Installation Instructions for SEL-TPR

2
Installation Instructions for SEL-TPR 3-Phase, Remote Large Target, 600 A Junction Shield 25-0217.A Page 1 of 2 SCHWEITZER ENGINEERING LABORATORIES, INC. 2350 NE Hopkins Court • Pullman, WA 99163-5603 U.S.A. Phone: +1.509.332.1890 • Fax: +1.509.332.7990 selinc.com • [email protected] Install the Display Install the Internal Adapter Ring (if Required) and the Phase Sensor(s) Elastimold 15, 25, and 35 kV PCE elbows with molded test points require the internal adapter rings. Complete Steps A–H. Hubbell, Chardon, RTE, Cooper, or GE-Chardon elbows with molded test points do not require the adapter ring. Complete Steps E–H only. = Mount the stainless-steel bracket to position the “L” display for optimum viewing. Use the integral threaded stud and hex nut to mount the display to the bracket. Hand tighten the hex nut. Do not overtighten. Note: Optional Display Panel Mount Kits are sold separately. Consult the factory for ordering information. Internal adapter ring Fold into a “U” shape Align the ridge with the groove Release the “U” shape and press the ridge into the groove Ø2.0 (Ø50) 7.7 (195) 3.2 (83) 3.7 (95) 2.5 (64) 1.7 (43) APPROX< 2.5 (65) Before installation of fault indicators and sensors, read and understand all instructions in their entirety. For assis- tance, contact Customer Service at (509) 332-1890 or by email at [email protected]. CAUTION Install fault indicators and sensors in accordance with normal safe operating practices. These instructions are not intended to replace or supersede exist- ing safety or operating requirements. Only trained qualified personnel should install or operate fault indicators and sensors. Hex Nut “L” Display Stainless-Steel Bracket Ridge A B Ridge Ridge Groove C D

Transcript of Installation Instructions for SEL-TPR

Installation Instructions for SEL-TPR3-Phase, Remote Large Target, 600 A Junction Shield

25-0217.A

Page 1 of 2

SCHWEITZER ENGINEERING LABORATORIES, INC.2350 NE Hopkins Court • Pullman, WA 99163-5603 U.S.A.Phone: +1.509.332.1890 • Fax: +1.509.332.7990selinc.com • [email protected]

Install the Display

Install the Internal Adapter Ring (if Required) and the Phase Sensor(s)➤ Elastimold 15, 25, and 35 kV PCE elbows with molded test points require the internal adapter rings. Complete Steps A–H.

➤ Hubbell, Chardon, RTE, Cooper, or GE-Chardon elbows with molded test points do not require the adapter ring. Complete Steps E–H only.

=

➤ Mount the stainless-steel bracket to position the “L” display for optimum viewing.

➤ Use the integral threaded stud and hex nut to mount the display to the bracket. Hand tighten the hex nut. Do not overtighten.

Note: Optional Display Panel Mount Kits are sold separately. Consult the factory for ordering information.

Internal adapter ring Fold into a “U” shape Align the ridge with the groove Release the “U” shape and press the ridge into the groove

Ø2.0 (Ø50)

7.7(195)

3.2(83)

3.7(95)

∅2.5(∅64)

1.7 (43)

APPROX< 2.5(65)

Before installation of fault indicators and sensors, read and understand all instructions in their entirety. For assis-tance, contact Customer Service at (509) 332-1890 or by email at [email protected].

CAUTIONInstall fault indicators and sensors in accordance with normal safe operating practices. These instructions are not intended to replace or supersede exist-ing safety or operating requirements. Only trained qualified personnel should install or operate fault indicators and sensors.

Hex Nut

“L” Display

Stainless-Steel Bracket

Ridge

A B

Ridge

RidgeGroove

C D

25-0217.A

Page 2 of 2

SCHWEITZER ENGINEERING LABORATORIES, INC.2350 NE Hopkins Court • Pullman, WA 99163-5603 U.S.A.Phone: +1.509.332.1890 • Fax: +1.509.332.7990selinc.com • [email protected]

Installation Instructions for SEL-TPR 3-Phase, Remote Large Target, 600 A Junction Shield

Remove the test point cap. Clean and dry the test point. Apply a sili-cone dielectric grease to the inside

of the sensor boot.

Position one junction arm around the elbow. Use a sliding

motion to move the junction arm behind the cable.

When both junction arms are around the cable, slide the phase sensor up to the test point of the

T-Body.

Use a push/twist motion to seat the phase sensor on the test

point.

Magnetic Cable Guides hold cables and leads neatly within the enclosure.

Catalog Number: MCG

Test Point Cap

E F G

Test Point

H