Access Audit Report - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/21_...
Transcript of Access Audit Report - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/21_...
Access Audit Report Mizo Govt. Higher Secondary School
Science Building Aizawl, Mizoram
Submitted under:
Sugamya Bharat Abhiyan (Accessible India Campaign)
Department of Empowerment of
Persons with Disabilities
Ministry of Social Justice & Empowerment
Government of India
Page | 1
,,
ACCESS AUDIT REPORT
THE MIZO GOVT. HIGHER SECONDARY SCHOOL - SCIENCE BUILDING
MAC DONALD HILL ZARKAWT AIZAWL, MIZORAM – 796001
Submitted under:
Sugamya Bharat Abhiyan (Accessible India Campaign under Department of Empowerment of Persons with Disabilities,
Ministry of Social Justice & Empowerment, Government of India)
Prepared By:
Centre For Rehabilitation and Training For Multiple Disability
Birubari, Guwahati - 781016, Kamrup (Metro), Assam. Phone : 0361-2470990/2478912, Mobile : +91-9207049810
Email : [email protected]
Page | 2
Accessible India Campaign (Sugamya Bharat Abhiyan)
Accessible India Campaign is a nationwide flagship campaign of the Department of
Empowerment of Persons with Disabilities, Ministry of Social Justice and
Empowerment, Government of India, for achieving universal accessibility for persons
with disabilities and to create an enabling and barrier free environment, with a focus
on three verticals of built-environment accessibility, transportation system
accessibility and information and communication eco-system accessibility.
The task involved under the initiative, include identification of important public
buildings in 48 selected cities across India, conducting access audits and retro-fittings
of ramps, lifts, toilets, and signage in the buildings; making 75 important railway
stations and all international airports fully accessible and ensuring that at least 50% of
all web sites and public documents of the central and the state governments meet
accessibility standards. Specific timelines have been set all the above goals.
Aizawl, the capital city of the state of Mizoram is one of the selected cities, wherein
33 government / public buildings have been identified for conducting access audits
and retro-fittings to ensure barrier free environment.
Shishu Sarothi, a not-for-profit organization working in the field of disability for the
past around 30 years is an empanelled Access Auditor under the said initiative, and
participated in the Invitation for Bid process and was duly awarded the Work Order
bearing No. F.No.4-14/2015-A/C dated 19.03.2016 for conducting access audit of 33
buildings in Aizawl city.
Page | 3
Table of Contents
1. Introduction
1.1 Accessibility in the built-environment Page 4
1.2 The Legal Framework Page 4
2. Access Audit
2.1 Purpose of Access Audit Page 5
2.2 Standards Page 5
2.3 Premises where Access-Audit was conducted Page 5
2.4 Access Audit Team Page 6
3. Access Audit Report
3.1 External Environment
3.1.1. Parking Lot Page 6
3.1.2. Alighting Page 7
3.1.3. Accessible Route Page 7
3.2 Internal Environment
3.2.1. Accessible Entrance Page 9
3.2.2. Reception & Lobby Page 10
3.2.3. Stairs Page 10
3.2.4. Ramps Page 11
3.2.5. Handrails Page 12
3.2.6. Elevators / Lifts Page 13
3.2.7. Escalators / Passenger conveyors Page 13
3.2.8. Corridors Page 13
3.2.9. Doors and doorways Page 14
3.2.10. Accessible Toilets Page 15
3.2.11. Cafeteria Page 17
3.2.12. Drinking water facilities Page 17
3.2.13. Control and operating mechanisms Page 18
3.2.14. Signages Page 19
3.2.15. Emergency Evacuation Page 20
3.2.16. Common building elements Page 21
3.3 Information, communication and services Page 22
4. Conclusion Page 23
5. Appendix Page i - lxiv
Page | 4
1. Introduction:
1.1. Accessibility in the built-environment:
Environmental access is a set of norms and standards designed to provide safe and
independent use of varied environments such as transportation, roads, buildings and
communication by persons with disabilities. Universal design is a commitment for
designing products and environments for the broadest population possible, especially
for the people who have not been considered as part of the general population.
1.2. The Legal Framework
The importance of promoting greater access as an effective approach to reversing
exclusion and enhancing the equalization of
opportunities in a sustainable way has been the
mandate of the United Nations Convention on the
Rights of Persons with Disabilities (UNCRPD),
approved by the General Assembly in December
2006, ratified by India on October 1, 2014 and
which entered into force in May, 2008.
The Convention also mandates that all
Governments shall take measures for
implementation of minimum standards and
guidelines for accessibility of facilities and services
open to the public; to ensure that private entitles
that offer facilities / services open to the public
comply with all aspects of accessibility for persons
with disabilities; train stakeholders on accessibility
issues; provide Braille signage and live assistance,
professional sign language interpreters to facilitate
accessibility to buildings and other facilities open
to the public.
Further, Goal No. 3 of the Incheon Strategy,
which provides the Asian and Pacific Region and
the world the first set of regionally agreed distinct
inclusive development goals, mentions that access
to the physical environment, public transportation, knowledge, information and
communication is a precondition for persons with disabilities to fulfill their rights in
an inclusive society.
Sections 44, 45 and 46 of The Persons with Disabilities (Equal Opportunities,
Protection of Rights and Full Participation) Act, 1995, categorically provides for
non-discrimination in transport, on the roads and in built environments.
Article 9 of the UNCRPD on
“Accessibility” stipulates that
persons with disabilities are
to be enabled to live
independently and
participate fully in all aspects
of life. The Article casts an
obligation on all signatory
governments to “….take
appropriate measures to
ensure to persons with
disabilities access, on an
equal basis with others, to the
physical environment, to
transportation, to
information and
communication, including
information and
communications technologies
and systems, and to other
facilities and services open or
provided to the public, both in
urban and in rural areas…..”
Page | 5
2. Access Audit:
2.1. Purpose of an access audit
The purpose of an access audit is to assess how a particular building or environment
performs in terms of access and ease of use by a wide range of actual and potential
users, including person with disabilities and to recommend access improvements. The
aim of the access audit and its follow-up are to:
Identify the extent of the problem of access to public buildings and
recommend changes / additions to make the environment accessible
To create awareness of the importance of the concept of barrier-free
environments for persons with disabilities
To enforce the inclusion of accessibility for persons with disabilities in the
official agenda of government and private agencies.
The report includes observations, measurements, sketches and photographs covering
all parts of the public building audited including the external and internal environment
as well as the services provided in the building.
2.2. Standards:
The accessibility standards and parameters adhered to in the instant access audit are as
per the revised guidelines (2014) of the Central Public Works Department Manual,
Handbook on Barrier-Free and Accessibility (URL: http://cpwd.gov.in). For some
points not specifically covered by the said Handbook, reference has been taken from
the Harmonized Guidelines and Space Standards for Barrier Free Built
Environment of the Ministry of Urban Development Government of India.
2.3. Premises where Access-Audit was conducted:
The Mizo Govt. Higher Secondary School is a Co-ed school with around 1,000
students from Arts, Science, Commerce and Computer Technique (Vocational
Training Unit). While the former three wings are spread over the main school
premises, which takes up a hill, the latter is located outside the main school premises.
The different buildings have separate staff rooms for teaching staff of the respective
wings.
The College was established in the year 1996 with two streams, Arts and Commerce,
and Science was introduced in the year 2000. Computer Technique under Vocational
Training Unit was started a few years later.
The Mizo Govt. Higher Secondary School - Science Building, is a three-storied
building, with classrooms, staffroom and laboratories.
Page | 6
2.4. Access Audit Team:
Access Audit Team Name Designation
Access Auditor Ms Amvalika Senapati Coordinator, Disability Law Unit,
Shishu Sarothi
Architect Mr. Devadeep Gupta Alternate Architect & Installation Artist, Guwahati
Persons with Disability K. Lalhmingsanga Treasurer, Mizoram Blind Society
Accompanying Official from the Mizo Govt. Higher Secondary School :
Ms. Lalrinpuii, Lecturer, Contact: +91-9436151763
Date of Access Audit : April 28, 2016 (Thursday)
3. Access Audit Report:
This report gives a narrative outline of existing facilities, lays down the areas of concern
with pictorial illustrations of the existing infrastructure. The report comes with an annexure
which is a compilation of recommendations with technical details along with photographs
and suggestions.
The Audit is structured into three parts, viz, the external environment, internal environment
and information, communication and services.
3.1. External environment
The external environment includes the following:
3.1.1. Parking lot:
There is some parking area in front of the Commerce building, which is commonly used for
both the Science and Commerce building.
There is no reserved accessible parking bay for persons with disabilities.
(a)
(b)
Fig. 1: Reserved accessible parking to be provided in the space where a car is parked as shown in (b), commonly for both the Science / Commerce Building.
Page | 7
Recommendations:
Reserved parking bay for people with disability should be provided as shown in Fig.
1(b).
Parking bay for people with disability has to be constructed preferably along with a
proper shed, adjacent to the space identified, which leads to the access route.
The parking bay and the adjacent access route has to be laid with tactile floor
guidance tiles along on a firm pathway, minimum 1200mm wide, laid with anti-skid
tiles and built as per CPWD guidelines, for independent navigation / mobility of
people with visual impairment.
Appropriate disability signage to be used for the reserved parking bay for persons
with disabilities along with directional signage leading to the tactile pathway /
accessible route.
3.1.2. Alighting
Right now there is no designated space for alighting of people with disabilities. But
after parking bay for people with disabilities have been identified and transformed,
there is space adjacent to the reserved parking bay to design alighting point with
required signposts, step free access and tactile guidance.
Recommendations:
Alighting point has to be constructed next to the reserved parking bay [(Fig. 1(b)].
Alighting point should be leveled and cleared out of traffic lane.
Proper sign-posts and signage to be installed along with tactile guidance tiles,
hazard warnings and positional files.
Step free route leading from the alighting area to the main entrance of the building
has to be constructed.
3.1.3. Accessible Route
The Science Block can be accessed from within the campus (Fig. 2) or from an
external access route 3000 mm wide (Fig. 3). The internal route is completely
inaccessible.
As the school is spread over a hill, there is no plain pathway or accessible route. The
Science Building is connected to the Arts / Admin Building through steps cut in hills
(Fig. 2).
There are two main gates for the School from the vehicular road. One of the gates [Fig.
3(a)] lead to a common route to the Commerce and the Science Block. The Commerce
Page | 8
building is adjacent to the common parking area for the two buildings and the Science
block is just beyond it.
The pathway is slightly sloped and the surface of the pathway is different in different
places, not leveled and even, concrete in places and soil in others.
The pathway is free of barriers and obstacles. No gratings are present in the pathway.
There is no tactile guiding path including directional, hazard warning and positional
files provided for independent navigation.
The route from parking to the main entrance is long and there is no resting space along
the way.
There is no accessible directional signage directing to the accessible entrance.
There is no adequate artificial light on the pathways after sunset.
Fig. 2: Route from the Arts block up to the Science
Building within the campus
Page | 9
(a)
(b)
(c)
Fig. 3: External access route 3000 mm wide to the Science / Commerce Building
Recommendations:
The existing route (Fig. 3) connecting the entrance gate, parking, alighting point and
the main entrance to the building should be upgraded. It can be made accessible by
installation of adequate tactile guiding path including directional, hazard warning and
positional tiles provided for independent navigation.
Adequate resting spaces should be made along the way from the parking to the
entrance.
Accessible directional signage should also be put up directing to the accessible
entrance.
3.2. Internal environment
The internal environment includes the following:
3.2.1. Accessible Entrance:
There is no entrance per se for the Science Building. Steps lead to corridors which in
turn leads to different classrooms and department offices.
Page | 10
The main entrance is not accessible for persons with disabilities.
The entrance has adequate landing of 1500 mm x 1500 mm and is well illuminated.
There is no difference in floor finish at the door entrance easily identifiable by blind
users.
Fig 4: Entrance to Science building
Recommendations:
The stepped entrance should be made accessible by providing a ramp to connect
the plinth level of the building. (Refer to 3.2.4).
Accessible signage to identify the accessible entrance to be installed.
Floor finish at the door entrance to be clearly identifiable for visually impaired
people.
3.2.2. Reception and lobby:
There is no reception counter in the Science Building.
The main office in the Arts / Administrative Block is called / understood as the common
reception for all the school buildings, including the Science building.
3.2.3. Stairs:
There is one 1100 mm wide staircase in the Science Block, with uniform step risers and
treads of 150 mm and 300 mm respectively.
The first flight of stairs does not have any handrails, whereas for all other flights, there
is a concrete handrail on one side, with the supporting wall on the other.
There are no colour contrast strips at the edge of the steps.
There is no tactile warning provided at the beginning and end of the stairs.
There is adequate illumination on the stairs, which are non-slippery and non-glary.
Under stair areas are well cordoned off.
Page | 11
Approach to some stairs are obstructed with hap-hazardly kept furniture on the stair
landings [Fig 5(b)].
(a)
(b)
Fig. 5: Staricases in the Science Block
Recommendations:
Handrails should be fitted in all stairs as per specifications.
There should be tactile warning provided at the beginning and end of the stairs.
Colour contrast strips to be provided at the edge of the steps.
Stairs to be well maintained.
Stair landings to be unobstructed.
3.2.4. Ramp:
There is no ramp in the building.
No ramp can be suggested to connect the
upper floors of the buildings due to
space constraint.. However, ramped
access to ensure step-free access for
persons with disabilities up to the main
entrance / plinth level is possible.
Fig. 6: Ramp running adjacent to verandah
to be provided in the Science Block
Page | 12
Recommendations:
It is recommended that ramped access should be constructed to the plinth of the Science
block.
Modular ramp may also be installed in place of constructing concrete ramp (Refer to
Appendix).
Ramp should have a gradient not steeper than 1:12, with a minimum width of 1800 mm.
Handrails should be provided on both sides of the ramp.
There should be tactile warning blocks installed 300 mm from the top, bottom and
landings of the ramp runs in external environment.
The floor surface should be non-slippery and non-glary.
3.2.5. Handrails:
Handrails in the Science Block are concrete handrails provided at a single height of
900 mm. In some stairs, there are no handrails.
Handrails do not have clear contrast in colour from the background wall and floors.
Handrails are not circular, non-slippery, have an uninterrupted grip and the ends of the
handrails are grouted and without any sharp edges
Fig. 7: Handrails (or absence of it) in the Science Block
Recommendations:
Handrails should be provided on both sides of the stairs and ramps (when installed).
Handrails should be provided at two heights of 900mm and 760mm.
Handrails should contrast in colour from the background wall and the floor.
Page | 13
Handrails should be circular, non-slippery, have an uninterrupted grip and the ends
of the handrails should be either grouted or turned downwards.
There should be adequate hand clearance between the wall and the handrails.
3.2.6. Elevators / Lifts:
There is no lift / elevator in the Science building. Though one is required to address the
need for vertical accessibility, lift cannot be suggested in this building due to difficult
terrain, space constraint and / or without a lot of internal dismantling of existing rooms
/ corridors to make way for lift shaft and lift lobby.
3.2.7. Escalators / Passenger conveyors:
There are no Escalators/Passenger Conveyors present in the premises and none are also
needed. In any case, escalators / passenger conveyors are not considered as accessible
for disabled people and, hence, not recommended.
3.2.8. Corridors:
The corridors in the Science building are 1500 mm wide and meet the minimal
required width as per specifications.
While some corridors are free, others have protruding objects or barriers like
furniture, doors and windows opening onto corridors, which remain unguarded.
Fig. 8: Corridors in the Science Building
Most corridors have 1500 mm x 1500 mm space to allow a wheelchair user to turn
around at some point on the corridor.
The floor finish is mostly exposed concrete, not slippery and not glary.
The corridors are well illuminated.
Page | 14
No handrails are provided on either sides of the corridors in the ground floor,
whereas, there are handrails on one side in the upper floors.
There is no clear colour contrast between the corridor walls, floors etc.
Recommendations:
Handrails should be provided at least on the outer side of the corridors in the
ground floor [Fig. 6]. It is not feasible to suggest handrails on the other side as
there are too many doors.
Corridors to be kept free of protruding object and, if unavoidable, they should be
guarded.
Corridor floors to have clear colour contrast from background walls ceiling etc.
3.2.9. Doors & doorways:
Doors in the building are above the desired minimum width of 900 mm, except for
some toilets doors.
The doors are easy to open and do not take too much energy.
Most doors have handle / latches.
The colour of the door frame do not contrast in colour with the door and the background
wall in most cases.
Most doors in the buildings are one-
way swing, double hinged doors.
Most doors have thresholds higher
than the acceptable height of 12 mm.
Most doors open in the corridors,
including the toilet doors.
Where there are two doors in a series,
there is at least 1500 mm deep space
between the two doors.
None of the doors are fitted with
vision panels.
Kick plates have not been provided on
the doors.
Automatic doors are not provided at
the building entrance.
Page | 15
Fig. 9: Doors and doorways in the Science building
Recommendations:
Width of toilet doors to be increased to 900 mm width.
Lever type handle should be used with a horizontal bar 800mm from the floor and a
vertical bar in the opening side with its lower edge at 800mm from the floor.
The colour of the door frame should have clear contrast in colour with the door and the
background wall.
Where unavoidable, thresholds should not be more than 12 mm high.
Door closures to be avoided.
Kick plates can be provided in the most accessed doors like the toilet doors.
Doors to be provided with guardrails where it opens into a route of travel.
Automatic doors are not recommended at the building entrance as there is no clear
entrance as such.
3.2.10. Accessible toilets:
The Science Block has four cubicles each for boys and girls in one toilet block.
There is no accessible toilet for persons with disabilities in the school building.
Recommendations:
The first two cubicles to be dismantled and made into one unisex accessible toilet to
be used by students with disabilities. The other toilets can be maintained separately
for boys and girls.
The toilet door must be outward opening, double hinged or sliding door.
Page | 16
The WC should be installed in a corner
with centerline of the WC at a distance
of 450mm to 500mm from the adjacent
wall. The front edge of WC should
project 750mm of/from the rear wall.
Indian style WC should not be used and
WC should be provided with a
backrest.
The seat height of the WCC should
be 450mm.
Fig. 10: Toilets in the Science building
Door to the accessible toilet should have a minimum width of 900 mm and should
have beleveled thresholds.
Page | 17
Lever type flush control is to be installed at a height of 1100mm from the floor
surface, or on the transfer side of the WC. The force required to flush should be
comfortable.
There should be 800mm of clear transfer space next to the WC.
A horizontal grab bar is to be installed on the adjacent wall, at a height of 200mm
from the WC seat.
A fold up grab bar is to be installed at a centerline distance of 320m-200mm from
the WC seat.
There should be colour contrast between the floor, wall and sanitary fittings.
There should be an alarm system within easy reach to alert persons outside, in case
of emergency.
Visual alarm must be there to alert people with hearing disability in case of
emergency.
The door should be able to be locked from inside but also released from outside
in case of emergency.
The accessible toilet should not be kept locked or used as a janitor’s room.
The toilet should be kept clean and well-maintained.
Mirrors should be placed at accessible heights.
All toilet accessories, soap dispensers, coat hooks should be at accessible reach.
In addition to the accessible toilets, the other toilets (Boys / Girls) should also follow
standardization of placement of utilities like
- Basin taps to be placed at the centre of the basin.
- Soap dispensers must be either at the immediate right or left side of the basin.
- Water jets on the right or left side of the WC.
- Flush must be either immediately behind the seat or at the centre.
- WC water tap must be either at the right or left of the WC.
3.2.11. Cafeteria:
There is no cafeteria / canteen for this building / school.
3.2.12. Drinking Water facilities:
Drinking Water facility is available in the building at one end of the corridor on the ground
floor. It is housed inside a room (kept open during school hours) and the threshold of the
room obstructs clear approach to the same. As such, the facility is not easily accessible for
persons with disabilities.
Page | 18
The facility is available at a height of 700 mm from the floor level and it has knob-type
taps. There are no glasses for drinking water. Also, they are not well maintained and there
is no signage to indicate the presence of the drinking water facility.
Recommendations:
Drinking Water facility should be at
an accessible height (Refer to
Appendix).
It is recommended that the approach
to the Drinking Water facility should
be kept clear.
The tap should be lever type and
easily operable.
Drinking glasses should be made
available and kept at an accessible
height not higher than 1200 mm. Fig. 11: Dirinking water faciltiy in
the Science building
Proper signage should indicate the presence of the drinking water facility.
3.2.13. Control and operating mechanisms:
The switches or controls are not placed at consistent heights throughout the building and
some are beyond the accessible standards.
No touch panels have been installed for operating controls or switches.
Little pressure is required to operate the switches or controls.
Switches or controls have no contrast in colour from surrounding face plate panel,
background walls etc.
There is no information on controls / switches which are in relief (embossed letters and /
or Braille information) for tactile reading.
Recommendations:
The operable part of controls such as vending machines, electrical switches, wall
sockets should be:
- Located adjacent to the clear floor space with dimensions of at least 900mm x
1200mm;
- Located at the height of between 400mm and 1200mm, measured from the floor,
with the exception of vending machines where the upper limit is relax able to
1300 mm;
- Electrical sockets must not be placed at a height lower than 400mm from the
floor.
- Controls should be placed at not less than 400mm from room corners.
Page | 19
All controls should be colour-contrasted, with the surrounding face plate panel
and the face plate contrasting with the background wall on which they are mounted.
Information on controls and switches should be in relief (embossed
letters/symbols accompanied with Braille information) for tactile reading.
3.2.14. Signages:
There are prominent visible signage present for the different classrooms and staffroom,
but no accessible signages in alternate formats like Braille / audio signs and so on.
Also signages are not present for other provisions like parking, drinking water etc.
There is adequate illumination of visual signage.
Fig. 12: Signages in the Science building
Recommendations:
There should be prominent visible signage using the international symbol of
accessibility, identifying accessible entrance, reserved car parking, reception etc.
Signages for presence of toilets for persons with disabilities and availability of
other facilities in the building should be conspicuously placed in the building.
Signage size should comply with not less than 60mm for doors, 110 mm for
corridors and 200mm for external use.
All visual signage in the facility should be provided with Braille and Tactile
supplements.
Where ever possible, audio signage should be provided along with Braille and
Tactile signage.
All Braille and tactile signage should be placed between the height of 900 mm
and 1500 mm, with ideal location at 1050 mm above the finished floor level.
If Braille and tactile signs are provided at a door, the same should be located
alongside the door at the latch side.
Page | 20
Where tactile signs are provided at double doors with one active leaf, the tactile
signs should be on the inactive leaf.
Where tactile signs are provided at double doors with two active leafs, the tactle
signs should be located at the right hand side of the door.
Braille specifications in all signages should follow the handbook specifications.
All visual signage in the building should use high colour contrast.
There should be both visual and auditory substitutes for public address systems
and LED Display board information in the building.
3.2.15. Emergency evacuation:
There is no emergency evacuation provision in the Science building.
Recommendations:
Emergency evacuation provision should be laid out for the building, taking into
account people with disabilities.
For the ground floor of the Science building, evacuation would not be a
challenge (once ramp is constructed). However, for the upper floors, a refuge
area has to be identified near the stairs, with adequate signage, including
directional signage leading to it.
There should be an alerting system both visual and audible.
The alerting buttons should be between 600mm and 1200mm from the floor
and have a high contrast with the background wall.
There should be directional signage leading to the refuge area and the
evacuation plans have the refuge area marked on them.
All emergency and directional signage should be accessible.
The refuge area should be minimally a 900mm x 1200mm space for
parking a wheelchair.
Smoke barriers around the refuge area is not essential in this case, as refuge
area would be in the corridor near the stairs and the space is not confined but
open
There should be an audio and visual two way communication system in the
refuge area at the height of 1000mm.
Evacuation plans should be prominently displayed in the building.
Evacuation plans and building maps should be made available in tactile /
Braille formats.
The plan should be of right size and easy to read.
Page | 21
The accessible evacuation route and the refuge points should be shown on the
plan.
The plan should have a ‘you are here’ point identified on it.
The plan should contrasts well with the background wall.
The Staff should be trained to assist persons with disabilities in evacuation.
Evacuation chairs should be available for the building and there should be staff
trained to use them in case of emergency.
3.2.16. Common building elements:
3.2.16.1. Colour contrast (in critical surfaces, sudden change in level, toilets,
stairs, handrails, doors, switches and sockets, skirting, free standing
obstacles and signage):
Colour contrast in critical surfaces is minimal or almost not present in the
Science Building. It is seen to some extent as far as signages are
concerned, but they do not comply with standard specifications.
It may be mentioned that contrast is conspicuously missing in critical
surfaces like sudden change in level, toilets and toilet fittings, stairs,
doors and doorways, switches and so on and so forth.
Recommendations:
Colour contrast to be ensured in all critical surfaces as per specifications,
including in toilets and toilet fittings, stairs, doors and doorways, level
differences, switches etc.
3.2.16.2. Flooring:
Floors are mostly exposed cement in the building. Floors are not slippery
and not glary.
There is no clear colour contrast between floors and background walls in
most cases.
Recommendations:
Flooring has to be as per specifications highlighted in the Appendix to this
Report.
There should be difference in floor tiles from corridors and rooms in all
buildings.
Page | 22
3.3. Information, communication and services:
The School does not have a website and there is also no alternate accessible formats
of publications / brochures. None of its staff are trained in Indian Sign Language
and neither are there Sign Language interpreters available on call. There is no
facility of availability of a wheelchair; the staff have never attended any disability
sensitization sessions nor do they have trainings on how to extend assistance to
people with disabilities. However, it may be noted that staff / teachers are keen to
extend whatever assistance they can. Also there is no Equal Opportunities Policy in
place to promote employment of staff with disability.
Recommendations:
School to develop an accessible website in compliance with accessibility norms
as per Web Content Accessibility Guidelines 2.0 (WCAG 2.0).
Relevant information in publications / brochures to be made accessible for the
public in alternate accessible formats.
Also all written content in notice boards etc to be provided in alternate accessible
formats.
Staff to be given awareness of accessible facilities in the premises.
There should be a simple procedure of enquiry / complaint lodging or making
suggestions for a student with disability.
There should be trained staff to extend live assistance to disabled people
whenever needed and especially during emergencies etc.
All staff to have disability sensitization sessions from time to time.
Department to develop and implement an Equal Opportunities Policy to
promote employment of staff with disability.
Reasonable adjustment of school environment should be made, whenever the
need arise, to accommodate disabled staff / student.
Services like availability of wheelchairs, loop induction system, sign
language interpreter etc. should be ensured.
All accessibility equipments in the building to be regularly checked and
maintained in good working condition.
There should be a policy to allow guide dogs, wherever a disabled person is
accompanied by one.
Page | 23
4. Conclusion:
The Mizo Govt. H.S. School - Science Building is largely not accessible for persons
with disabilities, in view of the fact that most classrooms as well as laboratories in the
building are in the upper floors without any scope for vertical accessibility.
However, as it stands, there is scope to incorporate other barrier-free built environment
provisions along with ensuring of accessible information, communication and services.
There are positive aspects like availability of parking and vehicular access route to the
building, wide corridors, drinking water facility. With necessary changes /
incorporations as recommended in this report, the aforesaid can be made accessible for
persons with disabilities.
It is recommended that control contrast be improved in all relevant surfaces; signages
be provided for parking etc and also existing signages be modified as per guidelines
with regard to size, placement etc; adequate directional, positional tiles and hazard
warning be provided as per standard specifications, evacuation plan be put into place;
floor finish be upgraded; controls / switches to comply with standards and have
consistency throughout the building; doors to be corrected to open inwards; ramps be
constructed and / or modular ramps installed for accessible entrances to the building;
accessible toilet be made by dismantling existing toilets to allow for required
dimensions and so on and so forth.
_________________________________