M001 MECHANICAL SCHEDULES & GENcochisetech.net/wp-content/uploads/2016/11/90-Mechanical.pdfb. test...

4
MECHANICAL SCHEDULES & GENERAL NOTES DO NOT SCALE DRAWING M001 THIS DRAWING IS CLASSIFIED AS PART OF AN UNPUBLISHED COLLECTION OF VISUAL ART. UNDER THE 1978 COPYRIGHT ACT, IT IS AN EXCLUSIVE ORIGINAL WORK OF AUTHORSHIP. NONE OF THE PICTORIAL, GRAPHIC OR TECHNICAL CHARTS OR DRAWINGS DEPICTED ON THIS SHEET MAY BE REPRODUCED OR TRANSMITTED IN ANY FORM OR BY ANY MEANS WITHOUT THE EXPRESS PRIOR WRITTEN PERMISSION OF THE ARCHITECT. THIS PLAN IS PRODUCED ONLY FOR THIS PROJECT ON THIS SITE AND MAY NOT BE USED AT OTHER LOCATIONS. SHEET TITLE: ORIGINAL ISSUE: Preliminary SEAL: REV DATE DESCRIPTION SHEET NUMBER: PROJECT: AC489 PROJECT: BAPTIST CHURCH SIERRA VISTA, AZ VILLAGE MEADOWS DESCRIPTION DESCRIPTION DESCRIPTION DESCRIPTION DESCRIPTION MM-DD-YY MM-DD-YY MM-DD-YY MM-DD-YY MM-DD-YY MM-DD-YY 4 1 2 3 5 6 DESCRIPTION ORIGINAL ISSUE Preliminary 0 DANIEL COOK ARCHITECT2909 WASHINGTON BLVD - OGDEN, UT 84401PH: 800-552-7137www.BGWSERVICES.com SIERRA VISTA, ARIZONA 85635 1407 S EL CAMINO REAL PRELIMINARY DRAWING! NOT FOR CONSTRUCTION! T H C TITLE SECTION SHEET # MECH ROOF PLAN DETAIL # SHEET # 1 EQUIPMENT CALLOUT SCOPE OF WORK FOR LENNOX PROVIDED EOC, AND MECHANICAL CONTRACTOR CONTROL INSTALLATION AND MECHANICAL CONTRACTOR CONTRACTED INDEPENDENT TEST AND BALANCE. A. EQUIPMENT OPERATIONS CHECK (EOC) (LENNOX PROVIDED) THROUGH BGWS • TEST ALL LENNOX EQUIPMENT BASED ON THE STANDARD LENNOX EOC REPORT. • CONTACT LENNOX SUPPORT WITH ANY EQUIPMENT DEFICIENCIES AND COORDINATE REPAIR OR REPLACEMENT AS NECESSARY TO ASSIST IN PROVIDING OPERATIONAL EQUIPMENT PRIOR TO OPENING DATE. • DISTRIBUTE COPIES OF EOC REPORT AS REQUESTED BY LENNOX. B. TEST AND BALANCE (TAB) (MECHANICAL CONTRACTOR CONTRACTED) • UPON ARRIVAL TO THE SITE, INSPECT MECHANICAL SYSTEM AND NOTE ANY DEFICIENCIES THAT COULD PREVENT PROPER OPERATION AND/OR BALANCING OF THE MECHANICAL SYSTEM TO THE OWNER, GENERAL CONTRACTOR AND MECHANICAL CONTRACTOR. • INSPECT ALL MECHANICAL EQUIPMENT FOR PROPER INSTALLATION PER MEP DESIGN. • TEST ALL MECHANICAL EQUIPMENT PER NEBB STANDARDS FOR AIR BALANCE FOR PROPER OPERATION. • THE BALANCING OF THE MECHANICAL SYSTEM WILL BE PERFORMED TO MEET NEBB STANDARDS UNLESS SPECIFICALLY REQUESTED OTHERWISE, IN WRITING, BY OWNER OR OWNERS ENGINEERING FIRM. • BALANCE ALL RTU’S, GRILLS, REGISTERS AND EXHAUST FANS PER MECHANICAL DESIGN AS NOTED ON MEP DRAWINGS PER NEBB STANDARDS FOR AIR BALANCE. • GENERATE A FIELD REPORT OF ANY OUTSTANDING MECHANICAL DEFICIENCIES, IF ANY, THAT COULD NOT BE RESOLVED DURING THE TAB VISIT AND DISTRIBUTE A COPY TO THE OWNER, GENERAL CONTRACTOR AND MECHANICAL CONTRACTOR AND NOTE IF A RE-VISIT WILL BE REQUIRED. • GENERATE A COMPLETE TAB REPORT AND SUBMIT TO THE OWNER AND AS DIRECTED WITHIN ONE (1) WEEK OF THE COMPLETION OF THE AIR BALANCE. C. CONTROL INSTALLATION (BGW SUPPLY CONTRACTED CONTROL CONTRACTOR) • PROVIDE CONTROL INSTALLATION DRAWINGS SHOWING CABLE RUNS AND LOCATIONS. • PROVIDE AND TERMINATE PLENUM CABLE FOR LENNOX PROVIDED THEROMOSTATS, HUMIDITY SENSORS AND CO2 SENSORS CONDUIT IN SPACE. • PROVIDE, PLENUM COMMUNICATION CABLE BETWEEN RTUS INSTALLED BY ELECTRICAL CONTRACTOR. • PROVIDE, AND TERMINATE PLENUM CABLE FOR LENNOX PROVIDED SPACE SENSORS AND HUMIDITY SENSORS CONDUIT IN SPACE, IF REQUIRED. WIRE INSTALLATION BY ELECTRICAL CONTRACTOR. • PROGRAM AND COMMISSION CONTROLS AS REQUIRED TO MEET OWNER SPECIFICATIONS. • PROVIDE REPORT DETAILING COMMISSION OF CONTROLS AND SUBMIT TO OWNER. • PROVIDE OWNER OPERATORS 2 HOURS OF TRAINING. D. WARRANTY • LENNOX PROVIDES A ONE (1) YEAR PARTS WARRANTY ON THE WORKMANSHIP OF ALL LENNOX PROVIDED MATERIAL, AND EQUIPMENT, STARTING AT CERTIFICATE OF OCCUPANCY. E. CLARIFICATIONS AND RESPONSIBILITY OF MECHANICAL & ELECTRICAL CONTRACTOR • CONDUIT, RACEWAYS SHALL BE FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR. CONTROL CONTRACTOR WILL REQUIRE A CONDUIT, AND WIRE RACEWAY PATH FOR THE SPACE SENSORS IN AREAS NOT ACCESSIBLE, SUCH AS WALLS, SANCTUARY AND GYMNASIUM AREAS, SUCH THAT ELECTRICAL CONTRACTOR CAN INSTALL CONTROL WIRE AND SPACE SENSORS. • CABLE (PROVIDED BY THE CONTROL CONTRACTOR) SHALL BE PULLED OR INSTALLED AT EACH LOCATION SHOWN ON THE CONTROL DRAWINGS. (INSTALLED BY ELECTRICAL CONTRACTOR) • ELECTRICAL CONTRACTOR SHALL INSTALL ALL SENSORS AND PANEL. • THE EOC, TAB, AND CONTROL INSTALLATION SCOPE WILL BE COORDINATED WITH THE GENERAL AND/OR MECHANICAL CONTRACTOR. • THE GENERAL OR MECHANICAL CONTRACTOR WILL NOTIFY LENNOX WITH AT LEAST FOURTEEN (14) DAYS ADVANCED NOTICE THAT THE HVAC SYSTEM IS 100% COMPLETE AND READY FOR EOC AND CONTROL TERMINATION. O HIGH VOLTAGE MUST BE CONNECTED TO EACH UNIT O GAS MUST BE CONNECTED TO EACH UNIT O PROPER PHASE ROTATION MUST BE CONFIRMED AT THE DISCONNECT O ALL STAGES OF HEATING AND COOLING MUST BE CONFIRMED OPERATIONAL O UNITS CAN BE PUT IN STANDALONE OPERATION BY SETTING THE UNIT OPERATION TO L CONNECTION/RETURN AIR BACK UP MODE. CONSULT THE M-2 PRODIGY CONTROL MANUAL FOR INSTRUCTIONS OR CONTACT LENNOX NATIONAL ACCOUNT TECHNICAL SUPPORT 1-800-367-6285 FOR ASSISTANCE. • THE MECHANICAL CONTRACTOR WILL PROVIDE A REPRESENTATIVE ON-SITE DURING THE EOC SERVICE TO ADDRESS DEFICIENCIES FOUND. LENNOX WILL MAKE ALL REASONABLE ATTEMPTS TO RESOLVE DEFICIENCIES, IF ANY, WITH THE MECHANICAL CONTRACTOR WHILE ONSITE. F. WORKING HOURS • WORKING HOURS SHALL FOLLOW CONSTRUCTIONS HOURS OR AS REQUESTED BY THE GENERAL CONTRACTOR 1 1 RTU 1 1 1 1 1 MECHANICAL GENERAL NOTES MECHANICAL LEGEND DROP RISE DROP 20x10 16''Ø RISE DROP RISE 16''Ø FSD 16x10 FD SD E-1 CFM D-1 CFM D-1 CFM 20x10 20x10 20x10 14''Ø 12x10 12x10 D-1 CFM D-1 CFM 16''Ø 6''Ø EXHAUST AIR REGISTER - SQUARE SUPPLY DIFFUSER - SQUARE FIRE/SMOKE DAMPER SMOKE DAMPER LINEAR DIFFUSERS - SIDE MOUNT FLEXIBLE DUCT FIRE DAMPER MANUAL BALANCING DAMPER SLOPED DUCT DROP SLOPED DUCT RISE FLAT OVAL DUCT DUCT - RISE UNDER FLOOR ROUND DUCT POSITIVE PRESSURE DUCT - DROP ROUND DUCT RECTANGULAR DUCT ROUND DUCT - DROP ROUND DUCT - RISE SOUND ATTENUATOR ROUND TO ROUND TRANSITION RECTANGULAR TRANSITION - OFFSET RECTANGULAR TO ROUND TRANSITION RECTANGULAR TRANSITION LINEAR DIFFUSER - BOTTOM MOUNT SUPPLY DIFFUSER - ROUND SECTION CALLOUT DETAIL CALLOUT THERMOSTAT OR TEMPERATURE SENSOR HUMIDISTAT CARBON DIOXIDE DETECTOR POINT OF CONNECTION POINT OF DEMOLITION REVISION DELTA KEYED NOTE CALLOUT M301 1 SCALE: 1/8" = 1' - 0" M501 1 R-1 CFM RETURN AIR REGISTER - SQUARE 92ºF Db SUMMER HVAC DESIGN DATA OUTSIDE DESIGN TEMPS.: 64ºF Wb SUMMER 17ºF Db WINTER DESIGN ALTITUDE: 175 FT. INTERIOR DESIGN DATA ALL SUMMER WINTER Db 75º %HUMIDITY 50% 72º 40% Db %HUMIDITY NOTE: ALL ROUND DUCTWORK, FITTINGS AND VOLUME CONTROL DAMPERS ARE TO BE SPIROSAFE GASKETED DUCT MANUFACTURED BY LINDAB. BGW HAS A NATIONAL ACCOUNT AGREEMENT WITH LINDAB INC. FOR THIS PROJECT CONTACT LINDAB TAKE OFF DEPARTMENT AT (757) 488-7234 EXT. 381 FOR SPIRAL DUCT QUOTATION. THE DRAWINGS INDICATE DIAGRAMMATICALLY THE EXTENT OF THE WORK. DUE TO THE SCALE OF THE DRAWINGS, OFFSET, FITTINGS, AND ACCESSORIES MAY NOT BE INDICATED. WORK INDICATED, BUT HAVING DETAILS OMITTED, SHALL BE COMPLETELY PROVIDED BY CONTRACTOR TO PERFORM FUNCTION INTENDED AT NO ADDITIONAL COST. CONTRACTOR SHALL EXAMINE THE ARCHITECTURAL, STRUCTURAL, PLUMBING, MECHANICAL, AND ELECTRICAL DRAWINGS AND SPECIFICATIONS TO AVOID CONFLICT WITH OTHER TRADES. MINOR VARIATIONS IN LOCATION OF EQUIPMENT SHALL BE MADE ON WRITTEN APPROVAL OF THE ENGINEER AT NO ADDITIONAL COST. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR PAYMENT, ORDERING, DELIVERY COORDINATION RECEIVING AND INSTALLATION OF ALL THE LINDAB SUPPLIED MATERIAL. THE CONTRACTOR IS REQUIRED TO REVIEW THE MECHANICAL DRAWINGS, MAKING ANY NECESSARY MODIFICATIONS TO ACCOUNT FOR FIELD VARIANCES AND SEND THESE FINAL DRAWINGS TO LINDAB FOR A DUCT QUOTATION. THESE REVISED PLANS ARE TO BE E-MAILED 72 HOURS BEFORE BID TIME TO LINDAB TAKE OFF FOR A PRODUCT QUOTATION. THE CONTRACTOR MUST APPROVE THE FINAL DUCT DRAWINGS AND BILL OF MATERIAL BEFORE PLACING THE ORDER WITH LINDAB. NOTE: MECHANICAL CONTRACTOR TO REVIEW ALL DRAWINGS FOR CONFLICTS WITH STRUCTURE AND OTHER TRADES. MECHANICAL CONTRACTOR TO RESOLVE ALL CONFLICTS WITH ENGINEER PRIOR TO ORDERING, FABRICATING OR INSTALLING DUCTWORK. NOTE: 1) SPACE ABOVE CEILING IS TO BE USED AS A RETURN AIR PLENUM. ALL MATERIALS TO BE PLENUM RATED. 2) ALL TERMINAL SUPPLY DUCT BRANCHES TO BE EQUIPPED WITH MANUAL BALANCING DAMPER. 3) FLEX DUCT (MAXIMUM 60" LONG) TYPICAL ON EACH DIFFUSER EXCEPT IN EXPOSED APPLICATIONS. 4) PROVIDE TURNING VANES IN ALL RECTANGULAR ELBOWS. EF-1 SYMBOL GREENHECK G-123-B ROOF CFM ARRANGEMENT, ROTATION & DISCHARGE DOWNBLAST 825 EXHAUST FAN SCHEDULE 0.35 12" SPECIFICATION SECTION 233423 HEIGHT ABOVE ROOF (INCHES) SP "WG TYPE MANUFACTURER AND MODEL NO. OPERATING WEIGHT (LBS.) ACCESSORIES AND REMARKS 995 RPM FAN DETAIL NO. RPM MOTOR 1140 H.P. ELECTRICAL VOLT/Ø/Hz. 76 CONTROL METHOD 1/6 EF-2 EF-3 150 0.35 12" 1323 1550 47 1/20 EF-4 GREENHECK G-080-D WALL SWITCH EF-5 5 0.3 929 1140 66 1/6 GREENHECK G-097-B EF-6 EF-7 EF-8 120/1/60 BACKDRAFT DAMPER GREENHECK G-123-B 750 0.35 12" WALL SWITCH 958 1140 76 1/6 BACKDRAFT DAMPER BACKDRAFT DAMPER BACKDRAFT DAMPER BACKDRAFT DAMPER WALL SWITCH WALL SWITCH 12" BACKDRAFT DAMPER WALL SWITCH BACKDRAFT DAMPER WALL SWITCH BACKDRAFT DAMPER WALL SWITCH EF-9 BACKDRAFT DAMPER 24" x 24" OVERALL SIZE DIFFUSER AND GRILLE SCHEDULE D-1 SYMBOL TITUS TMS MIN./MAX. CFM 0/100 4-WAY BLOW 6"Ø NECK SIZE SUPPLY AIR TYPE ACCESSORIES AND REMARKS LAY-IN D-2 TITUS TMS 100/240 8"Ø D-3 TITUS TMS 240/400 10"Ø 24" x 24" 4-WAY SUPPLY AIR 24" x 24" 4-WAY SUPPLY AIR LAY-IN LAY-IN SPECIFICATION SECTION 233713 MANUFACTURER AND MODEL NO. D-4 TITUS TMS 400/520 12"Ø 24" x 24" 4-WAY SUPPLY AIR LAY-IN D-7 250/425 360º SUPPLY AIR NECK MOUNT D-8 375/600 360º SUPPLY AIR NECK MOUNT 24" x 24" E-1 0/130 4-WAY 6"Ø LAY-IN E-2 130/260 8"Ø E-3 260/400 10"Ø 24" x 24" 4-WAY 24" x 24" 4-WAY LAY-IN LAY-IN 24" x 24" D-5 TITUS 300FL 0/130 4-WAY SUPPLY AIR D-6 24" x 24" R-1 TITUS PXP 500/1100 N/A RETURN AIR LAY-IN R-2 TITUS PXP 0/500 24" x 12" LAY-IN RETURN AIR N/A N/A N/A EXHAUST AIR EXHAUST AIR EXHAUST AIR 120/1/60 120/1/60 120/1/60 1. PROVIDE ALL LABOR, MATERIALS, AND EQUIPMENT NECESSARY TO CONSTRUCT A COMPLETE, OPERATIONAL HVAC SYSTEM FOR THE ENTIRE PROJECT AS SHOWN ON THESE DRAWINGS, INCLUDING ALL NECESSARY FEES AND PERMITS. 2. THE ENTIRE INSTALLATION SHALL CONFORM TO THE MOST RECENTLY ADOPTED REQUIREMENTS OF THE INTERNATIONAL MECHANICAL CODE, INTERNATIONAL PLUMBING CODE, INTERNATIONAL BUILDING CODE, AND ALL OTHER APPLICABLE CITY, COUNTY, AND STATE CODES AND REGULATIONS IN EFFECT AT THE DATE OF THE PERMITTING. 3. COORDINATE THE INSTALLATION OF ALL HVAC PIPING, DUCTWORK, AND EQUIPMENT WITH PLUMBING PIPING, PLUMBING EQUIPMENT, FIRE PROTECTION PIPING AND ALL OTHER TRADES INCLUDING BUT NOT LIMITED TO: THE MECHANICAL CONTRACTOR, ELECTRICAL CONTRACTOR, FIRE PROTECTION CONTRACTOR, GENERAL CONTRACTOR, AND ANY CONTRACTOR HIRED DIRECTLY BY THE OWNER PRIOR TO FABRICATION AND INSTALLATION. WHERE CONFLICTS MAY OCCUR, THEY SHALL BE RESOLVED PRIOR TO INSTALLATION. 4. THE DRAWINGS SHOW THE GENERAL DESIGN, ARRANGEMENTS AND THE EXTENT OF THE SYSTEM. IT SHALL BE THE WORK OF THE CONTRACTOR TO MAKE SUCH SLIGHT ALTERATIONS AS MAY BE NECESSARY TO MAKE THE SYSTEM COMPLETE AND OPERATIONAL IN ACCORDANCE WITH THE DESIGN INTENT. MAJOR DEVIATIONS SUCH AS CHANGES IN COMPONENT SIZES, WEIGHTS, QUANTITIES, OR MATERIAL REQUIRE PRIOR APPROVAL BY THE CONSULTING ENGINEER. 5. ALL HVAC INFORMATION IS NOT SHOWN ON THE HVAC DRAWINGS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING INFORMATION ON ALL OTHER CONSTRUCTION DOCUMENTS INCLUDING ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS. 6. THE WORKING DRAWINGS ARE DIAGRAMMATIC. BECAUSE OF THE SMALL SCALE OF THE DRAWINGS, THEY DO NOT SHOW EVERY OFFSET, BEND OR ELBOW NECESSARY FOR THE COMPLETE INSTALLATION IN THE SPACE PROVIDED. ALL LOCATIONS FOR HVAC EQUIPMENT AND PIPING SHALL BE CHECKED AND COORDINATED WITH THE ARCHITECTURAL, MECHANICAL, STRUCTURAL AND ELECTRICAL DRAWINGS. 7. SPACE ABOVE ALL CEILINGS IS EXTREMELY LIMITED. CAREFUL COORDINATION IS REQUIRED WITH ALL TRADES BEFORE ANY PIPE, DUCT, OR EQUIPMENT IS ORDERED AND/OR INSTALLED. 1/8" SCALE SHOP DRAWINGS (SUBMITTED TO BGW FOR APPROVAL) ARE REQUIRED FOR ALL DIVISION 23 WORK. 1/8" SCALE LINDAB DRAWINGS MUST BE REVIEWED BY MECHANICAL CONTRACTOR AND RETURNED TO BGW FOR MODIFICATION PRIOR TO DUCTWORK BEING ORDERED. ANY CONFLICTS AND/OR CHANGES FOUND DURING INSTALLATION THAT RESULT FROM LACK OF COORDINATION BY THE CONTRACTORS DURING THE SHOP DRAWING PROCESS ARE THE RESPONSIBILITY OF THE CONTRACTOR. 8. THE DRAWINGS AND SPECIFICATIONS HAVE BEEN PREPARED TO SUPPLEMENT EACH OTHER AND THEY SHALL BE INTERPRETED AS AN INTEGRAL UNIT WITH THE ITEMS SHOWN ON ONE AND NOT THE OTHER BEING FURNISHED AND INSTALLED AS THOUGH SHOWN AND CALLED OUT IN BOTH. 9. DETAILS: THE CONTRACTOR IS RESPONSIBLE TO REVIEW AND USE WHERE APPROPRIATE ALL OF THE MECHANICAL DETAILS SHOWN ON THE DRAWINGS. DETAILS MAY OR MAY NOT BE CALLED OUT ON THE DRAWINGS WITH SYMBOLS OR KEYED NOTES. ANY CHANGES RESULTING FROM FAILURE TO INSTALL THE MECHANICAL SYSTEM WITHOUT USING THE INCLUDED DETAILS IS THE RESPONSIBILITY OF THE CONTRACTOR. 10. PREPARE 6 COPIES OF SUBMITTALS IN AN INDEXED, LABELED FOLDER CONTAINING FULL PERFORMANCE, MATERIAL AND INSTALLATION INFORMATION ABOUT ALL EQUIPMENT, PIPING, COMPONENTS AND ACCESSORIES TO BE USED. 11. THE STRUCTURE SHOWN ON ALL DETAILS MAY OR MAY NOT PERTAIN TO A PORTION OR ANY PORTION OF THE BUILDING. COORDINATE MOUNTING REQUIREMENTS WITH ARCHITECTURAL AND STRUCTURAL DRAWINGS. 12. ANY PART OF THIS INSTALLATION THAT FAILS, IS UNFIT, OR BECOMES DAMAGED DURING CONSTRUCTION SHALL BE REPAIRED OR REPLACED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER. 13. ALL EQUIPMENT SHALL PROVIDE THE SCHEDULED PERFORMANCE AT THE SITE ALTITUDE. 14. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE EQUIPMENT MANUFACTURER'S RECOMMENDATIONS. PROVIDE ALL FITTINGS, TRANSITIONS, VALVES, DAMPERS, AND OTHER DEVICES AND ACCESSORIES REQUIRED FOR A COMPLETE, WORKABLE INSTALLATION. 15. THE MECHANICAL CONTRACTOR SHALL FURNISH ALL REQUIRED MOTORS. ALL MOTOR STARTING EQUIPMENT, WHEN NOT A PART OF THE EQUIPMENT, WILL BE FURNISHED BY THE ELECTRICAL CONTRACTOR. 16. THE ELECTRICAL CONTRACTOR SHALL RUN CONDUIT FOR ALL HVAC CONTROL WIRING. CONDUIT SHALL RUN FROM THERMOSTAT LOCATION TO ABOVE CEILING IN FINISHED AREAS AND TO MECHANICAL UNIT WHERE THERE IS NO CEILING. MECHANICAL CONTRACTOR WILL PROVIDE AND INSTALL PLENUM RATED CABLE. MECHANICAL CONTRACTOR SHALL COORDINATE LOCATION AND QUANTITY OF CONDUIT WITH ELECTRICAL CONTRACTOR. 17. THE CONTRACTOR IS RESPONSIBLE FOR HVAC EQUIPMENT CHECK-IN, SAFEKEEPING, AND DAMAGE. 18. PROPERLY LUBRICATE ALL PIECES OF EQUIPMENT BEFORE TURNING THE SYSTEM OVER TO THE OWNER. 19. TWO OPERATING AND MAINTENANCE MANUALS SHALL BE PROVIDED IN HARD BACK LOOSE LEAF BINDERS. MANUALS SHALL CONTAIN PRODUCT CUT SHEETS AND OPERATING AND MAINTENANCE INSTRUCTIONS ON ALL EQUIPMENT, ACCESSORIES, FIXTURES, VALVES, ETC., PROVIDED FOR THE PROJECT. 20. UPON COMPLETION OF THE WORK, REMOVE ALL SURPLUS MATERIALS AND RUBBISH. MAKE ALL REQUIRED PATCHING AND REPAIRS OF OTHER TRADES' WORK DAMAGED BY THIS CONTRACTOR, AND LEAVE THE PREMISES IN A CLEAN, ORDERLY CONDITION. 21. THE CONTRACTOR SHALL OPERATE THE SYSTEM AND DEMONSTRATE ALL ASPECTS TO THE ENGINEER AND/OR OWNER, TO PROVE ITS OPERATION. ALL FILTERS USED DURING CONSTRUCTION SHALL BE REPLACED PRIOR TO THE TEST RUN PERIOD. 22. THE CONTRACTOR SHALL GUARANTEE THE HVAC SYSTEM INCLUDING DUCTWORK FOR A PERIOD OF ONE YEAR FROM THE DATE OF CERTIFICATE OF OCCUPANCY. CONTRACTOR TO INCLUDE PRICE FOR FIRST YEAR LABOR WARRANTY ON ALL OWNER SUPPLIED EQUIPMENT. 23. THE CONTRACTOR SHALL, DURING CONSTRUCTION, MAINTAIN A SET OF AS-BUILT REDLINED RECORD DRAWINGS AT THE PROJECT SITE. ALL CHANGES IN LAYOUT, ROUTING, EQUIPMENT, COMPONENTS, AND ACCESSORIES SHALL BE RECORDED. THESE REDLINES SHALL BE GIVEN TO THE ARCHITECT/ENGINEER AFTER THE FINAL INSPECTION. HVAC GENERAL NOTES. 24. RECORD DRAWINGS SHALL BE PROVIDED TO THE OWNER, ALONG WITH A COMPLETE SET OF EQUIPMENT OPERATING AND MAINTENANCE MANUALS. REQUIRED ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY IDENTIFIED AND THE NAMES AND ADDRESSES OF AT LEAST ONE SERVICE AGENCY SHALL BE PROVIDED. BI-POLAR ION GENERATORS AND MODEL NO. MANUFACTURER IG-1 SYMBOL PLASMA AIR 101C 1,500 120/1/60 ELECTRICAL VOLTS/Ø/Hz 4 WATTS APPROX. WATTS ACCESSORIES AND REMARKS INTERLOCK WITH FAN CIRCUIT SPECIFICATION SECTION 233333 MAX. CFM IG-2 2,500 120/1/60 5 WATTS IG-3 3,500 120/1/60 6 WATTS IG-4 4,000 120/1/60 10 WATTS INTERLOCK WITH FAN CIRCUIT INTERLOCK WITH FAN CIRCUIT INTERLOCK WITH FAN CIRCUIT INSTALLED IN RTU NO. & (QUANTITY) PLASMA AIR 101D PLASMA AIR 101E PLASMA AIR 201D 7(1), 8(1), 13(1), 14(1) 4(1), 9(1) 2(1), 3(1), 6(1) 10(1), 11(1), 12(1), 13(1), 14(1), 15(2) IG-5 5,000 120/1/60 12 WATTS INTERLOCK WITH FAN CIRCUIT PLASMA AIR 201E 7(1), 8(1), 13(1), 14(1) IG-6 8,000 120/1/60 30 WATTS INTERLOCK WITH FAN CIRCUIT PLASMA AIR 51E 7(1), 8(1), 13(1), 14(1) IG-7 10,000 120/1/60 50 WATTS INTERLOCK WITH FAN CIRCUIT PLASMA AIR 51F 7(1), 8(1), 13(1), 14(1) AS ALLOWED BY THE 2009 INTERNATIONAL MECHANICAL CODE AND ASHRAE 62-2004 THE OUTSIDE AIR IN THE BUILDING HAS BEEN REDUCED TO 5 CFM PER PERSON. THE SCHEDULED ION GENERATORS REDUCE THE BUILDING POLLUTANTS AND PROVIDE IMPROVED AIR QUALITY WHILE ACHIEVING ENERGY SAVINGS. IG-8 1,400 120/1/60 1 WATTS INTERLOCK WITH FAN CIRCUIT PLASMA AIR 7100 7(1), 8(1), 13(1), 14(1) IG-9 2,800 120/1/60 2 WATTS INTERLOCK WITH FAN CIRCUIT PLASMA AIR 7200 7(1), 8(1), 13(1), 14(1) IG-10 4,200 120/1/60 3 WATTS INTERLOCK WITH FAN CIRCUIT PLASMA AIR 7300 7(1), 8(1), 13(1), 14(1) IG-11 6,000 120/1/60 4 WATTS INTERLOCK WITH FAN CIRCUIT PLASMA AIR 7400 AC-1(1), AC-2(1) UNITS SUPPLIED BY BGW SUPPLY INC. A DIVISION OF BGW ARCHITECTS THROUGH A NATIONAL ACCOUNT TITUS PAR TITUS PAR TITUS PAR ROOF DOWNBLAST ROOF DOWNBLAST ROOF DOWNBLAST ROOF DOWNBLAST ROOF DOWNBLAST ROOF DOWNBLAST ROOF DOWNBLAST ROOF DOWNBLAST 5 5 5 5 5 5 5 5 75 75 75 75 75 75 WALL SWITCH WALL SWITCH EOC, TAB, & CONTROL SCOPE OF WORK AC-1 SYMBOL SANYO 30K72R MASTER CONTROL 131 SPLIT AIR CONDITIONING UNIT SCHEDULE 208/1/60 SPECIFICATION SECTION 238126 VOLT/Ø/Hz. LOCATION MANUFACTURER AND MODEL NO. 85 ACCESSORIES AND REMARKS 0.5 64 FLA INDOOR UNIT WEIGHT (LBS) 208/1/160 29,800 COOLING CAPACITY (BTUH) 3/8" LIQUID 620-840 CFM RANGE DIMENSIONS W" x H" x D" 60" x 15" x 10" OUTDOOR UNIT VOLT/Ø/Hz. 16.5 143 FLA WEIGHT (LBS) DIMENSIONS W" x H" x D" 39" x 35" x 17" INDOOR TEMP (ºF) 95 REFRIGERANT LINES 5/8" GAS OUTDOOR TEMP (ºF) AC-2 SANYO 30K72R RACK ROOM 133 208/1/60 85 0.5 64 208/1/160 29,800 3/8" 620-840 60" x 15" x 10" 16.5 143 39" x 35" x 17" 95 5/8" TITUS 300FL TITUS 300FL LAY-IN 14" x 14" 10" x 10" 14" x 14" 12" x 12" 16" x 16" 375/600 360º SUPPLY AIR WALL MOUNT TITUS 300FL 12" x 4" 14" x 6" 62" x 18" R-3 TITUS 350FL 500/1100 N/A RETURN AIR WALL MOUNT R-4 0/500 74" x 38" RETURN AIR N/A 26" x 8" R-5 500/1100 N/A RETURN AIR R-6 0/500 14" x 14" RETURN AIR N/A TITUS 350FL TITUS 350FL TITUS 350FL WALL MOUNT WALL MOUNT WALL MOUNT 60" x 16" 72" x 36" 24" x 6" 12" x 12" ACCESSORIES AND REMARKS 8000 SYMBOL RTU-1 25 DESIGN COOLING 79.2 2200 230,139 206,536 62.1 105 DESIGN HEATING MOTOR RPM MOCP 175 152 MCA 5 H.P. TOTAL UNIT 208/3/60 1725 VOLT/Ø/Hz. ELECTRICAL 2625 1), 3), 4), 10), 11), 12), 13), 16), 17), 18) ROOFTOP UNITS SUPPLIED BY BGW SUPPLY INC. A DIVISION OF DCA ARCHITECTS THROUGH A LENNOX NATIONAL ACCOUNT DOWN DISCHARGE ROOFTOP UNIT SCHEDULE (ELECTRIC HEAT) RTU-2 RTU-4 6000 15 77.7 149,359 131,951 61.9 150 145 3 1725 2310 204 204 RTU-3 15 76.5 127,794 61.6 1725 1.0 SPECIFICATION SECTION 237413 MANUFACTURER AND MODEL NO. NOMINAL TONS COOLING NOMINAL HEATING CAPACITY (MBH) TOTAL CFM MIN. O.A. CFM E.S.P. ("Wg) TOTAL CAPACITY SENSIBLE CAPACITY EDB (°F) EWB (°F) O.A. (°F) INPUT (KW) OUTPUT (MBH) OPERATING WEIGHT (LBS.) 2310 204 6000 835 1300 148,756 1.0 1.0 3 150 145 DX COOLING (S)EER EFFICIENCY 10.5 12.0 12.0 1), 3), 4), 10), 11), 12), 13), 16), 17), 18) 1), 3), 4), 10), 11), 12), 13), 16), 17), 18) 1), 3), 4), 10), 11), 12), 13), 16), 17), 18) 5000 RTU-5 12.5 76.8 735 120,203 108,682 61.6 150 134 3 1725 1380 1), 3), 4), 10), 11), 12), 13), 16), 17), 18) RTU-6 RTU-8 6 76.3 61.5 1725 1550 4 76.3 40,561 34,212 61.5 50 47 0.75 1725 761 0.8 153 51 RTU-7 3 75.2 23,466 61.3 1725 0.8 916 745 51 25 2400 1100 75 200 62,376 28,769 52,991 0.8 0.8 2 0.5 50 49 30 25 300 11.2 12.0 12.5 12.8 1), 3), 4), 10), 11), 12), 13), 16), 17), 18) 1), 3), 4), 10), 11), 12), 13), 16), 17), 18) 1), 3), 4), 10), 11), 12), 13), 16), 17), 18) 60.0 60.0 60.0 45.0 15.0 15.0 7.5 ACCESSORIES: 1) ECONOMIZER WITH DUAL SENSIBLE CONTROL. 2) RETURN AIR SMOKE DETECTOR. 3) SUPPLY AIR SMOKE DETECTOR. 4) CO2 SENSOR WALL MOUNTED. 5) HUMIDITROL. 6) VIBRATION ISOLATION CURB. 7) SEISMIC RATED CURB. 8) POWER EXHAUST. 9) HUMIDISTAT. 10) PROGRAMMABLE THERMOSTAT. 11) FACTORY INSTALLED DISCONNECT. 12) STANDARD LENNOX CURB. 13) VERTICAL VENT EXTENSION. 14) COMBUSTION AIR EXTENSION. 15) NETWORK CONTROL PANEL AND SENSORS. 16) GFCI OUTLET, FIELD WIRED. 17) LP KIT-FIELD INSTALLED. 18) COIL GUARDS-FIELD INSTALLED. LENNOX LCH036H4E LENNOX LCH048H4E LENNOX LCH072H4B LENNOX LCH150S4B LENNOX LCH180H4B LENNOX LCH180H4B LENNOX LCH300S4B DOWN DOWN DOWN DOWN DOWN DOWN 105 105 105 105 105 105 8000 25 79.2 2200 230,139 206,536 62.1 105 175 152 5 1725 2625 DOWN 204 1.0 10.5 60.0 LENNOX LCH300S4B 0.3 929 1140 66 1/6 GREENHECK G-097-B 12" 120/1/60 0.3 929 1140 66 1/6 GREENHECK G-097-B 12" 120/1/60 0.3 929 1140 66 1/6 GREENHECK G-097-B 12" 120/1/60 0.3 929 1140 66 1/6 GREENHECK G-097-B 12" 120/1/60 0.3 929 1140 66 1/6 GREENHECK G-097-B 12" 120/1/60 204 204 204 153 51 51 25 204 208/3/60 208/3/60 208/3/60 208/3/60 208/3/60 208/3/60 208/3/60

Transcript of M001 MECHANICAL SCHEDULES & GENcochisetech.net/wp-content/uploads/2016/11/90-Mechanical.pdfb. test...

Page 1: M001 MECHANICAL SCHEDULES & GENcochisetech.net/wp-content/uploads/2016/11/90-Mechanical.pdfb. test and balance (tab) (mechanical contractor contracted) • upon arrival to the site,

MECHANIC

AL

SCHED

ULE

S& G

ENER

AL

NOTES

DO NOT SCALE DRAWING

M001

THIS

DR

AWIN

G IS C

LASSIFIE

D A

SP

AR

T O

F A

N U

NP

UB

LISHED

COLL

ECTIO

N O

F V

ISUAL

AR

T.

UND

ER

THE 1978

COP

YR

IGHT

ACT, IT IS A

N E

XCLU

SIV

EOR

IGIN

AL

WOR

K O

F A

UTHOR

SHIP

.NONE O

F T

HE P

ICTOR

IAL,

GR

AP

HIC

OR

TECHNIC

AL

CHAR

TS O

R D

RAWIN

GS

DEP

ICTED

ON T

HIS

SHEET M

AY

BE R

EP

ROD

UCED

OR

TR

ANSM

ITTED

IN A

NY F

OR

M O

RB

Y A

NY M

EANS W

ITHOUT T

HE

EXP

RESS P

RIO

R W

RITTEN

PER

MIS

SIO

N O

F T

HE A

RCHITECT.

THIS

PLA

N IS P

ROD

UCED

ONLY

FOR

THIS

PR

OJE

CT O

N T

HIS

SITE

AND

MAY N

OT B

E U

SED

AT

OTHER

LOCATIO

NS.

SHEET T

ITLE

:

OR

IGIN

AL

ISSUE: P

relim

inar

y

SEAL:

REV

DATE

DESCR

IPTIO

N

SHEET NUMBER:

PR

OJE

CT: A

C489

PR

OJE

CT:

BAP

TIS

T C

HUR

CH

SIE

RR

A V

ISTA, AZ

VILLA

GE M

EAD

OWS

DESCR

IPTIO

N

DESCR

IPTIO

N

DESCR

IPTIO

N

DESCR

IPTIO

N

DESCR

IPTIO

N

MM

-DD

-YY

MM

-DD

-YY

MM

-DD

-YY

MM

-DD

-YY

MM

-DD

-YY

MM

-DD

-YY

41 2 3 5 6

DESCR

IPTIO

N

OR

IGIN

AL

ISSUE

Pr

elim

inar

y0

DANIE

L COOK

AR

CHITECT│

290

9 W

ASHIN

GTO

N B

LVD

- O

GD

EN, UT

8440

1│P

H: 80

0-5

52-

7137│

www.B

GWSER

VIC

ES.c

om

SIE

RR

A V

ISTA, AR

IZONA 8

5635

140

7 S E

L CAM

INO R

EAL

PRELIMINARY D

RAWING!

NOT

FOR C

ONSTR

UCTION!

T

H

C

TITLE

SECTION

SHEET #

MECH ROOF PLAN

DETAIL #

SHEET #

1

EQUIPMENT CALLOUT

SCOPE OF WORK FOR LENNOX PROVIDED EOC, AND MECHANICAL CONTRACTOR CONTROLINSTALLATION AND MECHANICAL CONTRACTOR CONTRACTED INDEPENDENT TEST AND BALANCE.

A. EQUIPMENT OPERATIONS CHECK (EOC) (LENNOX PROVIDED) THROUGH BGWS

• TEST ALL LENNOX EQUIPMENT BASED ON THE STANDARD LENNOX EOC REPORT.• CONTACT LENNOX SUPPORT WITH ANY EQUIPMENT DEFICIENCIES AND COORDINATE REPAIROR REPLACEMENT AS NECESSARY TO ASSIST IN PROVIDING OPERATIONAL EQUIPMENT PRIORTO OPENING DATE.• DISTRIBUTE COPIES OF EOC REPORT AS REQUESTED BY LENNOX.

B. TEST AND BALANCE (TAB) (MECHANICAL CONTRACTOR CONTRACTED)

• UPON ARRIVAL TO THE SITE, INSPECT MECHANICAL SYSTEM AND NOTE ANY DEFICIENCIESTHAT COULD PREVENT PROPER OPERATION AND/OR BALANCING OF THE MECHANICALSYSTEM TO THE OWNER, GENERAL CONTRACTOR AND MECHANICAL CONTRACTOR.• INSPECT ALL MECHANICAL EQUIPMENT FOR PROPER INSTALLATION PER MEP DESIGN.• TEST ALL MECHANICAL EQUIPMENT PER NEBB STANDARDS FOR AIR BALANCE FOR PROPEROPERATION.• THE BALANCING OF THE MECHANICAL SYSTEM WILL BE PERFORMED TO MEET NEBBSTANDARDS UNLESS SPECIFICALLY REQUESTED OTHERWISE, IN WRITING, BY OWNER OROWNERS ENGINEERING FIRM.• BALANCE ALL RTU’S, GRILLS, REGISTERS AND EXHAUST FANS PER MECHANICAL DESIGN ASNOTED ON MEP DRAWINGS PER NEBB STANDARDS FOR AIR BALANCE.• GENERATE A FIELD REPORT OF ANY OUTSTANDING MECHANICAL DEFICIENCIES, IF ANY, THATCOULD NOT BE RESOLVED DURING THE TAB VISIT AND DISTRIBUTE A COPY TO THE OWNER,GENERAL CONTRACTOR AND MECHANICAL CONTRACTOR AND NOTE IF A RE-VISIT WILL BEREQUIRED.• GENERATE A COMPLETE TAB REPORT AND SUBMIT TO THE OWNER AND AS DIRECTED WITHINONE (1) WEEK OF THE COMPLETION OF THE AIR BALANCE.

C. CONTROL INSTALLATION (BGW SUPPLY CONTRACTED CONTROL CONTRACTOR)

• PROVIDE CONTROL INSTALLATION DRAWINGS SHOWING CABLE RUNS ANDLOCATIONS.• PROVIDE AND TERMINATE PLENUM CABLE FOR LENNOX PROVIDED THEROMOSTATS,HUMIDITY SENSORS AND CO2 SENSORS CONDUIT IN SPACE.• PROVIDE, PLENUM COMMUNICATION CABLE BETWEEN RTUS INSTALLED BYELECTRICAL CONTRACTOR.• PROVIDE, AND TERMINATE PLENUM CABLE FOR LENNOX PROVIDED SPACESENSORS AND HUMIDITY SENSORS CONDUIT IN SPACE, IF REQUIRED. WIREINSTALLATION BY ELECTRICAL CONTRACTOR.• PROGRAM AND COMMISSION CONTROLS AS REQUIRED TO MEET OWNERSPECIFICATIONS.• PROVIDE REPORT DETAILING COMMISSION OF CONTROLS AND SUBMIT TOOWNER.• PROVIDE OWNER OPERATORS 2 HOURS OF TRAINING.

D. WARRANTY

• LENNOX PROVIDES A ONE (1) YEAR PARTS WARRANTY ON THE WORKMANSHIP OF ALLLENNOX PROVIDED MATERIAL, AND EQUIPMENT, STARTING AT CERTIFICATE OF OCCUPANCY.

E. CLARIFICATIONS AND RESPONSIBILITY OF MECHANICAL & ELECTRICAL CONTRACTOR

• CONDUIT, RACEWAYS SHALL BE FURNISHED AND INSTALLED BY THE ELECTRICALCONTRACTOR. CONTROL CONTRACTOR WILL REQUIRE A CONDUIT, AND WIRE RACEWAY PATHFOR THE SPACE SENSORS IN AREAS NOT ACCESSIBLE, SUCH AS WALLS, SANCTUARY ANDGYMNASIUM AREAS, SUCH THAT ELECTRICAL CONTRACTOR CAN INSTALL CONTROL WIRE ANDSPACE SENSORS.• CABLE (PROVIDED BY THE CONTROL CONTRACTOR) SHALL BE PULLED OR INSTALLED ATEACH LOCATION SHOWN ON THE CONTROL DRAWINGS. (INSTALLED BY ELECTRICALCONTRACTOR)• ELECTRICAL CONTRACTOR SHALL INSTALL ALL SENSORS AND PANEL.• THE EOC, TAB, AND CONTROL INSTALLATION SCOPE WILL BE COORDINATED WITH THEGENERAL AND/OR MECHANICAL CONTRACTOR.• THE GENERAL OR MECHANICAL CONTRACTOR WILL NOTIFY LENNOX WITH AT LEASTFOURTEEN (14) DAYS ADVANCED NOTICE THAT THE HVAC SYSTEM IS 100% COMPLETE ANDREADY FOR EOC AND CONTROL TERMINATION.O HIGH VOLTAGE MUST BE CONNECTED TO EACH UNITO GAS MUST BE CONNECTED TO EACH UNITO PROPER PHASE ROTATION MUST BE CONFIRMED AT THE DISCONNECTO ALL STAGES OF HEATING AND COOLING MUST BE CONFIRMED OPERATIONALO UNITS CAN BE PUT IN STANDALONE OPERATION BY SETTING THE UNIT OPERATION TO LCONNECTION/RETURN AIR BACK UP MODE. CONSULT THE M-2 PRODIGY CONTROL MANUALFOR INSTRUCTIONS OR CONTACT LENNOX NATIONAL ACCOUNT TECHNICAL SUPPORT1-800-367-6285 FOR ASSISTANCE.• THE MECHANICAL CONTRACTOR WILL PROVIDE A REPRESENTATIVE ON-SITE DURING THEEOC SERVICE TO ADDRESS DEFICIENCIES FOUND. LENNOX WILL MAKE ALL REASONABLEATTEMPTS TO RESOLVE DEFICIENCIES, IF ANY, WITH THE MECHANICAL CONTRACTOR WHILEONSITE.

F. WORKING HOURS• WORKING HOURS SHALL FOLLOW CONSTRUCTIONS HOURS OR AS REQUESTED BY THEGENERAL CONTRACTOR

1

1

RTU1

1

1

1

1

MECHANICAL GENERAL NOTES MECHANICAL LEGEND

DROP

RISE

DROP

20x10

16''Ø

RISE

DROP

RISE

16''Ø

FSD

16x10

FD

SD

E-1CFM

D-1CFM

D-1CFM

20x10

20x10

20x10 14''Ø

12x10

12x10

D-1CFM

D-1CFM

16''Ø 6''Ø

EXHAUST AIR REGISTER - SQUARE

SUPPLY DIFFUSER - SQUARE

FIRE/SMOKE DAMPER

SMOKE DAMPER

LINEAR DIFFUSERS - SIDE MOUNT

FLEXIBLE DUCT

FIRE DAMPER

MANUAL BALANCING DAMPER

SLOPED DUCT DROP

SLOPED DUCT RISE

FLAT OVAL DUCT

DUCT - RISE

UNDER FLOOR ROUND DUCT

POSITIVE PRESSURE DUCT - DROP

ROUND DUCT

RECTANGULAR DUCT

ROUND DUCT - DROP

ROUND DUCT - RISE

SOUND ATTENUATOR

ROUND TO ROUND TRANSITION

RECTANGULAR TRANSITION - OFFSET

RECTANGULAR TO ROUND TRANSITION

RECTANGULAR TRANSITION

LINEAR DIFFUSER - BOTTOM MOUNT

SUPPLY DIFFUSER - ROUND

SECTION CALLOUT

DETAIL CALLOUT

THERMOSTAT OR TEMPERATURE SENSOR

HUMIDISTAT

CARBON DIOXIDE DETECTOR

POINT OF CONNECTION

POINT OF DEMOLITION

REVISION DELTA

KEYED NOTE CALLOUT

M3011

SCALE: 1/8" = 1' - 0"

M5011

R-1CFM RETURN AIR REGISTER - SQUARE

92ºF Db SUMMER

HVAC DESIGN DATA

OUTSIDE DESIGN TEMPS.: 64ºF Wb SUMMER17ºF Db WINTER

DESIGN ALTITUDE: 175 FT.

INTERIOR DESIGN DATA

ALL

SUMMER WINTER

Db

75º

%HUMIDITY

50% 72º 40%

Db %HUMIDITY

NOTE:

ALL ROUND DUCTWORK, FITTINGS AND VOLUME CONTROL DAMPERS ARE TO BESPIROSAFE GASKETED DUCT MANUFACTURED BY LINDAB. BGW HAS A NATIONALACCOUNT AGREEMENT WITH LINDAB INC. FOR THIS PROJECT CONTACT LINDABTAKE OFF DEPARTMENT AT (757) 488-7234 EXT. 381 FOR SPIRAL DUCT QUOTATION.

THE DRAWINGS INDICATE DIAGRAMMATICALLY THE EXTENT OF THE WORK. DUE TOTHE SCALE OF THE DRAWINGS, OFFSET, FITTINGS, AND ACCESSORIES MAY NOT BEINDICATED. WORK INDICATED, BUT HAVING DETAILS OMITTED, SHALL BECOMPLETELY PROVIDED BY CONTRACTOR TO PERFORM FUNCTION INTENDED ATNO ADDITIONAL COST.

CONTRACTOR SHALL EXAMINE THE ARCHITECTURAL, STRUCTURAL, PLUMBING,MECHANICAL, AND ELECTRICAL DRAWINGS AND SPECIFICATIONS TO AVOIDCONFLICT WITH OTHER TRADES. MINOR VARIATIONS IN LOCATION OF EQUIPMENTSHALL BE MADE ON WRITTEN APPROVAL OF THE ENGINEER AT NO ADDITIONALCOST.

MECHANICAL CONTRACTOR IS RESPONSIBLE FOR PAYMENT, ORDERING, DELIVERYCOORDINATION RECEIVING AND INSTALLATION OF ALL THE LINDAB SUPPLIEDMATERIAL.

THE CONTRACTOR IS REQUIRED TO REVIEW THE MECHANICAL DRAWINGS,MAKING ANY NECESSARY MODIFICATIONS TO ACCOUNT FOR FIELD VARIANCESAND SEND THESE FINAL DRAWINGS TO LINDAB FOR A DUCT QUOTATION. THESEREVISED PLANS ARE TO BE E-MAILED 72 HOURS BEFORE BID TIME TO LINDAB TAKEOFF FOR A PRODUCT QUOTATION.

THE CONTRACTOR MUST APPROVE THE FINAL DUCT DRAWINGS AND BILL OFMATERIAL BEFORE PLACING THE ORDER WITH LINDAB.

NOTE:

MECHANICAL CONTRACTOR TO REVIEW ALL DRAWINGSFOR CONFLICTS WITH STRUCTURE AND OTHER TRADES.MECHANICAL CONTRACTOR TO RESOLVE ALL CONFLICTSWITH ENGINEER PRIOR TO ORDERING, FABRICATING ORINSTALLING DUCTWORK.

NOTE:

1) SPACE ABOVE CEILING IS TO BE USED AS A RETURN AIRPLENUM. ALL MATERIALS TO BE PLENUM RATED.

2) ALL TERMINAL SUPPLY DUCT BRANCHES TO BEEQUIPPED WITH MANUAL BALANCING DAMPER.

3) FLEX DUCT (MAXIMUM 60" LONG) TYPICAL ON EACHDIFFUSER EXCEPT IN EXPOSED APPLICATIONS.

4) PROVIDE TURNING VANES IN ALL RECTANGULARELBOWS. �

EF-1

SYMBOL

GREENHECK G-123-B ROOF

CFM

ARRANGEMENT,ROTATION &DISCHARGE

DOWNBLAST 825

EXHAUST FAN SCHEDULE

0.35 12"

SPECIFICATIONSECTION 233423

HEIGHTABOVE ROOF

(INCHES)SP "WGTYPEMANUFACTURER AND

MODEL NO.

OPERATINGWEIGHT

(LBS.)ACCESSORIES AND

REMARKS

995

RPM

FANDETAIL

NO. RPM

MOTOR

1140

H.P.

ELECTRICAL

VOLT/Ø/Hz.

76

CONTROLMETHOD

1/6

EF-2

EF-3 150 0.35 12"1323 1550 471/20

EF-4

GREENHECK G-080-D WALL SWITCH

EF-5

5

0.3929 1140 661/6GREENHECK G-097-B

EF-6

EF-7

EF-8

120/1/60 BACKDRAFT DAMPER

GREENHECK G-123-B 750 0.35 12" WALL SWITCH958 1140 761/6 BACKDRAFT DAMPER

BACKDRAFT DAMPER

BACKDRAFT DAMPER

BACKDRAFT DAMPER

WALL SWITCH

WALL SWITCH

12"

BACKDRAFT DAMPERWALL SWITCH

BACKDRAFT DAMPERWALL SWITCH

BACKDRAFT DAMPERWALL SWITCH

EF-9 BACKDRAFT DAMPER

24" x 24"

OVERALLSIZE

DIFFUSER AND GRILLE SCHEDULE

D-1

SYMBOL

TITUS TMS

MIN./MAX.CFM

0/100 4-WAY

BLOW

6"Ø

NECKSIZE

SUPPLY AIR

TYPEACCESSORIESAND REMARKS

LAY-IN

D-2 TITUS TMS 100/240 8"Ø

D-3 TITUS TMS 240/400 10"Ø

24" x 24"4-WAY SUPPLY AIR

24" x 24"4-WAY SUPPLY AIR

LAY-IN

LAY-IN

SPECIFICATIONSECTION 233713

MANUFACTURER ANDMODEL NO.

D-4 TITUS TMS 400/520 12"Ø24" x 24"4-WAY SUPPLY AIR LAY-IN

D-7

250/425 360º SUPPLY AIR NECK MOUNT

D-8

375/600 360º SUPPLY AIR NECK MOUNT

24" x 24"E-1 0/130 4-WAY 6"Ø LAY-IN

E-2 130/260 8"Ø

E-3 260/400 10"Ø

24" x 24"4-WAY

24" x 24"4-WAY

LAY-IN

LAY-IN

24" x 24"D-5 TITUS 300FL 0/130 4-WAY SUPPLY AIR

D-6

24" x 24"R-1 TITUS PXP 500/1100 N/A RETURN AIR LAY-IN

R-2 TITUS PXP 0/500 24" x 12" LAY-INRETURN AIRN/A

N/A

N/A

EXHAUST AIR

EXHAUST AIR

EXHAUST AIR

120/1/60

120/1/60

120/1/60

1. PROVIDE ALL LABOR, MATERIALS, AND EQUIPMENT NECESSARY TO CONSTRUCT A COMPLETE, OPERATIONAL HVAC SYSTEM FOR THEENTIRE PROJECT AS SHOWN ON THESE DRAWINGS, INCLUDING ALL NECESSARY FEES AND PERMITS.

2. THE ENTIRE INSTALLATION SHALL CONFORM TO THE MOST RECENTLY ADOPTED REQUIREMENTS OF THE INTERNATIONAL MECHANICALCODE, INTERNATIONAL PLUMBING CODE, INTERNATIONAL BUILDING CODE, AND ALL OTHER APPLICABLE CITY, COUNTY, AND STATE CODESAND REGULATIONS IN EFFECT AT THE DATE OF THE PERMITTING.

3. COORDINATE THE INSTALLATION OF ALL HVAC PIPING, DUCTWORK, AND EQUIPMENT WITH PLUMBING PIPING, PLUMBING EQUIPMENT, FIREPROTECTION PIPING AND ALL OTHER TRADES INCLUDING BUT NOT LIMITED TO: THE MECHANICAL CONTRACTOR, ELECTRICALCONTRACTOR, FIRE PROTECTION CONTRACTOR, GENERAL CONTRACTOR, AND ANY CONTRACTOR HIRED DIRECTLY BY THE OWNER PRIORTO FABRICATION AND INSTALLATION. WHERE CONFLICTS MAY OCCUR, THEY SHALL BE RESOLVED PRIOR TO INSTALLATION.

4. THE DRAWINGS SHOW THE GENERAL DESIGN, ARRANGEMENTS AND THE EXTENT OF THE SYSTEM. IT SHALL BE THE WORK OF THECONTRACTOR TO MAKE SUCH SLIGHT ALTERATIONS AS MAY BE NECESSARY TO MAKE THE SYSTEM COMPLETE AND OPERATIONAL INACCORDANCE WITH THE DESIGN INTENT. MAJOR DEVIATIONS SUCH AS CHANGES IN COMPONENT SIZES, WEIGHTS, QUANTITIES, ORMATERIAL REQUIRE PRIOR APPROVAL BY THE CONSULTING ENGINEER.

5. ALL HVAC INFORMATION IS NOT SHOWN ON THE HVAC DRAWINGS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATINGINFORMATION ON ALL OTHER CONSTRUCTION DOCUMENTS INCLUDING ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICALDRAWINGS.

6. THE WORKING DRAWINGS ARE DIAGRAMMATIC. BECAUSE OF THE SMALL SCALE OF THE DRAWINGS, THEY DO NOT SHOW EVERY OFFSET,BEND OR ELBOW NECESSARY FOR THE COMPLETE INSTALLATION IN THE SPACE PROVIDED. ALL LOCATIONS FOR HVAC EQUIPMENT ANDPIPING SHALL BE CHECKED AND COORDINATED WITH THE ARCHITECTURAL, MECHANICAL, STRUCTURAL AND ELECTRICAL DRAWINGS.

7. SPACE ABOVE ALL CEILINGS IS EXTREMELY LIMITED. CAREFUL COORDINATION IS REQUIRED WITH ALL TRADES BEFORE ANY PIPE, DUCT,OR EQUIPMENT IS ORDERED AND/OR INSTALLED. 1/8" SCALE SHOP DRAWINGS (SUBMITTED TO BGW FOR APPROVAL) ARE REQUIRED FORALL DIVISION 23 WORK. 1/8" SCALE LINDAB DRAWINGS MUST BE REVIEWED BY MECHANICAL CONTRACTOR AND RETURNED TO BGW FORMODIFICATION PRIOR TO DUCTWORK BEING ORDERED. ANY CONFLICTS AND/OR CHANGES FOUND DURING INSTALLATION THAT RESULTFROM LACK OF COORDINATION BY THE CONTRACTORS DURING THE SHOP DRAWING PROCESS ARE THE RESPONSIBILITY OF THECONTRACTOR.

8. THE DRAWINGS AND SPECIFICATIONS HAVE BEEN PREPARED TO SUPPLEMENT EACH OTHER AND THEY SHALL BE INTERPRETED AS ANINTEGRAL UNIT WITH THE ITEMS SHOWN ON ONE AND NOT THE OTHER BEING FURNISHED AND INSTALLED AS THOUGH SHOWN AND CALLEDOUT IN BOTH.

9. DETAILS: THE CONTRACTOR IS RESPONSIBLE TO REVIEW AND USE WHERE APPROPRIATE ALL OF THE MECHANICAL DETAILS SHOWN ONTHE DRAWINGS. DETAILS MAY OR MAY NOT BE CALLED OUT ON THE DRAWINGS WITH SYMBOLS OR KEYED NOTES. ANY CHANGESRESULTING FROM FAILURE TO INSTALL THE MECHANICAL SYSTEM WITHOUT USING THE INCLUDED DETAILS IS THE RESPONSIBILITY OF THECONTRACTOR.

10. PREPARE 6 COPIES OF SUBMITTALS IN AN INDEXED, LABELED FOLDER CONTAINING FULL PERFORMANCE, MATERIAL AND INSTALLATIONINFORMATION ABOUT ALL EQUIPMENT, PIPING, COMPONENTS AND ACCESSORIES TO BE USED.

11. THE STRUCTURE SHOWN ON ALL DETAILS MAY OR MAY NOT PERTAIN TO A PORTION OR ANY PORTION OF THE BUILDING. COORDINATEMOUNTING REQUIREMENTS WITH ARCHITECTURAL AND STRUCTURAL DRAWINGS.

12. ANY PART OF THIS INSTALLATION THAT FAILS, IS UNFIT, OR BECOMES DAMAGED DURING CONSTRUCTION SHALL BE REPAIRED ORREPLACED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER.

13. ALL EQUIPMENT SHALL PROVIDE THE SCHEDULED PERFORMANCE AT THE SITE ALTITUDE.

14. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE EQUIPMENT MANUFACTURER'S RECOMMENDATIONS. PROVIDEALL FITTINGS, TRANSITIONS, VALVES, DAMPERS, AND OTHER DEVICES AND ACCESSORIES REQUIRED FOR A COMPLETE, WORKABLEINSTALLATION.

15. THE MECHANICAL CONTRACTOR SHALL FURNISH ALL REQUIRED MOTORS. ALL MOTOR STARTING EQUIPMENT, WHEN NOT A PART OF THEEQUIPMENT, WILL BE FURNISHED BY THE ELECTRICAL CONTRACTOR.

16. THE ELECTRICAL CONTRACTOR SHALL RUN CONDUIT FOR ALL HVAC CONTROL WIRING. CONDUIT SHALL RUN FROM THERMOSTATLOCATION TO ABOVE CEILING IN FINISHED AREAS AND TO MECHANICAL UNIT WHERE THERE IS NO CEILING. MECHANICAL CONTRACTORWILL PROVIDE AND INSTALL PLENUM RATED CABLE. MECHANICAL CONTRACTOR SHALL COORDINATE LOCATION AND QUANTITY OF CONDUITWITH ELECTRICAL CONTRACTOR.

17. THE CONTRACTOR IS RESPONSIBLE FOR HVAC EQUIPMENT CHECK-IN, SAFEKEEPING, AND DAMAGE.

18. PROPERLY LUBRICATE ALL PIECES OF EQUIPMENT BEFORE TURNING THE SYSTEM OVER TO THE OWNER.

19. TWO OPERATING AND MAINTENANCE MANUALS SHALL BE PROVIDED IN HARD BACK LOOSE LEAF BINDERS. MANUALS SHALL CONTAINPRODUCT CUT SHEETS AND OPERATING AND MAINTENANCE INSTRUCTIONS ON ALL EQUIPMENT, ACCESSORIES, FIXTURES, VALVES, ETC.,PROVIDED FOR THE PROJECT.

20. UPON COMPLETION OF THE WORK, REMOVE ALL SURPLUS MATERIALS AND RUBBISH. MAKE ALL REQUIRED PATCHING AND REPAIRS OFOTHER TRADES' WORK DAMAGED BY THIS CONTRACTOR, AND LEAVE THE PREMISES IN A CLEAN, ORDERLY CONDITION.

21. THE CONTRACTOR SHALL OPERATE THE SYSTEM AND DEMONSTRATE ALL ASPECTS TO THE ENGINEER AND/OR OWNER, TO PROVE ITSOPERATION. ALL FILTERS USED DURING CONSTRUCTION SHALL BE REPLACED PRIOR TO THE TEST RUN PERIOD.

22. THE CONTRACTOR SHALL GUARANTEE THE HVAC SYSTEM INCLUDING DUCTWORK FOR A PERIOD OF ONE YEAR FROM THE DATE OFCERTIFICATE OF OCCUPANCY. CONTRACTOR TO INCLUDE PRICE FOR FIRST YEAR LABOR WARRANTY ON ALL OWNER SUPPLIED EQUIPMENT.

23. THE CONTRACTOR SHALL, DURING CONSTRUCTION, MAINTAIN A SET OF AS-BUILT REDLINED RECORD DRAWINGS AT THE PROJECT SITE.ALL CHANGES IN LAYOUT, ROUTING, EQUIPMENT, COMPONENTS, AND ACCESSORIES SHALL BE RECORDED. THESE REDLINES SHALL BEGIVEN TO THE ARCHITECT/ENGINEER AFTER THE FINAL INSPECTION.HVAC GENERAL NOTES.

24. RECORD DRAWINGS SHALL BE PROVIDED TO THE OWNER, ALONG WITH A COMPLETE SET OF EQUIPMENT OPERATING ANDMAINTENANCE MANUALS. REQUIRED ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY IDENTIFIED AND THE NAMES AND ADDRESSES OFAT LEAST ONE SERVICE AGENCY SHALL BE PROVIDED.

BI-POLAR ION GENERATORS

AND MODEL NO.MANUFACTURER

IG-1

SYMBOL

PLASMA AIR 101C 1,500 120/1/60

ELECTRICAL

VOLTS/Ø/Hz

4 WATTS

APPROX. WATTS

ACCESSORIESAND REMARKS

INTERLOCK WITH FAN CIRCUIT

SPECIFICATIONSECTION233333

MAX. CFM

IG-2 2,500 120/1/60 5 WATTS

IG-3 3,500 120/1/60 6 WATTS

IG-4 4,000 120/1/60 10 WATTS

INTERLOCK WITH FAN CIRCUIT

INTERLOCK WITH FAN CIRCUIT

INTERLOCK WITH FAN CIRCUIT

INSTALLED IN RTUNO. & (QUANTITY)

PLASMA AIR 101D

PLASMA AIR 101E

PLASMA AIR 201D 7(1), 8(1), 13(1), 14(1)

4(1), 9(1)

2(1), 3(1), 6(1)

10(1), 11(1), 12(1), 13(1), 14(1), 15(2)

IG-5 5,000 120/1/60 12 WATTS INTERLOCK WITH FAN CIRCUITPLASMA AIR 201E 7(1), 8(1), 13(1), 14(1)

IG-6 8,000 120/1/60 30 WATTS INTERLOCK WITH FAN CIRCUITPLASMA AIR 51E 7(1), 8(1), 13(1), 14(1)

IG-7 10,000 120/1/60 50 WATTS INTERLOCK WITH FAN CIRCUITPLASMA AIR 51F 7(1), 8(1), 13(1), 14(1)

AS ALLOWED BY THE 2009 INTERNATIONAL MECHANICAL CODE AND ASHRAE 62-2004 THE OUTSIDE AIR IN THE BUILDING HAS BEEN REDUCED TO 5 CFM PER PERSON.THE SCHEDULED ION GENERATORS REDUCE THE BUILDING POLLUTANTS AND PROVIDE IMPROVED AIR QUALITY WHILE ACHIEVING ENERGY SAVINGS.

IG-8 1,400 120/1/60 1 WATTS INTERLOCK WITH FAN CIRCUITPLASMA AIR 7100 7(1), 8(1), 13(1), 14(1)

IG-9 2,800 120/1/60 2 WATTS INTERLOCK WITH FAN CIRCUITPLASMA AIR 7200 7(1), 8(1), 13(1), 14(1)

IG-10 4,200 120/1/60 3 WATTS INTERLOCK WITH FAN CIRCUITPLASMA AIR 7300 7(1), 8(1), 13(1), 14(1)

IG-11 6,000 120/1/60 4 WATTS INTERLOCK WITH FAN CIRCUITPLASMA AIR 7400 AC-1(1), AC-2(1)

UNITS SUPPLIED BY BGW SUPPLY INC. A DIVISION OF BGW ARCHITECTS THROUGH A NATIONAL ACCOUNT

TITUS PAR

TITUS PAR

TITUS PAR

ROOF DOWNBLAST

ROOF DOWNBLAST

ROOF DOWNBLAST

ROOF DOWNBLAST

ROOF DOWNBLAST

ROOF DOWNBLAST

ROOF DOWNBLAST

ROOF DOWNBLAST

5

5

5

5

5

5

5

5

75

75

75

75

75

75

WALL SWITCH

WALL SWITCH

EOC, TAB, & CONTROL SCOPE OF WORK

AC-1

SYMBOL

SANYO 30K72R MASTERCONTROL 131

SPLIT AIR CONDITIONING UNIT SCHEDULE

208/1/60

SPECIFICATIONSECTION 238126

VOLT/Ø/Hz.LOCATIONMANUFACTURER AND

MODEL NO.

85

ACCESSORIES ANDREMARKS

0.564

FLA

INDOOR UNITWEIGHT

(LBS)

208/1/16029,800

COOLINGCAPACITY

(BTUH)

3/8"

LIQUID

620-840

CFMRANGE

DIMENSIONSW" x H" x D"

60" x 15" x 10"

OUTDOOR UNIT

VOLT/Ø/Hz.

16.5143

FLAWEIGHT

(LBS)DIMENSIONSW" x H" x D"

39" x 35" x 17"

INDOORTEMP (ºF)

95

REFRIGERANTLINES

5/8"

GASOUTDOORTEMP (ºF)

AC-2 SANYO 30K72R RACKROOM 133 208/1/60 850.564 208/1/16029,800 3/8"620-840 60" x 15" x 10" 16.514339" x 35" x 17" 955/8"

TITUS 300FL

TITUS 300FL

LAY-IN14" x 14"

10" x 10"

14" x 14"

12" x 12"

16" x 16"

375/600 360º SUPPLY AIR WALL MOUNTTITUS 300FL 12" x 4"14" x 6"

62" x 18"R-3 TITUS 350FL 500/1100 N/A RETURN AIR WALL MOUNT

R-4 0/500 74" x 38" RETURN AIRN/A

26" x 8"R-5 500/1100 N/A RETURN AIR

R-6 0/500 14" x 14" RETURN AIRN/A

TITUS 350FL

TITUS 350FL

TITUS 350FL

WALL MOUNT

WALL MOUNT

WALL MOUNT

60" x 16"

72" x 36"

24" x 6"

12" x 12"

ACCESSORIES ANDREMARKS

8000

SYMBOL

RTU-1 25

DESIGN COOLING

79.22200 230,139 206,536 62.1 105

DESIGN HEATINGMOTOR

RPMMOCP

175152

MCA

5

H.P.

TOTAL UNIT

208/3/60 1725

VOLT/Ø/Hz.

ELECTRICAL

2625 1), 3), 4), 10), 11), 12), 13), 16), 17), 18)

ROOFTOP UNITS SUPPLIED BY BGW SUPPLY INC. A DIVISION OF DCA ARCHITECTS THROUGH A LENNOX NATIONAL ACCOUNT

DOWN

DISCHARGE

ROOFTOP UNIT SCHEDULE (ELECTRIC HEAT)

RTU-2

RTU-4 600015 77.7149,359 131,951 61.9 150145 3 1725 2310

204

204

RTU-3 15 76.5127,794 61.6 17251.0

SPECIFICATIONSECTION 237413

MANUFACTURER ANDMODEL NO.

NOMINALTONS

COOLING

NOMINALHEATINGCAPACITY

(MBH)TOTALCFM

MIN. O.A.CFM

E.S.P.("Wg)

TOTALCAPACITY

SENSIBLECAPACITY

EDB(°F)

EWB(°F)

O.A.(°F)

INPUT(KW)

OUTPUT(MBH)

OPERATINGWEIGHT

(LBS.)

2310204 6000 835

1300

148,756

1.0

1.0

3150145

DX COOLING

(S)EER

EFFICIENCY

10.5

12.0

12.0

1), 3), 4), 10), 11), 12), 13), 16), 17), 18)

1), 3), 4), 10), 11), 12), 13), 16), 17), 18)

1), 3), 4), 10), 11), 12), 13), 16), 17), 18)

5000RTU-5 12.5 76.8735 120,203 108,682 61.6 150134 3 1725 1380 1), 3), 4), 10), 11), 12), 13), 16), 17), 18)

RTU-6

RTU-8

6 76.3 61.5 1725

15504 76.340,561 34,212 61.5 5047 0.75 1725 761

0.8

153

51

RTU-7 3 75.223,466 61.3 17250.8

916

745

51

25

2400

1100 75

200

62,376

28,769

52,991

0.8

0.8

2

0.5

5049

3025

300

11.2

12.0

12.5

12.8

1), 3), 4), 10), 11), 12), 13), 16), 17), 18)

1), 3), 4), 10), 11), 12), 13), 16), 17), 18)

1), 3), 4), 10), 11), 12), 13), 16), 17), 18)

60.0

60.0

60.0

45.0

15.0

15.0

7.5

ACCESSORIES: 1) ECONOMIZER WITH DUAL SENSIBLE CONTROL. 2) RETURN AIR SMOKE DETECTOR. 3) SUPPLY AIR SMOKE DETECTOR. 4) CO2 SENSOR WALL MOUNTED. 5) HUMIDITROL. 6) VIBRATION ISOLATION CURB. 7) SEISMIC RATED CURB. 8) POWER EXHAUST. 9) HUMIDISTAT. 10) PROGRAMMABLE THERMOSTAT. 11) FACTORY INSTALLED DISCONNECT. 12) STANDARD LENNOX CURB. 13) VERTICAL VENT EXTENSION. 14) COMBUSTION AIR EXTENSION. 15) NETWORK CONTROL PANEL AND SENSORS. 16) GFCI OUTLET, FIELD WIRED.17) LP KIT-FIELD INSTALLED. 18) COIL GUARDS-FIELD INSTALLED.

LENNOX LCH036H4E

LENNOX LCH048H4E

LENNOX LCH072H4B

LENNOX LCH150S4B

LENNOX LCH180H4B

LENNOX LCH180H4B

LENNOX LCH300S4B

DOWN

DOWN

DOWN

DOWN

DOWN

DOWN

105

105

105

105

105

105

800025 79.22200 230,139 206,536 62.1 105 175152 5 1725 2625DOWN 204 1.0 10.560.0LENNOX LCH300S4B

0.3929 1140 661/6GREENHECK G-097-B 12" 120/1/60

0.3929 1140 661/6GREENHECK G-097-B 12" 120/1/60

0.3929 1140 661/6GREENHECK G-097-B 12" 120/1/60

0.3929 1140 661/6GREENHECK G-097-B 12" 120/1/60

0.3929 1140 661/6GREENHECK G-097-B 12" 120/1/60

204

204

204

153

51

51

25

204 208/3/60

208/3/60

208/3/60

208/3/60

208/3/60

208/3/60

208/3/60

Page 2: M001 MECHANICAL SCHEDULES & GENcochisetech.net/wp-content/uploads/2016/11/90-Mechanical.pdfb. test and balance (tab) (mechanical contractor contracted) • upon arrival to the site,

MECHANIC

AL

FLO

OR

PLA

N

DO NOT SCALE DRAWING

M101

THIS

DR

AWIN

G IS C

LASSIFIE

D A

SP

AR

T O

F A

N U

NP

UB

LISHED

COLL

ECTIO

N O

F V

ISUAL

AR

T.

UND

ER

THE 1978

COP

YR

IGHT

ACT, IT IS A

N E

XCLU

SIV

EOR

IGIN

AL

WOR

K O

F A

UTHOR

SHIP

.NONE O

F T

HE P

ICTOR

IAL,

GR

AP

HIC

OR

TECHNIC

AL

CHAR

TS O

R D

RAWIN

GS

DEP

ICTED

ON T

HIS

SHEET M

AY

BE R

EP

ROD

UCED

OR

TR

ANSM

ITTED

IN A

NY F

OR

M O

RB

Y A

NY M

EANS W

ITHOUT T

HE

EXP

RESS P

RIO

R W

RITTEN

PER

MIS

SIO

N O

F T

HE A

RCHITECT.

THIS

PLA

N IS P

ROD

UCED

ONLY

FOR

THIS

PR

OJE

CT O

N T

HIS

SITE

AND

MAY N

OT B

E U

SED

AT

OTHER

LOCATIO

NS.

SHEET T

ITLE

:

OR

IGIN

AL

ISSUE: P

relim

inar

y

SEAL:

REV

DATE

DESCR

IPTIO

N

SHEET NUMBER:

PR

OJE

CT: A

C489

PR

OJE

CT:

BAP

TIS

T C

HUR

CH

SIE

RR

A V

ISTA, AZ

VILLA

GE M

EAD

OWS

DESCR

IPTIO

N

DESCR

IPTIO

N

DESCR

IPTIO

N

DESCR

IPTIO

N

DESCR

IPTIO

N

MM

-DD

-YY

MM

-DD

-YY

MM

-DD

-YY

MM

-DD

-YY

MM

-DD

-YY

MM

-DD

-YY

41 2 3 5 6

DESCR

IPTIO

N

OR

IGIN

AL

ISSUE

Pr

elim

inar

y0

DANIE

L COOK

AR

CHITECT│

290

9 W

ASHIN

GTO

N B

LVD

- O

GD

EN, UT

8440

1│P

H: 80

0-5

52-

7137│

www.B

GWSER

VIC

ES.c

om

SIE

RR

A V

ISTA, AR

IZONA 8

5635

140

7 S E

L CAM

INO R

EAL

PRELIMINARY D

RAWING!

NOT

FOR C

ONSTR

UCTION!

1

2

MANUAL BALANCING DAMPER (TYPICAL).

CONTROL PANEL LOCATION.

KEYED NOTES

NOTE:

1) SPACE ABOVE CEILING IS TO BE USED AS A RETURN AIR PLENUM. ALL MATERIALS TO BE PLENUMRATED.

2) ALL TERMINAL SUPPLY DUCT BRANCHES TO BE EQUIPPED WITH MANUAL BALANCING DAMPER.

3) FLEX DUCT (MAXIMUM 60" LONG) TYPICAL ON EACH DIFFUSER EXCEPT IN EXPOSED APPLICATIONS.

4) PROVIDE TURNING VANES IN ALL RECTANGULAR ELBOWS.�

NOTE:

MECHANICAL CONTRACTOR TO REVIEW ALL DRAWINGS FOR CONFLICTS WITH STRUCTURE AND OTHERTRADES. MECHANICAL CONTRACTOR TO RESOLVE ALL CONFLICTS WITH ENGINEER PRIOR TO ORDERING,FABRICATING OR INSTALLING DUCTWORK.

R1

R2

R5

R4

DW

d d

B.9

14

UP TO EF-3

UP TO EF-4

UP TO EF-2

UP TO EF-5

UP TO EF-6

UP TO EF-7

UP TO EF-8

UP TO EF-9

UP TO EF-1

UP TO RTU-5

UP TO RTU-3

UP TO RTU-2

UP TO RTU-4

UP TO RTU-1

UP TORTU-6

UP TO RTU-7

UP TO RTU-8

6"Ø 6"Ø

6"Ø

6"Ø

6"Ø

6"Ø

6"Ø

6"Ø6"Ø

8"Ø

10"Ø

10"Ø

10"Ø14"Ø10"Ø10"Ø

10"Ø

10"Ø10"Ø

14"Ø

8"Ø

40x32

40x32

26"Ø26"Ø

10"Ø

10"Ø

14"Ø

14"Ø

14"Ø

14"Ø

14"Ø

14"Ø

24"Ø

20"Ø

18"Ø

22"Ø

14"Ø

14"Ø 14"Ø

14"Ø

14"Ø

16"Ø

20"Ø

22"Ø24"Ø

14"Ø

14"Ø

14"Ø

28"Ø

30"Ø

10"Ø

40x32

40x32

14"Ø

14"Ø

14"Ø

18"Ø

20"Ø

14"Ø

22"Ø14"Ø

10"Ø

24"Ø

26"Ø

14"Ø

26"Ø

14"Ø

24"Ø

28"Ø

30"Ø

14"Ø

14"Ø

14"Ø

14"Ø14"Ø

14"Ø

22"Ø20"Ø

16"Ø

1

1

8"Ø

16"Ø10"Ø10"Ø10"Ø 14"Ø

10"Ø8"Ø

1

20x14

10"Ø

18"Ø

18x18 8"Ø

10"Ø10"Ø

14"Ø12"Ø

6"Ø

6"Ø6"Ø

6"Ø10"Ø

10"Ø

1

20x18

6"Ø

12"Ø 10"Ø

10"Ø

14"Ø

8"Ø12"Ø

12"Ø

16"Ø

18"Ø

14"Ø

12"Ø

10"Ø

10"Ø

6"Ø

1

48x20

30x26

26"Ø 20"Ø

10"Ø

10"Ø10"Ø

10"Ø14"Ø

12"Ø

10"Ø

10"Ø

8"Ø

16"Ø

14"Ø

10"Ø

10"Ø

10"Ø

24"Ø

10"Ø18"Ø

18"Ø

16"Ø

16"Ø

12"Ø

10"Ø

6"Ø

8"Ø

10"Ø

6"Ø

10"Ø

10"Ø

18"Ø

8"Ø

16"Ø

12"Ø

10"Ø

8"Ø

12"Ø 12"ØSLOPE DOWN

DROP

28x24

28x24

10"Ø

8"Ø

16"Ø

14"Ø

12"Ø

10"Ø

6"Ø

8"Ø

8"Ø

8"Ø

8"Ø

8"Ø

24"Ø

14"Ø

10"Ø

12"Ø

8"Ø

8"Ø8"Ø

8"Ø

20"Ø 16"Ø

10"Ø

14"Ø

6"Ø

8"Ø

8"Ø

8"Ø

8"Ø

8"Ø

18"Ø

16"Ø

10"Ø

10"Ø

10"Ø

10"Ø

10"Ø

6"Ø

10"Ø

6"Ø

6"Ø

10"Ø

1

1

FSD

FSD FSD

FSD

FSD

T

T

T

TC

TC

T

T C

TC

26x16

40x24

40x24

24x24

24x24

26x20

18x12

DROP

8"Ø

22"Ø

22"Ø

12"Ø

8"Ø

10"Ø

14"Ø14"Ø

AC1AC

2

21'-0" A.F.F.

21'-0" A.F.F.21'-0" A.F.F.

21'-0" A.F.F.

15'-0" A.F.F.15'-0" A.F.F.15'-0" A.F.F.

15'-0" A.F.F.

15'-0" A.F.F.

9'-6" A.F.F.9'-6" A.F.F.

12'-0" A.F.F.

20'-0" A.F.F.

20'-0" A.F.F.

20'-10" A.F.F. 20'-10" A.F.F.

12'-0" A.F.F.

CHAPEL101

FOYER102

CATERING103

USHER104 VESTIBULE

106

PLAY ROOM107

CLASSROOM A108

R.R.109

CLASSROOM B110

R.R.111

CLASSROOM C112

CRAWLERS113

CHECK-IN114 R.R.

115

INFANTS116

OFFICE117

MEN'S118

JAN.119

CORRIDOR120

stg.121

R.R.122 STG.

123

TACTILE124

MOTOR SKILLS125

SENSORY126

MINISTRY127

COUNS.128

FAM. R.R.129

BACKSTAGE/STORAGE130

MASTER CONTROL131

BACK STAGE132

RACK ROOM133

GREEN ROOM134

R.R.135

MAN CAVE136

R.R.137

COUNS.138

BRIDE'S ROOM139

CORRIDOR140

JAN.141

WOMEN'S142

SPRK.143

STORAGE144

HOSPITALITY145

SANCTUARY147

PLATFORM148

CAFE150

san.149

MDP143.1

CHANGING146.1

26"Ø

u u

1

18

187

A A

B B

r r

j

15

15 17

n n

C C

165

5

2

3 9 10 1211

f

l

o o

q

t

6

e

h

4 8 13

p

s

m

k

G

R3

R3

6.1 6.9

h.9

26"Ø

14"Ø

500D-5 500

D-5

500D-5

500D-5

500D-5

500D-5

500D-5

500D-5

500D-5

500D-5

530D-7

530D-7

530D-7

530D-7

530D-7

530D-7

530D-7

530D-7530

D-7

530D-7

150E-2

150E-2

370D-3

225D-3

160D-2

255D-3

70D-1

90D-1

50D-1

305D-3

300D-3

380D-4

400D-4

70D-1

350D-3

350D-3

75D-1

380D-3

65D-1

220D-3

300D-3

375D-3

300D-3

350D-3

210D-2

190D-2

210D-2

190D-2

230D-235

D-1

165D-2

170D-2

200D-2

165D-2

165D-2

35D-1

185D-2

185D-2

200D-2

200D-2

100D-2

75D-1

320D-3

55D-1

75E-1

75E-1

75E-1

75E-1

75E-1

75E-1

75E-1

75E-1

75E-1

300E-3

300E-3

260E-3

265E-3

40D-1

180D-2

135D-2

285D-3

200D-2

200D-2

100D-1

250D-8

250D-8

R-5

290D-3

240D-3

150D-2

180D-2

200D-2

250D-3

295D-3

165D-2

165D-2

100D-2

400D-3

250D-3

250D-3

100D-2

R-3

R-3

270D-6

270D-6

230D-6

230D-6

R-4 R-4

285D-3

285D-3

285D-3

285D-3

285D-3

285D-3 285

D-3

R-6

285D-3

325D-3325

D-3325D-3

500D-5

500D-5

500D-5

500D-5 500

D-5

500D-5

500D-5

500D-5

500D-5500

D-5

500D-5

500D-5

500D-5

500D-5

500D-5500

D-5

500D-5

500D-5 500

D-5

500D-5

3RD PLACE105

BAPTISTRY146

1 MECHANICAL FLOOR PLANSCALE: 1/8" = 1'-0"

Page 3: M001 MECHANICAL SCHEDULES & GENcochisetech.net/wp-content/uploads/2016/11/90-Mechanical.pdfb. test and balance (tab) (mechanical contractor contracted) • upon arrival to the site,

MECHANIC

AL

ROOF P

LAN

DO NOT SCALE DRAWING

M102

THIS

DR

AWIN

G IS C

LASSIFIE

D A

SP

AR

T O

F A

N U

NP

UB

LISHED

COLL

ECTIO

N O

F V

ISUAL

AR

T.

UND

ER

THE 1978

COP

YR

IGHT

ACT, IT IS A

N E

XCLU

SIV

EOR

IGIN

AL

WOR

K O

F A

UTHOR

SHIP

.NONE O

F T

HE P

ICTOR

IAL,

GR

AP

HIC

OR

TECHNIC

AL

CHAR

TS O

R D

RAWIN

GS

DEP

ICTED

ON T

HIS

SHEET M

AY

BE R

EP

ROD

UCED

OR

TR

ANSM

ITTED

IN A

NY F

OR

M O

RB

Y A

NY M

EANS W

ITHOUT T

HE

EXP

RESS P

RIO

R W

RITTEN

PER

MIS

SIO

N O

F T

HE A

RCHITECT.

THIS

PLA

N IS P

ROD

UCED

ONLY

FOR

THIS

PR

OJE

CT O

N T

HIS

SITE

AND

MAY N

OT B

E U

SED

AT

OTHER

LOCATIO

NS.

SHEET T

ITLE

:

OR

IGIN

AL

ISSUE: P

relim

inar

y

SEAL:

REV

DATE

DESCR

IPTIO

N

SHEET NUMBER:

PR

OJE

CT: A

C489

PR

OJE

CT:

BAP

TIS

T C

HUR

CH

SIE

RR

A V

ISTA, AZ

VILLA

GE M

EAD

OWS

DESCR

IPTIO

N

DESCR

IPTIO

N

DESCR

IPTIO

N

DESCR

IPTIO

N

DESCR

IPTIO

N

MM

-DD

-YY

MM

-DD

-YY

MM

-DD

-YY

MM

-DD

-YY

MM

-DD

-YY

MM

-DD

-YY

41 2 3 5 6

DESCR

IPTIO

N

OR

IGIN

AL

ISSUE

Pr

elim

inar

y0

DANIE

L COOK

AR

CHITECT│

290

9 W

ASHIN

GTO

N B

LVD

- O

GD

EN, UT

8440

1│P

H: 80

0-5

52-

7137│

www.B

GWSER

VIC

ES.c

om

SIE

RR

A V

ISTA, AR

IZONA 8

5635

140

7 S E

L CAM

INO R

EAL

PRELIMINARY D

RAWING!

NOT

FOR C

ONSTR

UCTION!

1 PIPE CONDENSATE FULL SIZE TO NEAREST ROOF DRAIN.

KEYED NOTES

NOTE:

1) SPACE ABOVE CEILING IS TO BE USED AS A RETURN AIR PLENUM. ALL MATERIALS TO BE PLENUMRATED.

2) ALL TERMINAL SUPPLY DUCT BRANCHES TO BE EQUIPPED WITH MANUAL BALANCING DAMPER.

3) FLEX DUCT (MAXIMUM 60" LONG) TYPICAL ON EACH DIFFUSER EXCEPT IN EXPOSED APPLICATIONS.

4) PROVIDE TURNING VANES IN ALL RECTANGULAR ELBOWS.�

NOTE:

MECHANICAL CONTRACTOR TO REVIEW ALL DRAWINGS FOR CONFLICTS WITH STRUCTURE AND OTHERTRADES. MECHANICAL CONTRACTOR TO RESOLVE ALL CONFLICTS WITH ENGINEER PRIOR TO ORDERING,FABRICATING OR INSTALLING DUCTWORK.

R1

R2

R5

R4

d d

B.9

14

AC1

AC2

RTU5RTU

3

RTU4

RTU1

RTU6

RTU8

RTU7

RTU2

u u

1

18

187

A A

B B

r r

j

15

15 17

n n

C C

165

5

2

3 9 10 1211

f

l

o o

q

t

6

e

h

4 8 13

p

s

m

k

G

R3

R3

6.1 6.9

h.9

EF4

EF5

EF3

EF2

EF1

EF6

EF9

EF7

EF8

1 MECHANICAL ROOF PLANSCALE: 1/8" = 1'-0"

Page 4: M001 MECHANICAL SCHEDULES & GENcochisetech.net/wp-content/uploads/2016/11/90-Mechanical.pdfb. test and balance (tab) (mechanical contractor contracted) • upon arrival to the site,

MECHANIC

AL

DETAILS

DO NOT SCALE DRAWING

M501

THIS

DR

AWIN

G IS C

LASSIFIE

D A

SP

AR

T O

F A

N U

NP

UB

LISHED

COLL

ECTIO

N O

F V

ISUAL

AR

T.

UND

ER

THE 1978

COP

YR

IGHT

ACT, IT IS A

N E

XCLU

SIV

EOR

IGIN

AL

WOR

K O

F A

UTHOR

SHIP

.NONE O

F T

HE P

ICTOR

IAL,

GR

AP

HIC

OR

TECHNIC

AL

CHAR

TS O

R D

RAWIN

GS

DEP

ICTED

ON T

HIS

SHEET M

AY

BE R

EP

ROD

UCED

OR

TR

ANSM

ITTED

IN A

NY F

OR

M O

RB

Y A

NY M

EANS W

ITHOUT T

HE

EXP

RESS P

RIO

R W

RITTEN

PER

MIS

SIO

N O

F T

HE A

RCHITECT.

THIS

PLA

N IS P

ROD

UCED

ONLY

FOR

THIS

PR

OJE

CT O

N T

HIS

SITE

AND

MAY N

OT B

E U

SED

AT

OTHER

LOCATIO

NS.

SHEET T

ITLE

:

OR

IGIN

AL

ISSUE: P

relim

inar

y

SEAL:

REV

DATE

DESCR

IPTIO

N

SHEET NUMBER:

PR

OJE

CT: A

C489

PR

OJE

CT:

BAP

TIS

T C

HUR

CH

SIE

RR

A V

ISTA, AZ

VILLA

GE M

EAD

OWS

DESCR

IPTIO

N

DESCR

IPTIO

N

DESCR

IPTIO

N

DESCR

IPTIO

N

DESCR

IPTIO

N

MM

-DD

-YY

MM

-DD

-YY

MM

-DD

-YY

MM

-DD

-YY

MM

-DD

-YY

MM

-DD

-YY

41 2 3 5 6

DESCR

IPTIO

N

OR

IGIN

AL

ISSUE

Pr

elim

inar

y0

DANIE

L COOK

AR

CHITECT│

290

9 W

ASHIN

GTO

N B

LVD

- O

GD

EN, UT

8440

1│P

H: 80

0-5

52-

7137│

www.B

GWSER

VIC

ES.c

om

SIE

RR

A V

ISTA, AR

IZONA 8

5635

140

7 S E

L CAM

INO R

EAL

PRELIMINARY D

RAWING!

NOT

FOR C

ONSTR

UCTION!

COORDINATE DIFFUSER TYPE FORLAY-IN OR GYPSUM BOARD CEILING.

SUPPORT FLEX DUCT FROMSTRUCTURE ABOVE. ONE 1" X 22 GA

STRAP

FLEX DUCT SEE DRAWINGS FOR SIZE

MAKE BEND RADIUS 1-1/2 xDUCT RADIUS

NOTE:RETURN SIMILAR BUT WITHOUT DUCT

TIGHTENING BAND

CEILING MATERIAL

5 FT. MAXIMUM.MAX. SAG 1/2" PER FOOT OF SUPPORTSPACING.

SUPPORT FLEX DUCT FROMSTRUCTURE ABOVE. ONE 1" X 22 GASTRAP

METAL FASTENERS :OMARK INSUL-PINS, DURA DYNE FASTENERS OR GRIP NAILS.GRIP NAILS SHALL BE INSTALLED BY "GRIP NAIL AIR HAMMER"OR BY AUTOMATIC FASTENER EQUIP.

LINER TO BE ADHERED TO DUCT WITH 90%MIN. AREA COVERAGE OF ADHESIVE

ALL ENDS OF LINER TO BE COATED WITH ADHESIVE. ENDS OF LINERSHALL BE BUTTED FIRMLY TOGETHER AND TAPED OVER.

LAPPED & BUTTEDCORNERS

DUCT LINER (SEE SPEC. FORTHICKNESS)

TOP AND BOTTOM SECTION OF LINERSHALL OVERLAP THE SIDESDUCT LINER SEE SPEC FOR

THICKNESS

METAL FASTENERS 12" O.C. MAX. FORBELOW 2500 FPM VELOCITY

NOT MORE THAN 2" FROMEDGE OF LINER

THE VELOCITY RATED SIDE OF LINER MUSTFACE THE AIR FLOW

GALV. SHT.METAL DUCT

HHDRIVE

SLIP

AT JOINTS

2424

2224

2624

PLAINS SLIP

RECOMMENDEDGA.

2624

HEMMEDS SLIP

24

24242422

REIN-FORCEDBAR SLIP

MIN.H.

11

11

2624

2224

NONE REQUIREDNONE REQUIRED

1" X 1" X 1/8" @ 60 IN1" X 1" X 1/8" @ 60 IN

IN.

TRANSVERSE REINFORCING (1)

13 - 18

31 - 4219 - 30

UP THRU 12

ALTER'NTBAR SLIP

SHEETMETAL GA.(ALL FOUR

SIDES)

DIMENSION OF LONGESTSIDE. INCHES

MINIMUM REINFORCING ANGLESIZE AND MAXIMUM LONGITUDINALSPACING BETWEEN TRANSVERSE

JOINT & /OR INTERMEDIATEREINFORCING

(1) TRANSVERSE REINFORCING SIZE IS DETERMINED BYDIMENSION OF SIDE TO WHICH ANGLE IS APPLIED.

RECOMMENDEDGA.

RECOMMENDEDGA.

RECOMMENDEDGA.

W1

W2

1. ALL VANED ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BYSMACNA.

2. WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE VANE TYPEREGARDLESS OF 'W' DIMENSION. ALL SINGLE VANES SHALL HAVE A 2 INCHRADIUS, 1 INCH MAXIMUM.

3. SPACE BETWEEN VANES AND A 3/4 INCH TRAILING EDGE.4. WHEN W1 EQUALS W2 AND W1 IS GREATER THAN 20 INCHES, VANE SHALL BE

DOUBLE VANE TYPE.

TURNING VANES

12" MIN

ROOF MOUNTED EXHAUST FAN WITHBIRD SCREEN

ANCHOR CURB TOHOOD

CANT STRIP

BUILT-UP ROOFING

INSULATIONEXHAUST DUCT SEEDRAWINGS FOR SIZE

GRAVITY BACKDRAFT DAMPER

FRAMING ALL AROUND

ROOF CURB

FLASH AND COUNTERFLASH

1/4" SPONGE RUBBER GASKET ALLAROUND

SUPPORT ANGLE FOR DAMPERATTACHED TO CURB

UNION

TRUSS JOIST

DRAIN CONNECTIONFLUE OUTLET

ECONOMIZER AS SPECIFIED

GAS PIPING. RUN 6" MIN. ABOVE ROOF

SHUT OFF COCK

DIRT LEG

ROOF INSULATION

SEE PLANS FOR SIZE

RETURN AIRLAY IN CEILING

SUPPLY AIR

MAKE TRANSITIONS AS SHOWN ON DRAWINGS TOCONNECT TO DUCTWORK

PROVIDE FLEX CONNECTIONS AT UNIT

ROOF CURB

ELECTRICDISCONNECT

ROOFTOP UNIT

PROVIDE 3" OF ACOUSTICAL INSULATION BELOW THEENTIRE FAN SECTION OF UNIT. SEAL W/ RUBBER CAULKING

TO PREVENT SOUND TRANSFER THROUGH DECK.

TRUSS JOIST

FLUE OUTLET

ECONOMIZER AS SPECIFIED

GAS PIPING, RUN 6" MIN. ABOVE ROOF

SHUT OFF COCK

DIRT LEGROOF INSULATION

SEE PLANS FOR SIZE

LAY IN CEILINGRETURN AIR

SUPPLY AIR

MAKE TRANSITIONS AS SHOWN ON DRAWINGS TOCONNECT TO DUCTWORK PROVIDE FLEX CONNECTION

AT UNIT

ROOF CURB

ROOFTOP UNIT

ELECTRIC DISCONNECT

DRAIN CONNECTIONPROVIDE 3" OF ACOUSTICAL INSULATION BELOW THE

ENTIRE FAN SECTION OF UNIT. SEAL W/ RUBBER CAULKINGTO PREVENT SOUND TRANSFER THROUGH DECK.

UNION

DUCT

1-1/2" POCKET SLIP

NEOPRENE COATED FABRICBOLT ON 4" CENTER

1" FLANGE & HEM

NOTES:1. A VERTICAL DAMPER IS SHOWN. HORIZONTAL DAMPER INSTALLATION IS SIMILAR. FOLLOW DAMPER MANUFACTURERSINSTRUCTIONS, INCLUDING FASTENER OPTIONS AND GAGES FOR SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUSTBE INSTALLED IN THE PARTITION OR FLOOR, NOT OUTSIDE THE PENETRATION.

2. GALVANIZED SLEEVE: GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO DAMPER FRAME AND TO PERIMETERANGLES.

3. PERIMETER ANGLES: GALVANIZED STEEL, NOT LESS THAN 1-1/2"x1-1/2", 14 GAGE, TO PROVIDE 1" MINIMUM OVERLAP OFOPENING ON ALL 4 SIDES.

4. BREAKAWAY DUCT CONNECTION: CONTRACTORS OPTION OF TYPES SHOWN IN SMACNA LPDS, FIG. 2-13. SEAL JOINTS.

5. ACCESS PANELS: SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE LINK OR LINKS.

6. PROVIDE A CLEARANCE FOR DAMPER SLEEVE WITHIN WALL OPENING OF 1/8" PER FOOT OF WIDTH (OR HEIGHT), OR PERMANUFACTURER'S INSTALLATION INSTRUCTIONS. THE SLEEVE MAY REST ON BOTTOM OF OPENING, AND NEED NOT BECENTERED.

7. ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS AND MECANICAL ROOM FLOORS,SHALL BE PROVIDED WITH A 3" HIGH CONCRETE CURB AROUND OPENING FOR DUCT.

PERIMETER ANGLE, NOTE 3 (NOT FASTENED TOPARTITION)

SLEEVE, NOTE 2

DUCT CONNECTION NOTE 4

DAMPER COLLAR EXTENSIONINTEGRAL PART OF SLEEVE

SLEEVE, NOTE 2NOTE 6

FIRE BARRIER PARTITION ORCHASE

TYPICAL DUCT INSULATION

AP NOTE 5

FAN CONTACTOR

24V COIL

RED

BLACK

IONIZATIONUNIT

IN UNIT SUPPLYPLENUM

1 DIFFUSER CONNECTIONSCALE: N.T.S. 2 DUCT LINER

SCALE: N.T.S.

3 DUCT CONSTRUCTION DETAILSCALE: N.T.S. 4 SQUARE VANED ELBOWS

SCALE: N.T.S.

5 ROOF MOUNT EXHAUST FANSCALE: N.T.S.

6 ROOFTOP UNIT (GAS)SCALE: N.T.S.

7 ROOFTOP UNIT (GAS-SIDE DISCHARGE)SCALE: N.T.S. 8 FLEX CONNECTION

SCALE: N.T.S.

9 FIRE DAMPERSCALE: N.T.S. 10 ION GENERATOR WIRING DIAGRAM

SCALE: N.T.S.