Updated

Replace Interior Fluorescent Fixtures

Retrofit T12 Fluorescent Fixtures

Replace Interior T8 Fluorescent Fixtures

Lifecycle Replacement

Energy Efficiency Upgrade

Lifecycle Replacement

2013

2011

2035

$164,000

$110,000

$89,000

Unassigned

Medium

Unassigned

The T12 lamps are not energy efficient and may be phased out by manufacturers.

Concern:

Retrofit existing fixtures with new T8 lamps and electronic ballasts.

Recommendation:

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Event:

Type

Type

Type

Year

Year

Year

Cost

Cost

Cost

Priority

Priority

Priority

Updated:

Updated:

Updated:

MAR-10

MAR-10

MAR-10

The typical classroom lighting within the school consists of recessed 2 ft. x 4 ft. or recessed 1 ft. x 4 ft., T12 fluorescent fixtures. Surface mounted 1 ft. x 4 ft. or fluorescent wraps have been provided in areas of the school. The gymnasium lighting consists of 2-lamp T12 fluorescent fixtures with wire guards, surface mounted on the underside of the roof trusses.

The classroom lighting within the original school consists of recessed 2 ft. x 4 ft., T8 fluorescent fixtures.

Page 39: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 39 of 61

D5020.02.03.02 Emergency Lighting Battery Packs**

D5020.02.03.03 Exit Signs*

D5020.02.05 Special Purpose Lighting*

3 - Marginal

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

1976

2001

1976

Installed

Installed

Installed

30

30

30

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Replace Aged Emergency Lighting Battery Units

Failure Replacement 2010 $15,000 High

Some of the emergency lighting battery units are aged. Replacement parts are not readily available and units may notbe reliable.

Concern:

Replace aged emergency lighting battery units. Provide additional emergency lighting where required.

Recommendation:

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Type Year Cost Priority

Updated: MAR-10

The emergency lighting in the building is provided by battery powered emergency lighting units and remote emergency lighting heads.

Exit signs are generally located to indicate building exits and egress routes to exits. The majority of the exit signs in the main school have LED lamps.

Floodlighting theatrical fixtures have been provided in the stage area. The fixtures are controlled by portable dimming equipment.

Aged emergency lighting battery unit.

Page 40: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 40 of 61

D5020.03.01.01 Exterior Incandescent Fixtures*

D5020.03.01.04 Exterior H.P. Sodium Fixtures*

D5020.03.02 Lighting Accessories: Exterior (Lighting Controls)*

3 - Marginal

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

1967

1990

1990

Installed

Installed

Installed

30

30

30

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Replace Exterior Incandescent Lighting

Failure Replacement 2011 $1,000 Low

The incandescent exterior lighting is not energy efficient. The fixtures are aged.

Concern:

Replace existing incandescent exterior lighting with energy efficient exterior lighting fixtures.

Recommendation:

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Type Year Cost Priority

Updated: MAR-10

Recessed square incandescent fixtures are located at the main entrance.

Surface mounted 70W HPS fixtures have been provided around the perimeter of the building.

The exterior lighting is typically controlled by photocells.

Aged incandescent fixtures in entrance canopy.

Page 41: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 41 of 61

D5030.01 Detection and Fire Alarm**

D5030.02.02 Intrusion Detection**

3 - Marginal

4 - Acceptable

Rating

Rating

1976

1995

Installed

Installed

25

25

Design Life

Design Life

MAR-10

MAR-10

Updated

Updated

Replace Fire Alarm System

Replace Intrusion Detection System

Failure Replacement

Lifecycle Replacement

2010

2020

$110,000

$30,000

High

Unassigned

The Edwards 6500 fire alarm panel is obsolete and replacement parts are difficult to source. Strobes have not been provided within the building.

Concern:

Replace fire alarm system with new addressable system. Provide strobes to meet the requirements of the A.B.C.

Recommendation:

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-10

MAR-10

The fire alarm system is a single stage, conventional, zoned system with an Edwards 6500 fire alarm control panel. The control panel is located in the Caretaker's room (Rm. 149). An active graphic remote annunciator is located in the main entrance vestibule. The audible devices within the school are bells. Duct mounted smoke detection has been provided for the air handling unit. There are 12 active zones and 8 spare zones.

The security system is a Silent Knight - Regency system with the main panels located in the mechanical room 150. A security system keypad has been installed at the main entrance. PIR motion detectors have been provided throughout the school.

Consequences of Deferral:The hearing impaired may not know the building is in alarm.

Edwards 6500 fire alarm control panel.

Page 42: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 42 of 61

D5030.03 Clock and Program Systems*

D5030.04.01 Telephone Systems*

D5030.04.04 Data Systems*

4 - Acceptable

5 - Good

5 - Good

Rating

Rating

Rating

1990

2003

2003

Installed

Installed

Installed

25

25

25

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

The clocks within the school are typically battery powered clocks.

The telephone system is a rack mounted Nortel Business Communications Manager system. Nortel telephone handsets are located in areas such as the classrooms and general office. A telephone backboard and BIX block have been provided for termination of telephone cabling.

The servers and patch panels are rack mounted. Cat. 5E or Cat 6 cables are used for the network wiring within the school. Supernet and a fiber feed have been brought into the school. Wireless networking has been provided within the school.

Page 43: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 43 of 61

D5030.05 Public Address and Music Systems**

D5030.06 Television Systems*

3 - Marginal

5 - Good

Rating

Rating

1976

1967

Installed

Installed

25

20

Design Life

Design Life

MAR-10

MAR-10

Updated

Updated

Install new Public Address system

Failure Replacement 2010 $30,000 Medium

The public address system is nearing the end of its life cycle, sound quality is poor.

Concern:

Replace public address system.Recommendation:

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Type Year Cost Priority

Updated: MAR-10

The public address system is a rack mounted Dukane system with selector switches for the individual classrooms. Speakers are typically round, recessed ceiling mounted units. The system rack is located in the general office area. Call switches are located in each classroom.

A cable TV outlet has been provided in the library.

Dukane public address system.

Page 44: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 44 of 61

E1020.03 Theater and Stage Equipment*

E1090.07 Athletic, Recreational, and Therapeutic Equipment*

E2010.02 Fixed Casework** - 1967 Section

E2010.02 Fixed Casework** - 1975 Section

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

1967

1967

1967

1975

Installed

Installed

Installed

Installed

25

15

35

35

Design Life

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Updated

Replace Fixed Casework - 1967 Section

Replace Fixed Casework - 1975 Section

Lifecycle Replacement

Lifecycle Replacement

2013

2013

$250,000

$300,000

Unassigned

Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)S6 EQUIPMENT, FURNISHINGS AND SPECIAL CONSTRUCTION

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-10

MAR-10

A vinyl folding partition and curtains are located on the gymnasium stage area.

Fixed & movable basketball hoops, climbing ropes, climbing bar walls, gymnastic rings (suspended) and an electronic scoreboard are located in the gymnasium. A movable panel divider is located in the gymnasium.

Each classroom is equipped with custom open faced and/or cabinet wood units along the exterior wall. The science room & prep rooms have upper and lower cabinet wood units with a clear finish. The library has fixed and moveable wood shelving casework. Glass display cabinets are located in the main entrance area and in the corridors. The staff room is equipped with upper and lower wood cabinet units. The kitchen & washrooms have plastic laminate counter tops. All the cabinets have a plastic laminate finish. Solid core wood doors at under stage storage

Each classroom is equipped with custom open faced and/or cabinet wood units along the exterior wall. The industrial arts lab, home economics/sewing room, music room & science rooms have fixed tables & upper and lower cabinet wood unitsaround the perimeter of the room. The industrial arts lab has wood tables with laminated wood plank table top & wood working benches. Glass display cabinets are located in the corridors. The washrooms have plastic laminate counter tops.

Page 45: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 45 of 61

E2010.03.06 Curtains and Drapes** - All Section

E2020.02.03 Furniture*

4 - Acceptable

4 - Acceptable

Rating

Rating

1967

0

Installed

Installed

30

0

Design Life

Design Life

MAR-10

MAR-10

Updated

Updated

Replace Curtains throughout the school ( 26 exterior windows)

Lifecycle Replacement 2013 $26,000 Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Type Year Cost Priority

Updated: MAR-10

Fabric curtains in administration area and classrooms.

All classroom, labs and offices areas are equipped with movable desks and chairs.

Page 46: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 46 of 61

F1010.02.04 Portable and Mobile Buildings** - 1985 Section

4 - AcceptableRating

1985Installed

30Design Life

MAR-10Updated

Building Envelope Lifecycle Replacement

Electrical Lifecycle Replcaement

Interior Lifecycle Replacement

Lifecycle Replacement

Lifecycle Replacement

2015

2015

$55,000

$15,000

Unassigned

Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-10

MAR-10

Portable C85CS13 - Age 1985- Area 90m2 Structure: - Wood frame construction with concrete piles bearing on undisturbed soil. Envelope: - Cladding - A painted plywood sheathing skirt with vents is located at the base of the elevation. The exterior skin has a painted vertical wood & metal siding finish with wood framing construction. - Windows - The exterior windows (1) are aluminum frame operable single-hung type windows (original). The window hasprotective metal security screens. - Roof Covering - The roof has an SBS roof assembly. Interior: - Flooring - Carpet (90%) & Sheet Vinyl (10%) at entrance - Ceiling - 2'x4' Suspended Acoustical tile ceiling - Walls - Painted gypsum board walls with either metal or wood wall construction. - Interior Doors - Painted steel door & frame assembly - Equipment - Chalkboards, tackboards, open wood shelving, wall mounted coat hooks & curtains. Electrical Summary A 120/240V Commander panel (single phase, 3-wire) has been provided for the portable. The lighting fixture used in the portable classroom is a surface mounted 1' x 4', T12 fluorescent fixture. A P.A. speaker and a battery clock have been provided in the portable. The portable is connected to the school fire alarm system. The electrical systems for the portable were found to be in acceptable condition. Mechanical Summary The portable is heated by a natural gas fired forced air furnace with a supply air distribution duct system that runs along one wall just below ceiling level. The furnace is controlled by a digital thermostat. The furnace is located in an enclosure in one corner of the portable. The enclosure has an exterior combustion air supply for the furnace and a fresh air supply for the portable. The portable has a rooftop exhaust fan and two rooftop turbine type ventilators. Storm drainage from the portable roof is collected by two roof drains which discharge to interior rain water leaders which discharge to the school storm sewer system. Fire protection is provided by a fire extinguisher in the common corridor which provides access to the six portables and the connecting link.

Page 47: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 47 of 61

Mechanical Lifecycle Replacement

Lifecycle Replacement

Lifecycle Replacement

2015

2015

$22,000

$18,000

Unassigned

Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-10

MAR-10

Page 48: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 48 of 61

F1010.02.04 Portable and Mobile Buildings** - 1989 Section

4 - AcceptableRating

1989Installed

30Design Life

MAR-10Updated

Building Envelope Lifecycle Replacement

Electrical Lifecycle Replacement

Interior Lifecycle Replacement

Lifecycle Replacement

Lifecycle Replacement

2019

2019

$55,000

$15,000

Unassigned

Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-10

MAR-10

Portable C89CS10 - Age 1989- Area 90m2 (includes interior corridor) Structure: - Wood frame construction with concrete piles bearing on undisturbed soil. Envelope: - Cladding - A painted plywood sheathing skirt with vents is located at the base of the elevation. The exterior skin has a painted vertical wood & metal siding finish with wood framing construction. - Windows - The exterior windows (1) are aluminum frame operable single-hung type windows (original). The window hasprotective metal security screens. - Roof Covering - The roof has an SBS roof assembly. Interior: - Flooring - Sheet Vinyl (100%) installed in Summer 2009 - Ceiling - 2'x4' Suspended Acoustical tile ceiling - Walls - Painted gypsum board walls with either metal or wood wall construction. - Interior Doors - Painted steel door & frame assembly - Equipment - Chalkboards, tackboards, open wood shelving, wall mounted coat hooks & curtains. Electrical Summary A 120/240V Commander panel (single phase, 3-wire) has been provided for the portable. The lighting fixture used in the portable classroom is a recessed 1' x 4', T12 fluorescent fixture. A P.A. speaker and a battery clock have been provided in the portable. The portable is connected to the school fire alarm system. The electrical systems for the portable were found to be in acceptable condition. Mechanical Summary The portable is heated by a natural gas fired forced air furnace with a supply air distribution duct system that runs along one wall just below ceiling level. The furnace is controlled by a digital thermostat. The furnace is located in an enclosure in one corner of the portable. The enclosure has an exterior combustion air supply for the furnace and a fresh air supply for the portable. The portable has a rooftop exhaust fan and two rooftop turbine type ventilators. Storm drainage from the portable roof is collected by two roof drains which discharge to interior rain water leaders which discharge to the school storm sewer system. Fire protection is provided by a fire extinguisher in the common corridor which provides access to the six portables and the connecting link.

Page 49: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 49 of 61

Mechanical Lifecycle Replacement

Lifecycle Replacement

Lifecycle Replacement

2019

2019

$22,000

$18,000

Unassigned

Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-10

MAR-10

Page 50: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 50 of 61

F1010.02.04 Portable and Mobile Buildings** - 1997 Section

5 - GoodRating

1997Installed

30Design Life

MAR-10Updated

Building Envelope Lifecycle Replacement

Lifecycle Replacement 2027 $55,000 Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Type Year Cost Priority

Updated: MAR-10

Portable C97CS21 - Age 1997- Area 90m2 Structure: - Wood frame construction with concrete piles bearing on undisturbed soil. Envelope: - Cladding - A painted plywood sheathing skirt with vents is located at the base of the elevation. The exterior skin has a painted vertical wood & metal siding finish with wood framing construction. - Windows - The exterior windows (2) are aluminum frame operable single-hung type windows (original). The window hasprotective metal security screens. - Roof Covering - The roof has an SBS roof assembly. Interior: - Flooring - Carpet (90%) & Sheet Vinyl (10%) at entrance - Ceiling - 2'x4' Suspended Acoustical tile ceiling - Walls - Painted gypsum board walls with either metal or wood wall construction. - Interior Doors - Painted steel door & frame assembly - Equipment - Chalkboards, tackboards, open wood shelving, wall mounted coat hooks & curtains. Electrical Summary A 120/240V Cutler Hammer panel (single phase, 3-wire) has been provided for the portable. The lighting fixture used in the portable classroom is a recessed 1' x 4', T8 fluorescent fixture. A P.A. speaker and a battery clock have been provided in the portable. The portable is connected to the school fire alarm system. The electrical systems for the portable were found to be in acceptable condition. Mechanical Summary The portable is heated by a natural gas fired forced air furnace with a supply air distribution duct system that runs along one wall just below ceiling level. The furnace is controlled by a digital thermostat. The furnace is located in an enclosure in one corner of the portable. The enclosure has an exterior combustion air supply for the furnace and a fresh air supply for the portable. The portable has a rooftop exhaust fan and two rooftop turbine type ventilators. Storm drainage from the portable roof is collected by two roof drains which discharge to interior rain water leaders which discharge to the school storm sewer system. Fire protection is provided by a fire extinguisher in the common corridor which provides access to the six portables and the connecting link.

Page 51: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 51 of 61

Electrical Lifecycle Replacement

Interior Lifecycle Replacement

Mechanical Lifecycle Replacement

Lifecycle Replacement

Lifecycle Replacement

Lifecycle Replacement

2027

2027

2027

$15,000

$22,000

$18,000

Unassigned

Unassigned

Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Event:

Type

Type

Type

Year

Year

Year

Cost

Cost

Cost

Priority

Priority

Priority

Updated:

Updated:

Updated:

MAR-10

MAR-10

MAR-10

Page 52: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 52 of 61

F1010.02.04 Portable and Mobile Buildings** - 1997 Section

5 - GoodRating

1997Installed

30Design Life

MAR-10Updated

Building Envelope Lifecycle Replacement

Electrical Lifecycle Replacement

Lifecycle Replacement

Lifecycle Replacement

2027

2027

$55,000

$15,000

Unassigned

Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-10

MAR-10

Portable C97CS02 - Age 1997- Area 90m2 (includes interior corridor) Structure: - Wood frame construction with concrete piles bearing on undisturbed soil. Envelope: - Cladding - A painted plywood sheathing skirt with vents is located at the base of the elevation. The exterior skin has a painted vertical wood & metal siding finish with wood framing construction. - Windows - The exterior windows (2) are aluminum frame operable single-hung type windows (original). The window hasprotective metal security screens. - Roof Covering - The roof has an SBS roof assembly. Interior: - Flooring - Carpet (90%) & Sheet Vinyl (10%) at entrance - Ceiling - 2'x4' Suspended Acoustical tile ceiling - Walls - Painted gypsum board walls with either metal or wood wall construction. - Interior Doors - Painted steel door & frame assembly - Equipment - Chalkboards, tackboards, open wood shelving, wall mounted coat hooks & curtains. Electrical Summary A 120/240V Cutler Hammer panel (single phase, 3-wire) has been provided for the portable. The lighting fixture used in the portable classroom is a recessed 1' x 4', T8 fluorescent fixture. A P.A. speaker and a battery clock have been provided in the portable. The portable is connected to the school fire alarm system. The electrical systems for the portable were found to be in acceptable condition. Mechanical Summary The portable is heated by a natural gas fired forced air furnace with a supply air distribution duct system that runs along one wall just below ceiling level. The furnace is controlled by a digital thermostat. The furnace is located in an enclosure in one corner of the portable. The enclosure has an exterior combustion air supply for the furnace and a fresh air supply for the portable. The portable has a rooftop exhaust fan and two rooftop turbine type ventilators. Storm drainage from the portable roof is collected by two roof drains which discharge to interior rain water leaders which discharge to the school storm sewer system. Fire protection is provided by a fire extinguisher in the common corridor which provides access to the six portables and the connecting link.

Page 53: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 53 of 61

F1010.02.04 Portable and Mobile Buildings** - East Link

4 - AcceptableRating

1984Installed

30Design Life

MAR-10Updated

Interior Lifecycle Replacement

Mechanical Lifecycle Replacement

Lifecycle Replacement - All

Lifecycle Replacement

Lifecycle Replacement

Lifecycle Replacement

2027

2027

2014

$22,000

$18,000

$75,000

Unassigned

Unassigned

Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Event:

Type

Type

Type

Year

Year

Year

Cost

Cost

Cost

Priority

Priority

Priority

Updated:

Updated:

Updated:

MAR-10

MAR-10

MAR-10

Link (corridor) - 1984 - Approx. Area - 90m2 Structure: - Wood frame construction with concrete piles bearing on undisturbed soil. Envelope: - Cladding - The exterior skin has a painted wood & metal siding finish with wood framing construction. - Roof Covering - The roof has an SBS roof assembly. - Exterior Doors - Fire-rated painted steel door & frame assembly are located in the common corridors.(2 doors) Interior: - Flooring - Sheet Vinyl - Ceiling - 2'x4' Suspended Acoustical tile ceiling - Walls - Gypsum board walls on wood frame construction. Electrical Summary The lighting fixture used in the portable corridor is a recessed 1' x 4', T8 fluorescent fixture. A 10" fire alarm bell and emergency lighting has been provided in the portable corridor. An LED exit sign has been provided at the end of the exit corridor. The electrical systems for the portable corridor were found to be in acceptable condition. Mechanical Summary The connecting link contains a storage room on the east side of the corridor. The storage room has a wall mounted exhaust fan and there are two rooftop turbine type ventilators on the link. The storage room and the entrance vestibule are heated from the adjacent portables.

Page 54: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 54 of 61

F1010.02.04 Portable and Mobile Buildings** - Storage Room

4 - AcceptableRating

1984Installed

30Design Life

MAR-10Updated

Lifecycle Replacement - Storage Room

Lifecycle Replacement 2014 $35,000 Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Type Year Cost Priority

Updated: MAR-10

Storage Room - 1984 - Area 45m2 Structure: - Wood frame construction with concrete piles bearing on undisturbed soil. Envelope: - Cladding - A painted plywood sheathing skirt with vents is located at the base of the elevation. The exterior skin has a painted vertical wood & metal siding finish with wood framing construction. - Roof Covering - The roof has an SBS roof assembly. Interior: - Flooring - Sheet Vinyl (100%) - Ceiling - 2'x4' Suspended Acoustical tile ceiling - Walls - Painted gypsum board walls with either metal or wood wall construction. - Interior Doors - Painted steel door & frame assembly

Page 55: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 55 of 61

F1010.02.04 Portable and Mobile Buildings**- 1984 Section

4 - AcceptableRating

1984Installed

30Design Life

MAR-10Updated

Building Envelope Lifecycle Replacement

Electrical Lifecycle Replcaement

Lifecycle Replacement

Lifecycle Replacement

2014

2014

$55,000

$15,000

Unassigned

Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated: MAR-10

Portable C84 CS18 - Age 1984- Area 90m2 (includes interior corridor) Structure: - Wood frame construction with concrete piles bearing on undisturbed soil. Envelope: - Cladding - A painted plywood sheathing skirt with vents is located at the base of the elevation. The exterior skin has a painted vertical wood & metal siding finish with wood framing construction. - Windows - The exterior windows (1) are aluminum frame operable single-hung type windows (original). The window hasprotective metal security screens. - Roof Covering - The roof has an SBS roof assembly. Interior: - Flooring - Carpet (90%) & Sheet Vinyl (10%) at entrance - Ceiling - 2'x4' Suspended Acoustical tile ceiling - Walls - Painted gypsum board walls with either metal or wood wall construction. - Interior Doors - Painted steel door & frame assembly - Equipment - Chalkboards, tackboards, open wood shelving, wall mounted coat hooks & curtains. Electrical Summary A 120/240V Commander panel (single phase, 3-wire) has been provided for the portable. The lighting fixture used in the portable classroom is a surface mounted 1' x 4', T12 fluorescent fixture. A P.A. speaker and a battery clock have been provided in the portable. The portable is connected to the school fire alarm system. The electrical systems for the portable were found to be in acceptable condition. Mechanical Summary The portable is heated by a natural gas fired forced air furnace (replaced in c.2002) with a supply air distribution duct system that runs along one wall just below ceiling level. The furnace is controlled by a digital thermostat. The furnace is located in an enclosure in one corner of the portable. The enclosure has an exterior combustion air supply for the furnace and a fresh air supply for the portable. The portable has a rooftop exhaust fan and two rooftop turbine type ventilators. Storm drainage from the portable roof is collected by two roof drains which discharge to interior rain water leaders which discharge to the school storm sewer system. Fire protection is provided by a fire extinguisher in the portable and by a fire extinguisher in the common corridor which provides access to the six portables and the connecting link.

Page 56: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 56 of 61

Interior Lifecycle Replacement

Mechanical Lifecycle Replacement

Lifecycle Replacement

Lifecycle Replacement

2014

2014

$22,000

$18,000

Unassigned

Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

Updated:

MAR-10

MAR-10

MAR-10

Page 57: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 57 of 61

F1010.02.04 Portable and Mobile Buildings**- 1986 Section

4 - AcceptableRating

1986Installed

30Design Life

MAR-10Updated

Building Envelope Lifecycle Replacement

Electrical Lifecycle Replcaement

Interior Lifecycle Replacement

Lifecycle Replacement

Lifecycle Replacement

2016

2016

$55,000

$15,000

Unassigned

Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-10

MAR-10

Portable C86CS10 - Age 1986- Area 90m2 Structure: - Wood frame construction with concrete piles bearing on undisturbed soil. Envelope: - Cladding - A painted plywood sheathing skirt with vents is located at the base of the elevation. The exterior skin has a painted vertical wood & metal siding finish with wood framing construction. - Windows - The exterior windows (1) are aluminum frame operable single-hung type windows (original). The window hasprotective metal security screens. - Roof Covering - The roof has an SBS roof assembly. Interior: - Flooring - Sheet Vinyl (100%) - Ceiling - 2'x4' Suspended Acoustical tile ceiling - Walls - Painted gypsum board walls with either metal or wood wall construction. - Interior Doors - Painted steel door & frame assembly - Equipment - Chalkboards, tackboards, open wood shelving, wall mounted coat hooks & curtains. Electrical Summary A 120/240V Commander panel (single phase, 3-wire) has been provided for the portable. The lighting fixture used in the portable classroom is a surface mounted 1' x 4', T12 fluorescent fixture. A P.A. speaker and a battery clock have been provided in the portable. The portable is connected to the school fire alarm system. The electrical systems for the portable were found to be in acceptable condition. Mechanical Summary The portable is heated by a natural gas fired forced air furnace (replaced in c.2004) with a supply air distribution duct system that runs along one wall just below ceiling level. The furnace is controlled by a digital thermostat. The furnace is located in an enclosure in one corner of the portable. The enclosure has an exterior combustion air supply for the furnace and a fresh air supply for the portable. The portable has a rooftop exhaust fan and two rooftop turbine type ventilators. Storm drainage from the portable roof is collected by two roof drains which discharge to interior rain water leaders which discharge to the school storm sewer system. Fire protection is provided by a fire extinguisher in the common corridor which provides access to the six portables and the connecting link.

Page 58: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 58 of 61

F1010.02.04 Portable and Mobile Buildings**- West Link with Ramp

4 - AcceptableRating

1984Installed

30Design Life

MAR-10Updated

Mechanical Lifecycle Replacement

Lifecycle Replacement - All

Lifecycle Replacement

Lifecycle Replacement

Lifecycle Replacement

2016

2016

2014

$22,000

$18,000

$75,000

Unassigned

Unassigned

Unassigned

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Event:

Type

Type

Type

Year

Year

Year

Cost

Cost

Cost

Priority

Priority

Priority

Updated:

Updated:

Updated:

MAR-10

MAR-10

MAR-10

1984 - Link 168 (corridor) with stairs & ramp - Approx. Area - 90m2 Structure: - Wood frame construction with concrete piles bearing on undisturbed soil. Envelope: - Cladding - The exterior skin has a painted wood & metal siding finish with wood framing construction. - Roof Covering - The roof has an SBS roof assembly. - Exterior Doors - Fire-rated painted steel door & frame assembly are located in the common corridors.(2 doors) Interior: - Flooring - Sheet Vinyl - Ceiling - 2'x4' Suspended Acoustical tile ceiling - Walls - Gypsum board walls on wood frame construction. - Ramp & Stairs -Non-slip vinyl flooring at ramp and steps. Metal railing and handrails to the steps and ramp. - Equipment - Single tier metal lockers Electrical Summary The lighting fixture used in the portable corridor is a recessed 1' x 4', T8 fluorescent fixture. A 10" fire alarm bell and emergency lighting has been provided in the portable corridor. An LED exit sign has been provided at the end of the exit corridor. The electrical systems for the portable corridor were found to be in acceptable condition. Mechanical Summary The connecting link contains a storage room on the east side of the corridor and an entrance vestibule with a wheelchair ramp on the west side of the corridor. The storage room has a wall mounted exhaust fan and there are two rooftop turbine type ventilators on the link. The storage room and the entrance vestibule are heated from the adjacent portables.

Page 59: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 59 of 61

F2020.01 Asbestos*

F2020.04 Mould*

F2020.09 Other Hazardous Materials*

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

1967

1967

1967

Installed

Installed

Installed

0

0

0

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

No asbestos materials reported provided.

No mould known or reported

No hazardous materials known or reported

Page 60: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 60 of 61

K4010.01 Barrier Free Route: Parking to Entrance*

K4010.02 Barrier Free Entrances*

K4010.03 Barrier Free Interior Circulation*

4 - Acceptable

3 - Marginal

4 - Acceptable

Rating

Rating

Rating

1967

1967

1967

Installed

Installed

Installed

0

0

0

Design Life

Design Life

Design Life

MAR-10

MAR-10

MAR-10

Updated

Updated

Updated

Provided power operators for barrier free access atthe main north-east entrance

Barrier Free Access Upgrade 2010 $5,000 Low

No automatic access is currently provided from any exterior entrance doors.

Concern:

Provided power operators for barrier free access at the main north-east entrance.

Recommendation:

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)S8 FUNCTIONAL ASSESSMENT

Event:

Type Year Cost Priority

Updated: MAR-10

A designated handicapped parking stall in main parking lot is adjacent to the main north-east entrance. Signage for the designated handicap parking space is provided.

The main entrance doors are not equipped with power assisted operators.

Generally, barrier free access is provided throughout the public spaces of the school including the attached portables via a ramp.

Page 61: RECAPP Facility Evaluation Report - Alberta · RECAPP Facility Evaluation Report ... The total area of the school is 4400 square meters ... Two natural gas fired domestic hot water

Report run on: March 25, 2010 10:19 AM Page 61 of 61

K4010.04 Barrier Free Washrooms*

3 - MarginalRating

1967Installed

0Design Life

MAR-10Updated

Provide a unisex washroom

Barrier Free Access Upgrade 2010 $40,000 Medium

The washrooms do not meet current barrier free standards. Concern:

Provide a unisex washroom centrally located within the school.

Recommendation:

Calgary - St. Vincent De Paul Elementary / Jr. High School (B2829A)

Event:

Type Year Cost Priority

Updated: MAR-10

Student washrooms incorporate handicapped toilet stalls, however do not meet current barrier free standards.