Unbranded ASAT Calculator Sales and Marketing Introduction Presentation

download Unbranded ASAT Calculator Sales and Marketing Introduction Presentation

of 19

Transcript of Unbranded ASAT Calculator Sales and Marketing Introduction Presentation

  • 8/10/2019 Unbranded ASAT Calculator Sales and Marketing Introduction Presentation

    1/19

    Introduction to the

    ASD Suppression ActuationThreshold (ASAT) Calculator

    July 2007

    13574_03_ASAT Calculator Sales and Marketing Introduction Presentation

  • 8/10/2019 Unbranded ASAT Calculator Sales and Marketing Introduction Presentation

    2/19

    Agenda

    1. Background

    2. Functions & Use

    3. Benefits

    4. Package & Support

  • 8/10/2019 Unbranded ASAT Calculator Sales and Marketing Introduction Presentation

    3/19

    Background

    Mission Critical Facilities Protection

    Protection of mission critical facilities against a fire

    event is achieved through:

    - Early intervention (initiated by VEW)

    - Suppression (initiated by VEW/EW)

    Conventional practice for suppression system

    actuation:

    - Conventional spot-type smoke detectors in a

    Coincidence Detection arrangement

  • 8/10/2019 Unbranded ASAT Calculator Sales and Marketing Introduction Presentation

    4/19

    Example of Conventional Coincidence

    Detection

    Suppression actuation through Coincidence Detectionof cross-

    zoned spot-type smoke detectors

  • 8/10/2019 Unbranded ASAT Calculator Sales and Marketing Introduction Presentation

    5/19

  • 8/10/2019 Unbranded ASAT Calculator Sales and Marketing Introduction Presentation

    6/19

    FM Official Listing

    ASATCalculatoris officially listed as an approved

    design tool in the FM Approval Guide, Chapter 14

    (Electrical Signalling)

  • 8/10/2019 Unbranded ASAT Calculator Sales and Marketing Introduction Presentation

    7/19

    Agenda

    1. Background

    2. Functions & Use

    3. Benefits

    4. Package & Support

  • 8/10/2019 Unbranded ASAT Calculator Sales and Marketing Introduction Presentation

    8/19

    Use ofASATCalculator

    ASATCalculatoris applicable for ceiling and floorvoid protection in enclosures with continuous or

    periodic air circulation with different airflow patterns

    and magnitudes

    Telecommunication facilities, base-stations

    Computer/server rooms

    Offices etc.

  • 8/10/2019 Unbranded ASAT Calculator Sales and Marketing Introduction Presentation

    9/19

    Use ofASATCalculator

    ASATCalculatorFirethreshold value

    predominantly used for Suppression system

    actuation with a pre-engineered VESDA

    coincidence detection scheme

    But it may also be used for:

    Evacuation annunciation and procedure

    Fire Brigade notification

    HVAC system shutdown or conversion to

    smoke mode

    Automated equipment shutdown

  • 8/10/2019 Unbranded ASAT Calculator Sales and Marketing Introduction Presentation

    10/19

    VESDA Coincidence Detection Schemes

    VESDA Detector 1 VESDA Detector 2

    Alternating

    VESDA pipe

    VESDADetector 1

    VESDADetector 2

    CoincidenceDetectionCylinder

    CoincidenceDetection Detector

    (CDD)

    VESDA exhaust

    sampling

    VESDA Detector

    Hybriddetection

    NormalProtection

    Group OverReturn Air

    Vent

    VESDA ceiling

    (floor void) / AHU

    sampling

    Single ASD

    detector with

    staged alarms

  • 8/10/2019 Unbranded ASAT Calculator Sales and Marketing Introduction Presentation

    11/19

    Design:ASATCalculator

    Required Inputs for the Calculator

    1. Project name

    2. Units (Metricor Imperial)

    3. Entire enclosure floor area (m2or ft2)

    4. Average ceiling height (mor ft)

    5. Floor void height (if applicable) (mor ft)

    6. Spot-type smoke detector nominal sensitivity (%/mor %/ft)

    7. VESDA sampling hole spacing (m or ft)

    8. Enclosure air change rate (air change/hour)

    9. Ventilation scheme

  • 8/10/2019 Unbranded ASAT Calculator Sales and Marketing Introduction Presentation

    12/19

    Design:ASATCalculator Inputs & Outputs

  • 8/10/2019 Unbranded ASAT Calculator Sales and Marketing Introduction Presentation

    13/19

  • 8/10/2019 Unbranded ASAT Calculator Sales and Marketing Introduction Presentation

    14/19

    Agenda

    1. Background

    2. Functions & Use

    3. Benefits

    4. Package & Support

  • 8/10/2019 Unbranded ASAT Calculator Sales and Marketing Introduction Presentation

    15/19

    Benefits of Using ASD for both VEWSD and

    Suppression Actuation

    Detect smoke early enough to allow time to:

    Investigate and respond before disruption to businesscontinuity, loss of assets or risks to lifeAvoid costly suppression releaseAvoid the costs of nuisance alarms

    Ensure the most timely and reliable actuation of suppression:

    High sensitivity overcomes the smoke detectionchallenges presented by smoke dilution (air movementand the scrubbing of filters)

    Cumulative sampling ensures reliable detection in highairflow environments

    Active sampling of ASD ensures consistent performance

    in a range of airflows

    Avoid duplication of detection schemes by using ASD for bothveryearly detection of smoke in high airflow environments andthecontrol of suppression releaseAvoid the current practice in Datacom facilities of usingASD for VEWSD in addition to spot-type smokedetectors for suppression actuation

  • 8/10/2019 Unbranded ASAT Calculator Sales and Marketing Introduction Presentation

    16/19

    Benefits of Using theASATCalculator

    Proven equivalence to industry-standard spot-typesmoke detector sensitivities (but improved

    performance)

    Thresholds calculated to specific environmental

    parameters

    Supported as manufacturers recommendations and

    validated by verification procedure as part of

    commissioning FM Approved method of calculating fire thresholds

    for suppression actuation

  • 8/10/2019 Unbranded ASAT Calculator Sales and Marketing Introduction Presentation

    17/19

    Agenda

    1. Background

    2. Functions & Use

    3. Benefits

    4. Package & Support

  • 8/10/2019 Unbranded ASAT Calculator Sales and Marketing Introduction Presentation

    18/19

    Package

    ASATCalculatorsoftware tool(Microsoft Excel)

    Part No.: VSW-088

    File No.: 13625

    Technical Data SheetPart No.: 21188, DOC No.: 13583

    ASATCalculatorProduct GuidePart No.:21187,DOC No.: 12748

    ASATVerification & Commissioning Procedure DOC No.: 12746

    Marketing White PaperWhat A Coincidence! Very Early

    Warning Smoke Detection Together With Suppression

    Actuation DOC No.: 11843

    Design Guide for Telecommunications and Data ProcessingFacilitiesDOC No.: 11782

    Detailed technical reports(available on request)

  • 8/10/2019 Unbranded ASAT Calculator Sales and Marketing Introduction Presentation

    19/19

    Availability & Support

    Release of the ASATCalculatorto channel

    partners and to end users by request (August

    2007)

    Channel training by requestApplications Engineering Group (AEG) support

    on major projects by request