Smoke Test Procedures for Use ofFire CurtainsSmoke Test Proceduresfor Use of Fire Curtains
AFG-HK-954 AFG-HK-954
|
This report takes into account the particular
instructions and requirements of our client.
It is not intended for and should not be relied
upon by any third party and no responsibilityis undertaken to any third party.
Job number 217005-00217005-00
Ove Arup & Partners Hong Kong Ltd
Level 5 Festiva l Walk
80 Tat Chee Avenue
Kowloon Tong
Kowloon
Hong Kong
www.arup.com
Comment [HELP1]: Read ALL commentsbelow for a tutorial on report writing.
Theupper left "Quick Access toolbar"(Qcontains equivalent buttons to the floatingQuickEdit toolbar (QET), allowing changing tlandscape report sizes, changing to anothercolour, removing the draft watermark etc.
Ctrl+Shft+Bwill toggle comments betweenBalloons and Reviewing Pane. If you closethis pane, you can redisplay it via the "HeNotes" button on the QAT.
Do NOT attempt to delete the Frame. Thican be hidden on Print. Warning: Revision &
Date will not display if you exceed 7 lines forClient Name, Project Title & Report Titlecombined. For best print quality use Word'sinbuilt PDF maker via the Print Options "CreaPDF" button on the QAT. (Alternatively useSave As | PDF.)
Any text updated within the Frame willautomatically reflect in headers, footers andall other pages APART FROM on the DocumVerification, which is a historical record andmust be filled in manually (or via the Revisibutton).
Comment [HELP2]: Style Shortcuts:Ctrl+1, Ctrl+2, etc. Rep/Spec HeadingCtrl+Shft+1 etc - No number Rep Heading
Alt+1, Alt+2, etc. App HeadingAlt+Shft+1 etc - No number App HeadingCtrl+Shft+P Body Text
Ctrl+Shft+L Open Bulleted ListCtrl+Shft+K Closed Bulleted ListCtrl+Shft+U Open Numbered ListCtrl+Shft+S Closed List (no bullets)Ctrl+Shft+T Closed Table TextCtrl+Shft+I Visible ImageCtrl+Shft+R Reference
OvaWord Shortcuts:Ctrl+Shft+A Insert Appendix/DividerCtrl+Shft+B Balloon/Help toggleCtrl+Shft+C Change No. of ColumnsCtrl+Shft+D Insert new DV sheetCtrl+Shft+E Change Contents levelsCtrl+Shft+J Insert CVCtrl+Shft+W Change headings colourCtrl+Shft+X Insert an Image BoxCtrl+Shft+Y Alternative heading stylesCtrl+Shft+Z Change size of reportCtrl+Shft+O Switch page orientation
(correcting header & footer widths)Comment [HELP3]: Optional Client LogoFront Cover:Include any client logo in the empty cell to thleft of the Arup logo below.
If you require a customised report with speformatting for a particular project, please [email protected] for advice.
7/30/2019 217005 110710 HK954 Smoke Test Procedures_Issue
2/8
AFG-HK-954 | Issue | 10 July 2012
217005 110710 HK954 SMOKE TEST PROCEDURES_ISSUE.DOCXDOCUMENT1217005 110710 HK954 SMOKE TEST PROCEDURES_ISSUE.DOCX
Document Verification
Job title Hysan Place at 500 Hennessy Road, Hong
KongHysan Place at 500 Hennessy Road, Hong
Job number
217005-00217005-00Document title Smoke Test Procedures for Use of Fire
CurtainsSmoke Test Procedures for Use of Fire
File reference
Document ref AFG-HK-954 AFG-HK-954
Revision Date Filename
Draft 1 22 Jun
2012
Description First draft
Prepared by Checked by Approved by
Name Frankie Sze Valerie Chan Young Wong
Signature
Issue 10 Jul
2012
Filename 217005 110710 HK954 Smoke Test Procedures_Issue.docxDescription
Prepared by Checked by Approved by
Name Frankie Sze Valerie Chan Young Wong
Signature
Filename
Description
Prepared by Checked by Approved by
Name
Signature
Filename
Description
Prepared by Checked by Approved by
Name
Signature
Issue Document Verification with Document
Comment [HELP4]: The DocumentVerification is a historical record and shouldfilled in MANUALLY.
Alternatively the Revision button (viaQAT/QET) can still be used.
IMPORTANT: If you did not use the Revisionbutton and you MANUALLY added a new ReDate here within the Document Verification,back to the front cover frame and change ReDate there also, to ensure these are shownthroughout the document.
7/30/2019 217005 110710 HK954 Smoke Test Procedures_Issue
3/8
Woods Bagot Asia Hysan Place at 500 Hennessy Road, Hong Kong
Smoke Test Procedures for Use of Fire Curtains
AFG-HK-954 | Issue | 10 July 2012
217005 110710 HK954 SMOKE TEST PROCEDURES_ISSUE.DOCXDOCUMENT1217005 110710 HK954 SMOKE TEST PROCEDURES_ISSUE.DOCX
Contents
Page
1 Introduction 1
1.1 Project Description 1
1.2 Objective 21
2 Smoke Test Details 2
2.1 Smoke Generator 2
2.2 Test Monitoring Equipment 32
3 Test Procedures 3
4 Safety Procedures 43
4.1 Safety Measures and Precautions 43
4.2 Safety Officer 4
4.3 Safety Notes 4
5 Test Report 54
Appendix ASmoke Generator
Comment [HELP5]: The Contents button (QAT/QET) may be used to modify contentslevels, or to select additional Table of Contensections for Tables, Figures, Photos etc.
IMPORTANT: Do not delete any unusedheadings from Contents page. These arehidden until needed and do not take up anyspace. Select Print Preview to review how thdocument will print.
7/30/2019 217005 110710 HK954 Smoke Test Procedures_Issue
4/8
Woods Bagot Asia Hysan Place at 500 Hennessy Road, Hong Kong
Smoke Test Procedures for Use of Fire Curtains
AFG-HK-954 | Issue | 10 July 2012
DOCUMENT1217005 110710 HK954 SMOKE TEST PROCEDURES_ISSUE.DOCX
Page 1
1 Introduction
1.1 Project Description
The retail unit at 500 Hennessy Road is 3-storey high (G/F, 1/F and 2/F),occupying the south west corner of the shopping arcade. The retail unit isseparated from the rest of the shopping arcade with fire rated construction.
The three floors of the retail unit will be interconnected by vertical openings atriple height void immediately above the retail main entrance (at G/F), a passengerlift serving the three floors and an internal open staircase. In order to maintain thefire separation between the floors and to limit the extent of the compartmentvolume of each floor, fire curtains are proposed to protect the triple height voidand the open staircase on the 1/F and 2/F, and the passenger lift on the G/F, 1/Fand 2/F. A Fire Engineering Report to justify the use of fire curtains was
submitted to the Buildings Department (BD) and presented to the Fire SafetyCommittee (FSC).
1.2 Comments from FSC Meeting
All the comments from the FSC (meeting held on the 4th
January 2012), exceptone, have been addressed in the Fire Engineering Report for 500 Hennessy RoadUse of Fire Curtain in SW Corner Retail U nit (Rev E) dated 2
ndAril 2012 and
submitted to the BD (BD Ref: BD2/3017/04 Pt 10).
The purpose of this document is to address the remaining FSC comment, which isstated below:
It was suggested that a hot smoke test should be conducted for the checking ofsmoke leakage performance and validation of the fire engineering design
Hot smoke test is normally carried out for high ceiling and irregular shape atria totest the performance of the smoke extraction system in the space. The FSDCircular Letter (refNo. 2/2002) stated that the purpose of the hot smoke test is toensure the satisfactory installation of a smoke extraction system. The hotsmoke test is conducted on the basis of not affecting the building elements and notoperating the sprinkler system, based on a 1MW fire size.
As per the Fire Service Installations (FSI) code requirements, smoke extraction isnot required in this retail unit. Hence, there is no provision for smoke extractionanywhere in the retail unit. Without smoke extraction to remove hot smoke, theaccumulated hot gas during the test may result in activation of the sprinklersystem and potential damage to the glazed faade and other building elements.Refer to Appendix B for the calculation of the average temperature of the smokeplume.
On this basis, a cold smoke test without the heat source is proposed instead. Thisis considered adequate to address the intention of the FSC comment, which is todemonstrate the smoke leakage performance of the fire curtain and to validate thefire engineering design i.e. to show that the fire curtain can achieve the sameperformance as a code compliant fire shutter installation. It should be noted thatthere is no requirement in the code for fire shutter to be tested for smoke leakage
Formatted: Not Highlight
Formatted: Highlight
7/30/2019 217005 110710 HK954 Smoke Test Procedures_Issue
5/8
Woods Bagot Asia Hysan Place at 500 Hennessy Road, Hong Kong
Smoke Test Procedures for Use of Fire Curtains
AFG-HK-954 | Issue | 10 July 2012
DOCUMENT1217005 110710 HK954 SMOKE TEST PROCEDURES_ISSUE.DOCX
Page 2
performance. Therefore, there is no requirement in the code for fire curtain toachieve any smoke leakage performance.
1.3 Objective of Smoke TestThe smoke test will be carried out on site before the grand opening of the retailunit. It is proposed to locate the cold smoke test at the bottom of the triple heightvoid at G/F because this will test the performance of the longest fire curtain withoverlapping condition. The longest overlapping fire curtains are located on the 1/Fand 2/F openings to the triple height void.
In order to address the FSC comment, the objectives of the smoke test areproposed as follows:
Demonstrate the automatic closing of the fire curtains across the retail unitupon the detection of smoke by the automatic smoke detectors providedfor each fire curtain. [Note: this is to show that the operation of the fire
curtain is the same as the fire shutter. In fact, the design has been enhancedto operate all fire curtains across the retail unit instead of just the firecurtain of the activated smoke detector]
Observe the conditions on the 1/F and 2/F, which are separated from eachother and from the G/F by fire curtains. The occupants on those floorsshould be able to evacuate using the exits provided on those floors. [Note:this is to show the minimal smoke leakage through the closed fire curtainswill not affect the evacuation of occupants]
The duration of the smoke test will be 5 minutes, to demonstrate the conditionduring evacuation.
2 Smoke Test Details
2.1 Smoke Generator
A smoke generator will be used for the smoke test. A smoke delivery pipeconnected to the generator will be used to guide smoke to the top of the tripleheight void, as shown onFigure 1Figure 1. If required, a very small heat sourcewill be used to assist the rising of the smoke, to overcome the potential highambient temperature in the triple height void.
It is proposed to use one of the following types of smoke generator as supplied byHong Kong Fire Services Department (FSD) for hot smoke test in the past:
Pepper Fog Smoke Generator Mark-X11-D, or
Golden Eagle Smoke Generator
Further description of the above smoke generators is attached in Appendix A.
Smoke will accumulate in the triple height void and activate the smoke detectors(VESDA system) in the void, which will then cause the fire curtains in the retailunit to close.
7/30/2019 217005 110710 HK954 Smoke Test Procedures_Issue
6/8
Woods Bagot Asia Hysan Place at 500 Hennessy Road, Hong Kong
Smoke Test Procedures for Use of Fire Curtains
AFG-HK-954 | Issue | 10 July 2012
DOCUMENT1217005 110710 HK954 SMOKE TEST PROCEDURES_ISSUE.DOCX
Page 3
2.2 Test Monitoring
There will be designated observer at each observation point to record the
following information: Start of the smoke generator, time t=0
Automatic Aactivation of the smoke detection system (VESDA)
The activation of the fire alarm system, the visual alarm by the firecurtains, the shutting down of the normal ventilation system
The fire curtains starting to close along the triple height void and acrossthe retail unit
The complete closure of the fire curtains along the triple height void andacross the retail unit. Observe the closing time
Conditions on the 1/F and 2/F during the test
Observers should also take note on the simultaneous operation of all the firecurtains across the retail unit.
Figure 1: Schematic diagram for retail unit (Section)
There will be video recording of the test on G/F to observe the condition in thetriple height void and on the 1/F and 2/F to observe the condition on that floor.Where photography is used, there should be no flash as this will exaggerates theactual smoke density seen under normal lighting conditions.
2.3 Test Procedures
The smoke test will proceed in accordance with the following sequence of events:
1) Carry out safety briefing for the onsite staff and participant
2) Set up the smoke generator in position
3) Commence video recording
4) Start smoke generator
Smoke
Generator
Legend
Fire curtain
Observation points
Video recording
G/F
1/F
2/F
7/30/2019 217005 110710 HK954 Smoke Test Procedures_Issue
7/8
Woods Bagot Asia Hysan Place at 500 Hennessy Road, Hong Kong
Smoke Test Procedures for Use of Fire Curtains
AFG-HK-954 | Issue | 10 July 2012
DOCUMENT1217005 110710 HK954 SMOKE TEST PROCEDURES_ISSUE.DOCX
Page 4
5) Observe the automatic activation of the smoke detection system (VESDA)
6) Automatic operation of the fire alarm system, ventilation shut-down andall the fire curtains in the retail unit
7) Mute fire alarm system 30s after activation
8) Observe the condition on the 1/F and 2/F throughout the test
9) Stop operation of smoke generator after 5 minutes of test period
10)Stop video recording
11)Manually turn on the ventilation system for smoke purge
12)Re-set the fire curtains and other fire services installations
3 Safety Procedures
3.1 Safety Measures and Precautions
At the envisaged time of the test, it is expected that many of the building finisheswill be in place. It will therefore be necessary to provide adequate protection tosmoke sensitive materials to avoid damage from the effects of the smoke test.
Face masks will be made available for use by key personnel and spectators uponrequest, in case they are concerned by the properties of the tracer smoke from thegenerator.
Warnings and notifications shall be given to construction workers present in thetest site and adjacent areas that may be affected by the migration of smoke.
3.2 Safety OfficerA Safety Officer shall be in charge of the smoke test and shall be responsible forthe safety of organisers and spectators.
3.3 Safety Notes
1. At the commencement of the smoke test, all organisers and spectators shallassemble at the test site area to be briefed on safety procedures.
2. The nominated Safety Officer shall be identified at the briefing andintroduce members of his organising team and spectators.
3. The Safety Officer shall commence the briefing by explaining the sequence
of events for the test.4. The Safety Officer shall point out the exit doors for the test site area
5. All spectators are free to use the exit doors at any time during the test shouldthey feel that they should do so.
6. The Safety Officer shall demonstrate the evacuation signal. Upon hearingthe evacuation signal during the course of the test, all spectators must leavethe building in an orderly manner via the exit doors.
7/30/2019 217005 110710 HK954 Smoke Test Procedures_Issue
8/8
Woods Bagot Asia Hysan Place at 500 Hennessy Road, Hong Kong
Smoke Test Procedures for Use of Fire Curtains
AFG-HK-954 | Issue | 10 July 2012
DOCUMENT1217005 110710 HK954 SMOKE TEST PROCEDURES_ISSUE.DOCX
Page 5
7. At no time shall the spectator enter the test area, nor re-enter the buildingonce they have evacuated, unless permitted to do so by the Safety Officer.
8. The Safety Officer shall point out the designated spectator areas.
9. Spectators shall only stand in the designated spectator areas whilst the test isin progress.
10. Spectators shall not be allowed to enter the test site area during the testperiod unless authorised by the Safety Officer.
11. Specific instructions by the Safety Officer shall be followed exactly andpromptly at all times during the test.
12. The Safety Officer shall finish the briefing by answering any questionswhich spectators may have concerning safety measures and the manner inwhich the test will be conducted.
4 Test Report
After the on-site demonstration test of smoke, a test report will be submitted to theauthority for record. The intent of the test is to demonstrate the smoke leakageperformance of the proposed fire curtains and validate the fire engineering design.
Based on the objectives of the smoke test (in Section 1.3), the outcome of the testis considered acceptable under the following conditions:
The fire curtains across the retail unit closing automatically upon thedetection of smoke by the automatic smoke detection system (VESDA)
The fire curtains close within 15 to 60 seconds (time measured from themoment the fire curtains start to close)
The ability of the occupants on 1/F and 2/F to evacuate using the exitsprovided on those floors.
The test report will describe the observation of test with photos. VCD/DVD(s)will be also attached in the report. The test report together with the videos of testwill be submitted to FSD within 2 weeks of test.