The importance of Leak Reduction and Refrigerant Recovery Julio Esteban Smart Refrigerant S.A....
-
Upload
sandra-tyler -
Category
Documents
-
view
224 -
download
3
Transcript of The importance of Leak Reduction and Refrigerant Recovery Julio Esteban Smart Refrigerant S.A....
The importance of Leak Reduction and The importance of Leak Reduction and Refrigerant RecoveryRefrigerant Recovery
Julio EstebanJulio EstebanSmart Refrigerant S.A.Smart Refrigerant S.A.PanamáPanamá
IntroductionIntroduction
Leak tightness in compliance with regulations
Example: F-Gas Regulation (EC) 846/2006
Direct leak detection methods
Indirect leak detection methods
Recovery refrigerants from systems
Refrigerant reclaim
Leak tightness in compliance with RegulationsLeak tightness in compliance with Regulations
During service and maintenance the following actions are considered as deliberate venting:
- Venting of “surplus” refrigerant if system has been overcharged.- Venting of refrigerant instead of recovering when service is made.- Use of refrigerant as a traces for leak detection.- Breaking vacuum with refrigerant.- Use of refrigerant as pressurised gas for cleaning purposes.- Addition of refrigerant to a system known to be leaking.
Actions considered as inadvertent loss:- Leaks of refrigerant from joints, seals, gaskets before identifying the leak.- Loss of refrigerant from relief valves to prevent danger.- Loss of residual refrigerant dissolved in oil after normal recovery.- Loss of small quantities of gas from charging lines during connection and
disconnection to the system.- Loss of small quantities of gas along with NCG’s when system is purged.
F-Gas Regulation (EC) 846/2006 F-Gas Regulation (EC) 846/2006
Places duties on operators and personnel involved in manufacture, installation service and maintenance of systems containing Fluorinated greenhouse gases covered by the Kyoto Protocol.
Operators of stationary refrigeration, air conditioning and heat pump equipment shall:
1.Prevent leakage of these gases2.Repair any detected leak as soon as possible.
Operators shall ensure that systems are checked as follows:
Systems with ≥ 3 Kgs. to be checked at least once every 12 months. Systems with ≥ 30 Kgs. to be checked at least once every 6 months. Systems with ≥ 300 Kgs. to be checked at least once every 3 months.
Fixed leak detection systems must be installed in systems containing ≥ 300 Kgs. and these must be checked for proper functioning once a year.
Records on all systems must be kept, including information on type of gas, quantities recovered/added, identification of company and technician carrying out the job, dates, results of leaks inspections, etc. They must be available on request of Authorities.
Reasons to prevent leaks:
Environmental impact
Running costs. Costs will escalate as leakage reduces efficiency of system. Double impact, loss of refrigerant and higher power consumption (CO2 emissions).
Servicing costs (reparation, exchange of components, etc.)
Health and safety hazards (suffocation, intoxication, etc.)
Direct Leak detection methodsDirect Leak detection methods
FIXED REFRIGERANT LEAK DETECTORS
-Some systems commercially available on the market.-Fixed multi point systems monitor installations for refrigerant leaks continuously.-Can be configured to activate different alarms depending on the level of refrigerant detected.-Different refrigerant detection technologies available for different applications (NH3, HFCs, HCFCs, CO2, HCs, etc.)-Sensors can be placed in different areas within the installation (compressor housings, plant rooms, racks, condenser, suction/liquid filter assemblies, etc.-Different leak detection systems must be installed if there is more than one refrigerant in the installation.
Direct Leak detection methodsDirect Leak detection methods
PORTABLE REFRIGERANT LEAK DETECTORS
-Available ranges of electronic refrigerant leak detectors with sensitivity to rates as small as 3 g/yr.-Different models for different refrigerants (Halogenated, Hydrocarbons, CO2, etc.)-Operation principle: Corona discharge, heated diode, infrared, ultrasonic.-Ultraviolet indication fluids or colored dyes (not widely recommendable, first must ensure compatibility with system components). Not applicable in systems with efficient oil separation devices.-Bubble solutions. Simple but recommended to use in conjunction with the use of portable electronic detectors.
-Other leak testing methods: Pressurizing system with N2, vacuum testing, etc.
Direct Leak detection methodsDirect Leak detection methods
REFRIGERANT PORTABLE DEVICES
HC LEAK DETECTORS (FOR COMBUSTIBLE GASES)
CO2 LEAK DETECTORS
HALOGENATED REFRIGERANT LEAK DETECTORS
Indirect Leak detection methodsIndirect Leak detection methods
In addition to direct detection methods, good practice during the service and maintenance procedures by employing indirect detection techniques may identify a requirement for further direct refrigeration detection procedures to be implemented:Manual checks by analysis of one or more of the following parameters:
- Pressure- Temperature- Compressor current- Etc.
Any presumption of refrigerant loss shall be followed by a testing for leakage using a direct method. These presumptions could be:-A fixed refrigeration detection system indicates a leak.-The system produces abnormal noises, vibrations, ice, less cooling capacity.-Corrosions, oil leaks, component damage at leak points.-Indication of refrigerant loss from sight glass or level indicators.-Damage in safety switches, pressure switches, gauges, etc.
Recovering refrigerants from systemsRecovering refrigerants from systems
Once a system has been identified as having a leak, in order to effect any repair, it is necessary to remove the refrigerant.
The most effective way to remove refrigerant from systems is by means of a recovery unit transferring the refrigerant to a recovery cylinder.
Recovery units available currently in the market include units for halogenated refrigerants, units for Hydrocarbons (insulated electrically to avoid sources of ignition) and units for HFOs (R-1234yf, R32, etc.)
Zeotropic blends such as R407c, R410a, etc. must always be recovered but in case of systems with leaks, need to be checked before reuse to determine if components of the blend remain as originally, otherwise the blend must be sent for disposal.
Recovering refrigerants from systemsRecovering refrigerants from systems
Recovery unit for Halogenated refrigerants
Recovery unit for HCs and HFOs
Recovering refrigerants from systemsRecovering refrigerants from systems
RECOVERYTransfer of refrigerant from a system to a recovery cylinder.Check for reuse, recycling or reclaiming.
RECYCLINGIn a single pass at the same time of the recovery process, gas goes through an extra filter drier and an oil separator. Refrigerant is ready for re-use if there is no crossed contamination
RECLAIMINGBrings the refrigerant to a virgin state according to ARI-740 standards. Purity must be certified by gas chromatography and moisture testings.
Recovering refrigerants from systemsRecovering refrigerants from systemsRECYCLING EQUIPMENT
Built in recycling kit on a recovery unit (Recovery/Recycling unit)
Add on module for existing recovery machines:
Recovering refrigerants from systemsRecovering refrigerants from systemsRECLAIMING UNITS
Type LV
Meets all EPA certification requirements
Manufactured to customer’s specifications with options to handle different refrigerants including R12, R22, R407c, R410a… and many more
1 HP Hermetic compressor
Reclaim capacity: 1.4 kgs. Liquid per minute. Vapour slightly less.
On board storage capacity: 14 Kgs.
Recovering refrigerants from systemsRecovering refrigerants from systemsRECLAIMING UNITS
Type JV
Meets all EPA certification requirements
Manufactured to customer’s specifications with options to handle different refrigerants including R12, R22, R407c, R410a… and many more
2 HP Hermetic compressor
Reclaim capacity: 2.3 kgs. Liquid per minute. Vapour slightly less.
On board storage capacity: 40 Kgs.
Recovering refrigerants from systemsRecovering refrigerants from systems
RECLAIMING UNITS Always reclaim in batchesAscertain type of refrigerantUsing “manifold” – batch in larger cylinder, in a single passUntil moisture level comes downDuring process, draining oil and acids is important
Recovering refrigerants from systemsRecovering refrigerants from systems
ARI 700
* Sets quality levels for (reclaimed) refrigerants* Indicators are
* Moisture content* Oil content* Purity level (cross contamination)* Acid levels* Particle levels
A simple laboratory able to perform gas chromatography is recommended to verify the quality.
Julio Esteban Smart Refrigerant S.A. PANAMA Tel.: +507-60455353 Email: [email protected]
GRACIAS POR SU ATENCION !!!!
THANK YOU !!!!