K. F. Chan (Mr.) ELEC 3105 1 LUMEN METHOD Utilization factor -- Ratio of flux received by reference plane to total rated lamp flux in the installation. Utilization factor of a lighting installation depends only on polar curve of the luminaire, the room geometry (represented by room index) and reflectances of the ceiling, wall and floor.

Transcript of B 4b Lumen Method

Page 1: B 4b Lumen Method

K. F. Chan (Mr.) ELEC 3105 1

LUMEN METHOD

Utilization factor-- Ratio of flux received by reference plane to total rated lamp flux in the installation.

Utilization factor of a lighting installation depends only on polar curve of the luminaire, the room geometry (represented by room index) and reflectances of the ceiling, wall and floor.

Page 2: B 4b Lumen Method

K. F. Chan (Mr.) ELEC 3105 2

Maintenance factor –

-- LSF

-- LLMF

-- LMF

-- RSMF

Page 3: B 4b Lumen Method

K. F. Chan (Mr.) ELEC 3105 3

LUMEN METHOD

E= N x n x ø x UF x MF

A

where MF = LLMF x LSF x LMF x RSMF

E =Maintained illuminance, lux

A = Area, m2

Ø = Initial lamp flux, lumen

Page 4: B 4b Lumen Method

K. F. Chan (Mr.) ELEC 3105 4

Page 5: B 4b Lumen Method

K. F. Chan (Mr.) ELEC 3105 5

LLMF & LSF

Page 6: B 4b Lumen Method

K. F. Chan (Mr.) ELEC 3105 6

(Taken from Table 3.4 of CIBSE Code for Lighting, 2002)

Page 7: B 4b Lumen Method

K. F. Chan (Mr.) ELEC 3105 7

Page 8: B 4b Lumen Method

K. F. Chan (Mr.) ELEC 3105 8

Page 9: B 4b Lumen Method

K. F. Chan (Mr.) ELEC 3105 9

Page 10: B 4b Lumen Method

K. F. Chan (Mr.) ELEC 3105 10

LMF

Page 11: B 4b Lumen Method

K. F. Chan (Mr.) ELEC 3105 11

LMF

(Taken from Table 3.5 and 3.6 of CIBSE Code for Lighting, 2002)

Page 12: B 4b Lumen Method

K. F. Chan (Mr.) ELEC 3105 12

RSMF

Page 13: B 4b Lumen Method

K. F. Chan (Mr.) ELEC 3105 13

RSMF

(Taken from Table 3.7 of CIBSE Code for Lighting, 2002)

Page 14: B 4b Lumen Method

K. F. Chan (Mr.) ELEC 3105 14