REFRIGERANT RECOVERY UNIT OPERATING MANUAL
of 16
/16
Embed Size (px)
Transcript of REFRIGERANT RECOVERY UNIT OPERATING MANUAL
Twin Thunder 220
NOTICE FOR USE
Please read the Operation Manual carefully and follow the instructions while operating this unit.
For a long lifetime and safe running, please read this manual carefully before operating, testing
or maintaining this unit.
CONTENT
PARTS DIAGRAM …………………………………………………………………………8
WIRING DIAGRAM ………………………………………………………………………..9
RECOVERY METHOD……………………………………………………………………10
SELF-PURGE METHOD………………………………………………………………….11
Notice
Notice means that mis-operation can do harm to the unit and lower the performance of the unit,
or even make the unit unable to work properly.
For your better understanding of the security labels in this manual, we have listed the
content of these security labels for your reference.
Warning
Warning
Before starting the equipment, be sure that it is well grounded.
Warning
While using electrical wire, the wire must be well connected and grounded.
Warning
Only a qualified electrician should do the wire connection according to
the technical standard and circuit diagram.
Warning
Be sure the power is off before examining or repairing the recovery unit.
Warning
If the original power supply cord is damaged, choose carefully for the replacing one,
or you may directly buy from us.
Warning
When the unit breaks down, be sure the power is off before you do any operation.
Warning
Please consider the current capacity of power supply, ammeter, electrical wire and socket.
Warning
Use only authorized refillable refrigerant tanks. It requires the use of recovery tanks
with a minimum working pressure of 4.0MPa(580psi). Do not overfill the recovery tank .Tank
is full at 80% capacity. There should be enough space incase liquid expansion. Overfilling
of the tank may cause a violent explosion.
Warning
Warning
Always wear safety goggles and protective gloves while working with refrigerants to
protect your skin and eye from refrigerant gases or liquid. Avoid getting in touch with
caustic gas or liquid.
Warning
Be sure that the room where you are working is thoroughly ventilated.
Notice
Be sure the unit is working under the right power supply.
Notice
When using an electric cable it should be a minimum 2.0mm 2 AWG and no longer
than 7.5 meters, or it may cause the voltage drop and damage the compressor.
Notice
The input pressure of the unit should not exceed 2.6MPa(377psi).
Notice
The unit need to be laid horizontally, otherwise it will lead to unexpected vibration,
noise or even abrasion.
Notice
The ventilation opening of the unit must not be blocked.
Notice
If the overload protector pops, reposition it after 5 minutes.
Notice
There is a safe valve with the recovery unit, when the high pressure switch damaged and
internal pressure above 4.0 MPa(580psi), safe valve will release pressure to ensure
safety.
OPERATION MANUAL
1. Do not mix different refrigerants together in one tank, or they could not be separated or used.
2. Before recovering the refrigerant, the tank should achieve the vacuum level: -75cmHg(29.6inHg), which is for purging
non-condensable gases. Each tank was full of nitrogen when it was manufactured in the factory, thus the nitrogen should be
evacuated before the first use.
3. The input and out valves must be closed, the recover/self-purge valve to position "self-purge",
the input and output fittings should be covered with protective caps when the unit is not in operation .The air moisture is harmful to
the recovery and will shorten the life span of the unit.
4. A filter drier should always be used and should be replaced frequently. And each type of refrigerant must have its own filter. For
the sake of ensuring the normal operation of the unit, please use the filter specified by our company. High quality filter drier will
bring high quality services.
5. Special-caution is needed when recovering from burnt system, and two dry filters are needed.
6. The unit has an Internal High Pressure Shut-Off Switch. If the pressure inside the system is above 3.0MPa (435psi), compressor
will automatically shut off and the red light turns on. To restart the compressor, please lower the internal pressure and press the start
button, then turn on the power to restart the compressor.
When High Pressure Protection is initiated, please find out the cause and deal with it before restarting the unit.
Cause of High Pressure Protection and Trouble Shooting:
The input value of the refrigerant tank is closed——open the valve will help solve the problem.
The connecting hose between the recovery unit and refrigerant tank is stuck——close all the valves and replace the
connecting hose.
The temperature of the refrigerant tank is too high, pressure is too high——give it some time to cool down and the
pressure will come back to normal.
7. The unit has an Internal Low Pressure Shut-Off Switch and Bypass Switch. When the Bypass Switch is on“Auto”, if the
pressure inside the system is below -8inHg~ -12inHg(-20.3cmHg~-30.4cmHg), the unit will automatically shut off and the Green
Alarm Light turns on.If it needs restart the compressor, please increase the input pressure above 0.08MPa(11psi) or turn the
Bypass switch on manual and then press the start button.
8. The recovery unit must be used together with a refrigeration storage tank which is equipped with a float level sensor, before
starting the unit, please connect the 80% O.F.P. cable with the float level sensor on the tank. In the process of recovering, if the
recovered liquid refrigerant reaches 80% capacity of the tank, the recovery unit will automatically stop and the Red Alarm Light
turns on. Please change a empty tank before restart. Meanwhile, a electronic scale is required to monitor the whole process of
recovery.
9. In order to gain maximum recover speed, a hose with inner diameter bigger than 4mm is recommended and the hose should
better be shorter than 1.5m.Too narrow or too long hose will reduce the recovery rate.
10. While recovering large amounts of liquid, please use the Push/Pull Mode.
(See Push/Pull Mode operation on Page12)
11.After recovering, make sure there is no refrigerant left in the unit. Read the Purge Operation carefully. Liquid refrigerant
remained in the unit may be expanded and destroy the components.
12. If the unit is to be stored or not used for any length of time, we recommend that it be completely evacuated of any residual
refrigerant and purged with dry nitrogen.
13. Connection hose with check valve is recommended, it can prevent refrigerant lose.
14. The intake port is equipped with filter screen, please wash it frequently to keep it clean.
15. The Low Pressure Gauge shows the pressure of the intake port of the compressor and the High Pressure Gauge shows the
pressure of the outlet port of the recovery unit.
3.Specifications
Refrigerants
Category IV R-22R-401AR-401BR-402BR-407CR-407DR-408A
R-409AR-411AR-411BR-412AR-502R-509
Category V R-402AR-404AR-407AR-407BR-410A R-507
Power 220V,50Hz
Motor speed 1450RPM
Recovery
Rate
Vapor 0.40Kg/min 0.50Kg/min 0.50Kg/min
Liquid 3.00Kg/min 3.50Kg/min 3.50Kg/min
Push/Pull 7.50Kg/min 8.50Kg/min 9.50Kg/min
Operating temperature 0~40
Dimensions 430mm(L)×270(W)mm×375mm(H)
Net weight 16.0 kg
5.PARTS DIAGRAM
NO. COMPONENT
NO. COMPONENT
2 Front Panel 9 Fan
3 Control Valve 10 Fan Cover
4 Copper Pipes 11 Power Supply Cord
5 Junction Box Cover 12 Base
6 Compressor 13 Plastic Cover
7 Running Capacitor
Wiring diagram
7.Recovery Method
1. Turn the Input Valve Knob to position "Close", turn the Recover/Self-Purge Valve Switch
to position "Recovery", turn Bypass Switch to position "MANUAL".
2. Correctly and firmly connect the pipes (see Connection Drawing)
3. Connect the unit to the right power supply (as shown on the Name Plate), turn the power
on
5. Open the valve of recovery tank.
6. Open the liquid valve of the manifold gauge.
7. Turn the Output Valve Switch to position "ON" to recover the liquid.
8. Please turn the Bypass Switch to position "AUTO" so that the unit will automatically stop
when finished.
Notice
If compressor impact occurs, turn the Input Valve Switch slowly to position
"liquid" in a clockwise direction until the impact stops, don’t let the pressure
goes below to“ 0 “, otherwise the inlet mouth can’t exhaust the gas.
If it is difficult to start or restart after power off, please turn the input
valve to position "off", turn the power on and press the Start Button to start
the unit.
9. When liquid recovery is finished, turn the input valve to position "Open" and open the
liquid valve of the manifold gauge for faster recovery.
10. The unit will automatically stop when recovery is finished, please do the purge operation
after finishing recovery.
1
1 No need to turn the power off when the bypass switch turn to “MANUAL” position , turn the
Recover/Self-Purge Valve to “self-purge” position, turn the input valve to “self-purge” position to start
self-purge.
2 When the Bypass switch is turned to “AUTO” position, After recovering the unit will automatically stop. Then turn
the Bypass Switch to “MANUAL” position, press Start Button to start the unit. Turn the Input Valve Knob to
“Self-Purge” Position, Turn the Recover/Self-Purge Valve to “Self-Purge” Position and start self-purge.
2Run until desired vacuum is achieved or the unit is under low pressure protection the unit will automatically shut off.
The purge process is over.
Turn off the liquid port of tank.
Close the check valve of output hose.
Close the vapor and liquid ports of the manifold gauge sets.
Close the HVAC ports connected with the manifold gauge sets.
Recovery/Self-Purge Method Knob Diagram
CAUTION:
After each use the unit must be purge, make sure there is no refrigerant left in the unit. Liquid refrigerant remained may
expand and damage the components.
9.Push-Pull Method
Push/Pull method only works with large systems where the liquid refrigerant is no less than 10 Kg.
CAUTION:
While using the “push/pull” method, a electric scale must be used to avoid overfilling the recovery tank. Once the siphon is
started, it can overfill the recovery tank even if the tank is equipped with a float level sensor. The siphon can continue even if the
machine was turned off. You must manually close the valves on the tank and the unit to prevent overfilling.
1.Turn the input valve switch to “Open” position, turn the self purge valve to “self-purge” position, turn the output valve to
“Open” position .
2.Correctly and firmly connect the hoses(See Connection Drawing):
3. Turn on the power and turn the bypass switch to “MANUAL” position, press the start button
to start the unit.
Push-Pull Method Knob Diagram
4.Open the gas valve and liquid valve of the refrigerant tank.
5.When the showing of electric scale is not changing or changing very slowly, it means that the liquid recovery is finished, and
it’s time for gas recovery.
6.Close the gas valve of the refrigerant tank and then turn the power off.
7.Close all the valves and disconnect all the external hose. Connect the hoses according to the Recovery Operation to do the gas
refrigerant recovery.
8.Purge
CAUTION:
When the scale rises to 80% capacity of the recovery tank, turn off the power right away and close all input valves and
output valves immediately.
2Factory service is needed
Compressor don't
Protection
well connected, red light on.
3.Lower pressure
protection,green light
2 Check the connection.
Compressor can't
2 Motor failure or other
component damage
2Factory service is needed
Compressor starts
the motor off
1.Read carefully the Operation Manual and
follow the instructions while operating
2.Give the motor some time to restart
3.Follow the Purge Operation to do the
Purging
position, then restart the unit.
6.After cooling the circuit breaker for 5
minutes, reset it.
2 Piston ring of the compressor
is damaged
down the pressure
Not vacuum enough
Warranty
Terms of Warranty
1. This product is to be repaired free of charge if a failure occurs despite proper use during the period of
warranty.
2. This warranty is valid for 1 year starting from the date of purchase.
3. In any of the following cases, this product is to be excluded from free-of-charge repair.
1) Failures incurred by improper use.
2) Failures due to handling and storage beyond its specifications.
3) Failures due to modifications or repairs not done by the manufacturer or its entrusted
technicians.
4) Failures due to consumable components.
5) Other failures not deemed to be the manufacturer’s responsibilities.
Product Name: Refrigerant Recovery Machine
Model: TA110X-220 Serial number:
Date of purchase: M: /D: /Y:
Period of warranty: For 1 year starting from M: /D: /Y:
Customer
Name:
Address:
Address and name:
* To the dealer: Kindly take a few minutes and fill out the above form.
1-17-20 Inadauemachi, Higashi-Osaka City, Osaka, 577-0002, JAPAN
Phone: 81-6-6748-9310 Fax: 81-6-6748-9320
NOTICE FOR USE
Please read the Operation Manual carefully and follow the instructions while operating this unit.
For a long lifetime and safe running, please read this manual carefully before operating, testing
or maintaining this unit.
CONTENT
PARTS DIAGRAM …………………………………………………………………………8
WIRING DIAGRAM ………………………………………………………………………..9
RECOVERY METHOD……………………………………………………………………10
SELF-PURGE METHOD………………………………………………………………….11
Notice
Notice means that mis-operation can do harm to the unit and lower the performance of the unit,
or even make the unit unable to work properly.
For your better understanding of the security labels in this manual, we have listed the
content of these security labels for your reference.
Warning
Warning
Before starting the equipment, be sure that it is well grounded.
Warning
While using electrical wire, the wire must be well connected and grounded.
Warning
Only a qualified electrician should do the wire connection according to
the technical standard and circuit diagram.
Warning
Be sure the power is off before examining or repairing the recovery unit.
Warning
If the original power supply cord is damaged, choose carefully for the replacing one,
or you may directly buy from us.
Warning
When the unit breaks down, be sure the power is off before you do any operation.
Warning
Please consider the current capacity of power supply, ammeter, electrical wire and socket.
Warning
Use only authorized refillable refrigerant tanks. It requires the use of recovery tanks
with a minimum working pressure of 4.0MPa(580psi). Do not overfill the recovery tank .Tank
is full at 80% capacity. There should be enough space incase liquid expansion. Overfilling
of the tank may cause a violent explosion.
Warning
Warning
Always wear safety goggles and protective gloves while working with refrigerants to
protect your skin and eye from refrigerant gases or liquid. Avoid getting in touch with
caustic gas or liquid.
Warning
Be sure that the room where you are working is thoroughly ventilated.
Notice
Be sure the unit is working under the right power supply.
Notice
When using an electric cable it should be a minimum 2.0mm 2 AWG and no longer
than 7.5 meters, or it may cause the voltage drop and damage the compressor.
Notice
The input pressure of the unit should not exceed 2.6MPa(377psi).
Notice
The unit need to be laid horizontally, otherwise it will lead to unexpected vibration,
noise or even abrasion.
Notice
The ventilation opening of the unit must not be blocked.
Notice
If the overload protector pops, reposition it after 5 minutes.
Notice
There is a safe valve with the recovery unit, when the high pressure switch damaged and
internal pressure above 4.0 MPa(580psi), safe valve will release pressure to ensure
safety.
OPERATION MANUAL
1. Do not mix different refrigerants together in one tank, or they could not be separated or used.
2. Before recovering the refrigerant, the tank should achieve the vacuum level: -75cmHg(29.6inHg), which is for purging
non-condensable gases. Each tank was full of nitrogen when it was manufactured in the factory, thus the nitrogen should be
evacuated before the first use.
3. The input and out valves must be closed, the recover/self-purge valve to position "self-purge",
the input and output fittings should be covered with protective caps when the unit is not in operation .The air moisture is harmful to
the recovery and will shorten the life span of the unit.
4. A filter drier should always be used and should be replaced frequently. And each type of refrigerant must have its own filter. For
the sake of ensuring the normal operation of the unit, please use the filter specified by our company. High quality filter drier will
bring high quality services.
5. Special-caution is needed when recovering from burnt system, and two dry filters are needed.
6. The unit has an Internal High Pressure Shut-Off Switch. If the pressure inside the system is above 3.0MPa (435psi), compressor
will automatically shut off and the red light turns on. To restart the compressor, please lower the internal pressure and press the start
button, then turn on the power to restart the compressor.
When High Pressure Protection is initiated, please find out the cause and deal with it before restarting the unit.
Cause of High Pressure Protection and Trouble Shooting:
The input value of the refrigerant tank is closed——open the valve will help solve the problem.
The connecting hose between the recovery unit and refrigerant tank is stuck——close all the valves and replace the
connecting hose.
The temperature of the refrigerant tank is too high, pressure is too high——give it some time to cool down and the
pressure will come back to normal.
7. The unit has an Internal Low Pressure Shut-Off Switch and Bypass Switch. When the Bypass Switch is on“Auto”, if the
pressure inside the system is below -8inHg~ -12inHg(-20.3cmHg~-30.4cmHg), the unit will automatically shut off and the Green
Alarm Light turns on.If it needs restart the compressor, please increase the input pressure above 0.08MPa(11psi) or turn the
Bypass switch on manual and then press the start button.
8. The recovery unit must be used together with a refrigeration storage tank which is equipped with a float level sensor, before
starting the unit, please connect the 80% O.F.P. cable with the float level sensor on the tank. In the process of recovering, if the
recovered liquid refrigerant reaches 80% capacity of the tank, the recovery unit will automatically stop and the Red Alarm Light
turns on. Please change a empty tank before restart. Meanwhile, a electronic scale is required to monitor the whole process of
recovery.
9. In order to gain maximum recover speed, a hose with inner diameter bigger than 4mm is recommended and the hose should
better be shorter than 1.5m.Too narrow or too long hose will reduce the recovery rate.
10. While recovering large amounts of liquid, please use the Push/Pull Mode.
(See Push/Pull Mode operation on Page12)
11.After recovering, make sure there is no refrigerant left in the unit. Read the Purge Operation carefully. Liquid refrigerant
remained in the unit may be expanded and destroy the components.
12. If the unit is to be stored or not used for any length of time, we recommend that it be completely evacuated of any residual
refrigerant and purged with dry nitrogen.
13. Connection hose with check valve is recommended, it can prevent refrigerant lose.
14. The intake port is equipped with filter screen, please wash it frequently to keep it clean.
15. The Low Pressure Gauge shows the pressure of the intake port of the compressor and the High Pressure Gauge shows the
pressure of the outlet port of the recovery unit.
3.Specifications
Refrigerants
Category IV R-22R-401AR-401BR-402BR-407CR-407DR-408A
R-409AR-411AR-411BR-412AR-502R-509
Category V R-402AR-404AR-407AR-407BR-410A R-507
Power 220V,50Hz
Motor speed 1450RPM
Recovery
Rate
Vapor 0.40Kg/min 0.50Kg/min 0.50Kg/min
Liquid 3.00Kg/min 3.50Kg/min 3.50Kg/min
Push/Pull 7.50Kg/min 8.50Kg/min 9.50Kg/min
Operating temperature 0~40
Dimensions 430mm(L)×270(W)mm×375mm(H)
Net weight 16.0 kg
5.PARTS DIAGRAM
NO. COMPONENT
NO. COMPONENT
2 Front Panel 9 Fan
3 Control Valve 10 Fan Cover
4 Copper Pipes 11 Power Supply Cord
5 Junction Box Cover 12 Base
6 Compressor 13 Plastic Cover
7 Running Capacitor
Wiring diagram
7.Recovery Method
1. Turn the Input Valve Knob to position "Close", turn the Recover/Self-Purge Valve Switch
to position "Recovery", turn Bypass Switch to position "MANUAL".
2. Correctly and firmly connect the pipes (see Connection Drawing)
3. Connect the unit to the right power supply (as shown on the Name Plate), turn the power
on
5. Open the valve of recovery tank.
6. Open the liquid valve of the manifold gauge.
7. Turn the Output Valve Switch to position "ON" to recover the liquid.
8. Please turn the Bypass Switch to position "AUTO" so that the unit will automatically stop
when finished.
Notice
If compressor impact occurs, turn the Input Valve Switch slowly to position
"liquid" in a clockwise direction until the impact stops, don’t let the pressure
goes below to“ 0 “, otherwise the inlet mouth can’t exhaust the gas.
If it is difficult to start or restart after power off, please turn the input
valve to position "off", turn the power on and press the Start Button to start
the unit.
9. When liquid recovery is finished, turn the input valve to position "Open" and open the
liquid valve of the manifold gauge for faster recovery.
10. The unit will automatically stop when recovery is finished, please do the purge operation
after finishing recovery.
1
1 No need to turn the power off when the bypass switch turn to “MANUAL” position , turn the
Recover/Self-Purge Valve to “self-purge” position, turn the input valve to “self-purge” position to start
self-purge.
2 When the Bypass switch is turned to “AUTO” position, After recovering the unit will automatically stop. Then turn
the Bypass Switch to “MANUAL” position, press Start Button to start the unit. Turn the Input Valve Knob to
“Self-Purge” Position, Turn the Recover/Self-Purge Valve to “Self-Purge” Position and start self-purge.
2Run until desired vacuum is achieved or the unit is under low pressure protection the unit will automatically shut off.
The purge process is over.
Turn off the liquid port of tank.
Close the check valve of output hose.
Close the vapor and liquid ports of the manifold gauge sets.
Close the HVAC ports connected with the manifold gauge sets.
Recovery/Self-Purge Method Knob Diagram
CAUTION:
After each use the unit must be purge, make sure there is no refrigerant left in the unit. Liquid refrigerant remained may
expand and damage the components.
9.Push-Pull Method
Push/Pull method only works with large systems where the liquid refrigerant is no less than 10 Kg.
CAUTION:
While using the “push/pull” method, a electric scale must be used to avoid overfilling the recovery tank. Once the siphon is
started, it can overfill the recovery tank even if the tank is equipped with a float level sensor. The siphon can continue even if the
machine was turned off. You must manually close the valves on the tank and the unit to prevent overfilling.
1.Turn the input valve switch to “Open” position, turn the self purge valve to “self-purge” position, turn the output valve to
“Open” position .
2.Correctly and firmly connect the hoses(See Connection Drawing):
3. Turn on the power and turn the bypass switch to “MANUAL” position, press the start button
to start the unit.
Push-Pull Method Knob Diagram
4.Open the gas valve and liquid valve of the refrigerant tank.
5.When the showing of electric scale is not changing or changing very slowly, it means that the liquid recovery is finished, and
it’s time for gas recovery.
6.Close the gas valve of the refrigerant tank and then turn the power off.
7.Close all the valves and disconnect all the external hose. Connect the hoses according to the Recovery Operation to do the gas
refrigerant recovery.
8.Purge
CAUTION:
When the scale rises to 80% capacity of the recovery tank, turn off the power right away and close all input valves and
output valves immediately.
2Factory service is needed
Compressor don't
Protection
well connected, red light on.
3.Lower pressure
protection,green light
2 Check the connection.
Compressor can't
2 Motor failure or other
component damage
2Factory service is needed
Compressor starts
the motor off
1.Read carefully the Operation Manual and
follow the instructions while operating
2.Give the motor some time to restart
3.Follow the Purge Operation to do the
Purging
position, then restart the unit.
6.After cooling the circuit breaker for 5
minutes, reset it.
2 Piston ring of the compressor
is damaged
down the pressure
Not vacuum enough
Warranty
Terms of Warranty
1. This product is to be repaired free of charge if a failure occurs despite proper use during the period of
warranty.
2. This warranty is valid for 1 year starting from the date of purchase.
3. In any of the following cases, this product is to be excluded from free-of-charge repair.
1) Failures incurred by improper use.
2) Failures due to handling and storage beyond its specifications.
3) Failures due to modifications or repairs not done by the manufacturer or its entrusted
technicians.
4) Failures due to consumable components.
5) Other failures not deemed to be the manufacturer’s responsibilities.
Product Name: Refrigerant Recovery Machine
Model: TA110X-220 Serial number:
Date of purchase: M: /D: /Y:
Period of warranty: For 1 year starting from M: /D: /Y:
Customer
Name:
Address:
Address and name:
* To the dealer: Kindly take a few minutes and fill out the above form.
1-17-20 Inadauemachi, Higashi-Osaka City, Osaka, 577-0002, JAPAN
Phone: 81-6-6748-9310 Fax: 81-6-6748-9320