THE BASI CS OF

POWERQUAL I TY

IDEAL Test and M easurement 

Page 2: Pq - Equipo Ideal

8/4/2019 Pq - Equipo Ideal

http://slidepdf.com/reader/full/pq-equipo-ideal 2/15

Table of Contents 

What is Power Quality? 2

Sources of Poor Power Quality 3

Power Factor 4

Harmonics 8

Disturbances 12

IDEAL Power Clamps 14

IDEALSureTest Circuit Analyzer 16

IDEAL Power Analyzer 18

Technical Definitions 20

Power Clamp Features & Ordering 22

SureTest Features &Ordering 23

Power Analyzer Features &Ordering 24

D

1

Power Quality: An Introduction 

The Basics of Power Quality is a convenientguide to understanding the essential aspectsof monitoring and troubleshooting powerquality. Its easy-to-read format providesyou with a reference point on how todeal with the three key issues that makeup power quality: power factor, harmonicsand disturbances.

Just like our complete line of power qualitytesters and meters, this guide representsthe IDEAL Test &Measurement commitment

to helping the professional electrician.

IDEAL. The way every job should be.

Technical Support – Toll Free 877- 201- 9005

www.testersandmeters.com

Page 3: Pq - Equipo Ideal

8/4/2019 Pq - Equipo Ideal

http://slidepdf.com/reader/full/pq-equipo-ideal 3/15

Sources of Poor Power Quality 

Power Quality problems can be trackedto three origins - supply, internaldistribution and internal loads.

Supply This is the initial source of

power from the utility companysuch as the main transformerof a commercial building.It’s where power coming intothe facility can be monitored.

Internal Distribution 80% of all power qualityproblems occur in a company’sdistribution and grounding systems. Corroded connections,defective conduit, defective electrical devices, improperwiring and improper grounding are just some of theobstacles to be dealt with.

Internal Loads 

Everything from variable speed drives and high-techdevices to unsophisticated loads such as heaters andlights contribute to the quality of electrical power ina circuit. Internal loads can cause poor power factor,harmonics and disturbances.

A facility’s incoming power is typically monitored at the main transformer, referred to as the supply.

Industrial machines containing variable speed drives can cause a variety of costly power quality problems.

What Is Power Quality? 

The concept of power quality has often beenmisunderstood and oversimplified. But in this dayand age of sophisticated electronics, monitoringpower quality has become too important to ignore. Thewidespread use of high-tech devices has complicatedevery aspect of electrical power. Not only are these

devices more sensitive to the effects of power quality,but they can also impact it negatively. Poor powerquality can result in lost productivity, lost and corruptdata, damaged equipment and poor power efficiency.When added up, U.S. companies waste an estimated$26 billion on electrical power-related issues each year.*

“Power Quality” is a broad term used to describethe measurement of electrical power performance.It can be broken down into three key areas.Each will be discussed in the following pages.

*Electrical Contractor Magazine , “Surveying Power QualityOptions,” March 2000.

THREE KEY ASPECTS OF 

POWER QUALITY 

• Power Factor  • Harmonics  • Disturbances 

Page 4: Pq - Equipo Ideal

8/4/2019 Pq - Equipo Ideal

http://slidepdf.com/reader/full/pq-equipo-ideal 4/15

When power is “ in-phase,” voltage and current travel congruently,meaning they reach maximum height and zero simultaneously.A large motor load can cause current to lag behind voltage. This lagging effect, or phase shift, can cause a poor power factor.

Power FactorIn-Phase

Voltage

Current

Power FactorOut-of-Phase

Voltage

Current

Power Factor 

Power Factor is the ratio of true powerto apparent power in a circuit, or in otherwords, a circuit’s level of power efficiency.It is expressed as a ratio by using the equation below.

The most common reason to measure power factor isto determine the amount of power in a commercial orindustrial environment that is supplied but not utilized.When the power factor ratio is 1.00 it means that everywatt of power arriving from the utility company isput to use. But unfortunately, motors and electronicequipment apply a load to the circuit which can result inout-of-phase power. (See illustration on next page)

A power factor of less than 0.90 is considered poor.It means that a considerable amount of incoming poweris being used inefficiently. To make matters worse, utilitycompanies apply a penalty charge when power factordrops to low levels. Maintaining a healthy power factoris an important part of maximizingpower eff iciency.

W

VAWatts

Volts x Amps

To determine power factor,divide true power (watts) by apparent power (volt amps).

If true power and apparent power were equal, the result would be a power ratio of 1.00.

PF =PowerFactor

=

Page 5: Pq - Equipo Ideal

8/4/2019 Pq - Equipo Ideal

http://slidepdf.com/reader/full/pq-equipo-ideal 5/15

Identify the Problem The first step in resolving a power factor issue is toidentify the origin and extent of the problem with apower clamp or power analyzer. A healthy powerfactor is in the mid to upper 0.90s. As mentioned earlier,a poor power factor usually results from a motor causing

a phase-shift. Once the power factor is determined andthe motors are identified, correcting the problem is afairly simple process.

Implement a Solution The most common means of correcting a low powerfactor is to compensate the circuit with additionalcomponents. Most often, this compensation comesin the form of capacitor banks. While capacitor banksare a permanent solution, it is wise to continuemonitoring the circuit for any new problems.

Large motors make industrial operations especially 

susceptible to a poor power factor.

Troubleshooting Power Factor 

In nearly all cases, it is more cost-efficient to take stepstoward improving power factor than it is to live withexcessive utility charges. While the effects of powerfactor cannot necessarily be eliminated, they can beminimized if properly diagnosed.

A power clamp, such as the IDEAL 61-802 pictured above, is the best way to monitor a circuit’s power factor. With a single reading directly at the transformer, a power clamp can measure true power, apparent power and power factor.

Page 6: Pq - Equipo Ideal

8/4/2019 Pq - Equipo Ideal

http://slidepdf.com/reader/full/pq-equipo-ideal 6/15

HarmonicDistortion

60Hz Sine WaveWith HarmonicsFundamental

Sine Wave

2ndHarmonic 3rd

Harmonic

Notice that the fundamental frequency requires twice as long as the second harmonic and three times as long as the third harmonic to complete a single waveform.

Harmonic Factorization 

Breaking down the total harmonic distortion into individualharmonics is an analysis called harmonic factorization.Typically, only the odd-numbered harmonics are analyzed.They are created by non-linear loads and have the greatestimpact on an electrical system. The two most importantcategories for commercial and industrial settings are thezero sequence, or triplen harmonics (3rd, 9th, 15th, etc.) andthe negative sequence harmonics (5th, 11th, 17th, etc.) Thetriplen harmonics are most commonly found in commercialsettings and are caused by computers and other electronic

office equipment. Negative sequence harmonics arecommonly found in industrial environments and are causedby variable speed drives and other electronic equipment.

Total harmonic distortion (THD) is the percentage of distortion to the fundamental frequency. As a general rule, THD should not exceed 5% of voltage or 20% of current.

Harmonics 

Widespread use of electronic equipment intoday’s commercial and industrial environmentshas made harmonics an important but complexpower quality issue.

Most simple electric devices like motors and incandescentlighting are linear loads, which means AC impedance is

constant regardless of the applied voltage. In this case, thefundamental AC sine wave, pictured below, is unaffected.

On the other hand, non-linear loads such as personalcomputers and copy machines strip off AC power andconvert it to DC power. This process adds harmonics tothe fundamental frequency.

By definition, a harmonic is a frequency which is aninteger of the fundamental 60Hz wave. For example,the second harmonic of the fundamental frequency is120Hz, the third harmonic is 180Hz and so on.

The addition of harmonics to a system results indistortion to the voltage and current waveforms. Theimpact to the electrical system depends on the totalamount of distortion present and on which harmonicthe distortion is located.

60Hz Sine Wave

In the United States, the fundamental frequency of electricity is 60Hz.This illustration shows one cycle of that frequency.

Page 7: Pq - Equipo Ideal

8/4/2019 Pq - Equipo Ideal

http://slidepdf.com/reader/full/pq-equipo-ideal 7/15

Troubleshooting Harmonics 

Preventing harmonics from causing damage to electricalcircuits and expensive equipment can be a difficult task.To effectively troubleshoot the problem, the total harmonicdistortion and harmonic factorization should be analyzed.Knowing the amount and characteristics of the harmonics

will aid in identifying a solution.

In our commercial example, harmonics are not usuallyremoved. Removal of harmonics requires the use of filtersor devices that minimize the effects on the circuit, andthese are not always cost-efficient solutions.

The alternative to removing harmonics is to minimizethe effect they have on the system. Oversizing theneutral conductor or derating the existing transformersare possible solutions for a 3-phase, 4-wire systemaffected by triplen harmonics. While derating a motor ispossible, it is more common to use snubbers or filters toreduce the effects of harmonics in an industrial facility.

The IDEAL Power Analyzer can collect data concerning harmonic distortion as well as power quality issues like disturbances.

11

Commercial Environments 

In the 3-phase, 4-wire electrical system commonly foundin commercial buildings, current flows through eachphase conductor and returns in a common neutral con-ductor. In a balanced system, the neutral currents fromeach phase will mathematically cancel each other out. Any

imbalance in phase current will return on the neutral atthe fundamental frequency (60Hz). As this returncurrent is typically small, it is generally not considereda problem.

The characteristics of the triplen harmonics (3rd, 9th,15th, etc.) disrupt this balance. Rather than cancelingeach other out on the neutral, the triplen harmonicsfrom all three phases are mathematically added togetherin the neutral conductor. This can result in a higher thanexpected current which can cause excessive heat in theneutral conductor and transformer.

Industrial Environments 

The electrical loads within an industrial plant can begreatly affected by the negative sequence harmonics(5th, 11th, 17th, etc.). These harmonics counteract theenergy created by the electrical power system. Forexample, in a motor the negative sequence harmonicswill try to force the motor to turn in a reverse direction.The impact to the rotation of the motor depends onthe magnitude of the current harmonics. A level of20% distortion on the fifth harmonic means 20% of theenergy is working against the motor. This has a seriousimpact both to the torque produced by the motor andthe heat given off. This affects both production being runon the machine and the life of the motor.

10 

Page 8: Pq - Equipo Ideal

8/4/2019 Pq - Equipo Ideal

http://slidepdf.com/reader/full/pq-equipo-ideal 8/15

Transients Transients are short-duration, high-amplitude pulsessuperimposed on a normal voltage waveform. They canvary widely from twice the normal voltage to severalthousand volts and last from less than a microsecondup to a few hundredths of a second.

Transients are caused by a rapid release of energystored in an inductive or capacitive source in the electricalsystem, or from an external source such as lightning.

Troubleshooting Disturbances 

Disturbances may require a certain degree of monitoringin order to properly diagnose. The nature of disturbancesin industrial settings is often systematic but infrequent.By tracking a circuit over an extended period of timewith the IDEAL Power Analyzer, data can be saved andanalyzed later on a computer. This makes disturbanceseasier to pinpoint.

Unlike harmonics, reoccurring disturbances are oftenfairly easy to eliminate once they’ve been properly

identi fied. For example, devices like surge protectors area simple way to protect against transients.

TransientVoltage

While the duration of transients is unnoticeable to a human 

observer, their effect on power quality is still considerable.A single lightning strike can result in a transient large enough to destroy electronic devices.

13 

Disturbances 

The term “disturbances” is actuallyused to describe any kind of fluctuationin power. The most common types ofdisturbances are sags, swells, overvoltages,undervoltages, transients and outages.

Sags, Undervoltages and Outages 

Sags are momentary decreases in voltage. This decreaseis typically 80% of the normal voltage with a durationbetween 0.5 seconds and one minute. A decrease involtage lasting longer than a period of one minute iscalled an undervoltage and a complete loss of power iscalled an outage. Sags occur when there is a momentaryloss of available electricity due to the starting of heavyloads such as a motor or heavy machinery.

Swells and Overvoltages Swells are the opposite of sags. They are momentaryincreases involtage up to 120% of normal with a durationbetween 0.5 seconds and one minute. This surge of energymay occur when a motor or heavy machinery is shutdown abruptly. An increase in voltage lasting longerthan a period of one minute is called an overvoltage.

12 

Sags &Swells

Though they are caused by different factors, sags and swells often follow each other as the system attempts to compensate.This further increases their potential to cause damage.

Page 9: Pq - Equipo Ideal

8/4/2019 Pq - Equipo Ideal

http://slidepdf.com/reader/full/pq-equipo-ideal 9/15

Large, easy-to-readdual display

True RMS

Data hold

2000A AC/DCcurrent capability

15 

IDEAL 800 Series Power Clamps 

When testing power quality on high-voltagecircuits, a heavy-duty power clamp can help ensureaccuracy and safety. The 800 Series Power Clampsare True RMS clamps capable of measuring 2000AAC and DC currents for commercial and industrial

 jobs. They are designed to measure true power,

apparent power, reactive power and power factorin a single reading, bypassing the need for manualcalculations. Another key feature of these clampsis their ability to measure both single-phase andthree-phase circuits. Built to be rugged and versatile,the 800 Series is a necessity for commercial andindustrial power quality jobs.

14 

Calculates readingsfor both three-phase, three-wireand three-phase,four-wire circuits

Powermeasurements

An easy-to-read dual display is a useful feature for viewing measurements like: power factor and kW, volts and amps, or frequency and volts.

See page 22 for features and ordering information.

Page 10: Pq - Equipo Ideal

8/4/2019 Pq - Equipo Ideal

http://slidepdf.com/reader/full/pq-equipo-ideal 10/15

17 

Large, easy-to-readLED display

Easy, one-buttonoperation

Retractableground prong

Circuit/ Harmonics Analyzer 

In the past, measuring total harmonicdistortion (THD) was a task for bulky and expensiveequipment, but the SureTest Circuit Analyzer haschanged that. The SureTest is designed to troubleshootan electrical distribution system, analyzing both commoncircuit and power quality problems. It is the first hand-

held circuit analyzer capable of applying a full 15-ampload without causing interruption to equipment on thecircuit. It identifies and locates loose connections, badsplices or receptacles, loose ground connections andhigh-resistance grounds.

The SureTest model ST-1THD is specifically designed forcommercial and industrial environments where electroniclighting and electronic equipment are present. TheSureTest captures True RMS measurements, analyzespower measurements such as watts and power factor,and measures harmonic distortion to the 31st harmonic.

Comfortable,ergonomic design

The SureTest Circuit Analyzer is used for a multitude of power quality measurements including total harmonic distortion (THD).

16 

See page 23 for features and ordering information.

Page 11: Pq - Equipo Ideal

8/4/2019 Pq - Equipo Ideal

http://slidepdf.com/reader/full/pq-equipo-ideal 11/15

19 

Large, easy-to-useLCDdisplay

Lightweight,portable design 1 MBmemory

Comes standardwith a full range ofaccessories forcomplete analysis

IDEAL Power Analyzer 

There are a number of instrumentsdesigned for in-depth examination ofcommercial and industrial power quality issues likeharmonics and disturbances. What sets the IDEALPower Analyzer apart from the rest is its versatility andease-of-use. 1 MB of memory enables the saving of

parameters and allows for long periods of testing.Information can then be downloaded to a computer foranalysis. The Power Analyzer contains five base programswhich comprehensively test every power quality issuediscussed in this guide. The PowerVision analysissoftware creates a variety of tables and graphs tomake in-depth analysis of power quality problemseasier. It all adds up to the most complete, versatileand easy-to-use power quality tool anywhere.

18 

The versatility of the IDEALPower Analyzer enables four testing programs to run simultaneously for extended durations of time.

Easy-to-usepush buttonoperation

See pages 24-25 for features and ordering information.

Page 12: Pq - Equipo Ideal

8/4/2019 Pq - Equipo Ideal

http://slidepdf.com/reader/full/pq-equipo-ideal 12/15

Power Factor - The ratio of true power (watts) to the apparentpower (voltamperes). It is an indication of the efficiency of anelectrical system.

Power Quality - A broad term used to describe themeasurement of electrical power performance.

Sag - A reduction in ACvoltage up to 20% below nominal levellasting for a duration from one half cycle up to a few seconds.

Swell - An increase in ACvoltage up to 20% above nominallevel lasting for a duration from one half cycle up to afew seconds.

Transient - A release of positive or negative energy creating adisturbance within a single cycle of the AC waveform.

Total Harmonic Distortion (THD) - The percentage ofdistortion to the fundamental frequency caused by harmonicswithin the electrical system.

Triplen Harmonics - see zero sequence harmonics.

True Power - The power extended when one ampere of currentflows through a resistance of one ohm. Measured in Watts.

Voltage - A unit of measure of the electrical pressure in anelectrical system. Measured in Volts.

Voltamperes - Applied voltage multiplied by current. This isthe power utilized by a load or electrical system.

Watt - Often referred to as true power. It is the powerexpended when one ampere of current flows through aresistance of one ohm.

Zero Sequence Harmonics - Also called triplen harmonics,these are concurrent in direction with the fundamentalfrequency (3rd, 9th, 15th, etc.). They produce an amplitudethat is triple any one phase when they combine on the neutralof a 3-phase, 4-wire electrical system.

2120 

Technical Definitions 

Ampere - A unit of measure for the rate ofcurrent f low. Measured in Amps.

Apparent Power - Applied voltage multiplied bycurrent.This is the power utilized by a load or electrical system.Measured in Voltamperes (VA).

Frequency - The number of cycles per second that a waveform repeats itself. Measured in Hertz (Hz).

Harmonics - A frequency that is an integer (multiple)of the fundamental frequency caused by electronicequipment. Harmonics cause distortion to the voltage andcurrent waveforms.

Harmonic Factorization - Analysis where the total harmonicdistortion is broken down into the individual harmonics.

Linear Loads - A load where the load impedance is constant.The relationship between the voltage and current drawn fromthe circui t are proportional. Examples of linear loads aremotors and incandescent lighting.

Negative Sequence Harmonics - Odd-numbered harmonicswith a phase sequence opposite to the fundamental frequency(5th, 11th, 17th, etc.). They have a reversal effect on motorswithin an industrial facility.

Non-Linear Loads - A load where the load impedance isnot constant. The relationship between the voltage and currentis unique to the type of load, resulting in harmonics on thecircuit. Examples of non-linear loads are computers and variablespeed machines.

Odd-Numbered Harmonics - Odd-numbered integer of thefundamental frequency (60Hz). The 3rd harmonic of thefundamental frequency is 180Hz, the 5th is 300Hz, etc. Odd-numbered harmonics are typically created by non- linear loads.

Outage - The total loss of ACpower for greater that oneminute. Outages typically last from 15 minutes to a few hours.

D

Page 13: Pq - Equipo Ideal

8/4/2019 Pq - Equipo Ideal

http://slidepdf.com/reader/full/pq-equipo-ideal 13/15

Description Cat. No.

ST-1 Circuit Analyzer 61-150

ST-1P+ Circuit Analyzer 61-151

ST-1D Circuit Analyzer (120VAC) 61-152

ST-1THD Circuit/Harmonics Analyzer 61-156

ST-1THDC Circuit/Harmonics Analyzerfor use with Amp Clamp

ST-1THDC Circuit/Harmonics Analyzer Kit,61-181 Clamp Adapter Included

Ground Continuity Adapter 61-175

Isolated Ground Adapter 61-176

Extension Cord 61-177

Carrying Case 61-179500 Amp Clamp Adapter 61-181

23 

IDEAL SureTest ® 

Circuit Analyzer 

Common Features • Identify and locate high resistance connections,

bad splices/receptacles, high resistance grounds• Verify proper wiring and GFCI operation• Test voltage drop under actual 15A load

• Test line voltage

61-157

61-158

61-156(ST- 1THD)

• True RMS• Power factor• Harmonics• Event recording• Ground impedance• Load on branch• Dedicated circuits• Isolated grounds• False grounds

22 

IDEAL 800 Series Power Clamps 

Common Features • 2000A AC/DC current capability• True RMS• Kilowatts• Data hold

• Auto ranging• DCcurrent zero function• Oveload protection• Lifetime limited warranty

61-800

• 2000AAC current capability• 2500ADC current capability• Temperature• Analog output (current ranges)• Relative mode• Min/max• Audible continuity

61-802

• 2000A AC/DCcurrent capability

• kVA• kVAR• Power factor• Frequency• Dual display• Memory recall

Description Cat. No.

800 Series Power Clamp 61-800800 Series Power Clamp 61-802

Page 14: Pq - Equipo Ideal

8/4/2019 Pq - Equipo Ideal

http://slidepdf.com/reader/full/pq-equipo-ideal 14/15

25 

Description Cat. No.

800 Series Power Analyzer 61-805

Disturbances Program 61-474

Check-Meter Program 61-475

Fast-Check Program 61-476

2000/200AAC Clamp Adapter 61-453

500AAC Clamp Adapter 61-455

Standard Equipment 

1000AACClamp Adapters

Test Leads withAlligator Clips

Power Analyzer

RS232 Interface/ Power Supply

IDEAL Power Analyzer 

Features • Single- or three-phase measurements• True RMS• Data logging (1MBmemory)• Auto ranging• Min/max/avg• Energy and Harmonics Program• PowerVision™Software• Optional programs:

DisturbancesCheck-MeterFast-Check

• Lightweight, portable design• Easy-to-use push-button

operation• Password protected

on-screen setup• 160 x 160 pixel LCD• RS-232 interface• Customized data

collection• Real-time clock• Programmable trigger-

points and start/ stop time• Auto display shutoff• Rechargeable Ni-Cad battery• Intelligent battery charging system

Power M easurements • Kilowatts (kW)• Voltamperes (VA)• Inductive reactive power (kvarL)• Capacitive reactive power (kvarC)• Power factor (PF)• Frequency (Hz)• Kilowatt hours (kWh)• Reactive power per hour (kvarhL, kvarhC)

Harmonics Measurements • Total harmonic distortion (%THD)• Harmonic factorization to 51st harmonic

24 

61-805

Page 15: Pq - Equipo Ideal

8/4/2019 Pq - Equipo Ideal

http://slidepdf.com/reader/full/pq-equipo-ideal 15/15

IDEAL INDUSTRIES, INC.

Technical Hotline —Toll Free 877-201-9005Becker Place, Sycamore, IL 60178 —800-435-0705 in U.S.A.

Ajax, Ontario, L1S 2E1, Canada —800-527-9105 in Canada

Warrington, Cheshire WA5 5TN, England —44 1925 444.446

www.testersandmeters.com

 ©2000 IDEAL INDUSTRIES, INC.

Test & Measurement 

No part of this publication may be reproduced or transmitted in

any form or by any means, electronic or mechanical, including photocopy,recording, or any storage and retrieval system, without written permission.

Form No. P–2110 Rev. 12/ 00 Printed in U.S.A.