Download - DRAWING MUST BE VIEWED IN ADOBE READER TO ENABLE … · notes: 1. soprema detail drawings: refer to soprema and other related published documentation, product data sheets (pds) and

Transcript
Page 1: DRAWING MUST BE VIEWED IN ADOBE READER TO ENABLE … · notes: 1. soprema detail drawings: refer to soprema and other related published documentation, product data sheets (pds) and

THERMAL BARRIERTHERMAL BARRIER

PROJECT:

TITLE:

DRAWN BY: SOPREMA TECHNICAL SUPPORT, GGALLOWAY

NO.: DATE:REVISION:

DATE: 7.8.2015

SCALE: NTS

DRAWING NUMBER:

US.RSBS.03.04PARAPET WALL WITH METAL COPING

USAGE OF THIS DETAIL IS GOVERNED BY THE TERMS OF SERVICE FOR SOPREMA DETAILS.PLEASE CONSULT THESE TERMS OF SERVICE PRIOR TO UTILIZING THIS DRAWING.

US CORPORATE ADDRESS310 QUADRAL DRIVE

WADSWORTH, OHIO 44281www.soprema.usTel:330.334.0066

W I L L I A M G R A N T G A L L O W A Y

DRAWING MUST BE VIEWED IN ADOBE READER TO ENABLE CUSTOM LAYERING

NOTES:1. SOPREMA DETAIL DRAWINGS: REFER TO SOPREMA AND OTHER RELATED PUBLISHED DOCUMENTATION, PRODUCT DATA SHEETS (PDS) AND SAFETY DATA SHEETS (SDS) FOR ADDITIONAL

INFORMATION. ALL DETAIL DRAWINGS AND RELATED INSTALLATION GUIDELINES ARE PROVIDED BY SOPREMA FOR THE SOLE PURPOSE OF ISSUING A SOPREMA WARRANTY. ACCORDINGLY, THEDETAIL DRAWINGS ARE NOT OFFERED, AND SHOULD NOT BE CONSIDERED, AS A SUBSTITUTE FOR PROFESSIONAL DESIGN SERVICES.

2. HOT WORK: THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING APPROPRIATE CONDITIONS TO UTILIZE HEAT-WELDING EQUIPMENT. REFER TO THE NRCA CERTA RECOMMENDATIONS, LOCALCODES AND BUILDING OWNER'S REQUIREMENTS FOR HOT WORK OPERATIONS.

3. PRIMER: WHERE NOT SHOWN OR INDICATED ON DETAIL DRAWINGS, REFER TO MATERIAL PRODUCT DATA SHEETS FOR PRIMER APPLICATION REQUIREMENTS4. FLASHING PLIES MUST EXTEND VERTICALLY A MINIMUM OF 8" FROM ROOF SURFACE. FLASHING PLIES EXTENDING VERTICALLY MORE THAN 24" FROM ROOF SURFACE MUST BE ADHERED AND

MECHANICALLY FASTENED ALONG THE TOP LEADING EDGE. REFER TO PUBLISHED DOCUMENTATION.5. FOR 90° TRANSITIONS, FLASHING PLIES MUST MEET THE FOLLOWING REQUIREMENTS: HEAT WELD POLYESTER REINFORCED FLASHING BASE PLIES. HEAT WELD POLYESTER REINFORCED

GRANULE FLASHING CAP SHEET, OR HEAT WELD FOIL/FILM CLAD FLASHING CAP SHEET.

EXTEND FLASHING BASE PLY AMINIMUM OF 3" BEYOND BASE OF CANT

CANT

WEATHERPROOF MEMBRANE

ROOF EDGE SYSTEM

EXTEND FLASHING CAP SHEET AMINIMUM OF 1" BEYOND FLASHING BASE PLY

EXTEND FLASHING BASE PLY AMINIMUM OF 3" BEYOND BASE OF WALL

EXTEND FLASHING CAP SHEET AMINIMUM OF 1" BEYOND FLASHING BASE PLY

REMOVE/EMBED SURFACING AS REQUIREDREMOVE/EMBED SURFACING AS REQUIRED

FLASHING CAP SHEETFLASHING CAP SHEET

POLYESTER REINFOREDFLASHING BASE PLYPOLYESTER REINFOREDFLASHING BASE PLY

CAP SHEETCAP SHEET

BASE PLYBASE PLY

COVERBOARD

BASE SHEET/ANCHOR SHEET

VAPOR RETARDER/AIR BARRIERDECKDECKDECKDECKDECKDECKDECKDECK

FASTEN AT 8" O.C.ALONG TOP LEADING EDGE

FASTEN AT 8" O.C.ALONG TOP LEADING EDGE

2 PLY SBS MEMBRANE, INSULATED

EXTEND FLASHING BASE PLY AMINIMUM OF 3" BEYOND FASTENER PLATE

EXTEND FLASHING CAP SHEET AMINIMUM OF 1" BEYOND FLASHING BASE PLY

INSTALL FASTENER PLATE A MINIMUMOF 1" FROM WALL AND SPACED A

MAXIMUM OF 12" APART ALONG WALL

EXTEND FLASHING BASE PLY AMINIMUM OF 3" BEYOND FASTENER PLATE

EXTEND FLASHING CAP SHEET AMINIMUM OF 1" BEYOND FLASHING BASE PLY

INSTALL FASTENER PLATE A MINIMUMOF 1" FROM CANT AND SPACED A

MAXIMUM OF 12" APART ALONG WALL

BASE SHEET/ANCHOR SHEET

THERMAL BARRIER

INSULATION

INSULATION

INSULATION

INSULATIONEXTEND VAPOR RETARDER/AIR BARRIERA MINIMUM OF 3" BEYOND BASE OF WALL

VAPOR RETARDER/AIR BARRIER

FASTEN AT 8" O.C. INBOTH DIRECTIONS

FASTEN AT 8" O.C. INBOTH DIRECTIONS

BASE SHEET/ANCHOR SHEETBASE SHEET/ANCHOR SHEET