Vertical Upflow Air Handlers With Electric Heat · 2006-01-27 · 22-1753-01-0404 (EN) 3 Contents...

16
PUB. NO. 22-1753-01-0404 (EN) Vertical Upflow Air Handlers With Electric Heat 2TFB4018, 24, 30, 36A1D05, 08, 10A 2TFE4025A1D05, 08, 10A

Transcript of Vertical Upflow Air Handlers With Electric Heat · 2006-01-27 · 22-1753-01-0404 (EN) 3 Contents...

Page 1: Vertical Upflow Air Handlers With Electric Heat · 2006-01-27 · 22-1753-01-0404 (EN) 3 Contents Features and Benefits 2 2TFB4 Standard Equipment 2 2TFE3 Standard Equipment 2 Optional

PUB. NO. 22-1753-01-0404 (EN)

Vertical UpflowAir HandlersWith Electric Heat

2TFB4018, 24, 30, 36A1D05, 08, 10A2TFE4025A1D05, 08, 10A

Page 2: Vertical Upflow Air Handlers With Electric Heat · 2006-01-27 · 22-1753-01-0404 (EN) 3 Contents Features and Benefits 2 2TFB4 Standard Equipment 2 2TFE3 Standard Equipment 2 Optional

© 2004 American Standard Inc. All Rights Reserved 2 22-1753-01-0404 (EN)

Features andBenefits

OPTIONAL EQUIPMENT FOR HEATING UNITSEvaporator Defrost Control Kit All Cooling Models .................................................................................................... AY28X079 [ ]Evaporator Defrost Control Kit All Heat Pump Models ............................................................................................... AY28X084 [ ]

2TFB4 Standard Equipment• Internal mounted expansion valve kits

available

• Approved for modular or manufacturedhomes

• Factory installed service disconnect

• Internally enhanced finned coil tubing

• Primary and secondary drainconnections

• Optional extended warranties

• Five year limited parts warranty

2TFE3 Standard Equipment• Factory installed electric heaters

• Expansion valve refrigerant control

• Factory installed service disconnect

• Internally enhanced finned coil tubing

• Primary and secondary drainconnections

• Approved for modular or manufacturedhomes

• Optional extended warranties

• Five year limited parts warranty

• Shipped in vertical upflow, bottomreturn with front access & convertible tovertical upflow front return

• Tight cabinet - low leakage by design

• Attractive enamel finish

• R 4.2 – 1" insulation

• Exclusive easy clean coil and drain pan

• Easy to remove filters and blowers foreasy cleaning and replacement

• Filter rack with throwaway filter

• Easy access electrical controls andhook-up

• 200/230 volt primary and 24 voltsecondary transformer

• Built-in indoor fan delay function forincreased efficiency. No kit required.

• Multi-speed blower

• Direct drive motor

• Factory installed electric heaters

• AccuTron™ refrigerant control

• Shipped in vertical upflow, bottomreturn with front access & convertible tovertical upflow front return

• Variable speed ECM motor

• Enhanced Comfort-R™

• Soft start – cycle-on speed is rampedup gradually to reduce sound and draft

• Low voltage terminal board

• Tight cabinet – low leakage by design

• Attractive enamel finish

• R 4.2 – 1" insulation

• Exclusive easy clean coil and drain pan

• Easy to remove filters and blowers foreasy cleaning and replacement

• Filter rack with throw away filter

• Easy access electrical controls andhook-up

• 200/230 volt primary and 24 voltsecondary transformer

• Built-in indoor fan delay function forincreased efficiency. No kit required.

Page 3: Vertical Upflow Air Handlers With Electric Heat · 2006-01-27 · 22-1753-01-0404 (EN) 3 Contents Features and Benefits 2 2TFB4 Standard Equipment 2 2TFE3 Standard Equipment 2 Optional

22-1753-01-0404 (EN) 3

Contents

Features and Benefits 22TFB4 Standard Equipment 22TFE3 Standard Equipment 2Optional Equipment For Heating Units 2

General Data 42TFB4018A1D05A 42TFB4018A1D08A 42TFB4018A1D10A 42TFB4024A1D05A 52TFB4024A1D08A 52TFB4024A1D10A 52TFB4030A1D05A 62TFB4030A1D08A 62TFB4030A1D10A 62TFB4036A1D05A 72TFB4036A1D08A 72TFB4036A1D10A 72TFE3025A1D05A 82TFE3025A1D08A 82TFE3025A1D10A 8

Performance Data 9

Electrical Data 11

Refrigerant Circuit 13

Dimensions 15

Page 4: Vertical Upflow Air Handlers With Electric Heat · 2006-01-27 · 22-1753-01-0404 (EN) 3 Contents Features and Benefits 2 2TFB4 Standard Equipment 2 2TFE3 Standard Equipment 2 Optional

4 22-1753-01-0404 (EN)

GeneralData

Product SpecificationsMODELRATED VOLTS/PH/HZ.RATINGS 1HEATER CAPACITY (Volts)HEATER CAPACITY (BTUH)POWER CONNECTIONMin. Brch. Cir. Ampacity 2Recmd-Max. Overload Protection (amps)INDOOR COIL - TypeRows - F.P.I.Face Area (sq. ft.)Tube Size (in.)Refrigerant ControlDrain Connection Size (In.) 3DUCT CONNECTIONSINDOOR FAN - TypeDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HP - RPMF.L. Amps - L.R. AmpsFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)REFRIGERANT CONNECTIONSLine Size - Gas (in.)Line Size - Liquid (in.)DIMENSIONS (in.)Crated (H X W X D)UncratedWEIGHT (lbs.)Shipping - Net1 These Air Handlers are A.R.I certified with various Split System Air Conditioners and Heat Pumps (ARI STANDARD 210/240). Refer to the Split System Outdoor Unit Product Data Guides for performance data.2 Minimum Circuit Ampacity includes Blower Motor Amps3 3/4" Plastic Pipe (Ref.: ASTM 1785-76)

2TFB4018A1D05A208/230/1/60

See O.D. Specifications240v 208v

16400 12300230v 208v27 2330 25

PLATE FIN3 - 142.433/8

FCCV3/4 PVC SLIP

See Outline DrawingCentrifugal

10 x 812

See Fan Performance Table1/5 - 9301.0 / 1.4

YesThrowaway

1 - 18 x 20 - 1 In.Brazed

5/81/4

H X W X D40-1/2 x 23 x 20-3/8See Outline Drawing

115 / 93

2TFB4018A1D08A208/230/1/60

See O.D. Specifications240v 208v

26200 19700230v 208v42 3645 40

PLATE FIN3 - 142.433/8

FCCV3/4 PVC SLIP

See Outline DrawingCentrifugal

10 x 812

See Fan Performance Table1/5 - 9301.0 / 1.4

YesThrowaway

1 - 18 x 20 - 1 In.Brazed

5/81/4

H X W X D40-1/2 x 23 x 20-3/8See Outline Drawing

115 / 93

2TFB4018A1D10A208/230/1/60

See O.D. Specifications240v 208v

32800 24600230v 208v52 4560 45

PLATE FIN3 - 142.433/8

FCCV3/4 PVC SLIP

See Outline DrawingCentrifugal

10 x 812

See Fan Performance Table1/5 - 9301.0 / 1.4

YesThrowaway

1 - 18 x 20 - 1 In.Brazed

5/81/4

H X W X D40-1/2 x 23 x 20-3/8See Outline Drawing

115 / 93

Page 5: Vertical Upflow Air Handlers With Electric Heat · 2006-01-27 · 22-1753-01-0404 (EN) 3 Contents Features and Benefits 2 2TFB4 Standard Equipment 2 2TFE3 Standard Equipment 2 Optional

22-1753-01-0404 (EN) 5

Product SpecificationsMODELRATED VOLTS/PH/HZ.RATINGS 1HEATER CAPACITY (Volts)HEATER CAPACITY (BTUH)POWER CONNECTIONMin. Brch. Cir. Ampacity 2Recmd-Max. Overload Protection (amps)INDOOR COIL - TypeRows - F.P.I.Face Area (sq. ft.)Tube Size (in.)Refrigerant ControlDrain Connection Size (In.) 3DUCT CONNECTIONSINDOOR FAN - TypeDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HP - RPMF.L. Amps - L.R. AmpsFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)REFRIGERANT CONNECTIONSLine Size - Gas (in.)Line Size - Liquid (in.)DIMENSIONS (in.)Crated (H X W X D)UncratedWEIGHT (lbs.)Shipping - Net

2TFB4024A1D05A208/230/1/60

See O.D. Specifications240v 208v

16400 12300230v 208v27 2430 25

PLATE FIN3 - 142.433/8

FCCV3/4 PVC SLIP

See Outline DrawingCentrifugal

10 x 812

See Fan Performance Table1/3 - 11031.4 / 3.3

YesThrowaway

1 - 18 x 20 - 1 In.Brazed

3/45/16

H X W X D40-1/2 x 23 x 20-3/8See Outline Drawing

115 / 93

2TFB4024A1D08A208/230/1/60

See O.D. Specifications240v 208v

26200 19700230v 208v42 3745 40

PLATE FIN3 - 142.433/8

FCCV3/4 PVC SLIP

See Outline DrawingCentrifugal

10 x 812

See Fan Performance Table1/3 - 11031.4 / 3.3

YesThrowaway

1 - 18 x 20 - 1 In.Brazed

3/45/16

H X W X D40-1/2 x 23 x 20-3/8See Outline Drawing

115 / 93

2TFB4024A1D10A208/230/1/60

See O.D. Specifications240v 208v

32800 24600230v 208v52 4560 45

PLATE FIN3 - 142.433/8

FCCV3/4 PVC SLIP

See Outline DrawingCentrifugal

10 x 812

See Fan Performance Table1/3 - 11031.4 / 3.3

YesThrowaway

1 - 18 x 20 - 1 In.Brazed

3/45/16

H X W X D40-1/2 x 23 x 20-3/8See Outline Drawing

115 / 93

GeneralData

1 These Air Handlers are A.R.I certified with various Split System Air Conditioners and Heat Pumps (ARI STANDARD 210/240). Refer to the Split System Outdoor Unit Product Data Guides for performance data.2 Minimum Circuit Ampacity includes Blower Motor Amps3 3/4" Plastic Pipe (Ref.: ASTM 1785-76)

Page 6: Vertical Upflow Air Handlers With Electric Heat · 2006-01-27 · 22-1753-01-0404 (EN) 3 Contents Features and Benefits 2 2TFB4 Standard Equipment 2 2TFE3 Standard Equipment 2 Optional

6 22-1753-01-0404 (EN)

GeneralData

Product SpecificationsMODELRATED VOLTS/PH/HZ.RATINGS 1HEATER CAPACITY (Volts)HEATER CAPACITY (BTUH)POWER CONNECTIONMin. Brch. Cir. Ampacity 2Recmd-Max. Overload Protection (amps)INDOOR COIL - TypeRows - F.P.I.Face Area (sq. ft.)Tube Size (in.)Refrigerant ControlDrain Connection Size (In.) 3DUCT CONNECTIONSINDOOR FAN - TypeDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HP - RPMF.L. Amps - L.R. AmpsFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)REFRIGERANT CONNECTIONSLine Size - Gas (in.)Line Size - Liquid (in.)DIMENSIONS (in.)Crated (H X W X D)UncratedWEIGHT (lbs.)Shipping - Net

2TFB4030A1D05A208/230/1/60

See O.D. Specifications240v 208v

16400 12300230v 208v27 2430 25

PLATE FIN3 - 142.433/8

FCCV3/4 PVC SLIP

See Outline DrawingCentrifugal

10 x 812

See Fan Performance Table1/3 - 11251.5 / 4.1

YesThrowaway

1 - 18 x 20 - 1 In.Brazed

3/45/16

H X W X D40-1/2 x 23 x 20-3/8See Outline Drawing

115 / 93

2TFB4030A1D08A208/230/1/60

See O.D. Specifications240v 208v

26200 19700230v 208v42 3745 40

PLATE FIN3 - 142.433/8

FCCV3/4 PVC SLIP

See Outline DrawingCentrifugal

10 x 812

See Fan Performance Table1/3 - 11251.5 / 4.1

YesThrowaway

1 - 18 x 20 - 1 In.Brazed

3/45/16

H X W X D40-1/2 x 23 x 20-3/8See Outline Drawing

115 / 93

2TFB4030A1D10A208/230/1/60

See O.D. Specifications240v 208v

32800 24600230v 208v52 4660 50

PLATE FIN3 - 142.433/8

FCCV3/4 PVC SLIP

See Outline DrawingCentrifugal

10 x 812

See Fan Performance Table1/3 - 11251.5 / 4.1

YesThrowaway

1 - 18 x 20 - 1 In.Brazed

3/45/16

H X W X D40-1/2 x 23 x 20-3/8See Outline Drawing

115 / 931 These Air Handlers are A.R.I certified with various Split System Air Conditioners and Heat Pumps (ARI STANDARD 210/240). Refer to the Split System Outdoor Unit Product Data Guides for performance data.2 Minimum Circuit Ampacity includes Blower Motor Amps3 3/4" Plastic Pipe (Ref.: ASTM 1785-76)

Page 7: Vertical Upflow Air Handlers With Electric Heat · 2006-01-27 · 22-1753-01-0404 (EN) 3 Contents Features and Benefits 2 2TFB4 Standard Equipment 2 2TFE3 Standard Equipment 2 Optional

22-1753-01-0404 (EN) 7

Product SpecificationsMODELRATED VOLTS/PH/HZ.RATINGS 1HEATER CAPACITY (Volts)HEATER CAPACITY (BTUH)POWER CONNECTIONMin. Brch. Cir. Ampacity 2Recmd-Max. Overload Protection (amps)INDOOR COIL - TypeRows - F.P.I.Face Area (sq. ft.)Tube Size (in.)Refrigerant ControlDrain Connection Size (In.) 3DUCT CONNECTIONSINDOOR FAN - TypeDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HP - RPMF.L. Amps - L.R. AmpsFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)REFRIGERANT CONNECTIONSLine Size - Gas (in.)Line Size - Liquid (in.)DIMENSIONS (in.)Crated (H X W X D)UncratedWEIGHT (lbs.)Shipping - Net

2TFB4036A1D08A208/230/1/60

See O.D. Specifications240v 208v

26200 19700230v 208v45 4045 40

PLATE FIN4 - 142.433/8

FCCV3/4 PVC SLIP

See Outline DrawingCentrifugal

11 x 812

See Fan Performance Table3/4 - 11254.0 / 9.1

YesThrowaway

1 - 18 x 20 - 1 In.Brazed

7/83/8

H X W X D42-1/2 x 23 x 20-3/8See Outline Drawing

120 / 98

2TFB4036A1D10A208/230/1/60

See O.D. Specifications240v 208v

32800 24600230v 208v55 4860 50

PLATE FIN4 - 142.433/8

FCCV3/4 PVC SLIP

See Outline DrawingCentrifugal

11 x 812

See Fan Performance Table3/4 - 11254.0 / 9.1

YesThrowaway

1 - 18 x 20 - 1 In.Brazed

7/83/8

H X W X D42-1/2 x 23 x 20-3/8See Outline Drawing

120 / 98

2TFB4036A1D05A208/230/1/60

See O.D. Specifications240v 208v

16400 12300230v 208v30 2730 30

PLATE FIN4 - 142.433/8

FCCV3/4 PVC SLIP

See Outline DrawingCentrifugal

11 x 812

See Fan Performance Table3/4 - 11254.0 / 9.1

YesThrowaway

1 - 18 x 20 - 1 In.Brazed

7/83/8

H X W X D42-1/2 x 23 x 20-3/8See Outline Drawing

120 / 98

GeneralData

1 These Air Handlers are A.R.I certified with various Split System Air Conditioners and Heat Pumps (ARI STANDARD 210/240). Refer to the Split System Outdoor Unit Product Data Guides for performance data.2 Minimum Circuit Ampacity includes Blower Motor Amps3 3/4" Plastic Pipe (Ref.: ASTM 1785-76)

Page 8: Vertical Upflow Air Handlers With Electric Heat · 2006-01-27 · 22-1753-01-0404 (EN) 3 Contents Features and Benefits 2 2TFB4 Standard Equipment 2 2TFE3 Standard Equipment 2 Optional

8 22-1753-01-0404 (EN)

Product Specifications

GeneralData

MODELRATED VOLTS/PH/HZ.RATINGS 1HEATER CAPACITY (Volts)HEATER CAPACITY (BTUH)POWER CONNECTIONMin. Brch. Cir. Ampacity 2Recmd-Max. Overload Protection (amps)INDOOR COIL - TypeRows - F.P.I.Face Area (sq. ft.)Tube Size (in.)Refrigerant ControlDrain Connection Size (In.) 3DUCT CONNECTIONSINDOOR FAN - TypeDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HP - RPMF.L. AmpsFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)REFRIGERANT CONNECTIONSLine Size - Gas (in.)Line Size - Liquid (in.)DIMENSIONS (in.)Crated (H X W X D)UncratedWEIGHT (lbs.)Shipping - Net

2TFE3025A1D05A208/230/1/60

See O.D. Specifications240v 208v

16400 12300230v 208v30 2730 30

PLATE FIN3 - 142.433/8

NBTXV3/4 PVC SLIP

See Outline DrawingCentrifugal

10 x 81

VARIABLE SPEEDSee Fan Performance Table

1/24.3Yes

Throwaway1 - 18 x 20 - 1 In.

Brazed3/45/16

H X W X D40-1/2 x 23 x 20-3/8See Outline Drawing

115 / 93

2TFE3025A1D08A208/230/1/60

See O.D. Specifications240v 208v

16400 12300230v 208v46 4050 40

PLATE FIN3 - 142.433/8

NBTXV3/4 PVC SLIP

See Outline DrawingCentrifugal

10 x 81

VARIABLE SPEEDSee Fan Performance Table

1/24.3Yes

Throwaway1 - 18 x 20 - 1 In.

Brazed3/45/16

H X W X D40-1/2 x 23 x 20-3/8See Outline Drawing

115 / 93

2TFE3025A1D10A208/230/1/60

See O.D. Specifications240v 208v

16400 12300230v 208v56 4960 50

PLATE FIN3 - 142.433/8

NBTXV3/4 PVC SLIP

See Outline DrawingCentrifugal

10 x 81

VARIABLE SPEEDSee Fan Performance Table

1/24.3Yes

Throwaway1 - 18 x 20 - 1 In.

Brazed3/45/16

H X W X D40-1/2 x 23 x 20-3/8See Outline Drawing

115 / 931 These Air Handlers are A.R.I certified with various Split System Air Conditioners and Heat Pumps (ARI STANDARD 210/240). Refer to the Split System Outdoor Unit Product Data Guides for performance data.2 Minimum Circuit Ampacity includes Blower Motor Amps3 3/4" Plastic Pipe (Ref.: ASTM 1785-76)

Page 9: Vertical Upflow Air Handlers With Electric Heat · 2006-01-27 · 22-1753-01-0404 (EN) 3 Contents Features and Benefits 2 2TFB4 Standard Equipment 2 2TFE3 Standard Equipment 2 Optional

22-1753-01-0404 (EN) 9

PerformanceData

AIRFLOW PERFORMANCE2TFB4018A1D

CFM

230 VOLTS 208 VOLTS

EXTERNALSTATIC

PRESSURE(in. wg.) HI LO HI LO

0.00 920 720 815 625

0.10 880 685 785 575

0.20 830 640 735 530

0.30 775 585 675 465

0.40 705 520 600 405

0.50 630 450 535 335

0.60 550 365 445 270

0.70 455 275 -- --

NOTES: WITH WET COIL, FILTER & 10 KW ELECTRIC HEATER

AIRFLOW PERFORMANCE2TFB4024A1D

CFM

230 VOLTS 208 VOLTS

EXTERNALSTATIC

PRESSURE(in. wg.) HI LO HI LO

0.00 1075 890 1015 800

0.10 1030 850 975 755

0.20 975 800 935 715

0.30 915 745 860 670

0.40 845 680 815 605

0.50 770 610 755 535

0.60 525 690 650 450

0.70 600 435 520 360

NOTES: WITH WET COIL, FILTER & 10 KW ELECTRIC HEATER

AIRFLOW PERFORMANCE2TFB4030A1D

CFM

230 VOLTS 208 VOLTS

EXTERNALSTATIC

PRESSURE(in. wg.) HI LO HI LO

0.00 1140 1095 1100 1015

0.10 1095 1050 1050 975

0.20 1040 1000 995 925

0.30 980 945 930 875

0.40 915 880 860 815

0.50 845 810 795 750

0.60 765 730 720 655

0.70 685 650 605 550

NOTES: WITH WET COIL, FILTER & 10 KW ELECTRIC HEATER

AIRFLOW PERFORMANCE2TFB4036A1D

CFM

230 VOLTS 208 VOLTS

EXTERNALSTATIC

PRESSURE(in. wg.) HI LO HI LO

0.00 1285 1110 1258 1020

0.10 1242 1072 1215 982

0.20 1196 1029 1170 939

0.30 1150 979 1123 889

0.40 1101 927 1075 837

0.50 1041 883 1014 793

0.60 992 838 965 748

0.70 943 792 917 702

NOTES: WITH WET COIL, FILTER & 10 KW ELECTRIC HEATER

A800984P01A800983P01A800982P01 A801200P01

2TFE3025A1D AIR HANDLER AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)AIRFLOW SETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW1 SW2 SW3 SW4 0.1 0.2 0.3 0.5 0.7 0.9

1.5

LOW(350 CFM/TON) ON ON OFF ON CFM 525 525 500 450 445 440

NORMAL(400 CFM/TON) ON ON OFF OFF CFM 600 600 575 550 550 500

HIGH(450 CFM/TON) ON ON ON OFF CFM 650 650 650 650 625 575

2

LOW(350 CFM/TON) OFF ON OFF ON CFM 700 700 700 675 650 600

NORMAL(400 CFM/TON) OFF ON OFF OFF CFM 800 800 800 800 800 750

HIGH(450 CFM/TON) OFF ON ON OFF CFM 900 900 900 900 875 825

2.5

LOW(350 CFM/TON) ON OFF OFF ON CFM 850 850 850 875 850 850

NORMAL(400 CFM/TON) ON OFF OFF OFF CFM 1000 1000 1000 1000 950 850

HIGH(450 CFM/TON) ON OFF ON OFF CFM 1125 1125 1125 1125 1125 900

3**

LOW(350 CFM/TON) OFF OFF OFF ON CFM 1050 1050 1050 1050 1000 850

NORMAL(400 CFM/TON) OFF OFF OFF OFF CFM 1200 1200 1200 1125 1050 950

HIGH(450 CFM/TON) OFF OFF ON OFF CFM 1300 1300 1250 1175 1100 1050

NOTES:1. ** Factory setting2. At continuous Fan setting: Airflow values are approximately 50% of listed values.3. With wet coil, filter in place, and 10KW electric heater.

Page 10: Vertical Upflow Air Handlers With Electric Heat · 2006-01-27 · 22-1753-01-0404 (EN) 3 Contents Features and Benefits 2 2TFB4 Standard Equipment 2 2TFE3 Standard Equipment 2 Optional

10 22-1753-01-0404 (EN)

PerformanceData

AIRFLOW ADJUSTMENTIf the airflow needs to be increased or decreased, see theAirflow Label on the air handler or the Blower PerformanceTable in the Service Facts. Information on changing the speedof the blower motor for your specific outdoor model size is in theBlower Performance Table.

Blower speed changes are made on the ECM Fan Control. TheECM Fan control controls the variable speed motor.

There is a bank of 8 dip switches (see Figure 1), located at theupper part of the board. The dip switches work in pairs to matchthe airflow for the outdoor unit size (tons), cooling airflowadjustment, cooling off delay options, and heating airflowadjustment. The switches appear as shown in Figure 2.

COOLING OFF - DELAY OPTIONS

SWITCH SETTINGS SELECTION NOMINALAIRFLOW

5 - OFF 6 - OFF NONE SAME

5 - ON 6 - OFF 1.5 MINUTES 100% *

5 - OFF 6 - ON 3 MINUTES 50%

5 - ON 6 - ON ENHANCED** 50 - 100%

* - This setting is equivalent to the BAY24X045 relay benefit

** - This ENHANCED MODE selection provides a ramping up and ramping down of the blower speed to provide improved comfort, quietness, and potential energy savings. The graph shows the ramping process.

OFF OFF

50%

80%

100% if necessary

50%

DehumidifyWarm Air Heating

Fast Coil CoolingFast Coil Heating Efficiency

7.5minutes

3minutes

1minute

FA

N O

PE

RA

TIO

N (

CF

M)

as required

INDOOR BLOWER TIMINGThe ICM Fan Control controls the variable speed indoor blower.The FAN-OFF period is set on the ICM Fan Control board bydip switches #5 and #6. The blower off-delay settings are asfollows:

1

DIP SWITCHES (AS SHIPPED)

COOLING HEATING

AIRFLOW

FAN OFFDELAY

AUXILIARYHEAT SPEEDS

2

Page 11: Vertical Upflow Air Handlers With Electric Heat · 2006-01-27 · 22-1753-01-0404 (EN) 3 Contents Features and Benefits 2 2TFB4 Standard Equipment 2 2TFE3 Standard Equipment 2 Optional

22-1753-01-0404 (EN) 11

2TFB4018,24,30,36A1D08, D10

2TFB4018,24,30,36A1D05

ElectricalData

200 - 230 VOLT 60 HZ1 PH POWER SUPPLY PER LOCAL CODE

NOTES:

1. FOR 200V OPERATION SWAP RED HIGH VOLTAGE TRANSFORMER LEAD AND INSULATED CAP ON 200V CENTER TRANSFORMER TERMINAL.

2. FOR REPLACEMENT FUSE, USE 5.0 AMP AUTOMOTIVE STYLE FOR ALL MODELS.

200 - 230 VOLT 60 HZ1 PH POWER SUPPLY PER LOCAL CODE

NOTES:

1. FOR 200V OPERATION SWAP RED HIGH VOLTAGE TRANSFORMER LEAD AND INSULATED CAP ON 200V CENTER TRANSFORMER TERMINAL.

2. FOR REPLACEMENT FUSE, USE 5.0 AMP AUTOMOTIVE STYLE FOR ALL MODELS.

Page 12: Vertical Upflow Air Handlers With Electric Heat · 2006-01-27 · 22-1753-01-0404 (EN) 3 Contents Features and Benefits 2 2TFB4 Standard Equipment 2 2TFE3 Standard Equipment 2 Optional

12 22-1753-01-0404 (EN)

ElectricalData

2TFE3025A1D05

2TFE3025A1D08, D10

200 - 230 VOLT 60 HZ1 PH POWER SUPPLY PER LOCAL CODE

NOTES:

1. FOR 200V OPERATION SWAP RED HIGH VOLTAGE TRANSFORMER LEAD AND INSULATED CAP ON 200V CENTER TRANSFORMER TERMINAL.

2. FOR REPLACEMENT FUSE, USE 5.0 AMP AUTOMOTIVE STYLE FOR ALL MODELS.

Page 13: Vertical Upflow Air Handlers With Electric Heat · 2006-01-27 · 22-1753-01-0404 (EN) 3 Contents Features and Benefits 2 2TFB4 Standard Equipment 2 2TFE3 Standard Equipment 2 Optional

22-1753-01-0404 (EN) 13

RefrigerantCircuit

Refrigerant Circuit Drawing for 2TFB4036 Air Handlers

Refrigerant Circuit Drawing for 2TFB4018,24,30 Air Handlers

From Drawing D801091G01

From Drawing D800930 Sheet 1 Rev 4

Page 14: Vertical Upflow Air Handlers With Electric Heat · 2006-01-27 · 22-1753-01-0404 (EN) 3 Contents Features and Benefits 2 2TFB4 Standard Equipment 2 2TFE3 Standard Equipment 2 Optional

14 22-1753-01-0404 (EN)

Refrigerant Circuit Drawing for 2TFE3025 Air Handler

From Drawing D800930 Sheet 2 Rev 4

RefrigerantCircuit

Page 15: Vertical Upflow Air Handlers With Electric Heat · 2006-01-27 · 22-1753-01-0404 (EN) 3 Contents Features and Benefits 2 2TFB4 Standard Equipment 2 2TFE3 Standard Equipment 2 Optional

22-1753-01-0404 (EN

)15

2TFB / 2TFE Outline Drawing(All dimensions are in inches)

From Drawing D800913P01 Rev 5

Dim

ensio

ns

Page 16: Vertical Upflow Air Handlers With Electric Heat · 2006-01-27 · 22-1753-01-0404 (EN) 3 Contents Features and Benefits 2 2TFB4 Standard Equipment 2 2TFE3 Standard Equipment 2 Optional

P.I.

Trane has a policy of continuous product and product data improvement and it reserves the right to changedesign and specifications without notice.

TraneA business ofAmerican Standard Companieswww.trane.com