Upflow/Horizontal Right or Upflow/Horizontal Left Induced Draft Gas Furnace XR 80 PUB. NO. 22-1640-09 TDD-D-1 TUD1A040A9241A, TUD1A040A9301A, TUD1A060A9241A, TUD1A060A9361A, TUD1B060A9361A, TUD1B080A9241A, TUD1B080A9361A, TUD1B080A9481A, TUD1C080A9601A, TUD1B100A9361A, TUD1B100A9451A, TUD1C100A9481A, TUD1C100A9601A, TUD1D100A9721A, TUD1C120A9541A, TUD1D120A9601A, TUD1D140A9601A Single-Stage Fan Assisted Combustion System

Transcript of Upflow/Horizontal Right or Upflow/Horizontal Left Induced ... · Upflow/Horizontal Right or...

Page 1: Upflow/Horizontal Right or Upflow/Horizontal Left Induced ... · Upflow/Horizontal Right or Upflow/Horizontal Left Induced Draft Gas Furnace XR 80 PUB. NO. 22-1640-09 TDD-D-1 TUD1A040A9241A,

Upflow/Horizontal Rightor Upflow/Horizontal LeftInduced Draft Gas Furnace

XR 80

PUB. NO. 22-1640-09

TDD-D-1

TUD1A040A9241A, TUD1A040A9301A, TUD1A060A9241A,TUD1A060A9361A, TUD1B060A9361A, TUD1B080A9241A,TUD1B080A9361A, TUD1B080A9481A, TUD1C080A9601A,TUD1B100A9361A, TUD1B100A9451A, TUD1C100A9481A,TUD1C100A9601A, TUD1D100A9721A, TUD1C120A9541A,TUD1D120A9601A, TUD1D140A9601A

Single-Stage Fan AssistedCombustion System

Page 2: Upflow/Horizontal Right or Upflow/Horizontal Left Induced ... · Upflow/Horizontal Right or Upflow/Horizontal Left Induced Draft Gas Furnace XR 80 PUB. NO. 22-1640-09 TDD-D-1 TUD1A040A9241A,

2 Pub. No. 22-1640-09

GeneralFeatures

©American Standard Inc. 2006 All Rights Reserved

NATURAL GAS MODELSCentral Heating furnace designs arecertified by the American and CanadianGas Associations for both natural and L.P.gas. Limit setting and rating data wereestablished and approved under standardrating conditions using American NationalStandards Institute standards.

SAFE OPERATIONThe Integrated System Control has solidstate devices, which continuously monitorfor presence of flame, when the systemis in the heating mode of operation. Dualsolenoid combination gas valve andregulator provide extra safety.

QUICK HEATINGDurable, cycle tested, heavy gaugealuminized steel heat exchangerquickly transfers heat to provide warmconditioned air to the structure.

BURNERSMultiport Inshot burners will give years ofquiet and efficient service. All modelscan be converted to L.P. gas.

INTEGRATED SYSTEM CONTROLExclusively designed operationalprogram provides total control of furnacelimit sensors, blowers, gas valve, flamecontrol and includes self diagnostics forease of service. Also containsconnection points for E.A.C./humidifier.

AIR DELIVERYThe 4-speed, direct drive blower motor,has sufficient airflow for most heating andcooling requirements, will switch from

heating to cooling speeds on demand fromroom thermostat. The blower door safetyswitch will prevent or terminate furnaceoperation when the blower door isremoved.

STYLINGHeavy gauge steel and “wrap-around”cabinet construction is used in thecabinet with baked-on enamel finish forstrength and beauty. The heat exchangersection of the cabinet is completely linedwith foil faced fiberglass insulation. Thisresults in quiet and efficient operationdue to the excellent acoustical andinsulating qualities of fiberglass.

FEATURES ANDGENERAL OPERATIONThe XR 80 High Efficiency Gas Furnacesempoys an adaptive Hot Surface Ignitionsystem, which eliminates the waste of aconstant burning pilot. The integratedsystem control lights the main burnersupon a demand for heat from the roomthermostat. Complete front serviceaccess.a. Low energy power venterb. Vent proving pressure switch.

Page 3: Upflow/Horizontal Right or Upflow/Horizontal Left Induced ... · Upflow/Horizontal Right or Upflow/Horizontal Left Induced Draft Gas Furnace XR 80 PUB. NO. 22-1640-09 TDD-D-1 TUD1A040A9241A,

3Pub. No. 22-1640-09

Contents

General Features 2

Features and Benefits 4Standard Equipment 4Optional Equipment 4

General Data 5TUD1A040A9241A 5TUD1A040A9301A 5TUD1A060A9241A 6TUD1A060A9361A 6TUD1B060A9361A 6TUD1B080A9241A 7TUD1B080A9361A 7TUD1B080A9481A 7TUD1C080A9601A 7TUD1B100A9361A 8TUD1B100A9451A 8TUD1C100A9481A 8TUD1C100A9601A 8TUD1D100A9721A 9TUD1C120A9541A 9TUD1D120A9601A 9TUD1D140A9601A 9

Performance Data 10

Field Wiring 12

Dimensions 14

Electrical Data 15

Page 4: Upflow/Horizontal Right or Upflow/Horizontal Left Induced ... · Upflow/Horizontal Right or Upflow/Horizontal Left Induced Draft Gas Furnace XR 80 PUB. NO. 22-1640-09 TDD-D-1 TUD1A040A9241A,

4 Pub. No. 22-1640-09

Featuresand Benefits

XR 80 UPFLOW/HORIZONTAL RIGHT or LEFT

STANDARD EQUIPMENT• Power supply 115/1/60

• Multi-port In-shot burners

• Integrated solid state control withself diagnostics

• Silicon Nitride hot surface igniter withadaptive heat up

• Complete front service access

• Heavy guage aluminized steel heatexchanger

• Slide out blower assembly

• Blower door safety switch

• Direct drive, 4-speed motor

• Optional L.P. conversion kit

• Common vent

• Alternate bottom/left/right return air

• Hinged blower door

• Perfect Fit door latches

• Gasketed blower door

• Single wire twinning

• Selectable cooling fan off delay

• Left-right gas connection

• Optional L.P. conversion kit

• Common vent capability

• 24 volt fuse

• Manual reset flame roll out switches

• Insulated blower door

• Insulated blower compartment

• Accessory hook-up capability - Humand EAC

• Blower door safety switch

• Non-prorated 20-year heat ex-changer limited warranty

• 5-year limited parts warranty

XR 80 OPTIONAL EQUIPMENT

Thermostat ................................................................................................................................................................. BAYSTAT388 [ ]Thermostat, Heating/Cooling Single Stage (Mounts Horizontally) ...................................................................................... AY28X092 [ ]Thermostat, Heating/Cooling Single Stage (Mounts Vertically) ...................................................................................... BAYSTAT305 [ ]Thermostat, Electronic Programmable 1-Stage Heating/1-Stage Cooling .................................................................... TAYSTAT300C [ ]Propane Conversion Kit ........................................................................................................................................... BAYLPKT210A [ ]Electronic Air Filter, “Perfect Fit” Super Efficiency (14-1/2" Wide Gas Furnace) .......................................................... TFE145A9FR1 [ ]Electronic Air Filter, “Perfect Fit” Super Efficiency (17-1/2" Wide Gas Furnace) .......................................................... TFE175A9FR1 [ ]Electronic Air Filter, “Perfect Fit” Super Efficiency (21" Wide Gas Furnace) ................................................................ TFE210A9FR1 [ ]Electronic Air Filter, “Perfect Fit” Super Efficiency (24-1/2" Wide Gas Furnace) .......................................................... TFE245A9FR1 [ ]Electronic Air Filter, “Perfect Fit” High Efficiency (14-1/2" Wide Gas Furnace) ............................................................ TFM145A9FR1 [ ]Electronic Air Filter, “Perfect Fit” High Efficiency (17-1/2" Wide Gas Furnace) ............................................................ TFM175A9FR1 [ ]Electronic Air Filter, “Perfect Fit” High Efficiency (21" Wide Gas Furnace) .................................................................. TFM210A9FR1 [ ]Electronic Air Filter, “Perfect Fit” High Efficiency (24-1/2" Wide Gas Furnace) ............................................................ TFM245A9FR1 [ ]Electronic Air Filter, “Perfect Fit” Standard Efficiency (17-1/2" Wide Gas Furnace) .................................................... TFP175A9FR01 [ ]Electronic Air Filter, “Perfect Fit” Standard Efficiency (21" Wide Gas Furnace) ......................................................... TFP210A9FR01 [ ]Electronic Air Filter, “Perfect Fit” Standard Efficiency (24-1/2" Wide Gas Furnace) .................................................... TFP245A9FR01 [ ]Coil Enclosure (14-1/2" Wide Cabinets) ....................................................................................................................BAYCLE1400C [ ]Coil Enclosure (17-1/2" Wide Cabinets) ....................................................................................................................BAYCLE1700C [ ]Coil Enclosure (21" Wide Cabinets) ..........................................................................................................................BAYCLE2100C [ ]Coil Enclosure (24-1/2" Wide Cabinets) ....................................................................................................................BAYCLE2400C [ ]High Altitude Pressure Switch Kit ............................................................................................................................... BAYHALT248 [ ]Masonry Chimney Vent Kit ...................................................................................................................................... BAYVENT800B [ ]Filter Rack Kit ......................................................................................................................................................... BAYRACK960A [ ]

Page 5: Upflow/Horizontal Right or Upflow/Horizontal Left Induced ... · Upflow/Horizontal Right or Upflow/Horizontal Left Induced Draft Gas Furnace XR 80 PUB. NO. 22-1640-09 TDD-D-1 TUD1A040A9241A,

5Pub. No. 22-1640-09

MODELTYPERATINGS 22222Input BTUHCapacity BTUH (ICS) 33333AFUETemp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)HEAT EXCHANGERType-Fired

-UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 44444Ampacity (In Amps)Max Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs)

GeneralData

1 Central Furnace heating designs are certified by AGA and CSA.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian

applicaitons, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

PRODUCT SPECIFICATIONS 11111

TUD1A040A9241AUpflow / Horizontal

40,00032,000

80.030 - 60DIRECT10 x 6

14

See Fan Performance Table1 /5

1080115/1/60

CentrifugalDirect - 1

1/50 - 3000115/1/60

1.0No

High Velocity1 - 16x25 - 1in.

4 Round

Aluminized Steel - Type I

2 0

2 — 452 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

2115/1/60

6.31 51/2

H x W x D41-3/4 x 16-1/2 x 30-1/2

119 / 110

TUD1A060A9241AUpflow / Horizontal

60,00047,000

80.035 - 65DIRECT10 x 6

14

See Fan Performance Table1 /5

1080115/1/60

CentrifugalDirect - 1

1/50- 3000115/1/60

1.0No

High Velocity1 - 16x25 - 1in.

4 Round

Aluminized Steel - Type I

2 0

3 — 453 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

3115/1/60

10.4151/2

H x W x D41-3/4 x 16-1/2 x 30-1/2

124 / 115

TUD1A040A9301AUpflow / Horizontal

40,00032,000

80.030 - 60DIRECT10 x 6

14

See Fan Performance Table1 /3

1075115/1/60

CentrifugalDirect - 1

1/50 - 3000115/1/60

1.0No

High Velocity1 - 16x25 - 1in.

4 Round

Aluminized Steel - Type I

2 0

2 — 452 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

2115/1/60

6.31 51/2

H x W x D41-3/4 x 16-1/2 x 30-1/2

122 / 113

Page 6: Upflow/Horizontal Right or Upflow/Horizontal Left Induced ... · Upflow/Horizontal Right or Upflow/Horizontal Left Induced Draft Gas Furnace XR 80 PUB. NO. 22-1640-09 TDD-D-1 TUD1A040A9241A,

6 Pub. No. 22-1640-09

TUD1B080A9241AUpflow / Horizontal

80,00064,000

80.050 - 80DIRECT

9 x 714

See Fan Performance Table1 /5

1080115/1/60

CentrifugalDirect - 1

1/50- 3000115/1/60

1.0No

High Velocity1 - 17x25 - 1in.

4 Round

Aluminized Steel - Type I

2 0

4 — 454 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

4115/1/60

10.41 51/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

139 / 129

MODELTYPERATINGS 22222Input BTUHCapacity BTUH (ICS) 33333AFUETemp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)HEAT EXCHANGERType-Fired

-UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 44444Ampacity (In Amps)Max Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs)

TUD1A060A9361AUpflow / Horizontal

60,00047,000

80.030 - 60DIRECT10 x 6

14

See Fan Performance Table1/3

1075115/1/60

CentrifugalDirect - 11/50- 3000115/1/60

1.0No

High Velocity1 - 16x25 - 1in.

4 Round

Aluminized Steel - Type I

2 0

3 — 453 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

3115/1/60

9.0151/2

H x W x D41-3/4 x 16-1/2 x 30-1/2

127 / 118

TUD1B060A9361AUpflow / Horizontal

60,00047,000

80.030 - 60DIRECT10 x 7

14

See Fan Performance Table1 /3

1075115/1/60

CentrifugalDirect - 1

1/50- 3000115/1/60

1.0No

High Velocity1 - 17x25 - 1in.

4 Round

Aluminized Steel - Type I

2 0

3 — 453 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

3115/1/60

9.0151/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

137 / 127

1 Central Furnace heating designs are certified by AGA and CSA.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian

applicaitons, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

PRODUCT SPECIFICATIONS 11111

GeneralData

Page 7: Upflow/Horizontal Right or Upflow/Horizontal Left Induced ... · Upflow/Horizontal Right or Upflow/Horizontal Left Induced Draft Gas Furnace XR 80 PUB. NO. 22-1640-09 TDD-D-1 TUD1A040A9241A,

7Pub. No. 22-1640-09

GeneralData

C

MODELTYPERATINGS 22222Input BTUHCapacity BTUH (ICS) 33333AFUETemp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)HEAT EXCHANGERType-Fired

-UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 44444Ampacity (In Amps)Max Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs)

PRODUCT SPECIFICATIONS 11111

TUD1B080A9361AUpflow / Horizontal

80,00063,000

80.030 - 60DIRECT10 x 7

14

See Fan Performance Table1 /3

1075115/1/60

CentrifugalDirect - 1

1/50- 3000115/1/60

1.0No

High Velocity1 - 17x25 - 1in.

4 Round

Aluminized Steel - Type I

2 0

4 — 454 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

4115/1/60

10.41 51/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

142 / 132

TUD1B080A9481AUpflow / Horizontal

80,00064,000

80.030 - 60DIRECT10 x 8

14

See Fan Performance Table1 /3

1075115/1/60

CentrifugalDirect - 1

1/50- 3000115/1/60

1.0No

High Velocity1 - 17x25 - 1in.

4 Round

Aluminized Steel - Type I

2 0

4 — 454 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

4115/1/60

9.11 51/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

142 / 132

TUD1C080A9601AUpflow / Horizontal

80,00064,000

80.025 - 55DIRECT11 x10

14

See Fan Performance Table3 /4

1100115/1/60

CentrifugalDirect - 1

1/50- 3000115/1/60

1.0No

High Velocity1 - 20x25 - 1in.

4 Round

Aluminized Steel - Type I

2 0

4 — 454 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

4115/1/60

13.81 51/2

H x W x D41-3/4 x 23 x 30-1/2

162 / 151

Page 8: Upflow/Horizontal Right or Upflow/Horizontal Left Induced ... · Upflow/Horizontal Right or Upflow/Horizontal Left Induced Draft Gas Furnace XR 80 PUB. NO. 22-1640-09 TDD-D-1 TUD1A040A9241A,

8 Pub. No. 22-1640-09

GeneralData

1 Central Furnace heating designs are certified by AGA and CSA.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian

applicaitons, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

MODELTYPERATINGS 22222Input BTUHCapacity BTUH (ICS) 33333AFUETemp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)HEAT EXCHANGERType-Fired

-UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 44444Ampacity (In Amps)Max Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs)

PRODUCT SPECIFICATIONS 11111

TUD1B100A9361AUpflow / Horizontal

100,00079,000

80.040 - 70DIRECT10 x 7

14

See Fan Performance Table1 /3

1075115/1/60

CentrifugalDirect - 1

1/50- 3000115/1/60

1.0No

High Velocity1 - 17x25 - 1in.

4 Round

Aluminized Steel - Type I

2 0

5 — 455 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

5115/1/60

10.41 51/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

151 / 141

TUD1B100A9451AUpflow / Horizontal

100,00079,000

80.035 - 65DIRECT10 x 8

14

See Fan Performance Table1 /3

1075115/1/60

CentrifugalDirect - 1

1/50- 3000115/1/60

1.0No

High Velocity1 - 17x25 - 1in.

4 Round

Aluminized Steel - Type I

2 0

5 — 455 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

5115/1/60

10.41 51/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

153 / 143

TUD1C100A9481AUpflow / Horizontal

100,00079,000

80.035 - 65DIRECT10 x 8

14

See Fan Performance Table1 /2

1075115/1/60

CentrifugalDirect - 1

1/50- 3000115/1/60

1.0No

High Velocity1 - 20x25 - 1in.

4 Round

Aluminized Steel - Type I

2 0

5 — 455 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

5115/1/60

11.6151/2

H x W x D41-3/4 x 23 x 30-1/2

162 / 151

TUD1C100A9601AUpflow / Horizontal

100,00079,000

80.030 - 60DIRECT11 x 10

14

See Fan Performance Table1 /2

1075115/1/60

CentrifugalDirect - 1

1/50- 3000115/1/60

1.0No

High Velocity1 - 20x25 - 1in.

4 Round

Aluminized Steel - Type I

2 0

5 — 455 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

5115/1/60

12.81 51/2

H x W x D41-3/4 x 23 x 30-1/2

162 / 151

Page 9: Upflow/Horizontal Right or Upflow/Horizontal Left Induced ... · Upflow/Horizontal Right or Upflow/Horizontal Left Induced Draft Gas Furnace XR 80 PUB. NO. 22-1640-09 TDD-D-1 TUD1A040A9241A,

9Pub. No. 22-1640-09

GeneralData

1 Central Furnace heating designs are certified by AGA and CSA.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian

applicaitons, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

MODELTYPERATINGS 22222Input BTUHCapacity BTUH (ICS) 33333AFUETemp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)HEAT EXCHANGERType-Fired

-UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 44444Ampacity (In Amps)Max Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs)

PRODUCT SPECIFICATIONS 11111

TUD1D100A9721AUpflow / Horizontal

100,0008000080.0

30 - 60DIRECT11 x 10

14

See Fan Performance Table3 /4

1100115/1/60

CentrifugalDirect - 1

1/50 - 3000115/1/60

1.0No

High Velocity1 - 24x25 - 1in.

4 Round

Aluminized Steel - Type I

2 0

5 — 455 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

5115/1/60

13.11 51/2

H x W x D41-3/4 x 26-1/2 x 30-1/2

175 / 163

TUD1C120A9541AUpflow / Horizontal

120,00096,000

80.035 - 65DIRECT11 x 10

14

See Fan Performance Table1 /2

1075115/1/60

CentrifugalDirect - 1

1/50 - 3000115/1/60

1.0No

High Velocity1 - 20x25 - 1in.

4 Round

Aluminized Steel - Type I

2 0

6 — 456 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

6115/1/60

12.81 51/2

H x W x D41-3/4 x 23 x 30-1/2

176 / 164

TUD1D120A9601AUpflow / Horizontal

120,00096,000

80.030 - 60DIRECT11 x 10

14

See Fan Performance Table1 /2

1075115/1/60

CentrifugalDirect - 1

1/50 - 3000115/1/60

1.0No

High Velocity1 - 24x25 - 1in.

4 Round

Aluminized Steel - Type I

2 0

6 — 456 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

6115/1/60

12.81 51/2

H x W x D41-3/4 x 26-1/2 x 30-1/2

186 / 174

TUD1D140A9601AUpflow / Horizontal

140,000111,000

80.040 - 70DIRECT11 x 10

14

See Fan Performance Table3 /4

1075115/1/60

CentrifugalDirect - 1

1/50 - 3000115/1/60

1.0No

High Velocity1 - 24x25 - 1in.

4 Round

Aluminized Steel - Type I

2 0

7 — 457 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

7115/1/60

13.11 51/2

H x W x D41-3/4 x 26-1/2 x 30-1/2

193 / 181

Page 10: Upflow/Horizontal Right or Upflow/Horizontal Left Induced ... · Upflow/Horizontal Right or Upflow/Horizontal Left Induced Draft Gas Furnace XR 80 PUB. NO. 22-1640-09 TDD-D-1 TUD1A040A9241A,

10 Pub. No. 22-1640-09

PerformanceData

FURNACE AIRFLOW (CFM) VS. STATIC PRESSURE (ins. w.g.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

TUD1A040A9241A 4 -3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

1018847716617

1004832701599

982809678575

950779648544

910742610507

860697585463

802644512413

763585452357

660517384294

TUD1A040A9301A 4 -3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

130711721030892

126211401007876

12111100976856

11641053938893

1092996893789

1023937840744

949867779691

869791712630

783707636561

TUD1A060A9241A 4 -3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

1013835712611

997821702596

973800683573

941771655543

901734617505

852689571459

796636516406

731575452345

659506379277

TUD1A060A9361A 4 -3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

142612431042900

138912251039903

134511971027895

129811601005877

12361113973848

11711057931809

1099991879760

1020916817700

934831745629

TUD1B060A9361A 4 -3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

158813291090894

155413181090901

151712991093904

146812681076894

141212281052881

135111861028860

12781135978828

12001072917777

1102988836683

TUD1B080A9241A 4 -3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

1115919772643

1094912767655

1060891750648

1014857722622

956809681577

886747629512

803671565428

708582489325

600478401203

TUD1B080A9361A 4 -3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

139312101046900

138412091052903

136411981047895

133511771033888

129611471008869

12471107963842

11891058928808

1120999873766

1042930808717

TUD1B080A9481A 4 -3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

183913231092788

182113251090783

179613291091780

175613191083768

171013081076758

164112751059737

157312461040719

148012011005647

13921165970630

TUD1C080A9601A 4 -3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

2308200616901437

2281199716911437

2254198716911437

2209196016831434

2163193316741431

2095188816511418

2026184216271404

1950178015561369

1873171814851334

TUD1B100A9361A 4 -3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

147612491020873

146412571046887

144112521058890

140812341050883

136312031028864

13071158990834

12411101936794

11631030866742

1074946780680

TUD1B100A9451A 4 -3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

177113751127780

173113711141815

135513281124829

162413281124822

155612891094796

147912381049749

13921176989681

12961102914593

11911016825485

TUD1C100A9481A 4 -3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

1880166214281208

1846163514211215

1799159814021210

1740155113701193

1669149313261164

1595142412691124

1489134511991073

1381125611171009

126011571022935

TUD1C100A9601A 4 -3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

2181190816211443

2143188816091419

2104186815971395

2053183415821381

2001180015671367

1929174515331335

1856169014981302

1766163114381256

1676157213771209

Page 11: Upflow/Horizontal Right or Upflow/Horizontal Left Induced ... · Upflow/Horizontal Right or Upflow/Horizontal Left Induced Draft Gas Furnace XR 80 PUB. NO. 22-1640-09 TDD-D-1 TUD1A040A9241A,

11Pub. No. 22-1640-09

CFM VS. TEMPERATURE RISE

MODELCubic Feet Per Minute (CFM)

500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400

TUD1A040A9241A 59 49 42 37 33 30

TUD1A040A9301A 59 49 42 37 33

TUD1A060A9241A 63 56 49 44

TUD1A060A9361A 56 49 44 40 37 34 32

TUD1B060A9361A 56 49 44 40 37 34 32

TUD1B080A9241A 74 66 59 54

TUD1B080A9361A 59 54 49 46 42

TUD1B080A9481A 59 54 49 46 42 40 37 35 33

TUD1C080A9601A 54 49 46 42 40 37 35 33 31 30 28 27 26

TUD1B100A9361A 67 62 57 53 49

TUD1B100A9451A 62 57 53 49 46 44 41

TUD1C100A9481A 67 62 57 53 49 46 44 41 39 37

TUD1C100A9601A 62 57 53 49 46 44 41 39 37 35 34 32 31

TUD1D100A9721A 62 57 53 49 46 44 41 39 37 35 34 32 31

TUD1C120A9541A 63 59 56 52 49 47 44 42 40

TUD1D120A9601A 59 56 52 49 47 44 42 40

TUD1D140A9601A 69 65 61 58 55 52 49 47 45

PerformanceData

FURNACE AIRFLOW (CFM) VS. STATIC PRESSURE (ins. w.g.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

TUD1D100A9721ABOTTOM AND

LEFT SIDERETURN

4 -3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

2484 2458 2432 2387 2342SEE

NOTE1

2275 2208 2125 2041

TUD1D100A9721A 4 -3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

2447209717531459

2401208817501456

2356207917481453

2303205317321443

2249202817161434

2173197016901407

2097191216651380

1994183115941335

1892175015231289

TUD1C120A9541A 4 -3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

2162188916541427

2130188116431421

2097187316311414

2067183916191400

2037180516061386

1976177615721357

1914174615381327

1833167014831285

1752159314281243

TUD1D120A9601A 4 -3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

2135190616461423

21011881416321415

2066185616171407

2036181715961391

2005177715751375

1923172415351338

1840167114941300

1750160214271246

1659153313601192

TUD1D140A9601A 4 -3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

2462212817551450

2407211217461446

2351209617361442

2284205417191427

2216201117021411

2143194916561383

2069188716091354

1989179715641298

1908170615181241

Note 1: High speed CFM is based on bottom and left side return option for this model. Medium High, Medium Low, and Low speedtaps for this model do not have improved airflow with the addition of side return.

Page 12: Upflow/Horizontal Right or Upflow/Horizontal Left Induced ... · Upflow/Horizontal Right or Upflow/Horizontal Left Induced Draft Gas Furnace XR 80 PUB. NO. 22-1640-09 TDD-D-1 TUD1A040A9241A,

12 Pub. No. 22-1640-09

FieldWiring

FIELD WIRING DIAGRAM FOR HEATING ONLY

FIELD WIRING DIAGRAM FOR SINGLE STAGE HEATING/COOLING(OUTDOOR SECTION WITHOUT TRANSFORMER)

From Dwg.. 21B341437 Rev. 1

From Dwg.. 21B341436 Rev. 1

Page 13: Upflow/Horizontal Right or Upflow/Horizontal Left Induced ... · Upflow/Horizontal Right or Upflow/Horizontal Left Induced Draft Gas Furnace XR 80 PUB. NO. 22-1640-09 TDD-D-1 TUD1A040A9241A,

13Pub. No. 22-1640-09

FieldWiring

From Dwg.. 21B341422 Rev. 1

From Dwg.. 21B341423 Rev. 1

Page 14: Upflow/Horizontal Right or Upflow/Horizontal Left Induced ... · Upflow/Horizontal Right or Upflow/Horizontal Left Induced Draft Gas Furnace XR 80 PUB. NO. 22-1640-09 TDD-D-1 TUD1A040A9241A,

14 Pub. No. 22-1640-09

Dimensions

TUD

1 O

UTL

INE

DR

AW

ING

(AL

L D

IME

NS

ION

S A

RE

IN

IN

CH

ES

)

MO

DE

LD

IM "

A"

DIM

"B

"D

IM "

C"

DIM

"D

"

TU

D1A

040C

924A

TU

D1A

040C

930A

TU

D1A

060C

924A

TU

D1A

060C

936A

14-1

/2"

9-5/

8"13

-1/4

"13

"

TU

D1B

060A

936A

TU

D1B

080C

924A

TU

D1B

080C

936A

TU

D1B

080C

948A

TU

D1B

100C

936A

TU

D1B

100C

945A

17-1

/2"

9-5/

8"16

-1/4

"16

"

TU

D1C

080C

960A

TU

D1C

100C

948A

TU

D1C

100C

960A

TU

D1C

120C

954A

21"

13-1

/16"

19-3

/4"

19-1

/2"

TU

D1D

100C

972A

TU

D1D

120C

960A

TU

D1D

140C

960A

24-1

/2"

15-5

/16"

23-1

/4"

23"

Page 15: Upflow/Horizontal Right or Upflow/Horizontal Left Induced ... · Upflow/Horizontal Right or Upflow/Horizontal Left Induced Draft Gas Furnace XR 80 PUB. NO. 22-1640-09 TDD-D-1 TUD1A040A9241A,

15Pub. No. 22-1640-09

ElectricalData

SCHEMATIC DIAGRAMS FOR GAS FURNACES

TABLE A

SPEED TAPS FOR I.D. FAN MOTOR

MODELS HEAT"A"

PARK"B"

PARK"C"

*UD1A040A9241A YL RD BL

*UD1A040A9301A RD BL YL

*UD1A060A9241A BL RD YL

*UD1A060A9361A YL RD BL

*UD1B060A9361A RD YL BL

*UD1B080A9241A BL RD YL

*UD1B080A9361A BL RD YL

*UD1B080A9481A BL RD YL

*UD1C080A9601A RD BL YL

*UD1B100A9361A BL RD YL

*UD1B100A9451A BL RD YL

*UD1C100A9481A BL RD YL

*UD1C100A9601A YL BL RD

*UD1D100A9721A RD YL BL

*UD1C120A9541A BL RD YL

*UD1D120A9601A BL RD YL

*UD1D140A9601A BL RD YL

(1) RED - LOW(2) YELLOW - MED LOW(3) BLUE - MED HIGH(4) BLACK - HIGH

Page 16: Upflow/Horizontal Right or Upflow/Horizontal Left Induced ... · Upflow/Horizontal Right or Upflow/Horizontal Left Induced Draft Gas Furnace XR 80 PUB. NO. 22-1640-09 TDD-D-1 TUD1A040A9241A,

Since The Trane Company has a policy of continuous product and product data improvement, it reservesthe right to change design and specifications without notice.

The Trane Company6200 Troup HighwayTyler, TX 75707

File No. PL-UN-FURN-TDD-D-1 3/98 P.I.

Supersedes TDD-D-1 8/95