NYC Department of Education
Building Condition Assessment Survey 2019-2020
R881Architectural Inspection
Inspection Type Last EditedTime InInspectionId
PETRIDES COMPLEX - (BLDG H) - S.I., 715 OCEAN TERRACE, STATEN ISLAND, NY, 10301School:
4930 2020-07-14 08:20AM 2020-07-20 04:06PMARCHITECTURAL - ASSOCIATE
4955 2020-07-14 10:32AM 2020-07-23 06:37PMARCHITECTURAL - SENIOR
Asset DataQuestion Answer
Was the Building Fully Accessible for Inspection? Yes
Principal(s) Information
Principal Name Joanne Buckheit
Principal Organization NA
Meeting with Principal? No
Principal Feedback No Feedback from Principal
Custodian David Pedersen
Fireman Anthony Nagliocco and Thomas Bickerton
Building Square Footage 10,000
Comments on the Area (Square Feet) None
Comments on the Stories (Floors) plus Basements 1 (No Basement)
Comments on the Year Built 1967
Comments on the Student Population 0
Comments on the Staff Population NA
Comments on the Number of Classrooms 0
Weather Fair
Facade Photo
Safety City Boulevard - Northwest View
Main Entrance Photo
Facade A
Roof Photo Not taken
Have any Systems/Major Building Components been upgraded? Systems: New Roof and interior upgrades for DOE use.
Page 1 of 12 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R881Architectural InspectionYears: 2016
Have there been any New Building Additions? No New Construction
Tandem No Tandem
Leased Space? No
Priority ConditionExist
Last Year?
Priority
Category
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
No condition recorded
Structural Engineer Required
Structural
Condition Type
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
No condition recorded
Accessibility
Accessibility Status Question Response
Is the Primary or secondary entrance on an accessible route? Yes
Is the building a multi-story building? No
Do any of the following spaces exist? Classroom, Art Room, Auditorium, Cafeteria,
Computer, Gymnasiums, Library, Multipurpose Room, Science Labs
No
Are ALL occupied Spaces on the accessible route? Yes
Are there accessible toilets In the building? No
Physical Breakdown Structure Exists Complies Required DeficiencyAudio
Induction
System
Fire
Alarm
Strobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
YesExterior Entrances & Exits
NoNoExterior H/C Lifts
NoNoExterior Ramps and Railings
Interior Routes
NoNoCorridor and Lobby H/C Lifts
YesYesInterior Corridor Doors And
Hardware
YesInterior Corridors & Lobbies
NoInterior Elevators
YesInterior Lobby Doors And Hardware
NoInterior Ramps
Rooms & Spaces
NoArt Rooms
NoAuditorium
NoCafeteria
NoClassrooms
NoComputer Rooms
NoGymnasium
NoLibrary
NoMain Office
NoMulti-purpose Room
NoNurse's Office
NoPool
NoScience Lab
NoToilet Rooms (boys)
NoToilet Rooms (girls)
Toilet Rooms (staff)
Page 2 of 12 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R881Architectural Inspection
Physical Breakdown Structure Exists Complies Required DeficiencyAudio
Induction
System
Fire
Alarm
Strobe
Yes No1st Floor (Men's and
Women's)
INSUFFICIENT LATCH
CLEARENCE
WATER CLOSET
ARRANGEMENT
Building Template
Inspection
Question Response
Architectural
ATHLETIC FIELDS Does not exist
EXTERIOR Inspected
Does not existAREAWAY
InspectedAWNINGS AND CANOPIES
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existCHIMNEY
Does not existCOPING
Does not existCORNICE
InspectedDOORS
InspectedDOOR HARDWARE
Condition 3- Fair
No deficiencies recordedDeficiency
InspectedDOORS AND FRAMES
Condition 4- Between Fair and Poor
METAL:DETERIORATED DOOR AND FRAME - MAJOR
DETERIORATION
Deficiency
Deficiency Location/Instance
1Deficiency Quantity
Page 3 of 12 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R881Architectural Inspection
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Quantity Uom EACH
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade C
Violations No violations recorded
METAL:DETERIORATED DOOR - MINOR DETERIORATIONDeficiency
Deficiency Location/Instance
2Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade A
Violations No violations recorded
Does not existLINTELS
Does not existTRANSOM/SIDE LIGHT
Does not existEXTERIOR SOFFITS
InspectedEXTERIOR WALLS
SteelMaterial Type(s)
4,000Replacement Quantity
Replacement Uom S.F.
Instance on All Facades Inspected
4- Between Fair and PoorInstance Condition
Instance Quantity 4,000
Instance Quantity Uom S.F.
METAL PANEL:DAMAGED TRIMDeficiency
Page 4 of 12 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R881Architectural Inspection
Question Response
EXTERIOR
EXTERIOR WALLS
Roof Plan Reference
Elevation
Elevation Reference Facade A
25Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade C at Corner of Facade B
Violations No violations recorded
METAL PANEL:SEVERE DENTSDeficiency
Roof Plan Reference
Elevation
Elevation Reference Facade A, B and D
100Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Page 5 of 12 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R881Architectural Inspection
Question Response
EXTERIOR
EXTERIOR WALLS
Deficiency Photo 1
Facade A
Violations No violations recorded
METAL PANEL:MINOR RUSTINGDeficiency
Roof Plan Reference
Elevation
Elevation Reference Facade D
80Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade B
Violations No violations recorded
Does not existLOADING DOCK
InspectedLOUVER
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existPARAPETS
Does not existPLAZA DECK
InspectedROOF
InspectedROOFING
Replacement Quantity 10,000
Replacement Uom S.F.
InspectedLEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS
4- Between Fair and PoorCondition
DAMAGED/MISSINGDeficiency
Page 6 of 12 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R881Architectural Inspection
Question Response
EXTERIOR
ROOF
ROOFING
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS
Deficiency Location/Instance
200Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade D
Deficiency Photo 2
Corner of Facade A and B
Violations No violations recorded
Does not existROOF BARRIER
Does not existROOF CAGE
Does not existROOF FENCE
Does not existROOF HATCH/SMOKE HATCH
InspectedROOFING
Instance on Metal:Roof 1 Inspected
1- GoodInstance Condition
Instance Quantity 10,000
Instance Quantity Uom S.F.
“Does the roof have major mechanical equipment sitting on Dunnage
Steel less than 18" above the Roofing?"
No
Installation Year 2016
Source of Installation Year Documented
No deficiencies recordedDeficiency
Does not existROOFING DRAINS
InspectedSPECIALTIES
Does not existBULKHEAD/PENTHOUSE
Does not existCUPOLA/ SPIRES/ TOWERS
Does not existDORMER
Does not existDUNNAGE STEEL
Does not existROOF/GRAVITY TANK
Page 7 of 12 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R881Architectural Inspection
Question Response
EXTERIOR
ROOF
SPECIALTIES
Does not existSKYLIGHT/ROOF VENT
InspectedSTAIRS/RAMPS: EXTERIOR
Does not existBUILDING CHEEK/FLANK WALLS
Does not existRAILINGS
InspectedSTAIRS/RAMPS
Condition 3- Fair
CONCRETE:CRACKS/SPALLING - MINORDeficiency
Deficiency Location/Instance
12Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade C
Violations No violations recorded
InspectedWINDOWS
1,000Replacement Quantity
Replacement Uom S.F.
Does not existEXTERIOR GUARDS
Does not existLINTELS
InspectedWINDOWS
Material Type(s) Aluminum
Instance on Aluminum - Other:Facade B and D Inspected
5- PoorInstance Condition
Instance Quantity 1,000
Instance Quantity Uom S.F.
Installation Year 1966
Source of Installation Year Inspector Estimate
ALUMINUM - OTHER:DETERIORATEDDeficiency
Roof Plan Reference
Page 8 of 12 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R881Architectural Inspection
Question Response
EXTERIOR
WINDOWS
WINDOWS
Elevation
Elevation Reference All Facades
500Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE WINDOW
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 101 - Facade B
Violations No violations recorded
ALUMINUM - OTHER:BROKEN PANEDeficiency
Roof Plan Reference
Elevation
Elevation Reference Facade D
5Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Carpenter Shop
Violations No violations recorded
Page 9 of 12 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R881Architectural Inspection
Question Response
INTERIOR Inspected
Does not existAUDITORIUM
Does not existCAFETERIA
InspectedCLASSROOMS/CORRIDORS/ADMIN SPACES
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 3- Fair
WOOD:DETERIORATED DOORDeficiency
Room 101Deficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 101
Violations No violations recorded
InspectedFloor Finish
Condition 2- Between Good and Fair
CONCRETE:CRACKSDeficiency
Room 117Deficiency Location/Instance
25Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Violations No violations recorded
Does not existSpecialties
InspectedWalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existGYMNASIUM
InspectedINTERIOR DOOR HARDWARE
Condition 3- Fair
No deficiencies recordedDeficiency
Does not existINTERIOR GUARDS
Does not existKITCHEN
Does not existLIBRARY
Does not existLOCKER ROOM
Does not existMULTI-PURPOSE ROOM
Does not existPOOLS
Does not existSCIENCE DEMO ROOM
Does not existSCIENCE LAB
Does not existSCIENCE PREP ROOM
Does not existSHOWER ROOM
Does not existSTAIRS/RAMPS: INTERIOR
Page 10 of 12 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R881Architectural Inspection
Question Response
INTERIOR
InspectedSTRUCTURAL
InspectedCOLUMNS/BEAMS/BEARING WALLS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFLOOR STRUCTURE
Condition 3- Fair
CONCRETE SLAB ON GRADE:MINOR CRACKSDeficiency
1st FloorDeficiency Location/Instance
75Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Electrical Shop
Violations No violations recorded
InspectedFOUNDATION WALLS
Material Type(s) Concrete
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedROOF STRUCTURE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existVAULTS-BUNKERS
InspectedTOILET ROOMS - STAFF
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 5- Poor
METAL:DAMAGED LOUVERDeficiency
Room H-4Deficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room H-4
Violations No violations recorded
Page 11 of 12 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R881Architectural Inspection
Question Response
INTERIOR
TOILET ROOMS - STAFF
InspectedFloor Finish
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existTOILET ROOMS - STUDENTS
LIFE SAFETY Inspected
Does not existF.D. HOLDING AREA
Does not existSTEEL STAIRS
SITE Not required
Page 12 of 12 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)