Pandit Ravi Shankar University -...

83
Pandit Ravi Shankar University Raipur 25 May 2016

Transcript of Pandit Ravi Shankar University -...

Page 1: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

Pandit Ravi Shankar UniversityRaipur

25 May 2016

Page 2: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

2

Introduction : • Accessible India Campaign (Sugamya Bharat Abhiyan) is launched by the Department of Empowerment of

Persons with Disabilities, Ministry of Social Justice & Empowerment as a nationwide flagship campaign for achieving universal accessibility for persons with disabilities. The campaign focuses on Built Environment, Public Transportation and Information and Communication Technologies (ICT). As part of the vertical on Built Environment, the existing building is access audited to be made accessible & inclusive for persons with disabilities.

• Aim: to highlight access initiatives, which are non negotiable, and shall be provided for all services and facilities.

• Access Audit Report: is prepared with line illustrations, designs and sketches for successful implementation. The recommendations of the access audit are based on ground realities and cost effective solutions are provided. Checklist with access standards should be read in conjunction with this report. Numbering in the report is provided as per the numbers in checklist.

• Access Standards: “Harmonised Guidelines and Space Standards for Barrier Free Built Environment for Persons with Disabilities and Elderly Persons” 2016 by Ministry of Urban Development are sited. All measurements are in millimeters (mm).

• Acknowledgements: Directorate of Social Justice, Government of Chhattisgarh

Name of the building : Pandit Ravi Shankar UniversityCity : RaipurBuilding type and use : Educational

Page 3: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

3Executive Summary

Mandatory Implementation 1. Accessible website for persons with disabilities2. Alighting- with access route to main entrance of building3. Accessible parking with in 30 meters of accessible entrance4. Tactile pavers for all facilities and amenities including the access routes5. 1:12 gradient ramp for entrances6. 1:15 gradient ramp to first floor (for buildings with G +1)7. Staircase and ramp with handrails on both sides8. Controls and operations - height between 600-1100 mm9. Accessible drinking water unit10. Accessible urinal in Gent’s toilet on all floors11. Accessible toilets on all floors12. Accessible lift – all lifts to have Braille, audio, mirror, and grab bars13. Conference hall/ audi to have Induction Loop Unit14. Emergency evacuation measures, availability of Evac chair for persons with disabilities and staff

training and mock drills

Page 4: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

4

Life Science Department

Page 5: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

5External Environment

Life Science DepartmentExisting

• Height of Channel gate- 60 mm• It has slippery flooring•One step-height- 170 mm• Ramp with 1:12 gradient is recommended Refer Section 3, 4,6, and 8

Main Entrance

Accessible Parking

Alighting

Page 6: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

6

Existing

Life Science Department

Corridor

• Level difference near room no. 5 and room no. 23 to be leveled• Iron channel gate to be embedded while making ramp • Staircase near new gate. Step ht. 90+130 onwards+150 mm ; handrail

is at a height of 9990 mm• Sofit- open area under the staircase is not cordoned off by guard rails

Internal Environment

Iron channel gate Corridor with good illumination, however no handrails

Page 7: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

7

Existing

Life Science Department

General Laboratory• 1 step- ht 110 mm • Door- 1050 mm• Practical table is of height 850 mm• Washbasin in a corner at a height of 1020 mm• Level difference near room no. 5 and room no. 23 to be leveled• Iron channel gate to be embedded while making ramp • Staircase near new gate- step ht. 90+130 onwards+150 mm;

handrail is at a height of 9990 mm• Sofit- open area under the staircase is not cordoned off by guard

rails

Internal Environment

Page 8: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

8Internal Environment

Wash basins and ToiletsGirls Toilet• 1 Indian Seat • 2 urinals • No European type toilet is provided • Door at a height of 760 mmBoys Toilet • 3 urinals • 1 Indian seat

Life Science Department

Page 9: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

9Internal Environment

Toilets at the first floor• Gents: 2 urinals; 2 WC• Ladies: 2 WC, 1 WB• Size of the toilet- 1680 x 2720mm• Urinals- one urinal to be modified with

lower rim height and chest support bar• Refer accessible urinals. • All toilet fixtures to be in contrast color

to the wall tiles. Alternatively, wall tiles could be of contrast colour to the fixtures.

Life Science Department

RecommendationAccessible Toilet• 1 WC to be converted into girls accessible toilet.• An accessible boys toilet should be constructed next to toilet no. 25 (area available 2850 x 3140 mm)

Page 10: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

10

Life Science DepartmentExistingMicrobiology Lab / Class no. 21

• Signage to be in contrast colour, large fonts and in Braille. Refer Section 16- Signage• Seating benches are inadequate and black board to be replaced by green/ white board.

Internal Environment

Page 11: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

11

Life Science Department Seminar Hall

• Step- 240 mm • Table is of ht. 810 mm

Jagdish Chandra Bose • Hall entrance - 100 mm step down• Switches at a ht. of 1510 mm-1670 mm• Stage ht. 390 mm. To have a ramp with gradient 1:12 max. Ramp can be L-shape turn in the front all straight ramp along side wall• Induction loop unit should be provided in the hall.

Existing

Internal Environment

Page 12: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

12

Iron channel gate gap to be filled by rubber bidding; removed during closing

Tissue culture lab no. 5 room, corridor is obstructed by furniture

Life Science Department

Internal Environment

Signage to be in contrast colour, large fonts and in Braille.

Page 13: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

13

Geology Department

Page 14: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

14

Geology DepartmentExisting• It has a cattle trap with a gap of 80 mm- bridge

plate to • Main entrance has three steps with ht.

150+160+150mm• No ramp provided. L-shape ramp is

recommended by extending the stair landing and turned around the wall. Refer Section 3, 4, 6, and 8.

External Environment

Main entrance

Page 15: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

15

Geology Department

Internal Environment

Space identified for provision of ramp to first floor Space identified for accessible parkingApproach road to be maintained and paved pathway with tactile pavers should be provided

Page 16: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

16Internal Environment

Geology DepartmentExisting

• General ToiletsLadies: 1 Indian seat, 1 wash basin, 1 urinalGents: 1 Indian seat, 2 urinals, 1 wash basinAccessible toilet: Existing toilets to be modified to be converted into accessible toilets separately in ladies and gents toilets. • No access to drinking water.

Recommendation• Building is under renovation, hence, there is a scope for provision of ramp from ground floor to first floor to the left side of the building.• If there is scope for second floor onwards, then a lift is recommended

Page 17: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

17

Geology Department

Internal Environment

Corridor

• There is dumped furniture and almirahs blocking the corridors• Handrails are recommended on the walls • Illumination level of 150-200 lux level to be maintained in the corridor.• Refer Section 11 for corridor standards.

Page 18: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

18

Geology Department Staircase• Handrails are provided on one side only• Handrail height- 1130mm• Sofit area (open area under staircase is not cordoned off) and can be accidental hazard for persons with visual impairment. Refer Section 6 for staircase standards.

Way finding signage• Are painted inconspicuously on the stair case wall. Refer Section 16 for signage.• There are no tactile pavers provided. Refer Section 3 and 3a.

Internal Environment

Existing Proposed Proposed

Page 19: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

19

School of Studies in Statistics

Page 20: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

20

School of Studies in StatisticsExistingAccessible Parking and Alighting• Entrance has two steps of 170+170 mm. Refer Section 3 and 6. • Ramp is 1 m long and is a scooter ramp, extremely steep for wheelchair users. Refer Section 4, 6, and 8• Sofit under staircase should be cordon off. Refer Section 6.

External Environment

Approach road to be paved and accessible route with tactile pavers should be provided.

Page 21: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

21Internal Environment

Statistics DepartmentExistingGround floor toilet

Ladies• Area – 2270 * 2200mm• One Indian seat•Two wash basin

Gents• Width of the door- 710mm•One Indian seat•Two urinals- one urinal to be lowered down and chest support grab bar to be provided. Refer section on accessible urinals.

RecommendationStaff toilet (M/8) must be renovated to convert into accessible toilet. Space available is 2400*1500mmLadies toilet - (L- shape) near Professor Vyas Dubey room to be converted into accessible toilet. Refer Section 12 & 13.

Page 22: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

22Internal Environment

Statistics DepartmentExisting

First floor • Six classrooms and one seminar hall.• Staircase- unequal risers ranging from 150-190mm•Ht of handrail- 960mm

Seminar Hall•Height of stage- 290mm•Height of switches- 1700mm•Width of the entrance door- 370mm due to table blocking at back of door• Induction lop system should be provided

Recommendation

•Girls common room required (extension possible for common room), as suggested by girls students.•Accessible toilets for both boys and girls.•Extra fans in classrooms with all electrical fittings.

Page 23: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

23

School of Studies in StatisticsDrinking Water• Water unit is provided in a sunken area under the staircase. It was found that many people were struggling

to get down the high steps and there was inadequate draining.• It is recommended to cordon off the sofit area by guard rails and relocate drinking water unit to a location

having level access. Refer Section 6. • Refer Section 14 for accessible drinking water standards.

External Environment

Page 24: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

24

School of Studies in Law

Page 25: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

25

Law DepartmentExistingAccessible parking and Alighting• Main entrance of the Department have three unequal steps of 160+160+140 mm• There is no ramp provided. L-shape ramp with gradient 1:12 max. should be provided.• Refer Section3, 3a, 4, 6 and 8 for access standards of tactile pavers, ramp, steps, and handrails.

External Environment

Accessible parking – not in front of the steps and ramp; should be provided on the side of the entrance

Alighting- tar road No ramp found

Page 26: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

26Internal Environment

Law DepartmentExistingLadies Toilets with inconspicuous signage is displayed- ladies and gents text is reversed for the toilets, there by confusing the users. • Width of door- 600mm • Two Indian seats • Two washbasinsRefer Section on general toilets and signage 16.

Page 27: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

27Internal Environment

Law DepartmentAccessible Toilet

RecommendationsOld toilet near computer lab can be extended at the back side and accessible toilet cubicle of size 2050 x 1880mm should be provided. Refer Section 13. for accessible toilet

Accessible toilet to be provided as per the illustration

Space identified at the back sideof computer lab

Page 28: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

28Internal Environment

Law DepartmentClassroom• Height of switches- 1580 mm• Distance between two tables- 440mm• Benches are not appropriate; no leg clearance is available. Detachable seat and table are preferred for persons using mobility aids.

Seminar hall• Stage ht. 280mm• Switch ht. 1450mm• Four fans are provided out of which only 3 are working.

Drinking water unitHeight of water purifier (under the stairs) tap- 900mm Recommendation• Iron channel gate to seminar hall should be beveled or flushed in the ground.• Dustbins should be provided to prevent litter in the corridor and obstruction caused to all people.

Page 29: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

29

Law Department

Internal Environment

Classrooms• Room sigange are placed on the door frame• Doors are of contrast colour to wall• Doors do not have lever locks/ handles• Distance between two tables- 440mm• Benches are not appropriate; no leg clearance is available. • Detachable seat and table are preferred for persons using mobility aids.

Page 30: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

30

Institute of Pharmacy

Page 31: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

31

Institute of PharmacyExistingParking, alighting and accessible entrance• Accessible parking is identified on one side of the

steps. Refer Annexure 1, 2, 3 and 3a for parking and alighting.

• Entrance steps are of unequal ht. 100+160+160+160+170 mm.

• Risers to be equal height 150mm max. Refer Section 6.

• Straight ramp with gradient 1:12 max. should be provided on opposite side of the proposed parking.

• Handrails should be provided for steps and ramp. Refer Section 8.

External Environment

Corridor without handrails

Page 32: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

32Internal EnvironmentInstitute of PharmacyExisting•No signages are provided for certain lecture rooms/ class rooms. Refer Section 16. •Sofit area under the staircase is not cordoned off. Refer Section 6. •Height of water purifier tap is 1030mm. To be modified to make it accessible. Refer Section 13. • Two water cooler near M. Pharmacy Lab –930mm• Lecture hall no. 2 have combined desk (seat and table - 620mm gap), which could be not accessible for persons using mobility aids. It is recommended that some desks should have detachable seat and tables.

Sofit area under the staircase High water cooler Room signage too high

Benches should be provided with leg clearance

Page 33: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

33Internal EnvironmentInstitute of PharmacyExisting

Classroom • Height of switches- 1700mm. Refer Section 15- Control and Mechanisms • Height of stage- 200mm- to have a ramp from one side with gradient 1:12 max. Edge of the stage should have contrast colour band for easy identification be persons with low vision

Pharmacy Lab

• Signage too high. Refer Section 16 for sigange• Working slabs have stools for seating, which do not have arm and back rest

Page 34: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

34

Institute of Pharmacy

Internal Environment

Door frames in dull colour contrast

Inadequate aisle space in between chairs and working slabs/ shelves

Glazed shiny flooring

Space identified for ramp to first floor

Page 35: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

35Internal EnvironmentInstitute of PharmacyGeneral Toilets

Recommendations

• Ladies toilet can be made accessible as there is enough space inside the cubicle.• Accessible toilet cubicle for Gents should be constructed opposite existing Gents toilet.• A ramp should be constructed for gents toilet as there is a step down (130mm riser). Alternatively, floor to be raised at the corridor level while refurbishing the toilet. • Urinals to be made accessible by lowering one urinal rim height by 430mm and chest support grab bars should be provided.

Page 36: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

36

Auditorium

Page 37: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

37

AuditoriumExisting• No accessible entrance – back side have three unequal steps and front have multiple steps• Back entry- 150mm+120mm; ramp with gradient 1:12 max should be provided by covering the entire

width. Refer Section 4. • Accessible route should be provided – 1200mm wide pathway level and firm having tactile pavers. Refer

Section 3 and 3a

External Environment

Page 38: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

38Internal EnvironmentAuditoriumExisting

Main Entrance

Main entrance has staircase- first three steps height 190+180+200mm One step of 180 mm height with a channel gate followed by 4 more steps outside. Ramp at main entrance is proposed by opening one of the windows in the lobby and directly connected with road level. Refer Section4, 6, and 8.

Stage• Height of stage is 1130 mm (6steps). A ramp is proposed in front of the stage- 1m width and 13.30m length.• Height of green room steps (160+160) mm• Height of steps from green room to stage (220+210+210)mm• Induction loop system should be provided

Recommendation• Accessible toilet should be provided near two windows and the area identified for ramp provision in the lobby- area identified near fire extinguisher

Page 39: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

39Internal Environment

Auditorium

Recommended

Number of seats in aseating area

Number of required spaces forwheelchair users

up to 600 6 i.e. 1/100

up to 1000 6 + 2

over 10008+1 for each additional increment of 1000seats

Recommendations-Seating for wheelchair users• Some seats with removable or flip-up armrests should be provided at row ends to accommodate a wheelchair user or a person with limited ambulatory mobility. • A level floor area for wheelchair users should be placed at row ends and should be scattered on different levels so as to have a variety of seating and viewing locations.

Page 40: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

40Internal EnvironmentAuditoriumGeneral Toilets• All signage to be in contrasting colours.• For visitors and employees with low vision and vision impairments- pictogram (male pictogram in triangle and female pictogram in circle), marked on plates along with Braille & raised alphabets, to be mounted on wall next to door near the latch side, at a height between 1400mm-1600mm.• Warning paver strip/ thin rubber door mat to be provided 300mm before the toilet entrances. • Availability of sanitary material and disposal mechanism in ladies toilet.

Page 41: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

41Internal Environment

Auditorium

Steps to have contrast colour band on edges to prevent trip hazard

Water cooler to be brought forward to allow mobility aid users to access water taps

Handrails to be provided on both sidesincluding landing

Page 42: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

42

Library

Page 43: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

43

LibraryExisting• Entrance to the building is maintained, however there are gaps due to change of surface (tile and paved

flooring)• Steep ramp for100mm high step is provided, which should be modified as per Section 4.

External Environment

Page 44: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

44Internal Environment

LibraryExisting• Staircase- height of handrail- 1050mm•Height of step risers- (180+150+160)mm•Height of the water cooler tap 1130mm•Lift is under construction, and passage (700mm wide only) to lift is blocked by a table which should be relocated.• Size of the lift well- 1.68m x 2.16m

Recommendation• Pillars in circulation area should be painted in contrast color.• Lift to be provided as per Section 9.

Passage (700mm wide only)

Page 45: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

45Internal EnvironmentLibraryExisting

Ground floor-Bag counter height- 860mm

Reading Section• Height of counter- 1080mm• Reading table have a leg space of 590 mm and tables are at a height of 750mm

Page 46: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

46

LibraryGeneral Toilets

External Environment

Existing Gents toilet to be converted into accessible Gents toilet

Space identified for accessible toilet

Open urinals should have doors for girls

Level difference to be beveled Pictogram colour and size should be consistent for all toilets

Page 47: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

47

University Teaching Department

Page 48: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

48

University Teaching Department

External Environment

Accessible route

Page 49: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

49

University Teaching DepartmentExisting

External Environment

Corridor should have handrails on both sidesThere should be foot mats 9thin rubber mats preferred) / tactile pavers marking entry to room doors

Water dispenser should be lowered down to be accessible for wheelchair usersWater drainage should be maintained to prevent water spilling in the corridor

Page 50: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

50

University Teaching Department

Internal Environment

Existing•Entrance level difference - 70 mm• Uneven steps of ht. (180+150+150)mm•Handrail is provided only on one side- ht. 1090m• Channel and pipeline has a trip hazard.• Classroom door is of width-1000 mm• Switch ht.- 1560mm• Height of the tap of the drinking water unit is 1020mm

Recommendations

• Handrail should be extended on the first step also. Refer Section 6 and 8. • Metal strip on the stairs edges should be removed and anti skid color contrast bands should be provided.

Metal strip on the stairs edges

Page 51: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

51

University Teaching Department

Internal Environment

• An accessible toilet is proposed opposite to ladies toilet and Room no. E01• A gents accessible toilet is to be constructed behind existing drinking water unit.

Page 52: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

52

Recommendations and Access Standards

Page 53: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

53External Environment

1. Accessible Parking

Total number of parking spaces in open car parks or car park buildings:

Required minimum number of accessible spaces:

1 to 25 126 to 50 251 to 75 3

76 to 100 4

Recommendations• Parking lot nearest to the entrance gate of each deaprtment is identified as the accessible parking.• It’s within 30meters of the main entrance.• Overall minimum dimension 3600mm x 5000mm, including aisle space of 1200mm. • On the route from the entrance to the accessible parking spaces, signs should indicate the whereabouts

of accessible parking by the international symbol of accessibility.• These signs should be positioned at 2100mm height, so that they can be seen even if cars are parked in

the vicinity and shall be 600mm x 600mm size, to be identified from the driver’s seat.• All security guards/staff should be sensitized and well informed about reserved parking for persons with

disabilities.

Page 54: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

54

2100

mm

1. Accessible ParkingExternal Environment

Page 55: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

55

2. AlightingExternal Environment

Signage for alighting

Recommendations• Area outside the main gate of the building must be identified for alighting for persons with disabilities and the main entrance too•Alighting area should be level and free from traffic. • Signage and drop off area should be clearly marked.• Tactile pavers should be provided to guide persons with visual impairments from this area to the building entrance. Refer Section 3a.

Page 56: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

56External Environment3. Accessible RouteRecommendations• Accessible route (min 1200mm clear width) with tactile pavers, firm, level, anti skid surface, resting spaces at

max. 30m distances, and strategically placed directional signage should be provided to and from the entrances, parking, alighting points and other key destinations.

• In case of level differences, a ramp must be provided.

Page 57: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

57

Bollard Spacing

External Environment3. Accessible Route

Kerb Ramp

Page 58: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

58External Environment3. Gratings/ Cow CatcherRecommendations• Manholes and drains should have gratin covers with gap not wider than 10mm• Gratings should be perpendicular with pedestrian travel path.

Page 59: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

59External Environment3a. Tactile PaversRecommendations• Line-type indicate the correct path/route to follow.• Dot-type provides warning signal, to screen off obstacles,

drop-offs or other hazards, to discourage movement in anincorrect direction and to warn of a corner or junction.Should be placed 300mm at the beginning and end of theramps, stairs and entrance to any door.

Places to install tactile pavers: • In front of an area where traffic is present. • In front of an entrance/exit. • To and from a staircase or multi-level crossing facility. • In open space to orient persons with vision impairment.

Page 60: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

60Internal Environment

4. Accessible Entrance -RampRecommendations

• Gentle slope of gradient 1:12 max.• Landings every 750mm of vertical rise clear space of 1500mm x 1500mm minimum.• Minimum clear width -1200 mm.• Ramps and landing surfaces should be slip resistant/ anti-skid.• Handrails to be on both sides at two levels and at a height of 760mm and 900mm; both ends to be rounded and grouted and extend 300mm beyond top and bottom of ramp.• Strip of warning blocks should be placed 300mm before and after the ramp edges.

Page 61: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

61Internal Environment

4. Accessible Entrance -RampRecommendations

• L- shape ramp should have a level landing at the top and bottom of each run and also where the runchanges direction.

• Landings should be provided at regular intervals of not more than 9000 mm of every horizontal run.

Page 62: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

62

6. Stairs

• Step to be equal/uniform risers (height): 150mm and tread (step depth): 300mm.• Have continuous handrails on both sides including the wall (if any) at 760mm and 900mm height.• Warning strip to be placed 300mm at the beginning and at the end of all stairs. Landings also to have a row of warning strip.• Nosing to be avoided. • There needs to be signage indicating the floor level on each floor. It is also desirable to have a directory of services available on each floor at the landing areas.• Step edges- 50mm minimum should have bright contrasting colors, which helps persons with low vision to identify height and depth of each step. • Sofit- open area under the staircase should be cordoned off by guard rails.

Recommendations

Internal Environment

Contrast colour band on step edges

Page 63: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

63

8. HandrailsRecommendations

• Should be circular in section with a diameter of 38-45mm; • Should be at least 45mm clear of the surface to which they are attached; • Should be at two levels 760mm and 900mm from the floor; • Extend by at least 300mm beyond the head and foot of the flight and ramp in the line of travel and grouted in the ground; • Should be in bright color contrast to the surroundings (preferably red/yellow).

Internal Environment

Page 64: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

64Internal Environment

5. Reception/Enquiry CounterRecommendations

• A section of the counter to be lowered down to 800mm and height of the cut out in the glass should be at 1000mm max. • Two way mike system is ideal for effective communication in high noisy areas.• An induction loop system should be installed. • Background noise: It is most important to reduce any background noise internally and externally. Sound absorbent surfaces should be utilized to minimize reverberation, which could seriously affect the hearing of a person with hearing impairment.

Signage for Induction Loop System

Portable Induction Loop Unit

Page 65: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

65Internal Environment

9. Elevator/LiftRecommendations

• Call button & control panel: At a reach of 900mm-1000mm; at least 400mm from any corner or have a clear floor space of at least 900mm x 1200mm with no obstruction placed to prevent a wheelchair user from reaching the call button;• Control panel: Inside the lift to be on both the sides. Have buttons with Braille/ raised letters and in sharp contrast from the background to aid persons with visual impairments. • Braille information/raised numbers, audio and visual indicator, review mirror & kick plates to be fitted. • There should be no gap or difference in level between the lift door and the floor surface at each level. If such a gap is unavoidable, then it should not be more than 12 mm.• Review mirror & kick plates to be fitted. • Lift lobby to have ceiling hung floor number for easy identification by the visitors.• Grab Bars

Be placed at a height of 900mm from the floor level; andBe fixed on both sides and at the rear of the lift.

• Audio and Visual IndicatorsThe lift should have a voice announcement system along with a visual display to indicate the floor level.

Page 66: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

66

9. Elevator/Lift

Proposed

Internal Environment

Recommendations

Page 67: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

67Internal Environment

11. CorridorsRecommendations• Corridor should be kept free from potted plants furniture,

waste products and coolers, etc.• Window that can open inside or with sliding shutters are

proposed.• Handrails should be provided in the corridors for people to

take support and balance while walking.• Illumination level in corridors should not be less than 150-200

lux.• One thick strip of florescent/bright colour (orange/yellow) on

floor may be provided to give better orientation.• Threshold (door sill): at the entrances and level differences

more than 10mm, should be beveled i.e. provide slope onboth side of vertical height.

• Obstacles and protruding objects: more than 100mm from thewall, such as cluttered furniture, almirahs, telephone, fireextinguishers, benches, flower pots and decorative fixturesshould not be placed in the corridors.

• Width: be wide enough to allow easy access of people cases,parents with prams and people on crutches to pass eachother on route. The minimum width of the corridor should be1800mm with wheelchair turning spaces of 1500mm x1500mm at regular intervals.

Floor finishes and visual contrast in corridor

Page 68: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

68Internal Environment

12. Doors & DoorwaysProposed•All doors should provide a clear opening of 900mm minimum.• Be fitted with a lever action locks and D-handles of circular section, between 850mm and 1100mm from floor level.• Be color contrasted with the surrounding wall and should not be heavier than 22N to open.• Kick plates are recommended 300mm from the bottom, to resist wear and tear. • Where ever required, doors should be fitted with vision panels at least between 900mm and 1500mm from floor level.

Page 69: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

69Internal Environment

13. Accessible toiletRecommendations

• Ladies toilet - to be converted in unisexaccessible toilet as there are less women staff.

• One toilet compartment should have clearfloor space -2000mm x 2200mm minimum.

• Clear door opening of at least 900mm with thedoor swing outwards or be folding or slidingtype.

• A switch near the WC (one at 300mm and theother at 900mm from the floor level), whichactivates an emergency audio alarm (at thereception/attendants desk, etc.).

• Flooring to be anti-slip/matt finish.

U -shape moveable grab barL-shape stationary grab bar

Page 70: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

70Internal Environment

13. Water Closet & Wash Basin• Have clear space of not less than 900mm wide next to the water closet.• Be located between 460mm to 480mm from the centerline of the WC to the adjacent wall and have a clear dimension of 800mm from the edge of the WC to the rear wall to facilitate side transfer.• The top of the WC to be 450-480mm from the floor. • Grab bars at the transfer side of the WC and the adjacent wall. • On the transfer side of the WC- swing up type and on the wall side L-shape grab bars should be provided.• Wash basin- dimensions 520mm and 410mm, so mounted that the top edge is between 700mm-800mm fromthe floor; have a knee space of at least 760mm wide by 200mm deep by 650mm-680mm high.• Lever type handles for taps are recommended.• Mirror’s bottom edge to be 900-1000mm from the floor and the mirror may be inclined at an angle.• U-shape moveable grab bars are proposed on both the sides of the washbasin.

Page 71: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

71Internal Environment

14. Drinking Water

Recommendations• A lowered washbasin of dimensions 520mm and 410mm, so mounted that the top edge is between700mm-800mm from the floor; have a knee space of at least 760mm wide by 200mm deep by 650mm-680mm high.• This allows both front and parallel access to taps for students using mobility aids like wheel chair,crutches etc.• At least one tap on each floor, to be at maximum height 800mm and lever type handles for taps arerecommended.

Page 72: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

72Internal Environment

15. Controls and Operating MechanismsRecommendations

Operable part of controls such as vending machines, electrical switches, wall sockets and intercom buttons should be: • located adjacent to the clear floor space;• height between 600-1100 mm;• controls should be placed not less than 400 mm from room corners;• operable by one hand;• does not require tight grasping, pinching or twisting of the wrist; and operable with a force less than 22N.• Controls should be color-contrasted, with the surrounding face plate panel and the face plate contrasting with the background wall on which they should be mounted• The control panels /switch boards should be flushed to the wall

Page 73: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

73Internal Environment

16. Signage- Tactile MapRecommendations

• Tactile maps should be provided near the Enquiry counters which provide way-finding maps and directories.• It should include a list of officers, rooms numbers, and general building facilities locations. • It may include a tactile features/ legends with audio.• Tactile map should be marked by floor tactile guidance for persons with visual impairments to access it.

Page 74: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

74Internal Environment

16. SignageExisting• Signage are of varying colours, fonts, material and are

not strategically located• There are no Braille signage's in the entire university Life Science Department

Statistics Department

Life Science Department

Department of Law Institute of Pharmacy

Page 75: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

75

Preferred location of signage

Recommendations

Internal Environment16. Signage

Page 76: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

76Internal Environment

16. SignageRecommendations

• Floor wise key plans are proposed nextto steps.• Signage having big fonts, color contrastand well illuminated benefit everyoneparticularly persons with low vision.• Braille plates giving information offacilities etc. shall be provided on thehandrails of stairs.• Information in local language, Hindiand English: Principle names to also beindicated in Hindi and in English.• Color: Displays related to barrier-free facilities and routes to be simple and easy to distinguish. All signage displaying facilities for “Persons with Disability” to have a uniform colour (preferably blue and white).

Page 77: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

77Internal Environment

16. Signage

Braille locator

Internal way finding and directional signage

Recommendations

• Way finding signage in shall be provided at strategic locations. • Nameplates and numbers of the rooms to be in Braille & raised alphabets, bold & colour contrasted with their background. • Braille signage should be mounted between 1400-1600mm from floor level on the wall (on latch/ door handle side of all doors).• The individual characters to be between 15mm-50mm tall and raised by 1-1.5mm.

Internal way finding and directional signage

Page 78: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

78Internal Environment

16. Signage

Height and Placement

Page 79: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

79Internal Environment

General ToiletsRecommendations

• All signage to be in contrasting colours.• For visitors and employees with low vision and vision impairments- pictogram (male pictogram in triangle and female pictogram in circle), marked on plates along with Braille & raised alphabets, to be mounted on wall next to door near the latch side, at a height between 1400mm-1600mm.• Warning paver strip/ thin rubber door mat to be provided 300mm before the toilet entrances. • Availability of sanitary material and disposal mechanism in ladies toilet.

Page 80: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

80Internal Environment

Accessible UrinalsRecommendations

• At least one of the urinals in all Gents toilets on all floors should have grab bar; installed on each side andin the front to support ambulant persons with disabilities (for example, crutch users).

• Urinal rim height to be 430mm from finished floor level.• The front bar is to provide chest support; the sidebars are for the user to hold on to while standing.• There should not be any step/ level difference in front of accessible urinal.

Recommended

Page 81: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

81Internal EnvironmentColour ContrastRecommendations

Contrast colours should be provided between: • Columns in circulation area,• Critical Surfaces (walls, ceiling and floor),• Signage and background sign frame/ wall,• Step edges and risers/ treads on steps,• Handrails and background wall,• Doors and surrounding walls,• Switches/ sockets and background wall,• Toilet fixtures, accessories and background walls.

Page 82: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

82Internal Environment

17. Emergency EvacuationRecommendations

• Fire escape plan, emergency alarm both audio (hootertype) and visual (flashing bulb) to be provided at strategiclocations.

• Evacuation routes should be clearly identified. Routesshould be at least 1200mm wide, to ensure that a personusing a wheelchair and a non-disabled person are able topass each other along the route. The route should be freeof any level difference and should be kept free fromobstacles such as furniture, coolers, AC units, flower pots,etc.

• Evac chairs should be made available.

Page 83: Pandit Ravi Shankar University - disabilityaffairs.gov.indisabilityaffairs.gov.in/upload/uploadfiles/files/5_ Pt Ravi... · Pandit Ravi Shankar University ... • Staircase near new

Contact details:Ms. Anjlee Agarwal Executive Director & Access Consultant