THERMAL BARRIER THERMAL BARRIER PROJECT: TITLE: DRAWN BY: SOPREMA TECHNICAL SUPPORT, GGALLOWAY NO.: DATE: REVISION: DATE: 7.8.2015 SCALE: NTS DRAWING NUMBER: US.RSBS.03.04 PARAPET WALL WITH METAL COPING USAGE OF THIS DETAIL IS GOVERNED BY THE TERMS OF SERVICE FOR SOPREMA DETAILS. PLEASE CONSULT THESE TERMS OF SERVICE PRIOR TO UTILIZING THIS DRAWING. US CORPORATE ADDRESS 310 QUADRAL DRIVE WADSWORTH, OHIO 44281 www.soprema.us Tel:330.334.0066 WI LLI AM GRANT GALLOWAY DRAWING MUST BE VIEWED IN ADOBE READER TO ENABLE CUSTOM LAYERING NOTES: 1. SOPREMA DETAIL DRAWINGS: REFER TO SOPREMA AND OTHER RELATED PUBLISHED DOCUMENTATION, PRODUCT DATA SHEETS (PDS) AND SAFETY DATA SHEETS (SDS) FOR ADDITIONAL INFORMATION. ALL DETAIL DRAWINGS AND RELATED INSTALLATION GUIDELINES ARE PROVIDED BY SOPREMA FOR THE SOLE PURPOSE OF ISSUING A SOPREMA WARRANTY. ACCORDINGLY, THE DETAIL DRAWINGS ARE NOT OFFERED, AND SHOULD NOT BE CONSIDERED, AS A SUBSTITUTE FOR PROFESSIONAL DESIGN SERVICES. 2. HOT WORK: THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING APPROPRIATE CONDITIONS TO UTILIZE HEAT-WELDING EQUIPMENT. REFER TO THE NRCA CERTA RECOMMENDATIONS, LOCAL CODES AND BUILDING OWNER'S REQUIREMENTS FOR HOT WORK OPERATIONS. 3. PRIMER: WHERE NOT SHOWN OR INDICATED ON DETAIL DRAWINGS, REFER TO MATERIAL PRODUCT DATA SHEETS FOR PRIMER APPLICATION REQUIREMENTS 4. FLASHING PLIES MUST EXTEND VERTICALLY A MINIMUM OF 8" FROM ROOF SURFACE. FLASHING PLIES EXTENDING VERTICALLY MORE THAN 24" FROM ROOF SURFACE MUST BE ADHERED AND MECHANICALLY FASTENED ALONG THE TOP LEADING EDGE. REFER TO PUBLISHED DOCUMENTATION. 5. )25 75$16,7,216 )/$6+,1* 3/,(6 0867 0((7 7+( )2//2:,1* 5(48,5(0(176 +($7 :(/' 32/<(67(5 5(,1)25&(' )/$6+,1* %$6( 3/,(6 +($7 :(/' 32/<(67(5 5(,1)25&(' GRANULE FLASHING CAP SHEET, OR HEAT WELD FOIL/FILM CLAD FLASHING CAP SHEET. EXTEND FLASHING BASE PLY A MINIMUM OF 3" BEYOND BASE OF CANT CANT WEATHERPROOF MEMBRANE ROOF EDGE SYSTEM EXTEND FLASHING CAP SHEET A MINIMUM OF 1" BEYOND FLASHING BASE PLY EXTEND FLASHING BASE PLY A MINIMUM OF 3" BEYOND BASE OF WALL EXTEND FLASHING CAP SHEET A MINIMUM OF 1" BEYOND FLASHING BASE PLY REMOVE/EMBED SURFACING AS REQUIRED REMOVE/EMBED SURFACING AS REQUIRED FLASHING CAP SHEET FLASHING CAP SHEET POLYESTER REINFORED FLASHING BASE PLY POLYESTER REINFORED FLASHING BASE PLY CAP SHEET CAP SHEET BASE PLY BASE PLY COVERBOARD BASE SHEET/ANCHOR SHEET VAPOR RETARDER/AIR BARRIER DECK DECK DECK DECK DECK DECK DECK DECK FASTEN AT 8" O.C. ALONG TOP LEADING EDGE FASTEN AT 8" O.C. ALONG TOP LEADING EDGE 2 PLY SBS MEMBRANE, INSULATED EXTEND FLASHING BASE PLY A MINIMUM OF 3" BEYOND FASTENER PLATE EXTEND FLASHING CAP SHEET A MINIMUM OF 1" BEYOND FLASHING BASE PLY INSTALL FASTENER PLATE A MINIMUM OF 1" FROM WALL AND SPACED A MAXIMUM OF 12" APART ALONG WALL EXTEND FLASHING BASE PLY A MINIMUM OF 3" BEYOND FASTENER PLATE EXTEND FLASHING CAP SHEET A MINIMUM OF 1" BEYOND FLASHING BASE PLY INSTALL FASTENER PLATE A MINIMUM OF 1" FROM CANT AND SPACED A MAXIMUM OF 12" APART ALONG WALL BASE SHEET/ANCHOR SHEET THERMAL BARRIER INSULATION INSULATION INSULATION INSULATION EXTEND VAPOR RETARDER/AIR BARRIER A MINIMUM OF 3" BEYOND BASE OF WALL VAPOR RETARDER/AIR BARRIER FASTEN AT 8" O.C. IN BOTH DIRECTIONS FASTEN AT 8" O.C. IN BOTH DIRECTIONS BASE SHEET/ANCHOR SHEET BASE SHEET/ANCHOR SHEET

Transcript of DRAWING MUST BE VIEWED IN ADOBE READER TO ENABLE … · notes: 1. soprema detail drawings: refer to...

Page 1: DRAWING MUST BE VIEWED IN ADOBE READER TO ENABLE … · notes: 1. soprema detail drawings: refer to soprema and other related published documentation, product data sheets (pds) and

THERMAL BARRIERTHERMAL BARRIER

PROJECT:

TITLE:

DRAWN BY: SOPREMA TECHNICAL SUPPORT, GGALLOWAY

NO.: DATE:REVISION:

DATE: 7.8.2015

SCALE: NTS

DRAWING NUMBER:

US.RSBS.03.04PARAPET WALL WITH METAL COPING

USAGE OF THIS DETAIL IS GOVERNED BY THE TERMS OF SERVICE FOR SOPREMA DETAILS.PLEASE CONSULT THESE TERMS OF SERVICE PRIOR TO UTILIZING THIS DRAWING.

US CORPORATE ADDRESS310 QUADRAL DRIVE

WADSWORTH, OHIO 44281www.soprema.usTel:330.334.0066

W I L L I A M G R A N T G A L L O W A Y

DRAWING MUST BE VIEWED IN ADOBE READER TO ENABLE CUSTOM LAYERING

NOTES:1. SOPREMA DETAIL DRAWINGS: REFER TO SOPREMA AND OTHER RELATED PUBLISHED DOCUMENTATION, PRODUCT DATA SHEETS (PDS) AND SAFETY DATA SHEETS (SDS) FOR ADDITIONAL

INFORMATION. ALL DETAIL DRAWINGS AND RELATED INSTALLATION GUIDELINES ARE PROVIDED BY SOPREMA FOR THE SOLE PURPOSE OF ISSUING A SOPREMA WARRANTY. ACCORDINGLY, THEDETAIL DRAWINGS ARE NOT OFFERED, AND SHOULD NOT BE CONSIDERED, AS A SUBSTITUTE FOR PROFESSIONAL DESIGN SERVICES.

2. HOT WORK: THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING APPROPRIATE CONDITIONS TO UTILIZE HEAT-WELDING EQUIPMENT. REFER TO THE NRCA CERTA RECOMMENDATIONS, LOCALCODES AND BUILDING OWNER'S REQUIREMENTS FOR HOT WORK OPERATIONS.

3. PRIMER: WHERE NOT SHOWN OR INDICATED ON DETAIL DRAWINGS, REFER TO MATERIAL PRODUCT DATA SHEETS FOR PRIMER APPLICATION REQUIREMENTS4. FLASHING PLIES MUST EXTEND VERTICALLY A MINIMUM OF 8" FROM ROOF SURFACE. FLASHING PLIES EXTENDING VERTICALLY MORE THAN 24" FROM ROOF SURFACE MUST BE ADHERED AND

MECHANICALLY FASTENED ALONG THE TOP LEADING EDGE. REFER TO PUBLISHED DOCUMENTATION.5. FOR 90° TRANSITIONS, FLASHING PLIES MUST MEET THE FOLLOWING REQUIREMENTS: HEAT WELD POLYESTER REINFORCED FLASHING BASE PLIES. HEAT WELD POLYESTER REINFORCED

GRANULE FLASHING CAP SHEET, OR HEAT WELD FOIL/FILM CLAD FLASHING CAP SHEET.

EXTEND FLASHING BASE PLY AMINIMUM OF 3" BEYOND BASE OF CANT

CANT

WEATHERPROOF MEMBRANE

ROOF EDGE SYSTEM

EXTEND FLASHING CAP SHEET AMINIMUM OF 1" BEYOND FLASHING BASE PLY

EXTEND FLASHING BASE PLY AMINIMUM OF 3" BEYOND BASE OF WALL

EXTEND FLASHING CAP SHEET AMINIMUM OF 1" BEYOND FLASHING BASE PLY

REMOVE/EMBED SURFACING AS REQUIREDREMOVE/EMBED SURFACING AS REQUIRED

FLASHING CAP SHEETFLASHING CAP SHEET

POLYESTER REINFOREDFLASHING BASE PLYPOLYESTER REINFOREDFLASHING BASE PLY

CAP SHEETCAP SHEET

BASE PLYBASE PLY

COVERBOARD

BASE SHEET/ANCHOR SHEET

VAPOR RETARDER/AIR BARRIERDECKDECKDECKDECKDECKDECKDECKDECK

FASTEN AT 8" O.C.ALONG TOP LEADING EDGE

FASTEN AT 8" O.C.ALONG TOP LEADING EDGE

2 PLY SBS MEMBRANE, INSULATED

EXTEND FLASHING BASE PLY AMINIMUM OF 3" BEYOND FASTENER PLATE

EXTEND FLASHING CAP SHEET AMINIMUM OF 1" BEYOND FLASHING BASE PLY

INSTALL FASTENER PLATE A MINIMUMOF 1" FROM WALL AND SPACED A

MAXIMUM OF 12" APART ALONG WALL

EXTEND FLASHING BASE PLY AMINIMUM OF 3" BEYOND FASTENER PLATE

EXTEND FLASHING CAP SHEET AMINIMUM OF 1" BEYOND FLASHING BASE PLY

INSTALL FASTENER PLATE A MINIMUMOF 1" FROM CANT AND SPACED A

MAXIMUM OF 12" APART ALONG WALL

BASE SHEET/ANCHOR SHEET

THERMAL BARRIER

INSULATION

INSULATION

INSULATION

INSULATIONEXTEND VAPOR RETARDER/AIR BARRIERA MINIMUM OF 3" BEYOND BASE OF WALL

VAPOR RETARDER/AIR BARRIER

FASTEN AT 8" O.C. INBOTH DIRECTIONS

FASTEN AT 8" O.C. INBOTH DIRECTIONS

BASE SHEET/ANCHOR SHEETBASE SHEET/ANCHOR SHEET