Data Aire, Inc. dap4 BACnet Protocol Integration Instructions Integration Instruction ver1... ·...
Transcript of Data Aire, Inc. dap4 BACnet Protocol Integration Instructions Integration Instruction ver1... ·...
Data Aire, Inc.
dap4
BACnet Protocol Integration Instructions
Data Aire, Inc. 230 West BlueRidge Ave,
Orange, CA 92865
Document number: 600‐000‐959 August 2011 Revision 1.0
Data Aire’s dap4 BACnet BMS
Document: 600-000-959 2
Table of Content
I. BACnet IP –Setup Procedures for dap4 Ethernet Card ........................................ 3 II. BACnet MS/TP – Setup Procedures for dap4 MS/TP Card .................................. 6
A. Startup Checklist for dap4 BACnet MS/TP card B. General Procedure for setting up BACnet MS/TP Card
III. Troubleshooting Flow Charts ................................................................................ 9 IV. BACnet Object Definition .................................................................................... 12
Data Aire’s dap4 BACnet BMS
Document: 600-000-959 3
I. BACnet IP - Setup Procedures for dap4 Ethernet Card
Note: When connecting to the Ethernet card, a crossover cable must be used
1. Configure BMS PORT 1 into BACnet protocol in Menu G: Network Config of the dap4 controller.
2. All Ethernet cards were set up for a DHCP server. You must give the card its factory IP address to access the card and then switch it to the Ethernet protocol.
3. To do a factory reboot of the card, shut of power to the dap4 controller. Next, press
and hold the button on the card. Now, power on the dap4 controller. Wait approximately 20 seconds until the status LED begins to blink red 3 times slowly. After the first Red blink, release the push button. After releasing the button, wait approximately 50 seconds and the card is now able to be communicated to.
4. The default settings for the card are as follows.
IP address – 172.16.0.1 Net Mask – 255.255.0.0 Device Inst - 77000
5. Once you have reset the Ethernet card, you must now configure your network card in your PC to 172.16.0.* * any value other then 1.
6. After your PC’s network card is configured, open internet explorer and enter the card’s
IP address (172.16.0.1.) 7. The following prompt will be displayed on your PC’s Screen (user name – admin,
password – fadmin)
Data Aire’s dap4 BACnet BMS
Document: 600-000-959 4
8. After entering the correct information to log on to the Ethernet card, you will be taken to
the following screen.
9. Click the configuration tab on the left. Then click on the BACnet tab across the top of the screen.
Data Aire’s dap4 BACnet BMS
Document: 600-000-959 5
10. This field is where you can change the settings for the card. The device instance of the card is changed beside the pCOWeb Device Inst text. Each card must have its own unique device instance.
11. The variable ranges can be set on the same page. Scroll to the bottom to change
these ranges.
12. After you have set up your card, click Submit.
13. After your changes have been accepted, you may now change you IP address (if applicable.) While still under the configuration tab, click network across the top of the screen.
14. Under Eth0, change the IP address and Netmask to your desired values. 15. Scroll to the bottom of the screen and click submit.
16. It will take approximately 5 minutes for the IP address change to take
Data Aire’s dap4 BACnet BMS
Document: 600-000-959 6
II. BACnet MS/TP - Setup Procedures for dap4 MS/TP Card
A. Startup Checklist for dap4 BACnet MS/TP card
1. Configure BMS PORT 1 into BACnet protocol in Menu G: Network Config of the dap4 controller.
2. MS/TP card is installed in dap4 control (if yes, skip to step 5. If no, contact the manufacturer of your unit to make sure that the card is configured before proceeding to next step.)
3. Disconnect the power supply from the dap4 and remove the serial card cover
4. insert card in dap4 control. Line up the white terminal block on the card with pins in the serial card slot. Press firmly until card is fully seated in dap4.
5. Fit the cover supplied with the BACnet MS/TP card.
6. Run 18 AWG twisted pair shielded cable from your network to the BACnet MS/TP card. Make sure (+) goes to the middle of the terminal block while (–) goes to the right connection
7. Power on the dap4 control.
8. Status lights match following sequence:
Starting sequence: on power-up, or after restarting BACnet MS/TP card, the Status LED switches in the following sequence:
- 2 seconds after restarting: quick flash red-green-red-green - 5 seconds after restarting: green on steady - Around 50 seconds after restarting, the starting sequence has been completed, the
Status LED flashes to indicate the quality of communications with the dap4. - Quick green-OFF-green: communication with the dap4 is OK (dap4 ON-LINE); - Slow red-OFF-red: communication has not been established with the dap4 (dap4
OFF-LINE) - Green-red-green: BACnet MS/TP card detects errors or a temporary lack of response
from the dap4.
Data Aire’s dap4 BACnet BMS
Document: 600-000-959 7
The RS485 LED (right) indicates the status of communication with the BACnet MS/TP network (RS485). Starting sequence: on power-up or after rebooting BACnet MS/TP card, the RS485 LED switches in the following sequence:
- After approximately 50 seconds after restarting BACnet MS/TP card: slow green–red–green–red: at the end, BACnet will be active. Status of communication with the BACnet MS/TP network: once the starting sequence has been completed, the RS485 LED flashes to indicate the quality of communication with the BACnet MS/TP network:
- Green with occasional red flashes if communication is OK.
B. General Procedure for setting up BACnet MS/TP Card
Before starting the following steps, a RS485-USB adapter and Carel software BACset must be present. BACset, free software compatible for BACnet is available for download at http://www.carel.com.au/carelksa/web/eng/home.jsp. Get the latest version by going into the pCOweb tab and select BACnet.
1. After BACset has been installed, click on the MS/TP protocol. If you are using a router, select the correct router configuration. Once these two fields have been selected, click ok.
2. The following screen will now be presented.
Data Aire’s dap4 BACnet BMS
Document: 600-000-959 8
3. All cards from factory come with a factory default device instance of 77000. This value must match the device instance of the card in order to be able to read/write to the card.
4. The MS/TP station address (MAC Address) is defaulted to 0. Set this field to your desired address. *If you have 5 cards, all 5 cards must have different station addresses (1, 2, 3, 4, 5)*
5. Max Master field must be changed to the highest station address on the network. If the highest station address is 10, Max Master must be set to 10.
6. Assuming the dap4 controller is not the true master of the communications system, Max Info Frames should be set =< the Max Info Frames of your BAS.
7. The following fields should be changed to the maximum number of variables being communicated by the dap4 controller. If you have 40 analog variables, Max pCO Analogs should be set to 40.
8. Once all fields have been set accordingly, click Write at the top of the BACset program. The Read/Write status bar will start at 0% and go to 100%. Once at 100%, the write has been completed.
9. After all of the prior steps have been completed, you may now change the device instance of the card. *Note* This value must be different from card to card. There can be no conflicting device instances on the same network.
10. To change the device instance, click enable on the enable/disable device instance write. Once this is selected, you will be able to enter a value in the device instance write box that was originally grayed out. *All cards must have a different device instance and cannot conflict with any other unit’s device instance in the system*
11. Change the device instance to desired value and then click Write.
12. Once the status bar is at 100%, the card now has the new device instance.
C. Troubleshooting Flow Charts BACnet IP and MS/TP
Data Aire’s dap4 BACnet BMS
Document: 600-000-959 9
In addition, if the following error occurs when starting BACset in the MS/TP protocol, continue to the following section.
1. Open BACset and click on the BACnet/IP protocol.
Values are being
communicated through
BACnet protocol and
considered reliable
All values are “0”
from startup and/or
deemed unreliable
Dap4 control set for BAUD
rate of 19200, station
address of 1 and protocol
BACnet
Adjust setting on dap4
control, contact Data Aire
service if required
Card has latest
firmware on it?
Go to http://ksa.carel.com ,
under Connectivity tab, click
pCOweb, then choose the
latest firmware
Has BMS supervisory system
autodiscovered all points correctly?
Contact Data Aire Service
to make sure BACnet
card is configured
correctly
Communication
works correctly
Have BMS contractor auto‐
discover all the units in question
Values appear
reliable, but “freeze”
or periodically go to
“0” and a power start
is required
Yes
No
Yes
Yes
Yes
No
No
Yes
No
Yes
No
Data Aire’s dap4 BACnet BMS
Document: 600-000-959 10
2. If you receive the following error when attempting to open BACnet/IP, please skip to step 10.
3. At this point you should be able to double-click the bac door client that is running in your system tray. (Icon on the far left.)
4. Select the configure menu. 5. Set the MS/TP parameters Com Port (restart) to be correct for your 485 converter
6. Click OK
Data Aire’s dap4 BACnet BMS
Document: 600-000-959 11
7. Close BACset.
8. Reopen BACset and select the MS/TP protocol.
9. You should now be able to run BACset.
10. Go to your network adapter properties and remove the BACMAC protocol.
11. Re-boot
12. Open up BACnet/IP
13. You should see the same error but when it searches for a new IP it should find the proper one.
14. Go back to step 3 and follow the recommended procedure to configure you COM port
Data Aire’s dap4 BACnet BMS
Document: 600-000-959 12
BACnet Object Definitions
Type Object Description Read/Write Object Name Instance
No.
Analog Temperature of return air R Ret_Air_Tmp AV1
Analog Maximum Return air temp in last 24hrs
R Maximum AV2
Analog Minimum Return air temp in last 24hrs
R Minumum AV3
Analog Temperature setpoint R/W Temp_Setpoint AV4
Analog comp is staged on R/W Temp_Deadband AV5
Analog Humidity Sensor Calibration R Ain_offs AV6
Analog Calibration R Ain_offs AV7
Analog Temperature of chilled water * R CW_Tmp AV8
Analog Temperature of discharge air * R Disch_Air_Tmp AV9
Analog Calibration ‐ Optional discharge* R Ain_offs AV10
Analog Sensor Calibration ‐ Optional * R Ain_offs AV11
Analog Chilled water is requested * R/W EngSaver_Setpoint AV12
Analog Value of the analog input * R Opt1_Analog AV13
Analog Value of the analog input * R Opt2_Analog AV14
Analog Value of the analog input * R Opt3_Analog AV15
Analog Value of the analog input * R Opt4_Analog AV16
Analog Analog Sensor 1 Minimum Value *
R Y1 AV17
Analog Analog Sensor 1 Maximum Value *
R Y2 AV18
Analog Analog Sensor 1 Calibration * R Ain_offs AV19
Analog Analog Sensor 2 Minimum Value *
R Y1 AV20
Analog Analog Sensor 2 Maximum Value *
R Y2 AV21
Analog Analog Sensor 2 Calibration * R Ain_offs AV22
Analog Analog Sensor 3 Minimum Value *
R Y1 AV23
Analog Analog Sensor 3 Maximum Value *
R Y2 AV24
Analog Analog Sensor 3 Calibration * R Ain_offs AV25
Analog Analog Sensor 4 Minimum Value *
R Y1 AV26
Analog Analog Sensor 4 Maximum Value *
R Y2 AV27
Analog Analog Sensor 4 Calibration * R Ain_offs AV28
*: These points are optional – Optional sensors or components required
Data Aire’s dap4 BACnet BMS
Document: 600-000-959 13
Type Object Description Read/Write Object Name Instance
No.
Integer Lower limit alarm of discharge air temp *
R/W Disch_Air_Lo_SP AV1001
Integer Relative humidity displayed as xx%
R Humidity_dis AV1002
Integer Cooling Stages On = Cooling stages are currently on – This point applies to DX unit only
R/W Stages_On AV1003
Integer Number of heat stages running R Heaters_On AV1004
Integer Maximum humidity in last 24hrs R Maximum AV1005
Integer Minimum humidity in last 24hrs R Minumum AV1006
Integer
Cooling Utilization Over Last Hour ‐Percentage of cooling is used in the last hour of operation; this point applies to DX unit.
R Comp_duty AV1007
Integer
Heating Utilization Over Last Hour ‐Percentage of heating is used in the last hour of operation
R Heat_duty AV1008
Integer
Humidifier Utilization Over Last Hour ‐Percentage of humidifier is used in the last hour of operation
R Hum_duty AV1009
Integer Compressor 1 Runtime ‐This point applies to DX unit with one compressor ‐high
R C1_Hours_H AV1010
Integer Compressor 1 Runtime ‐This point applies to DX unit with one compressor ‐low
R C1_Hours_L AV1011
Integer Compressor 2 Runtime ‐This point applies to DX unit with dual compressor ‐ high
R C2_Hours_H AV1012
Integer Compressor 2 Runtime ‐This point applies to DX unit with dual compressor ‐ low
R C2_Hours_L AV1013
Integer Heater 1 Runtime ‐ high R Ht1_Hours_H AV1014
Integer Heater 1 Runtime ‐ low R Ht1_Hours_L AV1015
Integer Current second R CURRENT_SECOND AV1016
Integer Current minute R CURRENT_MINUTE AV1017
Integer Current hour R CURRENT_HOUR AV1018
Integer Current day R CURRENT_DAY AV1019
*: These points are optional – Optional sensors or components required
Data Aire’s dap4 BACnet BMS
Document: 600-000-959 14
Type Object Description Read/Write Object Name Instance
No.
Integer Current month R CURRENT_MONTH AV1020
Integer Current year R CURRENT_YEAR AV1021
Integer Alarm settting of return air temp to determine there is a fire
R/W Firestat_SP AV1022
Integer Humidity upper limit alarm R/W Hum_Hi_SP AV1023
Integer Upper limit alarm of return air temp
R/W Ret_Air_Hi_SP AV1024
Integer Humidity lower limit alarm R/W Hum_Lo_SP AV1025
Integer Lower limit alarm of return air temp
R/W Ret_Air_Lo_SP AV1026
Integer Amount hum must change from setpoint before acting
R/W Hum_deadband AV1027
Integer Humidity setpoint R/W Hum_setpoint AV1028
Integer Time before the system starts up
R/W Start_dly AV1029
Integer Optional Alarm 1 Delay R Del AV1030
Integer Optional Alarm 2 Delay R Del AV1031
Integer Optional Alarm 3 Delay R Del AV1032
Integer Message on optional alarm screen, some also add function
R Alarm1_txt AV1033
Integer Message on optional alarm screen, some also add function
R Alarm2_txt AV1034
Integer Message on optional alarm screen, some also add function
R Alarm3_txt AV1035
Integer Message on optional alarm screen, some also add function
R Alarm4_txt AV1036
Integer
Comps 0=none, 1=one,Carel Side BMS Side 2=one+UL, 3=two, 4=two+UL, 5=Four/two circuit
R Comp_sel AV1037
Integer
0=none, 1= comp limited,2=twocomp limited, 3= comp unlimited, 4=twocomp unlimited
R Dehum_mode AV1038
Integer Number of heat stages R Reheat_sel AV1039
Integer 0=none, 1=comp mod, 2=comp non, 3= comf mod, 4= conf non mod
R Hum_sel AV1040
Integer Text displayed on all alarm screens
R Alm_Contact_msg AV1041
*: These points are optional – Optional sensors or components required
Data Aire’s dap4 BACnet BMS
Document: 600-000-959 15
Type Object Description Read/Write Object Name Instance
No.
Integer 0= start wo/alarm, 1= start w/alarm, 2= requires reset of alarm
R PowerUp_sel AV1042
Integer 0=None, 1=short beeps, 2=long beep, 3=Constant
R Buzzer_Select AV1043
Integer % of 10volts of analog output #1 R CW_disp AV1044
Integer
Chilled Water Utilization Over Last Hour ‐ This applies to Chilled water or Energy saver units.
R WtrVlv_duty AV1045
Integer Humidifier Runtime ‐ high R Hum_Hours_H AV1046
Integer Humidifier Runtime ‐ low R Hum_Hours_L AV1047
Integer Blower Runtime ‐ high R Blower_Hours_H AV1048
Integer Blower Runtime ‐ low R Blower_Hours_L AV1049
Integer Optional Alarm 4 Delay R Del AV1050
Integer 0= no comp assist, 1=one comp assist, 2= two comp assist, 3... 4...
R Assist_sel AV1051
Integer Water valve type 0=none,1=chill, 2=Engy, 3=Aux chill,4=Disc Reg
R WtrVlv_sel AV1052
Integer Water valve voltage 0= 0‐10, 1=2‐10, 2=7‐10, 3=6‐9, 4=4‐7
R WtrVlv_Volts_sel AV1053
Integer % of 10volts of analog output #2 R Hum_Volts AV1054
Integer Dehumidifier Runtime ‐ High R Dehum_Hours_H AV1055
Integer Dehumidifier Runtime ‐ Low R Dehum_Hours_L AV1056
Integer Time between drain cycles 0=12hr, 1=24hr, 2=48hr,3=96hr, 4=None
R AutoFlush_dly AV1058
Integer Value sent to optional analog output#1
R Y4_Out AV1059
Integer Value sent to optional analog output#2
R Y5_Out AV1060
Integer Current Fan Airflow ‐ Based on calculated Pressure Differential formula*
R Air_Flow AV1061
Integer Name of the sensor * R Opt_Snsr1_name AV1062
Integer Analog Sensor 1 Type {0=NTC 1=PT1000 2=0‐1VDC 3=0‐10VDC 4=4‐20mA 5=ON/OFF 6=0‐5VDC
7=NTC HT 8=‐50T90 9=10T170} *
R Ain_type AV1063
*: These points are optional – Optional sensors or components required
Data Aire’s dap4 BACnet BMS
Document: 600-000-959 16
Type Object Description Read/Write Object Name Instance
No.
Integer Name of the sensor * R Opt_Snsr2_name AV1064
Integer
Analog Sensor 2 Type {0=NTC 1=PT1000 2=0‐1VDC 3=0‐10VDC 4=4‐20mA 5=ON/OFF 6=0‐5VDC
7=NTC HT 8=‐50T90 9=10T170} *
R Ain_type AV1065
Integer Name of the sensor * R Opt_Snsr3_name AV1066
Integer
Analog Sensor 3 Type {0=NTC 1=PT1000 2=0‐1VDC 3=0‐10VDC 4=4‐20mA 5=ON/OFF 6=0‐5VDC 7=NTC HT 8=‐50T90 9=10T170} *
R Ain_type AV1067
Integer Name of the sensor * R Opt_Snsr4_name AV1068
Integer
Analog Sensor 4 Type {0=NTC 1=PT1000 2=0‐1VDC 3=0‐10VDC 4=4‐20mA 5=ON/OFF 6=0‐5VDC 7=NTC HT 8=‐50T90 9=10T170} *
R Ain_type AV1069
Integer CW Fan speed (%) sent via BMS R/W CW_Fan_Speed_bms AV1070
Integer DX Fan speed (%) sent via BMS R/W DX_Fan_Speed_bms AV1071
Integer Maximum Fan speed (% of output) modulation.
R/W Fan_Speed_max AV1072
Integer Minimum Fan speed (% of output) modulation from pressure.
R/W Fan_Speed_min AV1073
Integer Fan pressure setpoint (0.01inches of water) *
R/W Fan_Pr_sp AV1074
Integer Fan pressure band (0.01 inches of water) *
R/W Fan_pr_band AV1075
Integer Maximum air flow limit of setpoint from BMS or valve modulation.
R/W Fan_AF_max AV1076
Integer Minimum air flow limit of setpoint from BMS or valve modulation.
R/W Fan_AF_min AV1077
Integer Fan K Factor R/W Fan_Kfactor AV1078
Integer Number of fans installed in this unit
R/W Num_Fans AV1079
Integer Heater 2 Runtime ‐ high R Ht2_Hours_H AV1081
Integer Heater 2 Runtime ‐ low R Ht2_Hours_L AV1082
Integer Heater 3 Runtime ‐ high R Ht3_Hours_H AV1083
Integer Heater 3 Runtime ‐ low R Ht3_Hours_L AV1084
Integer Energy Saver Runtime ‐ This optional point applies to energy saver units only –high *
R Engy_Hours_H AV1085
*: These points are optional – Optional sensors or components required
Data Aire’s dap4 BACnet BMS
Document: 600-000-959 17
Type Object Description Read/Write Object Name Instance
No.
Integer Energy Saver Runtime ‐ This optional point applies to energy saver units only ‐ low
R Engy_Hours_L AV1086
Integer Chilled Water Runtime ‐ This applies to chilled water units only ‐ high
R CW_Hours_H AV1087
Integer Chilled Water Runtime ‐ This applies to chilled water units only ‐ low
R CW_Hours_L AV1088
Integer
Compressor 3 Runtime ‐ This applies when unit has four stages tandem compressors ‐high
R C3_Hours_H AV1089
Integer
Compressor 3 Runtime ‐ This applies when unit has four stages tandem compressors ‐low
R C3_Hours_L AV1090
Integer
Compressor 4 Runtime ‐ This applies when unit has four stages tandem compressors. ‐high
R C4_Hours_L AV1091
Integer
Compressor 4 Runtime ‐ This applies when unit has four stages tandem compressors. ‐low
R C4_Hours_H AV1092
Integer Condenser Runtime ‐ high R Cond_Hours_H AV1093
Integer Condenser Runtime ‐ low R Cond_Hours_L AV1094
Integer Fan speed (% of output) when compressor cooling.
R DX_Fan_Speed AV1095
Integer Fan speed (% of output) when cold water cooling.
R CW_Fan_Speed AV1096
Integer Fan air flow setpoint for DX unit (cfm) *
R Fan_AF_DX_sp AV1097
Integer Fan air flow setpoint for CW unit (cfm) *
R Fan_AF_CW_sp AV1098
Integer Zone Airflow Setpoint kcfm * R/W ZM_Airflow_SP AV1099
Digital Dehumidify mode is running R Dehum_On BV1
Digital Humidifier is running R Hum_On BV2
Digital Energy saver is running R Engy_On BV3
Digital Cooling inhibit from Zone Master *
R Cool_Inhibit BV4
Digital Heat inhibited due to alarm condition
R Heat_Held BV5
*: These points are optional – Optional sensors or components required
Data Aire’s dap4 BACnet BMS
Document: 600-000-959 18
Type Object Description Read/Write Object Name Instance
No.
Digital Humidifier stopped due to alarm
R Humidifier_inhibit BV6
Digital Dehum is inhibited R Dehum_Inhibit BV7
Digital Reheat during dehum R Rht_during_dehum BV8
Digital Water under floor alarm R Floor_Wtr_alm BV9
Digital No air flow alarm R Air_Flow_alm BV10
Digital Dirty filter from digital input R Filter_alm BV11
Digital Alarm from humidifier digital input *
R Humidifier_alm BV12
Digital Temperature of return air above firestat alarm set point
R Firestat_alm BV13
Digital One or more comps has short cycled
R Shortcycle_alm BV14
Digital Sensor is out of range R Humidity_fail BV15
Digital Sensor is out of range R Ret_Air_fail BV16
Digital Maintenance Schedule Due alarm
R Maint_alm BV17
Digital High pressure alarm R C1_HP_alm BV18
Digital Low pressure alarm R C1_LP_alm BV19
Digital High pressure alarm R C2_HP_alm BV20
Digital Low pressure alarm R C2_LP_alm BV21
Digital Smoke detected from digital input *
R Smoke_alm BV22
Digital No water flow alarm * R Wtr_Flow_alm BV23
Digital Sensor is out of range R Disch_Air_fail BV24
Digital Temperature of return air above alarm set point
R RA_Tmp_hi_alm BV25
Digital Temperature of return air below alarm set point
R RA_Tmp_lo_alm BV26
Digital Humidity above alarm set point R Hum_hi_alm BV27
Digital Humidity below alarm set point R Hum_lo_alm BV28
Digital Fan overload R Fan_Overload BV29
Digital
Standby pump on: Check primary pump ‐Optional alarm. Pump failure input signal required *
R Stdby_Pump_On BV30
Digital Custom alarm #1 ‐Optional alarm. External alarm input required. Factory programmed custom message required *
R Cust_msg_Sw1 BV31
*: These points are optional – Optional sensors or components required
Data Aire’s dap4 BACnet BMS
Document: 600-000-959 19
Type Object Description Read/Write Object Name Instance
No.
Digital
Custom alarm #2 ‐Optional alarm. External alarm input required. Factory programmed custom message required *
R Cust_msg_Sw2 BV32
Digital
Custom alarm #3 ‐Optional alarm. External alarm input required. Factory programmed custom message required *
R Cust_msg_Sw3 BV33
Digital
Custom alarm #4 ‐Optional alarm. External alarm input required. Factory programmed custom message required *
R Cust_msg_Sw4 BV34
Digital Humidifier stopped due to custom alarm switch
R HumSw_Inhibit BV35
Digital Heat inhibited due to custom switch alarm condition
R Heat_inhibit BV36
Digital Reheat and humidification inhibited from operation
R Rht_Hum_inhibit BV37
Digital Temperature of discharge air below alarm set point *
R Disch_Tmp_lo_alm BV38
Digital
Manual override: Check bypassswitches ‐ Standard alarm.Carel Side BMS Side Manual override switch is on
R Override_Alm BV39
Digital High condensation from digital input *
R Condensation_alm BV40
Digital
Unit in standby, all functions held off ‐ Optional alarm. Control input signal required Factory setting required *
R Unit_In_Standby BV41
Digital Sensor is out of range R CW_sns_fail BV42
Digital Humidifier stopped due to custom alarm switch
R HumSw_Chk_Cyl BV43
Digital Cooling operation inhibited by BMS
R/W BMS_Cooling_inhibit BV44
Digital Heat inhibited due to BMS R/W BMS_Heat_inhibit BV45
Digital Humidifier operation inhibited by BMS
R/W BMS_Humidifier_inhibit BV46
Digital Dehumidify mode inhibited by bms
R/W BMS_Dehum_inhibit BV47
Digital Inhibit fan by bms R/W Fan_Inhibit_bms BV48
Digital Reduce control humidity cycling R Hum_Expect BV49
*: These points are optional – Optional sensors or components required
Data Aire’s dap4 BACnet BMS
Document: 600-000-959 20
Type Object Description Read/Write Object Name Instance
No.
Digital Temperature Mode 0=°C 1=°F
R/W USASHR_F_C BV50
Digital Lead compressor select 0= C1,1= C2
R Lead_Comp BV52
Digital Water valve direct or reverse acting
R WtrVlv_dir BV53
Digital Alarm: UPS power on: Check main power ‐Optional alarm. External alarm input required *
R Ups_On_alm BV54
Digital Loss of power requires manual reset of alarm
R PwrUp_alm BV55
Digital Local alarm #1: See tag inside door =Optional alarm. External alarm input required
R SeeTag_cust_alm1 BV56
Digital Local alarm #2: See tag inside door =Optional alarm. External alarm input required
R SeeTag_cust_alm2 BV57
Digital Local alarm #3: See tag inside door =Optional alarm. External alarm input required
R SeeTag_cust_alm3 BV58
Digital Local alarm #4: See tag inside door =Optional alarm. External alarm input required
R SeeTag_cust_alm4 BV59
Digital Enable short cycle alarm of the compressors
R ShortCycle_alm_en BV60
Digital
Supervisor (BMS) On‐Off. Show the state OFFbyBMS in main mask (1: Off; 0: On). See Instance BV62 for detail
R/W Superv_Off BV61
Digital This variable must change at least once every 5 minutes or unit will turn on
R/W BMS_Heartbeat BV62
*: These points are optional – Optional sensors or components required