Use of CO2 Concentrations or CO2 Balance to Estimate ... · ... of accuracy in quantifying air...

15
The authors are solely responsible for the content of this technical presentation. The technical presentation does not necessarily reflect the official position of the American Society of Agricultural and Biological Engineers (ASABE), and its printing and distribution does not constitute an endorsement of views which may be expressed. Technical presentations are not subject to the formal peer review process by ASABE editorial committees; therefore, they are not to be presented as refereed publications. Citation of this work should state that it is from an ASABE meeting paper. EXAMPLE: Author's Last Name, Initials. 2006. Title of Presentation. ASABE Paper No. 06xxxx. St. Joseph, Mich.: ASABE. For information about securing permission to reprint or reproduce a technical presentation, please contact ASABE at [email protected] or 269-429-0300 (2950 Niles Road, St. Joseph, MI 49085-9659 USA). An ASABE Meeting Presentation Paper Number: 064156 Use of CO 2 Concentrations or CO 2 Balance to Estimate Ventilation Rate of Modern Commercial Broiler Houses H. Xin 1 , H. Li 1 , R. T. Burns 1 , R. S. Gates 2 , D. G. Overhults 2 , J. W. Earnest 2 , L. B. Moody 1 , and S. J. Hoff 1 1 Dept. of Agricultural & Biosystems Engineering, Iowa State University, Ames, IA 2 Dept. of Biosystems & Agricultural Engineering, University of Kentucky, Lexington, KY Written for presentation at the 2006 ASABE Annual International Meeting Sponsored by ASABE Oregon Convention Center Portland, Oregon 9 - 12 July 2006 Abstract. Ventilation rate (VR) is one of the two key elements for quantifying aerial emissions from animal production facilities. Direct measurement of building VR can be challenging and impractical under certain circumstances, e.g., naturally ventilated animal housing. This study delineates VR of broiler houses with build-up litter as estimated via CO 2 balance or building CO 2 concentration. The indirectly derived VR compared favorably with the directly measured VR. Specifically, integration time of 30 min or longer leads to non-significant differences in VR between the indirect and the direct methods (P>0.2). Omission of CO 2 generation by the litter from total house CO 2 production results in an overall 7% underestimation of the building VR. The indirect method provides a possible, viable alternative for quantifying VR of naturally ventilated broiler confinement. Keywords. Air emissions, metabolic rate, indirect animal calorimetry, Fan Assessment Numeration System (FANS)

Transcript of Use of CO2 Concentrations or CO2 Balance to Estimate ... · ... of accuracy in quantifying air...

The authors are solely responsible for the content of this technical presentation. The technical presentation does not necessarily reflect the official position of the American Society of Agricultural and Biological Engineers (ASABE), and its printing and distribution does not constitute an endorsement of views which may be expressed. Technical presentations are not subject to the formal peer review process by ASABE editorial committees; therefore, they are not to be presented as refereed publications. Citation of this work should state that it is from an ASABE meeting paper. EXAMPLE: Author's Last Name, Initials. 2006. Title of Presentation. ASABE Paper No. 06xxxx. St. Joseph, Mich.: ASABE. For information about securing permission to reprint or reproduce a technical presentation, please contact ASABE at [email protected] or 269-429-0300 (2950 Niles Road, St. Joseph, MI 49085-9659 USA).

An ASABE Meeting Presentation Paper Number: 064156

Use of CO2 Concentrations or CO2 Balance to Estimate Ventilation Rate of Modern Commercial Broiler Houses

H. Xin1, H. Li1, R. T. Burns1, R. S. Gates2, D. G. Overhults2, J. W. Earnest2, L. B. Moody1, and S. J. Hoff1

1 Dept. of Agricultural & Biosystems Engineering, Iowa State University, Ames, IA 2 Dept. of Biosystems & Agricultural Engineering, University of Kentucky, Lexington, KY

Written for presentation at the 2006 ASABE Annual International Meeting

Sponsored by ASABE Oregon Convention Center

Portland, Oregon 9 - 12 July 2006

Abstract. Ventilation rate (VR) is one of the two key elements for quantifying aerial emissions from animal production facilities. Direct measurement of building VR can be challenging and impractical under certain circumstances, e.g., naturally ventilated animal housing. This study delineates VR of broiler houses with build-up litter as estimated via CO2 balance or building CO2 concentration. The indirectly derived VR compared favorably with the directly measured VR. Specifically, integration time of 30 min or longer leads to non-significant differences in VR between the indirect and the direct methods (P>0.2). Omission of CO2 generation by the litter from total house CO2 production results in an overall 7% underestimation of the building VR. The indirect method provides a possible, viable alternative for quantifying VR of naturally ventilated broiler confinement.

Keywords. Air emissions, metabolic rate, indirect animal calorimetry, Fan Assessment Numeration System (FANS)

ASABE Paper 064156 – Xin et al. P1

Introduction Quantification and mitigation of aerial emissions from animal feeding operations (AFOs) continue to draw attention from the animal industry, academic community, and local or federal environment regulatory agencies. Determination of aerial emission rate requires the knowledge of concentration of the substance in question and air exchange rate through the source at the given time. The advancement of electronic environmental monitoring instruments has made it possible to continuously monitor concentrations of common gases (e.g., NH3, H2S, CO2, CH4) from manure decomposition and/or animal respiration over prolonged period. Great strides have also been made recently toward improving the degree of accuracy in quantifying air exchange rate of mechanically ventilated buildings (Simmons et al., 1998; Gates et al., 2004; Xin et al., 2003). Nonetheless, continuously monitoring the operational status and regularly checking or calibrating the airflow capacity of ventilation fans is a non-trivial task. For instance, a commercial laying hen house can have as many as 100 ventilation fans. Moreover, our ability to quantify aerial emissions from naturally ventilated AFO facilities (e.g., most of grower-finisher turkey barns) has been rather limited due to lack of affordable and reliable means to determine air ventilation rate of the facility.

Consequently, indirect methods to estimate building ventilation rate with reasonable certainty would be particularly attractive when dealing with naturally ventilated barns or mechanically ventilated barns using an excess number of ventilation fans. One such indirect method involves the use of tracer gases in the ventilated building or space and monitoring of decay rate of the gas concentration, from which the ventilation rate is derived. Releasable tracer gases that have been used in livestock-related cases include carbon monoxide, helium and sulphur hexafluoride (SF6) (Phillips, et al., 2000, 2001). However, their applications in commercial production facilities are often limited because it requires uniform air-tracer mixing to ensure good result, which is difficult to achieve under commercial production settings. In addition to releasable tracers, metabolic carbon dioxide (CO2) is available in livestock buildings as a tracer. The validity of CO2 balance method depends on the reliability of the metabolic data of the animals and the degree of non-animal respiration CO2 contribution. The CO2 balance method was compared with direct measurement method for determining ventilation rate of modern manure-belt laying hen houses (Li et al., 2005), which showed good promise. Data on broiler metabolic rate have recently been updated by CIGR (2002). However, performance of the indirect method remains to be evaluated under field production conditions where decomposition of the litter may contribute to the in-house CO2 generation and thus to determination of the building ventilation rate.

The objective of this paper was to delineate the relationship between CO2 concentration of the exhaust air and ventilation rate of broiler houses with build-up litters. Direct measurement of the building ventilation rate was made by continuously monitoring the operational status of the in-situ calibrated ventilation fans.

Materials and Methods

Broiler Houses and Management

This study was a part of a larger project that measures gaseous and particulate matter (PM) emissions from two commercial broiler houses located in western Kentucky (figures 1 & 2). The two broiler houses were located on two farms 64 km (40 miles) apart. Both broiler houses were built in the early 90’s and each measured 13.1 x 155.5 m (43 x 510 ft). The houses had wooden truss structure with insulated drop ceilings. Supplemental heating was provided with 26 pancake brooders (8.8 kW or 30,000 Btu/hr each) and three gas-fired space furnace (65.9 kW or 225,000 Btu/hr each). House ventilation was provided through static-pressure controlled box air inlets (15 x 66 cm each) along the sidewalls (26 per sidewall) together with four 91-cm (36-in)

ASABE Paper 064156 – Xin et al. P2

diameter sidewall exhaust fans spaced approximately 37 m (120 ft) apart and ten 123-cm (48-in) diameter tunnel fans located at one end of the building. One of the sidewall fans (SW1) located in the brooding end of each house was used to provide minimum ventilation. The houses also were each equipped with two 24-m (80-ft) sections of evaporative cooling pads in the opposite end of the tunnel fans. Additional cooling was provided, as needed, with foggers distributed throughout the house. The houses were used to raise Cobb x Cobb, straight-run (i.e., mixed sex) broilers for the same integrator, hence following the same management practices. Initial chick placement was 25,800 in winter and 24,400 in summer. The birds were raised to 50 - 53 days for a market body weight of approximately 2.73 kg (6 lb). Mixture of rice hulls and sawdust was used as litter bedding. The data reported in this paper corresponded to a litter age of second flock in one house (location 1) and third flock in the other house (location 2).

Measurement Instruments and Data Acquisition

Two mobile air emissions monitoring units (MAEMU), designed and fabricated at Iowa State University, were used in this study (figures 1 & 2), one per monitored house/site. The monitored gases included ammonia (NH3), carbon dioxide (CO2), total hydrocarbon (THC), and methane (CH4), and were measured using a fast-response, stable and H2O-compensated photoacoustic multi-gas monitor (Innova 1412, Innova AirTech Instruments A/S, Denmark). Air samples were drawn from three locations in the house to account for potential spatial variations. One sampling location was near the primary minimum ventilation (36-in) sidewall fan (SW1) in the brooding half of the house; the second sampling location was near the third sidewall (36-in) exhaust fan (SW3) (non-brooding end); and the third sampling was near the center of the tunnel end of the house between the first two sets of tunnel fans. Placement of the air sampling ports were as follows: for the two sidewall sampling locations, the sampling ports were located 1.2 m (4 ft) away from the fan in the axial direction, 2.3 m (7.5 ft) in the radial direction, and 1 m (3 ft) above the floor; for the tunnel-end sampling location, the sampling port was located at the center across the house (i.e., 6.55 m or 21.5 ft from each sidewall) and 7.32 m (24 ft) from the end wall. In addition, an outside ambient air sample was taken at 2-hour intervals to provide the background concentration. The ambient sample intake line was located between the inlet boxes opposite of the sidewall with the exhaust fans. The amount of gas in the background was subtracted from that in the exhaust when calculating air emissions from the house.

A positive pressure gas sampling system (GSS) was designed and used for the MAEMU (fig. 3). Four pairs of 2-way solenoid valves (S1-S8) in the GSS were controlled by the data acquisition (DAQ) and control system to take air samples from the four sampling locations. When analyzing each of the in-house air samples, four 30-second measurement cycles by the Innova 1412 analyzer were performed to ensure attainment of 97% or better of true readings of the gaseous concentrations. Selection of the four measurement cycles was based on extensive testing of the instrument response time, both in the laboratory and in the field (injecting calibration gases into the most distant in-house air sampling port). If fans at all three in-house sampling locations were running, the time interval of a complete sampling cycle would be 360 s (120 × 3 = 360 s). To account for potential concentration changes during this period, linear interpolation between the two adjacent readings of the same location was performed to determine the concentrations in between sampling events. If SW4 and/or TF1 fans were not operating, sampling of these locations would be skipped, and the sampling would either remain at SW1 or switch to the background air. Fan airflow rates concomitant with the measured concentrations were used in the calculation of the house emission rate. Only the concentrations at the end of the sampling cycle (fourth readings at any given in-house location) were considered as valid measurements and used to calculate emissions. When sampling the ambient air, the measurement cycle lasted for 8 min to ensure stabilization following the large step change from in-house relatively higher concentrations to the lower ambient concentrations. As mentioned above, the outside ambient

ASABE Paper 064156 – Xin et al. P3

air sample was taken at 2-hour intervals because of its relatively constant gas levels. Burns et al. (2006) gave a more detailed description of the MAEMU development and operation.

The performance curves (airflow vs. static pressure) of the 14 ventilation fans were developed by in-situ calibration of each fan using the fan assessment numeration system (FANS) (Gates et al., 2004). Two 0 to 125 pa (0 to 0.5 inch WC) differential pressure transducers (Model 264, Setra, Boxborough, MA1) with analog output of 4-20 mA were used to measure building static pressure in both brooding and non-brooding portions of the broiler houses. The runtime of each of the 14 exhaust fans was monitored by continuously sensing its ON/OFF state with inductive current switches (ICS) (CR9321, CR MAGNETICS, INC, St. Louis, MO) attached to the power supply cord of the fan motor (figure 4). The 14 ICS were individually connected to a 150 Ω resistor and powered by a 5 VDC power supply. The voltage signals across the resistors were connected to the analog input module of the data acquisition system. These monitoring ICS have been in operation since October 2005 with zero failure or malfunction. Muhlbauer et al. (2006) gave a detailed description of the design, installation and performance of the ICS fan operation-monitoring device.

Relative humidity (RH) transmitters (HMW61U, Vaisala Inc, Woburn, MA) with a measurement range of 0.8 -100% and corresponding analog output of 4-20 mA were used to monitor RH in the houses. Type T thermocouples were used to monitor indoor and outdoor air temperature at the air sampling locations. Barometric pressure sensors (WE100, Global Water Instrumentation, Inc., Gold River, CA) with analog output of 4-20 mA were used for measuring atmospheric pressure.

The data acquisition system consisted of a PC and compact Fieldpoint (cFP-AI-110, National Instruments Corporation, Austin, TX). It is a data acquisition and automation controller composed of rugged I/O modules and intelligent communication interfaces. All the sensors with 4-20 mA analog output are powered by a 24 VDC power supply (100W) and connected directly to the analog input modules (cFP-AI-110, NI). The type T thermocouples were connected to a cFP-TC-120 thermocouple input module. Air sampling solenoid valves were controlled through cFP-DO-400 (NI) digital output module.

Data for fan operation status and other environmental variables were collected by the Compact FieldPoint controller and measurement I/O modules at 1- or 2-s intervals, and recorded as 30-s averages. Instantaneous ventilation rates were calculated based on the real-time fan operation status and building static pressure. The 10-min average of CO2 concentrations, static pressure, barometric pressure, air temperature, and fan runtime were then calculated and analyzed. In addition, a platform, automatic bird-weighing scale (RSC-2, ROTEM Computerized Controllers, Israel) was used to continuously monitor average body weight of the flock. The growth curves of the broilers for the flocks associated with the data analysis of this paper are shown in Figure 5.

The monitoring project follows the EPA’s Category I (most strict) quality assurance project plan (QAPP). Moody et al. (2006) gave a description of the QAPP for the monitoring project.

Direct Measurement of Building Ventilation Rate

As previously mentioned, a FANS unit was used to individually calibrate the airflow rate, thus developing the performance curves of the 14 ventilation fans. The FANS unit was placed upstream against the exhaust fan to be calibrated (figure 6). Since the house normally operated at static pressure of 15-25 Pa (0.06-0.10” H2O), airflow rates of the exhaust fans were evaluated at the static pressure levels of 10, 20, 30, and 40 Pa (0.04, 0.08, 0.12, 0.16” H2O). The tested

1 Mention of product or company names is for presentation clarity and does not imply endorsement by the authors or their affiliated organizations, nor exclusion of other suitable products.

ASABE Paper 064156 – Xin et al. P4

static pressure was achieved by adjusting the inlet opening through the inlet controller. Once the static pressure was stabilized, the FANS unit was run twice (up and down), with each run taking about 3 minutes. If the difference between the two runs was less than 2%, the result was considered acceptable and the average was taken as the data point. Otherwise the procedure was repeated. An inclined barometer (-12.5 to 62.3 Pa or -0.05 to 0.25” H2O) was also used to help set and read the static pressure. The output from the static pressure sensor transmitter of the house was also recorded and used in the subsequent analysis. To eliminate the effect of airflow reduction when a fan operates with its stage members vs. running alone, measurements of the individual fans were conducted for the same stage groupings. Individual fan performance curves were then developed for all the exhaust fans (see figure 7 for an example). Once the actual airflow curves were established for all the exhaust fans and fan operational combinations, the runtime of each fan was monitored and recorded continuously by sensing the ON/OFF state of the ICS driven by the current flow through the fan power supply cord (Muhlbauer et al., 2006). Concurrent measurement of the house static pressure was made with differential pressure sensors. Summation of airflows from the individual operating fans during each monitoring cycle yielded the overall house ventilation rate.

Indirect Determination of Building Ventilation Rate by CO2 Balance

The CO2-balance measurement method is based on the principle of indirect animal calorimetry. Namely, metabolic heat production of non-ruminants is related to oxygen (O2) consumption and CO2 production of the animals, of the following form (Brouwer, 1965):

THP = 16.18O2 + 5.02CO2 [1]

where

THP = total heat production rate of the animal, W⋅kg-1

O2 = oxygen consumption rate (mL⋅s-1⋅kg-1)

CO2 = carbon dioxide production rate (mL⋅s-1⋅kg-1)

The ratio of CO2 production and O2 consumption is defined as the respiratory quotient (RQ) of the animal, i.e.,

2

2

O

CORQ = [2]

Substituting equation [2] into [1] and rearranging gives:

02.5/18.162 +=

RQ

THPCO [3]

The CO2 production rate also can be related to building ventilation rate (V, m3⋅hr-1⋅kg-1) as following:

ie COCO

productionCOV

][][10

22

62

−×= [4]

where

[CO2]e and [CO2]i = CO2 concentration of exhaust and incoming air, respectively, ppmv

ASABE Paper 064156 – Xin et al. P5

THP of broilers, as reported by CIGR (2002), and RQ of growing broilers (0.90), as reported by Xin et al. (1996) were used to estimate CO2 production of the broilers using equation [3]. The CIGR THP equation is of the following form:

THP= 10.62 m0.75 [5]

where

m = bird body mass, kg

Data Processing

Because the use of heating fuel (LPG) was not monitored, CO2 production from the brooders and the space furnaces was unknown. Consequently, only the data that corresponded to the periods of no supplemental heating were used in the analysis. The non-supplemental heating periods were determined by monitoring the house temperature change. As a result, a total of 311-hour worth of data were used in deriving the CO2-balance ventilation rate and relate the CO2 concentrations to the directly measured ventilation rate from the two broiler houses during flock production. Table 1 lists the bird age and daily hours involved in this data analysis.

Results and Discussion

CO2 Production Rate from the Litter

Figure 8 shows the decaying CO2 level inside the broiler houses following removal of the flock. The CO2 concentration difference between the empty house and the outside air was around 35 ppm with a 60 m3/s (127,134 CFM) ventilation rate. This translated to a CO2 production rate of 4.0 g/s from the litter, and it should be included in the CO2 production rate from the broiler house when conducting the mass balance.

Directly Measured Ventilation Rate vs. CO2 Concentration Difference

Ideally, CO2 concentration in fresh inlet air is constant at about 350 ppm. In reality, CO2 concentrations of the inlet air ranged from 350 to 500 ppm presumably due to partial return of the house exhaust air. The difference in CO2 concentration between inlet and outlet air varied from 200 to 2566 ppm during the measurement period. The building ventilation rate [m3⋅s-1] and CO2 concentration difference [PPM] between the exhaust air and inlet air at various integration times were of the following functional relationships:

For 10 min integration time, VR = 3135.0 ∆CO2-0.7250 (R2 = 0.7054) [6]

For 30 min integration time, VR = 4455.6 ∆CO2-0.7857 (R2 = 0.9162) [7]

For 60 min integration time, VR = 4630.7 ∆CO2-0.7130 (R2 = 0.9164) [8]

For 120 min integration time, VR = 4970.4 ∆CO2-0.8043 (R2 = 0.9307) [9]

Table 1. Bird age and daily hours of data used in the analysis of CO2 level vs. building ventilation rate of broiler houses.

Daily hours of data Bird age, day House 1 House 2 24 3 25 11 26 8 29 6 30 12 35 12 36 16 37 6 38 11 39 24 40 16 10 41 22 14 42 7 43 14 9 44 24 9 45 8 15 46 24 47 6 12 48 10 49 2

ASABE Paper 064156 – Xin et al. P6

The relationships are further depicted in Figure 9. The degree of fitness by the regression equations increases with integration time, and the regression coefficient (R2 value) ranged from 0.70 for the 10 min integration time to 0.93 for the 120 min integration time. These functional relationships provide a possible alternative to estimate ventilation rate of naturally ventilated houses for floor-raised broilers.

Directly Measured vs. CO2-Balance Derived Ventilation Rate

Van Ouwerkerk and Pedersen (1994) indicated that to ensure the reliability of the CO2-balance method, the difference in CO2 concentration between outlet and inlet air should exceed 200 ppm. This criterion was met by our data. The dynamic profile of 10-min ventilation rates during a 36-hr period is depicted in Figure 10. Both the directly measured and the CO2-balance derived ventilation rates showed similar patterns in following the outside temperature profile. However, differences of various degrees existed between the two methods. The differences presumably resulted from the dynamic nature of the environmental conditions and activities of the birds, which would have led to deviation of the dynamic THP from the average values used in the calculation. The outside weather, especially wind conditions, also could have temporarily affected the performance of the exhaust fans, which in turn would affect determination of the directly measured ventilation rates.

Paired comparisons of ventilation rates between the direct and indirect methods are shown in Figure 11 for averaging or integration time intervals of 10-min, 30-min, 60-min, or 120-min. The number of observations associated with each of the time intervals were, respectively, 1785, 596, 287, and 144. The directly measured and the CO2-balance derived ventilation rate were of the following relationships for different integration times:

For 10 min integration time, VRCO2-balance = 1.0343 VRdirect (R2 = 0.9051) [10]

For 30 min integration time, VRCO2-balance = 1.0289 VRdirect (R2 = 0.9057) [11]

For 60 min integration time, VRCO2-balance = 1.0273 VRdirect (R2 = 0.9073) [12]

For 120 min integration time, VRCO2-balance = 1.0344 VRdirect (R2 = 0.8802) [13]

The p-values of the paired t-tests were 0.002, 0.235, 0.459 and 0.468, respectively, for the four integration time intervals. Hence, the results indicate that the CO2-balance method with a 30-min or longer integration time interval would yield ventilation rates not significantly different from those obtained by direct measurement (P>0.2). This result paralleled that for manure-belt laying hen houses, as reported by Li et al. (2004).

If only the CO2 production from bird respiration was considered, the CO2 balance method would underestimate the building ventilation rate by 7% (fig. 12).

Conclusions Ventilation rate (VR) of broiler houses with build-up litter, estimated via CO2 balance or building CO2 concentration, compared favorably with that directly measured. Specifically, integration time of 30 min or longer leads to non-significant differences between the indirectly derived VR and the directly measured VR (P>0.2). Omission of CO2 generation by the build-up litter from the total house CO2 production results in an overall 7% underestimation of the building VR. The indirect method provides a possible, viable alternative for quantifying VR of naturally ventilated broiler confinement.

ASABE Paper 064156 – Xin et al. P7

Acknowledgments Financial support of the study was provided in part by the Tyson Foods Inc.

Reference Brouwer, E. 1965. Report of sub-committee on constant and factors. In Energy Metabolism. Proc of

the 3rd Symposium held in Troon, Scotland, ed. K. L. Blaxter. Eur. Assoc for Anim. Prod. 11:441-443.

Burns, R. T., H. Xin, H. Li, S. Hoff, L. Moody, R. S. Gates, D. Overhults and J. Earnest. 2006. Monitoring system design for the southeastern broiler gaseous and particulate matter air emissions monitoring project. Symposium on Air Quality Measurement Methods and Technology, May 9 - 11, 2006, Durham, NC.

Casey, K.D., R.S. Gates, E.F. Wheeler, H. Xin, J.L. Zajaczkowski, P.A., Topper and Y. Liang. 2003. Ammonia emissions from Kentucky broiler houses during winter, Spring and Summer. Proceedings of A&WMA's 97th Annual Conference & Exhibition: Sustainable Development: Gearing Up for the Challenge. June 22-25, 2004. Pittsburgh, PA: A&WMA

CIGR. Heat and moisture production at animal and house level, 2002, 4th Report of working group on climatization of animal houses, CIGR International commission of agricultural engineering, section II, December 2002.

Feddes, J.J.R, J.J. Leonard and J.B. McQuitty. 1984. Carbon dioxide concentration as a measure of air exchange in animal housing. Canadian Agricultural Engineering 26(1): 53-56.

Gates, R. S., K. D. Casey, H. Xin, E. F. Wheeler, and J. D. Simmons. 2004. Fan assessment numeration system (FANS) design and calibration specifications. Transactions of the ASAE 47(5): 1709-1715.

Li, H., H. Xin, Y. Liang, R. S. Gates, E. F. Wheeler, and A. Heber. 2004. Comparison of direct vs. indirect ventilation rate determination for manure-belt laying hen houses. Trans. ASAE 48(1): 367-372.

Moody, L.B., H. Li, R. T. Burns, H. Xin, and R. S. Gates. 2006. AWMA QAPP paper. Quality Assurance Project Plan (QAPP) implementation for the southeastern broiler gaseous and particulate matter air emissions monitoring project. Symposium on Air Quality Measurement Methods and Technology, May 9 - 11, 2006, Durham, NC.

Muhlbauer, R. V., T. A. Shepherd, H. Li, R. T. Burns, H. Xin. 2006. Development and Testing of a Fan Monitoring System using Induction Operated Current Switches. ASABE Technical Paper, St. Joseph, MI: ASABE

Phillips, V. R., R. Scholtens, D.S. Lee, J.A. Garland and R.W. Sneath. 2000. A review of methods for measuring emission rates of ammonia from livestock buildings and slurry or manure stores, Part I: Assessment of basic approaches. J. Agric. Engng. Res. 77(4): 355-364.

Phillips, V. R., D.S. Lee, R. Scholtens, J.A. Garland and R.W. Sneath. 2001. A review of methods for measuring emission rates of ammonia from livestock buildings and slurry or manure stores, Part 2: Monitoring flux rates, concentrations and airflow rates. J. Agric. Engng. Res. 78(1): 1-14.

Simmons, J.D., T. E. Hannigan, and B.D. Lott. 1998. A portable anemometer to determine the output of large in-place ventilation fans. Applied Engineering in Agriculture 14(6):649-653.

Van Ouwerkerk E.N.J. and S. Pedersen. 1994. Application of the carbon dioxide mass balance method to evaluate ventilation rates in livestock buildings. XII World Congress on Agricultural Engineering: Volume 1. Proceedings of a conference held in Milan, Italy, August 29 - September 1, 1994, pp516-529.

Xin, H., Y. Liang, A. Tanaka, R.S. Gates, E.F. Wheeler, K.D. Casey, A.J. Heber, J. Ni and H. Li. 2003. Ammonia emissions from U.S. poultry houses: Part I – Measurement system and techniques. In Proc. Third International Conference on Air Pollution from Agricultural Operations. Oct 12-13, 2003, Raleigh, NC.

Xin, H., J.L. Sell, and D.U. Ahn. 1996. Effects of light and darkness on heat and moisture production of broilers. Transactions of the ASAE 36(6): 2255-2258.

ASABE Paper 064156 – Xin et al. P8

6.9m 7.4m

Brood CurtainEvaporative Coolers

SW1 SW2 SW3 SW4

9 7 5 3 1

10 8 6 4 2

Fan Numbers

Feed Bin Trailer Gravel Pad

Tyson Location 1 Drawing not to scale

Ditch

T, RH T, RH

32m 37m29.9m 41m15.8m

1.5m

71.6m

ControlRoom

155m (outside)

84.4m

15.8m

24.4m

Note: Curtain aligns with end of Feed Bin Pad.

T, RH, B

T

RH = Relative Humidity sample point

= Pressure Differential Sampling Point

= Air sampling point

= 0.9m (36 ”) sidewall fan

= 1.2m (48 ”) fan

T = Temperature sample point= Ambient air sampling point

B = Barometric pressure sample point

13.1m

Brood CurtainEvaporative Coolers

SW1 SW2 SW3 SW4

2 4 6 8 10

1 3 5 7 9 Fan Numbers

Feed Bin

Trailer

Tyson Location 2 Drawing not to scale

ControlRoom

T, RHT, RH

T

37m17.7m

41m37m25.3m 7.5m6.8m15.8m

1.5m

155m (outside)

24.4m

71.8m

86.7m

Note: Curtain aligns with end of Feed Bin Pad.

RH = Relative Humidity sample point

= Pressure Differential Sampling Point

= Air sampling point

= 0.9m (36”) sidewall fan

= 1.2m (48”) fan

T = Temperature sample point= Ambient air sampling point

T, RH and B

B = Barometric pressure sample point

13.1m

6.9m 7.4m

Brood CurtainEvaporative Coolers

SW1 SW2 SW3 SW4

9 7 5 3 1

10 8 6 4 2

Fan Numbers

Feed Bin Trailer Gravel Pad

Tyson Location 1 Drawing not to scale

Ditch

T, RH T, RH

32m 37m29.9m 41m15.8m

1.5m

71.6m

ControlRoom

155m (outside)

84.4m

15.8m

24.4m

Note: Curtain aligns with end of Feed Bin Pad.

T, RH, B

T

RH = Relative Humidity sample point

= Pressure Differential Sampling Point

= Air sampling point

= 0.9m (36 ”) sidewall fan

= 1.2m (48 ”) fan

T = Temperature sample point= Ambient air sampling point

B = Barometric pressure sample point

13.1m

Brood CurtainEvaporative Coolers

SW1 SW2 SW3 SW4

2 4 6 8 10

1 3 5 7 9 Fan Numbers

Feed Bin

Trailer

Tyson Location 2 Drawing not to scale

ControlRoom

T, RHT, RH

T

37m17.7m

41m37m25.3m 7.5m6.8m15.8m

1.5m

155m (outside)

24.4m

71.8m

86.7m

Note: Curtain aligns with end of Feed Bin Pad.

RH = Relative Humidity sample point

= Pressure Differential Sampling Point

= Air sampling point

= 0.9m (36”) sidewall fan

= 1.2m (48”) fan

T = Temperature sample point= Ambient air sampling point

T, RH and B

B = Barometric pressure sample point

13.1m

6.9m 7.4m

Brood CurtainEvaporative Coolers

SW1 SW2 SW3 SW4

9 7 5 3 1

10 8 6 4 2

Fan Numbers

Feed Bin Trailer Gravel Pad

Tyson Location 1 Drawing not to scale

Ditch

T, RH T, RH

32m 37m29.9m 41m15.8m

1.5m

71.6m

ControlRoom

155m (outside)

84.4m

15.8m

24.4m

Note: Curtain aligns with end of Feed Bin Pad.

T, RH, B

T

RH = Relative Humidity sample point

= Pressure Differential Sampling Point

= Air sampling point

= 0.9m (36 ”) sidewall fan

= 1.2m (48 ”) fan

T = Temperature sample point= Ambient air sampling point

B = Barometric pressure sample point

13.1m

Brood CurtainEvaporative Coolers

SW1 SW2 SW3 SW4

2 4 6 8 10

1 3 5 7 9 Fan Numbers

Feed Bin

Trailer

Tyson Location 2 Drawing not to scale

ControlRoom

T, RHT, RH

T

37m17.7m

41m37m25.3m 7.5m6.8m15.8m

1.5m

155m (outside)

24.4m

71.8m

86.7m

Note: Curtain aligns with end of Feed Bin Pad.

RH = Relative Humidity sample point

= Pressure Differential Sampling Point

= Air sampling point

= 0.9m (36”) sidewall fan

= 1.2m (48”) fan

T = Temperature sample point= Ambient air sampling point

T, RH and B

B = Barometric pressure sample point

13.1m

6.9m 7.4m

Brood CurtainEvaporative Coolers

SW1 SW2 SW3 SW4

9 7 5 3 1

10 8 6 4 2

Fan Numbers

Feed Bin Trailer Gravel Pad

Tyson Location 1 Drawing not to scale

Ditch

T, RH T, RH

32m 37m29.9m 41m15.8m

1.5m

77.7m

155m (outside)

84.4m

15.8m

24.4m

Note: Curtain aligns with end of Feed Bin Pad.

T, RH, B

T

RH = Relative Humidity sample point

= Pressure Differential Sampling Point

= Air sampling point

= 0.9m (36 ”) sidewall fan

= 1.2m (48 ”) fan

T = Temperature sample point= Ambient air sampling point

B = Barometric pressure sample point

13.1m

Brood CurtainEvaporative Coolers

SW1 SW2 SW3 SW4

2 4 6 8 10

1 3 5 7 9 Fan Numbers

Feed Bin

Trailer

Tyson Location 2 Drawing not to scale

ControlRoom

T, RHT, RH

T

37m17.7m

41m37m25.3m 7.5m6.8m15.8m

1.5m

155m (outside)

24.4m

86.7m

Note: Curtain aligns with end of Feed Bin Pad.

RH = Relative Humidity sample point

= Pressure Differential Sampling Point

= Air sampling point

= 0.9m (36”) sidewall fan

= 1.2m (48”) fan

T = Temperature sample point= Ambient air sampling point

T, RH and B

B = Barometric pressure sample point

13.1m

6.9m 7.4m

Brood CurtainEvaporative Coolers

SW1 SW2 SW3 SW4

9 7 5 3 1

10 8 6 4 2

Fan Numbers

Feed Bin Trailer Gravel Pad

Tyson Location 1 Drawing not to scale

Ditch

T, RH T, RH

32m 37m29.9m 41m15.8m

1.5m

71.6m

ControlRoom

155m (outside)

84.4m

15.8m

24.4m

Note: Curtain aligns with end of Feed Bin Pad.

T, RH, B

T

RH = Relative Humidity sample point

= Pressure Differential Sampling Point

= Air sampling point

= 0.9m (36 ”) sidewall fan

= 1.2m (48 ”) fan

T = Temperature sample point= Ambient air sampling point

B = Barometric pressure sample point

13.1m

Brood CurtainEvaporative Coolers

SW1 SW2 SW3 SW4

2 4 6 8 10

1 3 5 7 9 Fan Numbers

Feed Bin

Trailer

Tyson Location 2 Drawing not to scale

ControlRoom

T, RHT, RH

T

37m17.7m

41m37m25.3m 7.5m6.8m15.8m

1.5m

155m (outside)

24.4m

71.8m

86.7m

Note: Curtain aligns with end of Feed Bin Pad.

RH = Relative Humidity sample point

= Pressure Differential Sampling Point

= Air sampling point

= 0.9m (36”) sidewall fan

= 1.2m (48”) fan

T = Temperature sample point= Ambient air sampling point

T, RH and B

B = Barometric pressure sample point

13.1m

6.9m 7.4m

Brood CurtainEvaporative Coolers

SW1 SW2 SW3 SW4

9 7 5 3 1

10 8 6 4 2

Fan Numbers

Feed Bin Trailer Gravel Pad

Tyson Location 1 Drawing not to scale

Ditch

T, RH T, RH

32m 37m29.9m 41m15.8m

1.5m

71.6m

ControlRoom

155m (outside)

84.4m

15.8m

24.4m

Note: Curtain aligns with end of Feed Bin Pad.

T, RH, B

T

RH = Relative Humidity sample point

= Pressure Differential Sampling Point

= Air sampling point

= 0.9m (36 ”) sidewall fan

= 1.2m (48 ”) fan

T = Temperature sample point= Ambient air sampling point

B = Barometric pressure sample point

13.1m

Brood CurtainEvaporative Coolers

SW1 SW2 SW3 SW4

2 4 6 8 10

1 3 5 7 9 Fan Numbers

Feed Bin

Trailer

Tyson Location 2 Drawing not to scale

ControlRoom

T, RHT, RH

T

37m17.7m

41m37m25.3m 7.5m6.8m15.8m

1.5m

155m (outside)

24.4m

71.8m

86.7m

Note: Curtain aligns with end of Feed Bin Pad.

RH = Relative Humidity sample point

= Pressure Differential Sampling Point

= Air sampling point

= 0.9m (36”) sidewall fan

= 1.2m (48”) fan

T = Temperature sample point= Ambient air sampling point

T, RH and B

B = Barometric pressure sample point

13.1m

6.9m 7.4m

Brood CurtainEvaporative Coolers

SW1 SW2 SW3 SW4

9 7 5 3 1

10 8 6 4 2

Fan Numbers

Feed Bin Trailer Gravel Pad

Tyson Location 1 Drawing not to scale

Ditch

T, RH T, RH

32m 37m29.9m 41m15.8m

1.5m

71.6m

ControlRoom

155m (outside)

84.4m

15.8m

24.4m

Note: Curtain aligns with end of Feed Bin Pad.

T, RH, B

T

RH = Relative Humidity sample point

= Pressure Differential Sampling Point

= Air sampling point

= 0.9m (36 ”) sidewall fan

= 1.2m (48 ”) fan

T = Temperature sample point= Ambient air sampling point

B = Barometric pressure sample point

13.1m

Brood CurtainEvaporative Coolers

SW1 SW2 SW3 SW4

2 4 6 8 10

1 3 5 7 9 Fan Numbers

Feed Bin

Trailer

Tyson Location 2 Drawing not to scale

ControlRoom

T, RHT, RH

T

37m17.7m

41m37m25.3m 7.5m6.8m15.8m

1.5m

155m (outside)

24.4m

71.8m

86.7m

Note: Curtain aligns with end of Feed Bin Pad.

RH = Relative Humidity sample point

= Pressure Differential Sampling Point

= Air sampling point

= 0.9m (36”) sidewall fan

= 1.2m (48”) fan

T = Temperature sample point= Ambient air sampling point

T, RH and B

B = Barometric pressure sample point

13.1m

6.9m 7.4m

Brood CurtainEvaporative Coolers

SW1 SW2 SW3 SW4

9 7 5 3 1

10 8 6 4 2

Fan Numbers

Feed Bin Trailer Gravel Pad

Tyson Location 1 Drawing not to scale

Ditch

T, RH T, RH

32m 37m29.9m 41m15.8m

1.5m

77.7m

155m (outside)

84.4m

15.8m

24.4m

Note: Curtain aligns with end of Feed Bin Pad.

T, RH, B

T

RH = Relative Humidity sample point

= Pressure Differential Sampling Point

= Air sampling point

= 0.9m (36 ”) sidewall fan

= 1.2m (48 ”) fan

T = Temperature sample point= Ambient air sampling point

B = Barometric pressure sample point

13.1m

Brood CurtainEvaporative Coolers

SW1 SW2 SW3 SW4

2 4 6 8 10

1 3 5 7 9 Fan Numbers

Feed Bin

Trailer

Tyson Location 2 Drawing not to scale

ControlRoom

T, RHT, RH

T

37m17.7m

41m37m25.3m 7.5m6.8m15.8m

1.5m

155m (outside)

24.4m

86.7m

Note: Curtain aligns with end of Feed Bin Pad.

RH = Relative Humidity sample point

= Pressure Differential Sampling Point

= Air sampling point

= 0.9m (36”) sidewall fan

= 1.2m (48”) fan

T = Temperature sample point= Ambient air sampling point

T, RH and B

B = Barometric pressure sample point

13.1m

Figure 1. Schematic representation of the broiler house layout and monitoring locations.

Figure 2. One of the monitored broiler farms and the Mobile Air Emissions Monitoring Unit.

ASABE Paper 064156 – Xin et al. P9

Figure 3. Schematic representation of the positive pressure gas sampling system (GSS) used in the mobile air emissions monitoring unit for measurement of broiler house air emissions. The GSS futures continuous drawing of sample air from all locations with individual pumps. The sample air is by-passed when not analyzed.

Figure 4. Photographical views of the inductive current switch (ICS) fan operation-monitoring device (attached to the fan motor power supply cord).

Location 3

Location 2

Location 1

Ambient air

P 4

P 3

P 2

P 1

M1

S1

S5

S2

S3

S4

S6

S7

S8

Exhaust

Compact Fieldpoint DAQ

Filter Filter

Red line: heated line

ExhaustM2

INNOVA 1412

API 101E

VIG 200

Flow meter

P: PumpM: ManifoldS: Solenoid

S1- 4: Normal Closed S5 -8:Normally Open

Location 3

Location 2

Location 1

Ambient air

P 4

P 3

P 2

P 1

M1

S1

S5

S2

S3

S4

S6

S7

S8

Exhaust

Compact Fieldpoint DAQ

Filter Filter

Red line: heated line

ExhaustM2

INNOVA 1412

API 101E

VIG 200

Flow meter

P: PumpM: ManifoldS: Solenoid

S1- 4: Normal Closed S5 -8:Normally Open

ASABE Paper 064156 – Xin et al. P10

0.0

0.4

0.8

1.2

1.6

2.0

2.4

2.8

0 10 20 30 40 50

Bird age, day

Bird

wei

ght,

kg House 2House 1

Figure 5. Growth curves of the Cobb x Cobb straight-run broilers corresponding to the flock of this study, as measured with automatic (step-on) platform bird-weighing scales.

Figure 6. In-situ calibration of ventilation fan with a fan assessment numeration system(FANS) placed in the upstream of the ventilation fan.

ASABE Paper 064156 – Xin et al. P11

Figure 7. Airflow variations among the ventilation fans of the broiler house monitored.

0

500

1000

1500

2000

2500

3000

0:00 4:00 8:00 12:00 16:00 20:00 0:00Time, hr:min

CO

2 con

cent

ratio

n di

ffere

nce,

ppm

0

10

20

30

40

50

60

70

Vent

ilatio

n ra

te, m

3 /s

Empty House

Ventilation rate (10 exhaust fans

Bird Catching

CO2 concentration difference

Figure 8. Temporal CO2 concentration in the broiler houses following flock removal.

Variation in airflow rates among 0.9-m (36 inch) and 1.2-m (48 inch) fans, as measured with the FANS

0

5000

10000

15000

20000

25000

30000

35000

0 5 10 15 20 25 30 35 40 45Static Pressure, pa

Fan

airfl

ow ra

te, m

3 hr-1

1.2-m fans

0.9-m fans

ASABE Paper 064156 – Xin et al. P12

0

10

20

30

40

50

60

70

80

90

100

12:00 16:00 20:00 0:00 4:00 8:00 12:00 16:00 20:00 0:00

Time, hr:min

Vent

ilatio

n ra

te, m

3 /s

0

200

400

600

800

1000

1200

1400

CO

2 con

cent

ratio

n, p

pm

Directly measured VRCO2 inside,ppm

10-min average

10-min average

y = 3135x-0.725

R2 = 0.7054

0

10

20

30

40

50

60

70

80

0 200 400 600 800CO2 difference, ppm

Vent

ilatio

n ra

te, m

3 /s

30-min average

y = 4455.6x-0.7857

R2 = 0.9162

0

10

20

30

40

50

60

70

80

0 200 400 600 800CO2 difference, ppm

Vent

ilatio

n ra

te, m

3 /s

60-min average

y = 4630.7x-0.793

R2 = 0.9164

0

10

20

30

40

50

60

70

80

0 200 400 600 800CO2 difference, ppm

Vent

ilatio

n ra

te, m

3 /s

120-min average

y = 4970.4x-0.8043

R2 = 0.9307

0

10

20

30

40

50

60

70

80

0 200 400 600 800CO2 difference, ppm

Vent

ilatio

n ra

te, m

3 /s

Figure 9. CO2 concentration vs. ventilation rate of broiler houses (no supplemental heating).

ASABE Paper 064156 – Xin et al. P13

0

10

20

30

40

50

60

70

80

90

12:00 16:00 20:00 0:00 4:00 8:00 12:00 16:00 20:00 0:00

Time, hr:min

Vent

ilatio

n ra

te, m

3 /s

0

5

10

15

20

25

30

Tem

pera

ture

, o C

Indirectly determined VR

Directly measured VR

Inside Temp

Outside Temp

Figure 10. An example comparison of directly measured vs. CO2-balance derived (10-min) ventilation rate for the monitored broiler house.

10-min average

y = 1.0343xR2 = 0.9051

0

10

20

30

40

50

60

70

80

90

0 10 20 30 40 50 60 70 80 90Directly measured VR, m3/s

Indi

rect

ly d

eter

min

ed V

R, m

3 /s

30-min average

y = 1.0289xR2 = 0.9057

0

10

20

30

40

50

60

70

80

90

0 10 20 30 40 50 60 70 80 90Directly measured VR, m3/s

Indi

rect

ly d

eter

min

ed V

R, m

3 /s

60-min average

y = 1.0273xR2 = 0.9073

0

10

20

30

40

50

60

70

80

90

0 10 20 30 40 50 60 70 80 90Directly measured VR, m3/s

Indi

rect

ly d

eter

min

ed V

R, m

3 /s

120-min average

y = 1.0344xR2 = 0.8802

0

10

20

30

40

50

60

70

80

90

0 10 20 30 40 50 60 70 80 90Directly measured VR, m3/s

Indi

rect

ly d

eter

min

ed V

R, m

3 /s

Figure 11. Relationship of house ventilation rates from direct measurement vs. from CO2-balance derivation for the monitored broiler houses at different integration time intervals when CO2 production from both the litter and bird respiration was considered. The dash lines below and above the regression lines represent 95% confidence intervals of the observations.

ASABE Paper 064156 – Xin et al. P14

10-min average

y = 0.9307xR2 = 0.9011

0

10

20

30

40

50

60

70

80

90

0 10 20 30 40 50 60 70 80 90Directly measured VR, m3/s

Indi

rect

ly m

easu

red

VR, m

3 /s

Figure 12. Relationship of ventilation rates determined from direct measurement vs. from CO2-balance derivation for the monitored broiler houses at different integration time intervals, excluding the contribution of CO2 generation from the litter. The dash lines below and above the regression lines represent 95% confidence intervals of the observations.