Fauquier County Water and Sanitation Authority
7172 Kennedy Road
Warrenton, Virginia 20187
Appendix C ‐ Construction
Details
November 2017
TABLE OF CONTENTS
THRUST BLOCKS
Anchorage for 11‐1/4o, 22‐1/2o & 45o Upper Vertical Bends ........................... AV‐01
Buttresses for 11‐1/4o Horizontal Bend ............................................................ BB‐01
Buttresses for 22‐1/2o Horizontal Bend ............................................................ BB‐02
Buttresses for 45o Horizontal Bend ................................................................... BB‐03
Buttresses for 90o Horizontal Bend ................................................................... BB‐04
Buttresses for Tees, Plugs and Caps .................................................................. BT‐01
Buttresses for 11‐1/4o, 22‐1/2o & 45o Lower Vertical Bends ........................... BV‐01
GENERAL CONSTRUCTION
Pipe Embedment and Backfill for Ductile Iron Pipe ........................................... G‐01
Pipe Embedment and Backfill for Plastic Pipe .................................................... G‐02
Typical Gate Valve and Valve Box ...................................................................... G‐03
Standard Concrete Cradle and Encasement ...................................................... G‐04
Steel Casing Detail .............................................................................................. G‐05
Sanitary Sewer Design Calculation Sheet ........................................................... G‐06
SEWER CONSTRUCTION
Combination Air/Vacuum Release Valve for Sewage Force Main ..................... SC‐01
Waterproof Manhole Insert .............................................................................. SC‐02
External Manhole Chimney Seal ....................................................................... SC‐03
Internal Manhole Chimney Seal ........................................................................ SC‐04
Standard 4’ ID Precast Concrete Manhole ........................................................ SC‐05
Typical 5’ and 6’ Diameter Pre‐Cast Concrete Manhole with 4’ Stack .............. SC‐06
Typical 4’ Manhole with Outside Drop Connection .......................................... SC‐07
Inside Drop Manhole ...................................................................................... SC‐07A
Standard Sanitary Sewer Service Lateral Connection ....................................... SC‐08
Sanitary Sewer Service Lateral Connection with Riser ...................................... SC‐09
Sewage Force Main 2” Connection ................................................................... SC‐10
Small Diameter Sewage Force Main Service Connection to Gravity Sewer ...... SC‐11
Termination for Dead‐End Runs of HDPE Force Main (2” and Smaller) ............ SC‐12
Pressure Lateral Assembly ................................................................................ SC‐13
UTILITY LOCATION & EASEMENT LAYOUT
R‐2 Conventional & Larger Lot Subdivisions ..................................................... UL‐01
R‐3 & R‐4 Conventional and R‐2 Cluster Subdivisions ....................................... UL‐02
R‐3 & R‐4 Cluster Subdivisions .......................................................................... UL‐03
Townhouse Subdivisions on Public Roads......................................................... UL‐04
WATER DISTRIBUTION SYSTEM
Blow‐Off Detail ................................................................................................ WD‐01
Sampling Station ............................................................................................. WD‐02
Air Release Valve ............................................................................................. WD‐03
Typical Fire Hydrant ........................................................................................ WD‐04
WATER METERS
Standard Water Meter Box & Fittings Up to 1” ............................................. WM‐01
1‐1/2” and 2” Water Meter and Service Connection ..................................... WM‐02
Combined Domestic & Fire Service Meter Vault Detail ................................. WM‐03
Standard Water Subtraction Meter ............................................................... WM‐04
Temporary Hydrant Meter Assembly ............................................................. WM‐05
Standard Water Service Connection for Water Meter Sizes Up to 1” ............ WS‐01
AV-01
Not to Scale Revised: 03/31/05
Fauquier County
Water and Sanitation Authority
Anchorage for11-1/4°, 22-1/2° & 45° Upper Vertical Bends
Concrete Notes:1) Fc=3000 PSI AT 28 DAYS.2) Carry all bearing surfaces to undisturbed earth or firm subgrade.3) The anchorage dimensions shown are based on design water pressure of 150 psi. Where a higher pressure specification is required, the volume of the concrete (L x W x D) shall be adjusted proportionally according to the design pressure used.
Reinforcing Bar Notes:1) Reinforcing Bars shall be hooked at each end and embedded minimum 8" into concrete. Exposed portion of all bars shall be painted with a minimum two coats of bituminous paint.2) Where 3 bars are used, they shall be arranged as shown on the detail above.3) Where 4 bars are used, 2 bars shall be located at each of end of the bend, symmetrically located on either side of the fitting.
Reinforcing Bars (typ.)
8'' min.
Pipe Dia.(min.)
BB-01
Not to Scale Revised: 03/31/05
Notes:1) Dimensions D & E shall be adjusted based on required area for value of Hc.2) Dimensions F & G are constant for a given pipe size.3) Dimension D shall be adjusted for required pressure in excess of 150 psi before making adjustment for Hc (above).
Fauquier County
Water and Sanitation Authority
Buttresses for11-1/4° Horizontal Bend
Carry concrete toundisturbed earth or firmsubgrade.
Concrete Block DimensionsAt 150 PSI Pressure
Amount to be added todimension 'D' for each
50 psi (or portionthereof) design
pressure above 150 psi(up to 300 psi).
CS
= 1
000
PS
FΦ
= 15°
Sof
t Silt
y C
lay
& B
ette
r
CS
= 0
PS
FΦ
= 15°
Loos
e S
ilty
San
d
Adjustment to ConcreteArea for Different Height,
Hc. To Be Measured fromFinished Grade to C of Pipe
Soil and Concrete Notes:1) FC = 3000 psi at 28 days.2) CS = Soil cohesion in psf3) Φ = Angle of Internal Friction.4) All bearing surfaces shall be carried to undisturbed earth or firm subgrade.
BB-02
Not to Scale Revised: 03/31/05
Fauquier County
Water and Sanitation Authority
Buttresses for22-1/2° Horizontal Bend
Notes:1) Dimensions D & E shall be adjusted based on required area for value of Hc.2) Dimensions F & G are constant for a given pipe size.3) Dimension D shall be adjusted for required pressure in excess of 150 psi before making adjustment for Hc (above).
Soil and Concrete Notes:1) FC = 3000 psi at 28 days.2) CS = Soil cohesion in psf3) Φ = Angle of Internal Friction.4) All bearing surfaces shall be carried to undisturbed earth or firm subgrade.
Concrete Block DimensionsAt 150 PSI Pressure
Amount to be added todimension 'D' for each
50 psi (or portionthereof) design
pressure above 150 psi(up to 300 psi).
Adjustment to ConcreteArea for Different Height,
Hc. To Be Measured fromFinished Grade to C of Pipe
CS
= 1
000
PS
FΦ
= 15°
Sof
t Silt
y C
lay
& B
ette
r
CS
= 0
PS
FΦ
= 15°
Loos
e S
ilty
San
dCarry concrete toundisturbed earth or firmsubgrade.
BB-03
Not to Scale Revised: 03/31/05
Fauquier County
Water and Sanitation Authority
Buttresses for45° Horizontal Bend
Notes:1) Dimensions D & E shall be adjusted based on required area for value of Hc.2) Dimensions F & G are constant for a given pipe size.3) Dimension D shall be adjusted for required pressure in excess of 150 psi before making adjustment for Hc (above).
Soil and Concrete Notes:1) FC = 3000 psi at 28 days.2) CS = Soil cohesion in psf3) Φ = Angle of Internal Friction.4) All bearing surfaces shall be carried to undisturbed earth or firm subgrade.
Carry concrete toundisturbed earth or firmsubgrade.
Concrete Block DimensionsAt 150 PSI Pressure
Amount to be added todimension 'D' for each
50 psi (or portionthereof) design
pressure above 150 psi(up to 300 psi).
Adjustment to ConcreteArea for Different Height,
Hc. To Be Measured fromFinished Grade to C of Pipe
CS
= 1
000
PS
FΦ
= 15°
Sof
t Silt
y C
lay
& B
ette
r
CS
= 0
PS
FΦ
= 15°
Loos
e S
ilty
San
d
BB-04
Not to Scale Revised: 03/31/05
Fauquier County
Water and Sanitation Authority
Buttresses for90° Horizontal Bend
Notes:1) Dimensions D & E shall be adjusted based on required area for value of Hc.2) Dimensions F & G are constant for a given pipe size.3) Dimension D shall be adjusted for required pressure in excess of 150 psi before making adjustment for Hc (above).4) Special design required for lines 24" in diameter or greater.
Concrete Notes:1) FC = 3000 psi at 28 days.2) All bearing surfaces shall be carried to undisturbed earth or firm subgrade.
Concrete Block DimensionsAt 150 PSI Pressure
Amount to be addedto dimension 'D' for
each 50 psi (or portionthereof) design
pressure above 150psi (up to 300 psi).
Adjustment to ConcreteArea for Different Height,
Hc. To Be Measured fromFinished Grade to C of Pipe
Extend concrete toundisturbed earth.
BT-01
Not to Scale Revised: 03/31/05
Fauquier County
Water and Sanitation Authority
Buttresses forTees, Plugs and Caps
Notes:1) FC = 3000 psi at 28 days.2) Buttress block dimensions are appropriate for design water pressure less than or equal to 150 psi.3) Where design water pressure exceeds 150 psi, block dimensions shall be proprtioned based on actual design pressure.4) All bearing surfaces shall be extended to undisturbed earth or firm subgrade.5) Tapping assemblies and sleeves shall be buttressed as comparably sized tees.
BV-01
Not to Scale Revised: 03/31/05
Fauquier County
Water and Sanitation Authority
Buttresses for11-1/4°, 22-1/2° & 45° Lower Vertical Bends
Notes:1) FC = 3000 psi at 28 days.2) Buttress block dimensions are appropriate for design water pressure less than or equal to 150 psi.3) Where design water pressure exceeds 150 psi, block dimensions shall be proprtioned based on actual design pressure.4) Where soil bearing pressure is less than 2500 psi, dimension 'L' shall be muliplied by 2 and Dimension 'M' shall be multiplied by 1.5.4) All bearing surfaces shall be extended to undisturbed earth or firm subgrade.
G-01
Not to Scale Revised: 03/31/05
Fauquier County
Water and Sanitation Authority
Pipe Embedment and Backfillfor Ductile Iron Pipe
G-02
Not to Scale Revised: 03/31/05
Fauquier County
Water and Sanitation Authority
Pipe Embedment and Backfillfor Plastic Pipe
G-03
Not to Scale Revised: 11/28/17
Fauquier CountyWater and Sanitation Authority
Typical Gate Valveand Valve Box
WATER
G-04
Not to Scale Revised: 03/31/05
Fauquier County
Water and Sanitation Authority
Standard ConcreteCradle and Encasement
G-05
Not to Scale Revised: 03/31/05
Fauquier County
Water and Sanitation Authority
Steel CasingDetail
G-06
Not to Scale Revised: 03/31/05
Fauquier County
Water and Sanitation Authority
Sanitary SewerDesign Calculation Sheet
SC-01
Not to Scale Revised: 11/28/17
Fauquier CountyWater and Sanitation Authority
Combination Air/Vacuum Release Valvefor Sewage Force Main
SC-02
Not to Scale Revised: 03/31/05
Fauquier County
Water and Sanitation Authority
WaterproofManhole Insert
SC-03
Not to Scale Revised: 03/31/05
Fauquier County
Water and Sanitation Authority
ExternalManhole Chimney Seal
SC-04
Not to Scale Revised: 03/31/05
Fauquier County
Water and Sanitation Authority
Internal ManholeChimney Seal
SC-05
Not to Scale Revised: 03/31/05
Fauquier County
Water and Sanitation Authority
Standard 4' ID PrecastConcrete Manhole
SC-06
Not to Scale Revised: 03/31/05
Fauquier County
Water and Sanitation Authority
Typical 5' and 6' Diameter Pre-CastConcrete Manhole with 4' Stack
SC-07
Not to Scale Revised: 03/31/05
Fauquier County
Water and Sanitation Authority
Typical 4' Manholewith Outside Drop Connection
SC-07A
Not to Scale Revised: 11/28/17
Fauquier CountyWater and Sanitation Authority
Inside Drop Manhole
A A
SC-08
Not to Scale Revised: 03/31/05
Fauquier County
Water and Sanitation Authority
Standard Sanitary SewerService Lateral Connection
SC-09
Not to Scale Revised: 03/31/05
Fauquier County
Water and Sanitation Authority
Sanitary Sewer ServiceLateral Connection with Riser
SC-10
Not to Scale Revised: 03/31/05
Fauquier County
Water and Sanitation Authority
Sewage Force Main2" Connection
SC-11
Not to Scale Revised: 11/28/17
Fauquier CountyWater and Sanitation Authority
Small Diameter Sewage Force MainService Connection to Gravity Sewer
SC-12
Not to Scale Adopted: 04/29/09
Fauquier County
Water and Sanitation Authority
Termination for Dead-End Runs ofHDPE Force Main (2" and Smaller)
SC-13
Not to Scale Revised: 11/28/17
Fauquier CountyWater and Sanitation Authority
Pressure Lateral Assembly
10.00' (min.)
CL Road (Typ.)
Utility Easement Line (Typ.)Water Line (Typ.)
Curb & Gutter (Typ.)5' Sidewalk (Typ.)
5.00' (min.)ROW Line (Typ.)
15.00' (min.)
ROW Line (Typ.)
Sanitary Sewer Manhole@ CL Easement (Typ.)
Utility Easement Line (Typ.)
When routing sanitary sewer around curves inthe road, the manholes and the center line ofthe pipe shall be placed no closer than 5.0'from the Easement and ROW lines. Sanitary Sewer Lateral (Typ.)
Sanitary Sewer Line (Typ.)
Water Service (Typ.)Property Line (Typ.)Min. Yard Line (Typ.)
FCWSA Utility Location & Easement Layout Detail (UL-01)Showing Typical Water & Sewer Utility Locations and Minimum Easement Widths along Internal Subdivision Streets
in R-2 Conventional Subdivisions & other Subdivisions with lots sized 20,000 SF or greater
1 inch = ft.( IN FEET )
GRAPHIC SCALE
50 100
50
20025 50UL-01
Scale: 1" = 50' 03/05/07
Fauquier County
Water and Sanitation Authority
Utility Location & Easement LayoutR-2 Conventional & Larger Lot Subdivisions
Notes:1) All dimensions are minimums.2) Typical sanitary sewer line location shall be 7.5' outside the ROW with a 15' utility easement.3) Typical waterline location shall be 5' outside the ROW with a 10' utility easement.4) Curve radii of less than 250' on water lines will necessitate the use of fittings. Where fittings are used, the waterline shall be routed so that the centerline of the pipe remains a minimum 3' from both ROW and easement lines.5) Water valve boxes shall not be located in sidewalks, curb & gutter or pavement.6) This detail is applicable only for internal subdivision streets. Easement widths for all other streets and roads shall be in accordance with the Authority's Utility Standards Manual (USM) Section 1.09.7) All design and construction shall be in accordance with the Authority's USM.
8.00' (min.)
CL Road (Typ.)
Utility Easement Line (Typ.)
Utility Easement Line (Typ.)Water Line (Typ.)
Curb & Gutter (Typ.)5' Sidewalk (Typ.)
3.00' (min.) ROW Line (Typ.)
12.00' (min.)
ROW Line (Typ.)
Sanitary Sewer Manhole@ CL Easement (Typ.)
When routing sanitary sewer around curves inthe road, the manholes and the center line ofthe pipe shall be placed no closer than 3.0'from the Easement and ROW lines.
Sanitary Sewer Line (Typ.)
Water Service (Typ.)
Sanitary Sewer Lateral (Typ.)
Property Line (Typ.)Min. Yard Line (Typ.)
FCWSA Utility Location & Easement Layout Detail (UL-02)Showing Typical Water & Sewer Utility Locations and Minimum Easement Widths along Internal Subdivision Streets
in R-3 Conventional, R-4 Conventional and R-2 Cluster Subdivisions with Single Family Dwellings
1 inch = ft.( IN FEET )
GRAPHIC SCALE
50 100
50
20025 50
Scale: 1" = 50' 03/05/07
Utility Location & Easement LayoutR-3 & R-4 Conventional and R-2 Cluster
Subdivisions
UL-02
Fauquier County
Water and Sanitation Authority
Notes:1) All dimensions are minimums.2) Typical sanitary sewer line location shall be 6.0' outside the ROW with a 12' utility easement.3) Typical waterline location shall be 3' outside the ROW with an 8' utility easement.4) Curve radii of less than 250' on water lines will necessitate the use of fittings. Where fittings are used, the waterline shall be routed so that the centerline of the pipe remains a minimum 3' from both ROW and easement lines.5) Water valve boxes shall not be located in sidewalks, curb & gutter or pavement.6) This detail is applicable only for internal subdivision streets. Easement widths for all other streets and roads shall be in accordance with the Authority's Utility Standards Manual (USM) Section 1.09.7) All design and construction shall be in accordance with the Authority's USM.
5.00' (min.)
CL Road (Typ.)
Utility Easement Line (Typ.)Sanitary Sewer Line (Typ.)
Water Service (Typ.)Water Line (Typ.)
Curb & Gutter (Typ.)5' Sidewalk (Typ.)
2.00' (min.) ROW Line (Typ.)
10.00' (min.)
ROW Line (Typ.)
Sanitary Sewer Manhole@ CL Easement (Typ.)
When routing sanitary sewer around curves inthe road, the manholes and the center line ofthe pipe shall be placed no closer than 2.5'from the Easement and ROW lines.
Sanitary Sewer Lateral (Typ.)
Utility Easement Line (Typ.)
Property Line (Typ.)Min. Yard Line (Typ.)
FCWSA Utility Location & Easement Layout Detail (UL-03)Showing Typical Water & Sewer Utility Locations and Minimum Easement Widths along Internal Subdivision Streets
in R-3 Cluster and R-4 Cluster Subdivisions with Single Family Dwellings
1 inch = ft.( IN FEET )
GRAPHIC SCALE
50 100
50
20025 50
Scale: 1" = 50' 03/05/07
Utility Location & Easement LayoutR-3 & R-4 Cluster Subdivisions
UL-03
Fauquier County
Water and Sanitation Authority
Notes:1) All dimensions are minimums.2) Typical sanitary sewer line location shall be 5.0' outside the ROW with a 10' utility easement.3) Typical waterline location shall be 2' outside the ROW with a 5' utility easement.4) Curve radii of less than 250' on water lines will necessitate the use of fittings. Where fittings are used, the waterline shall be routed so that the centerline of the pipe remains a minimum 2' from both ROW and easement lines.5) Water valve boxes shall not be located in sidewalks, curb & gutter or pavement.6) This detail is applicable only for internal subdivision streets. Easement widths for all other streets and roads shall be in accordance with the Authority's Utility Standards Manual (USM) Section 1.09.7) All design and construction shall be in accordance with the Authority's USM.
5.00' (min.)
CL Road (Typ.)
Utility Easement Line (Typ.)
Sanitary Sewer Line (Typ.)
When routing sanitary sewer around curves inthe road, the manholes and the center line ofthe pipe shall be placed no closer than 2.5'from the Easement and ROW lines.
Utility Easement Line (Typ.)Water Line (Typ.)
Curb & Gutter (Typ.)5' Sidewalk (Typ.)
ROW Line (Typ.)
10.00' (min.)
ROW Line (Typ.)
Sanitary Sewer Manhole@ CL Easement (Typ.)
Water Service (Typ.)
Property Line (Typ.)Min. Yard Line (Typ.)
2.00' (min.)
Typ. Parallel Parking
FCWSA Utility Location & Easement Layout Detail (UL-04)Showing Typical Water & Sewer Utility Locations and Minimum Easement Widths along Internal Streets
in Townhouse Subdivisions with units fronting on Public Roads with parallel parking.
1 inch = ft.( IN FEET )
GRAPHIC SCALE
50 100
50
20025 50
Scale: 1" = 50' 03/05/07
Utility Location & Easement LayoutTownhouse Subdivisions on Public Roads
UL-04
Fauquier County
Water and Sanitation Authority
Notes:1) All dimensions are minimums.2) Typical sanitary sewer line location shall be 5.0' outside the ROW with a 10' utility easement.3) Typical waterline location shall be 2' outside the ROW with a 5' utility easement.4) Curve radii of less than 250' on water lines will necessitate the use of fittings. Where fittings are used, the waterline shall be routed so that the centerline of the pipe remains a minimum 2' from both ROW and easement lines.5) Water valve boxes shall not be located in sidewalks, curb & gutter or pavement.6) This detail is applicable only for internal subdivision streets. Easement widths for all other streets and roads shall be in accordance with the Authority's Utility Standards Manual (USM) Section 1.09.7) All design and construction shall be in accordance with the Authority's USM.
WD-01
Revised: 11/28/17
Fauquier CountyWater and Sanitation Authority
Not to Scale
Water Distribution SystemBlow-Off Detail
WATERWATER
WD-02
Fauquier CountyWater and Sanitation Authority
Water Distribution SystemSampling Station
Revised: 11/28/17Not to Scale
INSET
WD-03
Not to Scale Revised: 11/28/17
Fauquier CountyWater and Sanitation Authority
Water Distribution SystemAir Release Valve
WD-04
Not to Scale Revised: 11/28/17
Fauquier CountyWater and Sanitation Authority
Water Distribution SystemTypical Fire Hydrant
WM-01
Not to Scale Revised: 11/28/17
Fauquier CountyWater and Sanitation Authority
Standard Water Meter Box &Fittings Up to 1"
60° +/-
WM-02
Not to Scale Revised: 11/28/17
Fauquier CountyWater and Sanitation Authority
1-1/2" and 2" Water Meterand Service Connection
12"MIN.
WM-03
Not to Scale Revised: 11/28/17
Fauquier CountyWater and Sanitation Authority
Combined Domestic & Fire ServiceMeter Vault Detail
WM-04
Not to Scale Revised: 03/20/07
Fauquier CountyWater and Sanitation Authority
Standard Water Subtraction Meter
Fini
shed
Gra
de
Met
er Y
oke
Bar
Ford
AV
94-3
23W
-G
Ford
YLN
-23
(2)
Pol
yeth
ylen
e Tu
bing
Ex.
Cus
tom
er-o
wne
d S
ervi
ce L
ine
Typi
cal C
onne
ctio
n of
Sub
tract
ion
Met
er
Ford
Typ
e 'A
32-T
' or '
C32
-T' M
eter
Box
Cov
er.
Top
to b
e se
t bet
wee
n 1/
2" a
nd 2
" abo
ve fi
nish
ed g
rade
.
Ang
le V
alve
with
Pad
lock
Win
gs
14 G
auge
Insu
late
d C
oppe
rTr
acer
Wire
Atta
ched
Her
e
"Pig
-Tai
l" (fo
r con
nect
ion
toIrr
igat
ion
Sys
tem
) to
term
inat
e 2'
from
met
er b
arre
l
18" x
30"
Rou
nd C
oncr
ete
orP
VC
Pit-
Set
ter
Ang
led
Dua
l Che
ck V
alve
(Car
tridg
e S
tyle
)
Fill
Pit-
Set
ter w
ith S
and
or S
tone
Dus
tB
eddi
ng u
p to
the
Bot
tom
of t
heM
eter
Yok
e.
Met
er Y
oke
Det
ail
Sta
inle
ss S
teel
Inse
rts to
be
Use
d In
side
Pla
stic
Tub
ing.
Dra
in o
n M
eter
Sid
e of
Che
ck V
alve
.
Ford
HH
CA
94-3
23D
-G
18" Min.24" Max.
6" M
inim
um
Con
nect
To
Cus
tom
er S
ide
ofW
ater
Ser
vice
Lin
e
Met
er B
ox D
etai
lfo
r 5/8
" x 3
/4" W
ater
Sub
tract
ion
Met
er
Ford
Y50
2M
eter
Yok
e
Not
e: P
art N
umbe
rs s
how
n on
this
Det
ail a
re fr
om F
ord
Man
ufac
turin
gC
ompa
ny p
rodu
cts.
App
rove
d eq
uals
may
be
used
.
Not
e: A
LL c
ompr
essi
on fi
tting
s sh
all i
nclu
de g
rip jo
ints
.
Not
e: M
eter
box
lid
shal
l inc
lude
a 1
-3/4
" hol
efo
r mou
ntin
g a
touc
h re
ad p
ad.
To H
ouse
To Irrigation System
Ex.
Wat
er M
eter
(Prim
ary
Ser
vice
)
Pro
p. S
ubtra
ctio
n M
eter
Easement/R.O.W. Line
3' +/-3' +/-
NO
TE:
Irrig
atio
n se
rvic
e lin
e sh
all
be c
onne
cted
to th
e cu
stom
er's
serv
ice
line
on th
e cu
stom
er's
sid
eof
the
mai
n m
eter
.
WM-05
Not to Scale Revised: 11/28/17
Fauquier CountyWater and Sanitation Authority
Temporary HydrantMeter Assembly
WS-01
Not to Scale Revised: 11/28/17
Fauquier CountyWater and Sanitation Authority
Standard Water Service Connection For Water Meter Sizes Up to 1''