REFRIGERANT RECOVERY UNIT

OPERATING MANUAL

TA110X-220

Twin Thunder 220

Page 2: REFRIGERANT RECOVERY UNIT OPERATING MANUAL

NOTICE FOR USE

Please read the Operation Manual carefully and follow the instructions while operating this unit.

For a long lifetime and safe running, please read this manual carefully before operating, testing

or maintaining this unit.

Please keep this manual safely.

CONTENT

GENERAL SAFETY ………………………………………………………………………1

OPERATION GUIDELINES……………………………………………………………....3

SPECIFICATIONS…………………………………………………………………………6

Introduction of Operation Panel………..……………………………….…………….....7

PARTS DIAGRAM …………………………………………………………………………8

WIRING DIAGRAM ………………………………………………………………………..9

RECOVERY METHOD……………………………………………………………………10

SELF-PURGE METHOD………………………………………………………………….11

LIQUID PUSH/PULL METHOD ………………………………………………………….12

TROUBLE SHOOTING……………………………………………………………………14

Page 3: REFRIGERANT RECOVERY UNIT OPERATING MANUAL

1 .GENERAL SAFETY

SECURITY LABELS

Warning

Warning means that mis-operation can lead to body injury.

Notice

Notice means that mis-operation can do harm to the unit and lower the performance of the unit,

or even make the unit unable to work properly.

For your better understanding of the security labels in this manual, we have listed the

content of these security labels for your reference.

Warning

Only a qualified technician should operate this recovery unit.

Warning

Before starting the equipment, be sure that it is well grounded.

Warning

While using electrical wire, the wire must be well connected and grounded.

Warning

Only a qualified electrician should do the wire connection according to

the technical standard and circuit diagram.

Warning

Be sure the power is off before examining or repairing the recovery unit.

Warning

If the original power supply cord is damaged, choose carefully for the replacing one,

or you may directly buy from us.

Warning

When the unit breaks down, be sure the power is off before you do any operation.

Warning

Please consider the current capacity of power supply, ammeter, electrical wire and socket.

Warning

Use only authorized refillable refrigerant tanks. It requires the use of recovery tanks

with a minimum working pressure of 4.0MPa(580psi). Do not overfill the recovery tank .Tank

is full at 80% capacity. There should be enough space incase liquid expansion. Overfilling

of the tank may cause a violent explosion.

Page 4: REFRIGERANT RECOVERY UNIT OPERATING MANUAL

Warning

An electric scale is needed to prevent overfilling.

Warning

Always wear safety goggles and protective gloves while working with refrigerants to

protect your skin and eye from refrigerant gases or liquid. Avoid getting in touch with

caustic gas or liquid.

Warning

Be sure that the room where you are working is thoroughly ventilated.

Notice

Be sure the unit is working under the right power supply.

Notice

When using an electric cable ,it should be a minimum 2.0mm2 AWG and no longer

than 7.5 meters, or it may cause the voltage drop and damage the compressor.

Notice

The input pressure of the unit should not exceed 2.6MPa(377psi).

Notice

The unit need to be laid horizontally, otherwise it will lead to unexpected vibration,

noise or even abrasion.

Notice

Do not expose the equipment to sun or rain.

Notice

The ventilation opening of the unit must not be blocked.

Notice

If the overload protector pops, reposition it after 5 minutes.

Notice

There is a safe valve with the recovery unit, when the high pressure switch damaged and

internal pressure above 4.0 MPa(580psi), safe valve will release pressure to ensure

safety.

Page 5: REFRIGERANT RECOVERY UNIT OPERATING MANUAL

OPERATION MANUAL

1. Do not mix different refrigerants together in one tank, or they could not be separated or used.

2. Before recovering the refrigerant, the tank should achieve the vacuum level: -75cmHg(29.6inHg), which is for purging

non-condensable gases. Each tank was full of nitrogen when it was manufactured in the factory, thus the nitrogen should be

evacuated before the first use.

3. The input and out valves must be closed, the recover/self-purge valve to position "self-purge",

the input and output fittings should be covered with protective caps when the unit is not in operation .The air moisture is harmful to

the recovery and will shorten the life span of the unit.

4. A filter drier should always be used and should be replaced frequently. And each type of refrigerant must have its own filter. For

the sake of ensuring the normal operation of the unit, please use the filter specified by our company. High quality filter drier will

bring high quality services.

5. Special-caution is needed when recovering from burnt system, and two dry filters are needed.

6. The unit has an Internal High Pressure Shut-Off Switch. If the pressure inside the system is above 3.0MPa (435psi), compressor

will automatically shut off and the red light turns on. To restart the compressor, please lower the internal pressure and press the start

button, then turn on the power to restart the compressor.

When High Pressure Protection is initiated, please find out the cause and deal with it before restarting the unit.

Cause of High Pressure Protection and Trouble Shooting:

①The input value of the refrigerant tank is closed——open the valve will help solve the problem.

②The connecting hose between the recovery unit and refrigerant tank is stuck——close all the valves and replace the

connecting hose.

③The temperature of the refrigerant tank is too high, pressure is too high——give it some time to cool down and the

pressure will come back to normal.

7. The unit has an Internal Low Pressure Shut-Off Switch and Bypass Switch. When the Bypass Switch is on“Auto”, if the

pressure inside the system is below -8inHg~ -12inHg(-20.3cmHg~-30.4cmHg), the unit will automatically shut off and the Green

Alarm Light turns on.If it needs restart the compressor, please increase the input pressure above 0.08MPa(11psi) or turn the

Bypass switch on manual and then press the start button.

8. The recovery unit must be used together with a refrigeration storage tank which is equipped with a float level sensor, before

starting the unit, please connect the 80% O.F.P. cable with the float level sensor on the tank. In the process of recovering, if the

recovered liquid refrigerant reaches 80% capacity of the tank, the recovery unit will automatically stop and the Red Alarm Light

turns on. Please change a empty tank before restart. Meanwhile, a electronic scale is required to monitor the whole process of

recovery.

9. In order to gain maximum recover speed, a hose with inner diameter bigger than 4mm is recommended and the hose should

better be shorter than 1.5m.Too narrow or too long hose will reduce the recovery rate.

Page 6: REFRIGERANT RECOVERY UNIT OPERATING MANUAL

10. While recovering large amounts of liquid, please use the Push/Pull Mode.

(See Push/Pull Mode operation on Page12)

11.After recovering, make sure there is no refrigerant left in the unit. Read the Purge Operation carefully. Liquid refrigerant

remained in the unit may be expanded and destroy the components.

12. If the unit is to be stored or not used for any length of time, we recommend that it be completely evacuated of any residual

refrigerant and purged with dry nitrogen.

13. Connection hose with check valve is recommended, it can prevent refrigerant lose.

14. The intake port is equipped with filter screen, please wash it frequently to keep it clean.

15. The Low Pressure Gauge shows the pressure of the intake port of the compressor and the High Pressure Gauge shows the

pressure of the outlet port of the recovery unit.

Page 7: REFRIGERANT RECOVERY UNIT OPERATING MANUAL

3.Specifications

Refrigerants

Category III :R-12,R-134a,R-401C,R-406A,R-500,

Category IV :R-22,R-401A,R-401B,R-402B,R-407C,R-407D,R-408A,

R-409A,R-411A,R-411B,R-412A,R-502,R-509

Category V : R-402A,R-404A,R-407A,R-407B,R-410A ,R-507

Power 220V,50Hz

Motor 1HP AC 4-pole Capacitor Start Capacitor Running

Motor speed 1450RPM

Maximal current draw 10A

Compressor Oil-less, air-cooled, piston

Automatic safety shut-off 3.0MPa (435psi)

Recovery

Rate

Category III Category IV Category V

Vapor 0.40Kg/min 0.50Kg/min 0.50Kg/min

Liquid 3.00Kg/min 3.50Kg/min 3.50Kg/min

Push/Pull 7.50Kg/min 8.50Kg/min 9.50Kg/min

Operating temperature 0~40℃

Dimensions 430mm(L)×270(W)mm×375mm(H)

Net weight 16.0 kg

Page 8: REFRIGERANT RECOVERY UNIT OPERATING MANUAL

4. Introduction of Operation Panel

Page 9: REFRIGERANT RECOVERY UNIT OPERATING MANUAL

5.PARTS DIAGRAM

NO. COMPONENT

NO. COMPONENT

1 80% O.F.P. Cable 8 Starting Capacitor

2 Front Panel 9 Fan

3 Control Valve 10 Fan Cover

4 Copper Pipes 11 Power Supply Cord

5 Junction Box Cover 12 Base

6 Compressor 13 Plastic Cover

7 Running Capacitor

Page 10: REFRIGERANT RECOVERY UNIT OPERATING MANUAL

Wiring diagram

Page 11: REFRIGERANT RECOVERY UNIT OPERATING MANUAL

7.Recovery Method

1. Turn the Input Valve Knob to position "Close", turn the Recover/Self-Purge Valve Switch

to position "Recovery", turn Bypass Switch to position "MANUAL".

2. Correctly and firmly connect the pipes (see Connection Drawing)

3. Connect the unit to the right power supply (as shown on the Name Plate), turn the power

on

4. Press the Start Button to start the unit.

5. Open the valve of recovery tank.

6. Open the liquid valve of the manifold gauge.

7. Turn the Output Valve Switch to position "ON" to recover the liquid.

8. Please turn the Bypass Switch to position "AUTO" so that the unit will automatically stop

when finished.

Notice:

① If compressor impact occurs, turn the Input Valve Switch slowly to position

"liquid" in a clockwise direction until the impact stops, don’t let the pressure

goes below to“ 0 “, otherwise the inlet mouth can’t exhaust the gas.

②If it is difficult to start or restart after power off, please turn the input

valve to position "off", turn the power on and press the Start Button to start

the unit.

9. When liquid recovery is finished, turn the input valve to position "Open" and open the

liquid valve of the manifold gauge for faster recovery.

10. The unit will automatically stop when recovery is finished, please do the purge operation

after finishing recovery.

Page 12: REFRIGERANT RECOVERY UNIT OPERATING MANUAL

8.Self-Purge Method

1.

○1 No need to turn the power off when the bypass switch turn to “MANUAL” position , turn the

Recover/Self-Purge Valve to “self-purge” position, turn the input valve to “self-purge” position to start

self-purge.

○2 When the Bypass switch is turned to “AUTO” position, After recovering the unit will automatically stop. Then turn

the Bypass Switch to “MANUAL” position, press Start Button to start the unit. Turn the Input Valve Knob to

“Self-Purge” Position, Turn the Recover/Self-Purge Valve to “Self-Purge” Position and start self-purge.

2、Run until desired vacuum is achieved or the unit is under low pressure protection the unit will automatically shut off.

The purge process is over.

① Turn off the liquid port of tank.

② Close the check valve of output hose.

③ Close the vapor and liquid ports of the manifold gauge sets.

④ Close the HVAC ports connected with the manifold gauge sets.

Recovery/Self-Purge Method Knob Diagram

CAUTION:

After each use the unit must be purge, make sure there is no refrigerant left in the unit. Liquid refrigerant remained may

expand and damage the components.

Page 13: REFRIGERANT RECOVERY UNIT OPERATING MANUAL

9.Push-Pull Method

Push/Pull method only works with large systems where the liquid refrigerant is no less than 10 Kg.

CAUTION:

While using the “push/pull” method, a electric scale must be used to avoid overfilling the recovery tank. Once the siphon is

started, it can overfill the recovery tank even if the tank is equipped with a float level sensor. The siphon can continue even if the

machine was turned off. You must manually close the valves on the tank and the unit to prevent overfilling.

1.Turn the input valve switch to “Open” position, turn the self purge valve to “self-purge” position, turn the output valve to

“Open” position .

2.Correctly and firmly connect the hoses(See Connection Drawing):

3. Turn on the power and turn the bypass switch to “MANUAL” position, press the start button

to start the unit.

Push-Pull Method Knob Diagram

Page 14: REFRIGERANT RECOVERY UNIT OPERATING MANUAL

4.Open the gas valve and liquid valve of the refrigerant tank.

5.When the showing of electric scale is not changing or changing very slowly, it means that the liquid recovery is finished, and

it’s time for gas recovery.

6.Close the gas valve of the refrigerant tank and then turn the power off.

7.Close all the valves and disconnect all the external hose. Connect the hoses according to the Recovery Operation to do the gas

refrigerant recovery.

8.Purge

CAUTION:

When the scale rises to 80% capacity of the recovery tank, turn off the power right away and close all input valves and

output valves immediately.

Page 15: REFRIGERANT RECOVERY UNIT OPERATING MANUAL

10.Trouble shooting

Fault Cause Solution

Fan not revolving Mechanical damage 1、Replace the fan

2、Factory service is needed

Compressor don't

work

1、Shut off by High Pressure

Protection

2.80%O.F.P cable and tank are not

well connected, red light on.

3.Lower pressure

protection,green light

on(Recovery is not finished.)

1、 Lower the pressure of the unit

2、 Check the connection.

3、Check if the hoses are well connected.

Compressor can't

start

(Jammed)

1、External pressure is too high

2 、 Motor failure or other

component damage

1、Lower the pressure of the unit.

2、Factory service is needed

Compressor starts

but stops within a

few minutes

1 、 High Pressure Protection

caused by mis-operation shuts

the unit off, like:

Outlet valve closed, refrigerant

tank valve closed

2、Motor Overload Protection shut

the motor off

3.80% Over Filling Protection

shut the motor off.

4.Revovery finished, green light

on.

5.Overload during liquid

recovery process, light flashes

and off.

6. circuit breaker is off.

1.Read carefully the Operation Manual and

follow the instructions while operating

2.Give the motor some time to restart

3.Follow the Purge Operation to do the

Purging

4. See Self-purge method.

5. Turn the bypass switch to “MANUAL”

position, turn input valve knob to “off”

position, then restart the unit.

6.After cooling the circuit breaker for 5

minutes, reset it.

Page 16: REFRIGERANT RECOVERY UNIT OPERATING MANUAL

Low recovery

speed

1、 The pressure of the

refrigerant tank is too high

2、 Piston ring of the compressor

is damaged

1、Cool the tank down can help bringing

down the pressure

2、Factory service is needed

Not vacuum enough

1、Hose connection loosened

2、Leakage of the unit

1、Tighten the connecting hoses

2、Factory service is needed

Warranty

Terms of Warranty

1. This product is to be repaired free of charge if a failure occurs despite proper use during the period of

warranty.

2. This warranty is valid for 1 year starting from the date of purchase.

3. In any of the following cases, this product is to be excluded from free-of-charge repair.

1) Failures incurred by improper use.

2) Failures due to handling and storage beyond its specifications.

3) Failures due to modifications or repairs not done by the manufacturer or its entrusted

technicians.

4) Failures due to consumable components.

5) Other failures not deemed to be the manufacturer’s responsibilities.

Product Name: Refrigerant Recovery Machine

Model: TA110X-220 Serial number:

Date of purchase: M: /D: /Y:

Period of warranty: For 1 year starting from M: /D: /Y:

Customer

Name:

Address:

Phone number:

Dealer

Address and name:

* To the dealer: Kindly take a few minutes and fill out the above form.

1-17-20 Inadauemachi, Higashi-Osaka City, Osaka, 577-0002, JAPAN

Phone: 81-6-6748-9310 Fax: 81-6-6748-9320

Web Site: http://www.tascojapan.co.jp/