Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE...
Embed Size (px)
Transcript of Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE...
-
Copyright SEL 2008
Synchrophasor-Based Monitoring, Analysis, and Control
Roy Moxley Schweitzer Engineering Laboratories, Inc.
-
The Power System Is Changing
Photo Courtesy of Shawn Jacobs, OG&E
-
02 03 8/03 05 06 06 07 07+
Sync
hrop
haso
rs in
a Mete
r
Sync
hrop
haso
rs on
the W
eb
IEEE
Pro
tocol
in a R
elay
Sync
hrop
haso
rs in
a Rela
y
Retro
fit Sy
nchr
opha
sors
In a R
elay
Utilit
y Gra
de P
DC
SCAD
A Sy
nchr
opha
sors
Real-
Time C
ontro
l in
a Rela
y (Me
xico)
SEL Synchrophasor Vision
0
5
10
15
20
25
AG10
AB10
BCG1
0AB
C10
AG50
AB50
BCG5
0AB
C50
AG80
AB80
BCG8
0AB
C80
AG90
AB90
BCG9
0AB
C90
Fault Type and Distance
Tim
e (m
s)
Local side trip times WITHOUT synchrophasors Local side trip times WITH synchrophasors
Real-
Time V
ecto
r
Proc
esso
r
-
Synchrophasors Are StandardSEL-421
IEEE C37.118
SEL-451SEL-487ESEL-787SEL-734 SEL Fast MessageSEL-311A, B, CSEL-311LSEL-351SEL-351SSEL-351A
-
Protection AND Synchrophasors
0
5
10
15
20
25
AG90
AB90
BCG9
0AB
C90
AG50
AB50
BCG5
0AB
C50
AG20
AB20
BCG2
0AB
C20
AG10
AB10
BCG1
0AB
C10
Fault Type and Distance
Tim
e (m
s)
Remote side trip times WITHOUT synchrophasors Remote side trip times WITH synchrophasors
0
5
10
15
20
25
AG10
AB10
BCG1
0AB
C10
AG50
AB50
BCG5
0AB
C50
AG80
AB80
BCG8
0AB
C80
AG90
AB90
BCG9
0AB
C90
Fault Type and Distance
Tim
e (m
s)
Local side trip times WITHOUT synchrophasors Local side trip times WITH synchrophasors
Synchrophasors do not hurt relay performance
-
Relaying Has No Impact on PMCU Function
No lostdata
4 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.90
1
2
3
Local bus side phase A voltage synchrophasorSynchrophasor data check
Time (s)
-
Relays Are Right for Synchrophasors
Phasor measurement and control unit(PMCU) PMU
Minimal incremental cost
Reduced current and voltage connections
High-accuracy measurements
High reliability and availability
Future control applications
Relays are everywhere
-
SEL Synchrophasor Equipped Devices Worldwide !
North AmericaNorth America>20,000 units>20,000 units
South AmericaSouth America>2,000 units>2,000 units
Europe/AsiaEurope/Asia>3,000 units>3,000 units
Africa/Middle EastAfrica/Middle East>1,000 units>1,000 units
Asia Asia PacificPacific
>5,000 units>5,000 units
-
Application Options Not One Size Fits All
SEL-5078 Visualization
SEL-5077, SEL-5078 Archiving
System Operator, Reliability Council
SEL-3306 Hardware PDC SEL-5077 Software PDC
SEL-3378 Vector Processor
PMUs
-
Protection and Control Time Frame
~1.0 Second ~30 Seconds
Relay Action Human ActionControl Action
-
METER PM 13:22
-
Monitor a Gen Drop Test (New Zealand)
-
49.1
49.3
49.5
49.7
49.9
50.1
50.3
Timestamp 5/3/2007 3:10:18.6805/3/2007 3:11:06.6805/3/2007 3:11:54.6805/3/2007 3:12:42.6805/3/2007 3:13:30.6805/3/2007 3:14:18.6805/3/2007 3:15:06.680
Whakamaru_Frequency Huntly_Frequency
Test Shows System Remains Stable When 400 MW Dropped
Frequency recordings at both ends perfectly overlap and align in time.
-
Malin Round Mt. 500 kV Trips June 18, 2007
-
The MRI of Power Systems
NERC press release on Florida outage
Feb. 26, 2008:
Synchrophasors are Like the MRI of bulk power
systems
-
Synchrophasor-Based Control Now a Reality
-
Big Creek Controls Rector Static VAR Compensator
-
SCE Uses C37.118 From Relays and PMU
SCADAMaster
DNP3
IEEE C37.118
InformationProcessor
(Harris 5000/6000, IEC 60870-103, Modbus, SEL Fast Message, SES 92, Telegyr 8979, Conitel 2020, GETAC, Recon 1.1, CoDeSys, OPC, )
-
Impact of the Rector SVC: 6-14-07 (pre-SVC) vs. 8-30-07 (post-SVC)
Magunden Substation Voltage Comparison(Rector Substation Events 6-14-07 and 8-30-07)
220
222
224
226
228
230
232
234
236
238
240
-5.00 0.00 5.00 10.00 15.00 20.00 25.00
Time (seconds)
Mag
unde
n Vo
ltage
(kV)
Rector 8-30-2007 event (POST-SVC) Rector 6-14-2007 event (PRE-SVC)
The Rector SVC had the apparent effect of reducing the magnitude & duration of the fault-induced slow voltage
recovery
6-14-2007 (pre-SVC)
8-30-2007 (post-SVC)
NOTE: Voltages shown were measured ~70 miles south of Rector Substation (actual low voltage event was of greater
magnitude at Rector substation itself)
-
Effect of SVC Operation on Big Creek Before -
-
Effect of SVC Operation on Big Creek After -
-
Synchronous Vector ProcessingSystem
MeasurementFunction
CalculationOutput
Designation
Send Control to System(Application)
f(x)
-
Apply the
Collect synchronous phasor measurements
Collect logical inputs
Perform vector and scalar math
Make decisions
Produce outputs
Report data
-
Select Quantities From Each PMU
PMU1PMU2PMU3
Analogs| V1 |V1| I1 |I1FreqPSV42TE (time error)
Binary dataStatusTriggers
-
Integrate Wide-Area Protection and Control
Static Var Control
SEL-421
SEL-421
SEL-421
-
Apply Flexible Function Calculations
IEC 61131 engineMathTrigDifferentials
Preprogrammed blocksPowerAngle differenceModal analysisStation topology check
-
Combine Pre-Configured with Custom Functions
-
Provides Function Blocks
-
Map PMU Quantities to Phase Angle Difference Monitor
-
Improve Local Measurements
V A
Substation State and Topology Processor
Refined Is, Vs, Alarms,
and Topology52
52
52
52 52 52
-
Identify and Quarantine Bad Data
Measurements Measurements+
Calculate Median
Measurements+
Calculate Median+
Flag and Quarantine
Set Flag
-
Line TripStable
System Separation
Line Trip and Generation
LossUnstable
Real-Time Modal Analysis Monitor Predicts System Disturbances
-
Use Oscillation Frequency and Damping Ratio
For the complex Eigen value pair:
Oscillation frequency is:
Damping ratio is:
dj=
=2
f dosc
d
i
+
=2
2
-
Modal Analysis Shows System Response
-
Develop Custom ApplicationsVoltage Collapse Detection
Instability of Distributed Generation
Complex Power Swings
Others ?
-
Operating Point
Bifurcation Point
Utilities Are Operating Closer to the Edge
PU Nominal Load
Operating Point
Bifurcation Point
MarginMargin
1.61.51.31.00.0
0.5
1.0
-
Long Island: Monitor Angles Between Transmission Distribution Buses to Detect and Prevent Voltage Collapse
( )X)cos(2V)sin(1S 2
2s
max=
S = P + jQ
ZL = R + jX
rV
0VS
-
Calculate Voltage Stability Index (VSI)
SVP calculates maxima: P, Q, and S
Calculate margins:
QQQ maxmargin =
=
max
margin
max
margin
max
margin
SS
,QQ
,PP
minVSI
PPP maxginmar =
SSS maxmargin =
-
Improve Power Swing Detection
Actual Swing from 2003 Blackout
-
Wide-Area Measurement Is Better than Traditional Blinder Methods
Impedance Loci
Wide-Area Measurement
Replace and improve on local out of step
What if load or source impedance changes?
-
Delta/Delta-Dot Phase Plane Analysis
-20 0 20 40 60 80 100 120 140 160 180-200
-100
0
100
200
300
400
500
Angle Difference (deg)
Slip
(de
g/se
c)
-
Delta-Dot Delta-Doubledot Phase Plane
0 0.5 1 1.5 2 2.5 3 3.5 4-40
-30
-20
-10
0
10
20
30
40
Slip (Hz)
Acc
eler
atio
n (H
z/se
c)
-
Use Fast Operate Control Blocks for Closed-Loop Control
-
Synchrophasors Are StandardSEL-421
IEEE C37.118
SEL-451SEL-487ESEL-787SEL-734 SEL Fast MessageSEL-311A, B, CSEL-311LSEL-351SEL-351SSEL-351A
-
Synchrophasors Provide New and Improved Capabilities
Angle measurement
Disturbance analysis
Modal analysis
Out-of-step detection
Real-time control
What Else Can They Do For You?
-
Thank You!Thank You!
Synchrophasor-Based Monitoring, Analysis, and Control The Power System Is ChangingSEL Synchrophasor VisionSynchrophasors Are StandardProtection AND SynchrophasorsRelaying Has No Impact on PMCU FunctionRelays Are Right for SynchrophasorsSEL Synchrophasor Equipped Devices Worldwide !Application Options Not One Size Fits AllProtection and Control Time FrameMETER PM 13:22Monitor a Gen Drop Test (New Zealand)Test Shows System Remains Stable When 400 MW DroppedMalin Round Mt. 500 kV Trips June 18, 2007The MRI of Power SystemsSynchrophasor-Based Control Now a Reality Big Creek Controls Rector Static VAR CompensatorSCE Uses C37.118 From Relays and PMUImpact of the Rector SVC:6-14-07 (pre-SVC) vs. 8-30-07 (post-SVC)Effect of SVC Operation on Big CreekBefore - Effect of SVC Operation on Big Creek After -Synchronous Vector ProcessingApply theSelect Quantities From Each PMUIntegrate Wide-Area Protection and ControlApply Flexible Function CalculationsCombine Pre-Configured with Custom Functions Provides Function BlocksMap PMU Quantities to Phase Angle Difference MonitorSlide Number 30Improve Local MeasurementsIdentify and Quarantine Bad DataSlide Number 33Real-Time Modal Analysis MonitorPredicts System DisturbancesUse Oscillation Frequencyand Damping RatioModal AnalysisShows System ResponseDevelop Custom ApplicationsUtilities Are Operating Closer to the EdgeLong Island: Monitor Angles Between Transmission Distribution Buses to Detect and Prevent Voltage CollapseCalculate Voltage Stability Index (VSI)Improve Power Swing DetectionWide-Area Measurement Is Better than Traditional Blinder MethodsDelta/Delta-Dot Phase Plane AnalysisDelta-Dot Delta-Doubledot Phase PlaneUse Fast Operate Control Blocks for Closed-Loop ControlSynchrophasors Are StandardSynchrophasors Provide New and Improved CapabilitiesSlide Number 48