NYC Department of Education
Building Condition Assessment Survey 2018-2019
X876Architectural Inspection
Inspection Type Last EditedTime InInspectionId
BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457School:
4946 2019-05-21 12:39PM 2019-05-21 11:14PMARCHITECTURAL - ASSOCIATE
4991 2019-05-21 08:19AM 2019-06-27 05:08PMARCHITECTURAL - SENIOR
Asset DataQuestion Answer
Was the Building Fully Accessible for Inspection? Yes
Principal(s) Information
Principal Name G. Valcing
Principal Organization Bronx Leadership Academy - Bronx
Meeting with Principal? Yes
Principal Feedback The Principal had no comments regarding the Physical building
condition at this time.
Custodian Rich Leonard
Fireman Doodnauth Mangroo
Building Square Footage 48,000
Comments on the Area (Square Feet) None
Comments on the Stories (Floors) plus Basements 2 (No Basement)
Comments on the Year Built 1930
Comments on the Student Population 595
Comments on the Staff Population 96
Comments on the Number of Classrooms 26
Weather Fair
Facade Photo
Easter Avenue - West View
Main Entrance Photo
Facade A - Webster Avenue
Page 1 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X876Architectural InspectionRoof Photo
Roof 1 - North view
Have any Systems/Major Building Components been upgraded? Systems: Complete building renovation for conversion to school
use
Years: 1997
Systems: Limited Roofing repairs
Years: 2006
Systems: Limited Interior Flooring and sub- Flooring
replacement (1st Floor Corridor at Room 102 through
109)
Years: 2015
Systems: Partial interior Door replacement.
Years: 2016
Have there been any New Building Additions? No New Construction
Tandem No Tandem
Leased Space? Yes
Year Leased 1997
Inspection Type Full Inspection
Priority ConditionExist
Last Year?
Priority
Category
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
No condition recorded
Structural Engineer Required
Structural
Condition Type
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
No condition recorded
Accessibility
Accessibility Status Question Response
Physical Breakdown Structure Exists Complies Required Deficiency
FUNCTIONAL ACCESSIBILITY
Exterior Routes
YesExterior Entrances & Exits
NoNoExterior H/C Lifts
NoNoExterior Ramps and Railings
Interior Routes
NoNoCorridor and Lobby H/C Lifts
NoNoInterior Corridor Doors And Hardware
YesInterior Corridors & Lobbies
YesYesInterior Elevators
YesInterior Lobby Doors And Hardware
Page 2 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X876Architectural Inspection
Physical Breakdown Structure Exists Complies Required Deficiency
NoInterior Ramps
Rooms & Spaces
NoArt Rooms
NoAuditorium
Cafeteria
Yes Yes1st Floor
Classrooms
Yes Yes1st - 2nd Floors
NoComputer Rooms
Gymnasium
Yes Yes1st Floor
Library
Yes YesRoom 212
Main Office
Yes YesRoom 128
NoMulti-purpose Room
Nurse's Office
Yes YesRoom 115
NoPool
Science Lab
Yes YesRooms 222, 225
Toilet Rooms (boys)
Yes Yes1st - 2nd Floors
Toilet Rooms (girls)
Yes Yes1st - 2nd Floors
Toilet Rooms (staff)
Yes Yes1st - 2nd Floors
Building Template
Inspection
Question Response
Architectural
ATHLETIC FIELDS Does not exist
Page 3 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X876Architectural Inspection
Question Response
EXTERIOR Inspected
Does not existAREAWAY
Does not existAWNINGS AND CANOPIES
Does not existCHIMNEY
InspectedCOPING
Condition 2- Between Good and Fair
METAL:DETERIORATEDDeficiency
Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE-IN-KIND
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Roof 1- Facade E
Violations No violations recorded
Does not existCORNICE
InspectedDOORS
InspectedDOOR HARDWARE
Condition 3- Fair
No deficiencies recordedDeficiency
InspectedDOORS AND FRAMES
Condition 3- Fair
ROLL-UP DOOR:DETERIORATED DOOR - MINOR
DETERIORATION
Deficiency
Deficiency Location/Instance
2Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 4 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X876Architectural Inspection
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Deficiency Photo 1
Exit 1
Violations No violations recorded
InspectedLINTELS
Condition 2- Between Good and Fair
STEEL:MINOR RUSTINGDeficiency
Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom L.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Exit 4
Violations No violations recorded
Does not existTRANSOM/SIDE LIGHT
InspectedEXTERIOR SOFFITS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedEXTERIOR WALLS
Masonry, OtherMaterial Type(s)
21,000Replacement Quantity
Replacement Uom S.F.
Instance on Concrete Stucco Cement on Masonry - All Facades Inspected
2- Between Good and FairInstance Condition
Instance Quantity 21,000
Instance Quantity Uom S.F.
BRICK:DETERIORATED MASONRY SILLSDeficiency
Page 5 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X876Architectural Inspection
Question Response
EXTERIOR
EXTERIOR WALLS
Roof Plan Reference
Elevation
Elevation Reference Facade A
40Deficiency Quantity
Quantity Uom L.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade A
Violations No violations recorded
STUCCO CEMENT SURFACE:CRACKS, SPALLINGDeficiency
Roof Plan Reference
Elevation
Elevation Reference Facades A, D, F, H
15Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 6 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X876Architectural Inspection
Question Response
EXTERIOR
EXTERIOR WALLS
Deficiency Photo 1
Above Exit 1
Violations No violations recorded
Does not existLOADING DOCK
InspectedLOUVER
Condition 2- Between Good and Fair
BROKEN/ DENTED BLADESDeficiency
Roof Plan Reference
Elevation
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade F
Violations No violations recorded
InspectedPARAPETS
OtherMaterial Type(s)
4,500Replacement Quantity
Replacement Uom C.F.
Instance on Stucco over CMU Inspected
2- Between Good and FairInstance Condition
Instance Quantity 4,500
Instance Quantity Uom CF
No deficiencies recordedDeficiency
Does not existPLAZA DECK
InspectedROOF
Page 7 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X876Architectural Inspection
Question Response
EXTERIOR
ROOF
InspectedROOFING
Replacement Quantity 28,000
Replacement Uom S.F.
InspectedLEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedROOF BARRIER
4- Between Fair and PoorCondition
CHAIN LINK:DETERIORATED, MAJOR RUSTINGDeficiency
Deficiency Location/Instance
120Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Roof 1 perimeter
Violations No violations recorded
Does not existROOF CAGE
Does not existROOF FENCE
Does not existROOF HATCH/SMOKE HATCH
InspectedROOFING
Instance on Modified Bitumen:All Roofs Inspected
3- FairInstance Condition
Instance Quantity 28,000
Instance Quantity Uom S.F.
“Does the roof have major mechanical equipment sitting on Dunnage
Steel less than 18" above the Roofing?"
No
Installation Year 2008
Source of Installation Year Documented
MODIFIED BITUMEN:ROOFING:DELAMINATIONDeficiency
Deficiency Location/Instance
200Deficiency Quantity
Quantity Uom S.F.
Page 8 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X876Architectural Inspection
Question Response
EXTERIOR
ROOF
ROOFING
ROOFING
Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENT
REMOVAL
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Roof 1( all over the roof)
Violations No violations recorded
MODIFIED BITUMEN:FLASHING:BASE FLASHING
DETERIORATED
Deficiency
Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Roof 1
Violations No violations recorded
InspectedROOFING DRAINS
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedSPECIALTIES
InspectedBULKHEAD/PENTHOUSE
4- Between Fair and PoorCondition
BULKHEAD/PENTHOUSE
WALLS/EXTERIOR:CRACKS/SPALLING - MINOR
Deficiency
Page 9 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X876Architectural Inspection
Question Response
EXTERIOR
ROOF
SPECIALTIES
BULKHEAD/PENTHOUSE
Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Bulkhead
Violations No violations recorded
BULKHEAD/PENTHOUSE WALLS/INTERIOR:CMU OPEN
JOINTS
Deficiency
Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPOINT
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Bulkhead
Violations No violations recorded
BULKHEAD/PENTHOUSE DOORS:DETERIORATED DOOR
AND FRAME
Deficiency
Page 10 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X876Architectural Inspection
Question Response
EXTERIOR
ROOF
SPECIALTIES
BULKHEAD/PENTHOUSE
Deficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE DOOR AND FRAME
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
BH
Violations No violations recorded
Does not existCUPOLA/ SPIRES/ TOWERS
Does not existDORMER
InspectedDUNNAGE STEEL
4- Between Fair and PoorCondition
MINOR RUSTINGDeficiency
Deficiency Location/Instance
200Deficiency Quantity
Quantity Uom L.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Roof 1 Dunnage
Violations No violations recorded
Does not existROOF/GRAVITY TANK
Does not existSKYLIGHT/ROOF VENT
Does not existSTAIRS/RAMPS: EXTERIOR
Page 11 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X876Architectural Inspection
Question Response
EXTERIOR
InspectedWINDOWS
4,000Replacement Quantity
Replacement Uom S.F.
InspectedEXTERIOR GUARDS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedLINTELS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWINDOWS
Material Type(s) Aluminum
Instance on Aluminum - Double Hung:All Facades Inspected
3- FairInstance Condition
Instance Quantity 4,000
Instance Quantity Uom S.F.
Installation Year 1996
Source of Installation Year Documented
ALUMINUM - DOUBLE HUNG:DETERIORATEDDeficiency
Roof Plan Reference
Elevation
Elevation Reference All Facades
50Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE WINDOW
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Violations No violations recorded
INTERIOR Inspected
Does not existAUDITORIUM
CAFETERIA
Instance on 1st Floor Inspected
Ceiling
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 1st Floor Inspected
5- PoorInstance Condition
WOOD:DETERIORATED DOORDeficiency
EntrancesDeficiency Location/Instance
3Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
Page 12 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X876Architectural Inspection
Question Response
INTERIOR
CAFETERIA
Door(s)
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Entrance
Violations No violations recorded
Fixed Equipment
Instance on 1st Floor Does not exist
Floor Finish
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Sliding-folding Partition
Instance on 1st Floor Does not exist
Stage
Instance on 1st Floor Does not exist
Walls
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Window Curtains/Shades/Blinds
Instance on 1st Floor Does not exist
InspectedCLASSROOMS/CORRIDORS/ADMIN SPACES
InspectedCeiling
Condition 2- Between Good and Fair
TECTUM:DAMAGED/MISSINGDeficiency
Corridor near Room 126, Rooms 102, 128, 208, 222 and other
Locations
Deficiency Location/Instance
60Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 222
Violations No violations recorded
InspectedDoor(s)
Condition 5- Poor
WOOD:DETERIORATED DOORDeficiency
Page 13 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X876Architectural Inspection
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Door(s)
Rooms 105, 203, 213, 215Deficiency Location/Instance
5Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 203
Violations No violations recorded
METAL:DETERIORATED DOORDeficiency
Room 217Deficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 217
Violations No violations recorded
InspectedFloor Finish
Condition 2- Between Good and Fair
VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency
Rooms 222, 237, Corridor near Rooms 119, 123, 225, and other
Locations
Deficiency Location/Instance
400Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Corridor near Room 123
Violations No violations recorded
Page 14 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X876Architectural Inspection
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
InspectedSpecialties
InspectedClassroom Locker(s)
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existFixed Seating
InspectedWalls
Condition 2- Between Good and Fair
GYPSUM BOARD:DETERIORATEDDeficiency
Corridor near Rooms 107, 108, 202, 212 and other LocationsDeficiency Location/Instance
85Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Corridor near Room 212
Violations No violations recorded
GYMNASIUM
Instance on 1st Floor Inspected
Ceiling
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 1st Floor Inspected
4- Between Fair and PoorInstance Condition
METAL:DAMAGED LOUVERDeficiency
Rooms 111B, 111 CDeficiency Location/Instance
2Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 111B
Violations No violations recorded
Fixed Equipment
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
Page 15 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X876Architectural Inspection
Question Response
INTERIOR
GYMNASIUM
Fixed Equipment
No deficiencies recordedDeficiency
Floor Finish
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Seating
Instance on 1st Floor Does not exist
Sliding-folding Partition
Instance on 1st Floor Does not exist
Stage
Instance on 1st Floor Does not exist
Walls
Instance on 1st Floor Inspected
3- FairInstance Condition
WALL PADDING:DETERIORATEDDeficiency
North, South, East, West Sides of RoomDeficiency Location/Instance
140Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
West Side of Room
Violations No violations recorded
PLASTER:CRACKS/SPALLINGDeficiency
West Side of RoomDeficiency Location/Instance
100Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
West Side of Room
Violations No violations recorded
GYPSUM BOARD:DETERIORATEDDeficiency
Near Drinking FountainDeficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Page 16 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X876Architectural Inspection
Question Response
INTERIOR
GYMNASIUM
Walls
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Drinking Fountain
Violations No violations recorded
MASONRY:CRACKS/SPALLINGDeficiency
North, East Sides of RoomDeficiency Location/Instance
260Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
East Side of Room
Violations No violations recorded
Window Curtains/Shades/Blinds
Instance on 1st Floor Does not exist
InspectedINTERIOR DOOR HARDWARE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedINTERIOR GUARDS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
KITCHEN
Instance on 1st Floor Inspected
Ceiling
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
METAL PAN:DAMAGED/MISSINGDeficiency
Near Room 137D, OfficeDeficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 17 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X876Architectural Inspection
Question Response
INTERIOR
KITCHEN
Ceiling
Deficiency Photo 1
Near Room 137D
Violations No violations recorded
ACOUSTIC TILES:DAMAGED/MISSINGDeficiency
Room 137DDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 137D
Violations No violations recorded
Door(s)
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
CONCRETE:CRACKSDeficiency
Room 137DDeficiency Location/Instance
15Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 137D
Violations No violations recorded
Walls
Page 18 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X876Architectural Inspection
Question Response
INTERIOR
KITCHEN
Walls
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
LIBRARY
Instance on Room 212 Inspected
Built-in Furnishing
Instance on Room 212 Does not exist
Ceiling
Instance on Room 212 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on Room 212 Inspected
4- Between Fair and PoorInstance Condition
WOOD:DETERIORATED DOORDeficiency
EntranceDeficiency Location/Instance
2Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Entrance
Violations No violations recorded
Floor Finish
Instance on Room 212 Inspected
2- Between Good and FairInstance Condition
VINYL TILES:DETERIORATED SUBSTRATEDeficiency
Center of RoomDeficiency Location/Instance
40Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Center of Room
Violations No violations recorded
Walls
Page 19 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X876Architectural Inspection
Question Response
INTERIOR
LIBRARY
Walls
Instance on Room 212 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
LOCKER ROOM
Instance on 1st Floor - Boys (75 Lockers) Inspected
NoAlternative Use
Instance on 1st Floor - Girls (72 Lockers) Inspected
NoAlternative Use
Ceiling
Instance on 1st Floor - Boys (75 Lockers) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on 1st Floor - Girls (72 Lockers) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 1st Floor - Boys (75 Lockers) Inspected
3- FairInstance Condition
METAL:DAMAGED LOUVERDeficiency
EntranceDeficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Entrance
Violations No violations recorded
Instance on 1st Floor - Girls (72 Lockers) Inspected
3- FairInstance Condition
METAL:DAMAGED LOUVERDeficiency
EntranceDeficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Page 20 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X876Architectural Inspection
Question Response
INTERIOR
LOCKER ROOM
Door(s)
Entrance
Violations No violations recorded
Floor Finish
Instance on 1st Floor - Boys (75 Lockers) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on 1st Floor - Girls (72 Lockers) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Locker Room Lockers
Instance on 1st Floor - Boys (75 Lockers) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on 1st Floor - Girls (72 Lockers) Inspected
2- Between Good and FairInstance Condition
DAMAGED UNITSDeficiency
Locker 15Deficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Locker 15
Violations No violations recorded
Walls
Instance on 1st Floor - Boys (75 Lockers) Inspected
2- Between Good and FairInstance Condition
GYPSUM BOARD:DETERIORATEDDeficiency
Near EntranceDeficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Entrance
Violations No violations recorded
Page 21 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X876Architectural Inspection
Question Response
INTERIOR
LOCKER ROOM
Walls
Instance on 1st Floor - Girls (72 Lockers) Inspected
2- Between Good and FairInstance Condition
GYPSUM BOARD:DETERIORATEDDeficiency
Near EntranceDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Entrance
Violations No violations recorded
Does not existMULTI-PURPOSE ROOM
Does not existPOOLS
SCIENCE DEMO ROOM
Instance on Room 223 Inspected
NoAlternative Use
Instance on Room 224 Inspected
NoAlternative Use
Fixed Equipment
Instance on Room 223 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room 224 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
SCIENCE LAB
Instance on Room 222 Inspected
NoAlternative Use
Instance on Room 225 Inspected
NoAlternative Use
Fixed Equipment
Instance on Room 222 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room 225 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
SCIENCE PREP ROOM
Instance on Room 227 Inspected
NoAlternative Use
Fixed Equipment
Instance on Room 227 Inspected
2- Between Good and FairInstance Condition
Page 22 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X876Architectural Inspection
Question Response
INTERIOR
SCIENCE PREP ROOM
Fixed Equipment
No deficiencies recordedDeficiency
Does not existSHOWER ROOM
InspectedSTAIRS/RAMPS: INTERIOR
Do Letter Stair Signs Exist? 1
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 2- Between Good and Fair
METAL:DAMAGED LOUVERDeficiency
Stair A/1Deficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Stair A/1
Violations No violations recorded
Does not existPartition
InspectedRailings
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStairs and Landings
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWalls
Condition 2- Between Good and Fair
MASONRY:CRACKS/SPALLINGDeficiency
Stair C/1Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Stair C/1
Violations No violations recorded
Page 23 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X876Architectural Inspection
Question Response
INTERIOR
InspectedSTRUCTURAL
InspectedCOLUMNS/BEAMS/BEARING WALLS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFLOOR STRUCTURE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFOUNDATION WALLS
Material Type(s) Masonry
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedROOF STRUCTURE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existVAULTS-BUNKERS
InspectedTOILET ROOMS - STAFF
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFloor Finish
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedTOILET ROOMS - STUDENTS
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 5- Poor
WOOD:DAMAGED LOUVERDeficiency
Rooms 117, 118, 210, 211, 112ADeficiency Location/Instance
5Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 210
Page 24 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X876Architectural Inspection
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Door(s)
Violations No violations recorded
METAL:MISSING DOORDeficiency
Boys Locker RoomDeficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Boys Locker Room
Violations No violations recorded
InspectedFloor Finish
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStalls
Condition 3- Fair
BROKEN/MISSINGDeficiency
Boys Locker RoomDeficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Boys Locker Room
Violations No violations recorded
InspectedWalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
LIFE SAFETY Inspected
Does not existF.D. HOLDING AREA
Does not existSTEEL STAIRS
SITE Inspected
Does not existCONTAINERIZATION
Does not existDRAINAGE SYSTEM FOR ASPHALT
Does not existDRAINAGE SYSTEM FOR CONCRETE
Does not existDRAINAGE SYSTEM FOR SOIL
Does not existDRINKING FOUNTAINS
Page 25 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X876Architectural Inspection
Question Response
SITE
Does not existFENCES
Does not existIRRIGATION SYSTEM
InspectedPAVING
InspectedDOT Sidewalk
Does not existAsphalt
InspectedConcrete
3- FairCondition
DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency
Along Webster Avenue, East 172nd StreetDeficiency Location/Instance
425Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along Webster Avenue
Violations No violations recorded
Does not existPavers
InspectedSite Sidewalks & Walkways
Does not existAsphalt
InspectedConcrete
2- Between Good and FairCondition
CRACKS - MAJORDeficiency
Main EntranceDeficiency Location/Instance
15Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Main Entrance
Violations No violations recorded
Does not existPavers
Does not existStudent Non-Use
Does not existStudent Use
Does not existPLAYGROUNDS
Does not existPLAYING SURFACE
Does not existRETAINING WALLS
Does not existSEATING
Does not existSITE WALLS (NOT RETAINING WALLS)
Page 26 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X876Architectural Inspection
Question Response
SITE
Does not existSTAIRS/RAMPS: EXTERIOR
Page 27 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)