TRUETEMPERATURE CONTROLS SEQUENCE OF OPERATION WWW.TRUEMFG.COM
29
TRUETEMPERATURE CONTROLS SEQUENCE OF OPERATION WWW.TRUEMFG.COM
Control version will vary with model and age of cabinet.
LAE ELECTRONIC TEMPERATURE CONTROLS
LAE CURRENT PROBES:
GRAY- Thermostat
BLUE - Defrost
YELLOW - Display
LAE PRIOR PROBES:
Probes are identical.
LAE:
t1 = Thermostat
t2 = Defrost
t3 = Display
t3 probe is not installed and / or activated in all
applications if t3 is not installed and / or activated,
the display probe is t1.
30
TRUETEMPERATURE CONTROLS SEQUENCE OF OPERATION WWW.TRUEMFG.COM
LAE ELECTRONIC CONTROL GENERAL SEQUENCE OF OPERATION
1. Cabinet is plugged in.
a. Display will illuminate.
b. Interior light will illuminate on Glass Door Models only. Solid door cabinet lights are controlled by the door switch.
2. After the LAE control preprogrammed time delay of up to 6 minutes, the compressor and evaporator fan(s) will start if the
control is calling for cooling.
a. Control or condenser fans may be already pre-programmed from the factory so at the start of every compressor cycle or
during a defrost cycle, the condenser fan(s) will reverse for 30 seconds to blow dirt off the condensing coil.
3. The LAE control will cycle the compressor but may also cycle evaporator fan(s) on and off determined by the Set-Point and
Differential temperatures.
a. The Set-Point is the adjustable preprogrammed temperature.
b. The Differential is the non adjustable preprogrammed temperature.
c. The LAE control is designed to read and display a cabinet temperature not a product temperature.
This cabinet temperature may reflect the refrigeration cycle of the Set-Point and its Differential, or it may show an
average temperature.
The most accurate temperature on a cabinets operation is to verify the product temperature.
Example: If the Set-Point is -9°F/-23°C and the Differential is 10°F/5°C
(Set-Point) -9°F + 10 (Differential) = 1°F Or
(Set-Point) -23°C + 5 (Differential) = -18°C
The compressor and evaporator fan(s) will cycle off -9°F/-23°C and back on at 1°F/-18°C
4. The LAE control may be preprogrammed to initiate defrost by interval or at specific times of day.
a. At this time the “dEF” will appear on the display and compressor will turn off until a preprogrammed temperature or
duration is reached. During this time for freezers only, evaporator fan(s) will also turn off and the coil heater and drain tube
heaters will also be energized. Some cabinets may also change the rotation of the reversing condenser fan motor.
b. After the preprogrammed temperature or duration for defrost has been reached there may be a short delay for both the
compressor and evaporator fans to restart. At this time “dEF” may still appear on the display for a short time.
LAE ELECTRONIC TEMPERATURE CONTROLS
31
TRUETEMPERATURE CONTROLS SEQUENCE OF OPERATION WWW.TRUEMFG.COM
LAE MODEL TMW ELECTRONIC CONTROL GENERAL SEQUENCE OF OPERATION
1. Cabinet is plugged in.
a. Display will illuminate.
2. After the LAE control preprogrammed time delay of up to 6 minutes, the compressor will start if the control is calling
for cooling.
a. Control may be already preprogrammed from the factory so at the start of every compressor cycle, the condenser fan(s)
will reverse for 30 seconds to blow dirt off the condensing coil.
3. The LAE control will cycle the compressor on and off determined by the Set-Point and Differential temperatures.
a. The Set-Point is the adjustable preprogrammed temperature.
b. The Differential is the non adjustable preprogrammed temperature.
c. The LAE control is designed to read and display a cabinet temperature not a product temperature. This cabinet
temperature may reflect the refrigeration cycle of the Set-Point and it’s Differential, or it may show an average
temperature. The most accurate temperature on a cabinets operation is to verify the product temperature.
Example: If the Set-Point is -9°F/-23°C and the Differential is 10°F/5°C
(Set-Point) -9°F + 10 (Differential) = 1°F
Or
(Set-Point) -23°C + 5 (Differential) = -18°C
The compressor will cycle off -9°F/-23°C and back on at 1°F/-18°C
4. The LAE control is not and cannot be preprogrammed to initiate defrost, only refrigeration.
a. The cabinet will need to be manually defrosted. Unplug the cabinet or turn the LAE control to “OFF" per LAE
instruction sheet. The manual defrost frequency will depend on the units usage, environment, and the amount of frost.
LAE ELECTRONIC TEMPERATURE CONTROLS
32
TRUETEMPERATURE CONTROLS SEQUENCE OF OPERATION WWW.TRUEMFG.COM
LAE MODEL HEATED CABINET ELECTRONIC CONTROL GENERAL SEQUENCE OF OPERATION
1. Cabinet is plugged in.
a. Display will illuminate.
2. The LAE control will energize the heat elements if the control is calling for heat.
3. The LAE control will cycle the heating elements on and off determined by the Set-Point and Differential temperatures.
a. The Set-Point is the adjustable preprogrammed temperature.
b. The Differential is the non adjustable preprogrammed temperature.
c. The LAE control is designed to read and display a cabinet temperature not a product temperature. This cabinet
temperature may reflect the heating cycle of the Set-Point and it’s Differential. The most accurate temperature on a
cabinets operation is to verify the product temperature.
Example: If the Set-Point is 180°F/82.2°C and the Differential is 1°F/.56°C
(Set-Point) 180°F + 1 (Differential) = 181°F Or
(Set-Point) 82.2°C + .56 (Differential) = 82.76°C
The heating elements will cycle on 180°F/82.2°C and back off at 181°F/82.76°C
LAE ELECTRONIC TEMPERATURE CONTROLS
33
TRUETEMPERATURE CONTROLS SEQUENCE OF OPERATION WWW.TRUEMFG.COM
PRODUCT ADVISEMENT
DETERMINING THE TYPE OF ELECTRONIC CONTROL DISPLAY
Reason for Advisement
Both Danfoss and LAE electroinc controls utilize similar digital displays.
To provide the visual differences and operations between the displays used for the LAE Electronic Control and the Danfoss
Electronic control
NOTE: Displays do not interchange with each other due to wiring and programming limitations.
LAE electronic control board
Danfoss electronic control board
Previous Danfoss display
DISPLAY FOR LAE CONTROL
DISPLAY FOR DANFOSS CONTROL
Alarm Symbol
No Alarm Symbol
Info / Scroll
Defrost
Defrost / Down
Down
Manual / Up
Up
Power
Power
LAE ELECTRONIC TEMPERATURE CONTROLS
34
TRUETEMPERATURE CONTROLS SEQUENCE OF OPERATION WWW.TRUEMFG.COM
HOW TO USE AN LAE ELECTRONIC CONTROL
LOCKING AND UNLOCKING THE LAE CONTROLLER:
WHY: Locking of control is necessary to prevent changes to program that may
affect cabinet operation.
STEP 1 - To change lock setting press and release the Info button . “t1”
will appear. See image 1.
STEP 2 - Press the Down button until “Loc” appears. See image 2.
STEP 3 - While pressing and holding the Info button press the
Up or Down button to change the lock settings. If “no” appears, the
controller is unlocked. If “yes” appears, the controller is locked. See images 3 and
4.
STEP 4 - Once the lock setting has been set correctly release the info button
. Wait 5 seconds for the display to show temperature. See image 5.
HOW TO LOCK AND UNLOCK LAE CONTROLLER:
Image 3: If “no” appears on screen,
the controller is unlocked.
3
2
1
5
4
Image 4: If “yes” appears on screen, the
controller is locked.
LAE Control
Info / Set Point
Button
Manual Activation
Up Button
Manual Defrost /
Down Button
Stand-By
Button
LAE Control Icons
Compressor Running
Activation of 2nd Parameter Set
Alarm
Cabinet in Defrost
Evaporator Fan Running
LAE ELECTRONIC TEMPERATURE CONTROLS
35
TRUETEMPERATURE CONTROLS SEQUENCE OF OPERATION WWW.TRUEMFG.COM
HOW TO TURN OFF THE LAE ELECTRONIC CONTROL:
HOW TO TURN THE LIGHTS ON AND OFF:
ON Position
TURN OFF THE LAE ELECTRONIC CONTROL:
May need to unlock control.
WHY: Turning off the control will deactivate all electrical components.
CAUTION: Turning off the control will not shut off power to the cabinet.
Cabinet must be unplugged prior to any repair.
STEP 1 - To turn off control, press and hold the Stand-by button until
"OFF" appears. Release Stand-by button. See Image 2.
STEP 2 - To turn on control, repeat prior steps and a temperature
will appear.
TURN THE LIGHTS ON AND OFF:
May need to unlock control.
WHY: Light may be controlled by LAE Controller or interior light switch.
STEP 1 - To control interior / sign lights by the LAE Controller, press and release
the Manual Activation button .
STEP 2 - To control interior / sign lights by the interior door switch, depress the
rocker switch to the “ON” position. Light switch is located on inside top right of
the ceiling.
NOTE: Not all moels have an interior light switch. Location of interior light
switch will vary by model. Example shown is an interior switch on an Upright
Glass Door cabinet.
1
2
LAE Control
Manual Activation
Up Button
Info / Set Point
Button
Stand-By
Button
Manual Defrost /
Down Button
LAE ELECTRONIC TEMPERATURE CONTROLS
36
TRUETEMPERATURE CONTROLS SEQUENCE OF OPERATION WWW.TRUEMFG.COM
CHANGING THE “SET POINT”:
May need to unlock control.
WHY: To make an adjustment to the product/cabinet temperature.
NOTE: The electronic control CANNOT convert a Freezer to a Refrigerator or a
Refrigerator to a Freezer.
STEP 1 - To see the set point, press and hold the Info button .
See image 1.
STEP 2 - While still holding the Info button , press the Up or
Down button to change the “set point”.
STEP 3 - Once the “set point” has been set correctly release the Info
button . The display will show temperature. See image 2.
1
2
LAE Control
Manual Activation
Up Button
Info / Set Point
Button
Stand-By
Button
Manual Defrost /
Down Button
LAE ELECTRONIC TEMPERATURE CONTROLS
HOW TO CHANGE THE “SET POINT”:
37
TRUETEMPERATURE CONTROLS SEQUENCE OF OPERATION WWW.TRUEMFG.COM
INITIATE A MANUAL DEFROST:
May need to unlock control.
WHY: A one time additional defrost may be necessary to clear accumulated
frost / ice from evaporator coil.
The method to initiate a manual defrost is determined by the Defrost Mode Parameter “DFM” preprogrammed in the controller.
REGULAR TIME DEFROST (TIM)
If controller is preprogrammed for “TIM”, press and release the Manual Defrost
button until “dEF” appears.
REAL TIME CLOCK (RTC)
If controller is preprogrammed for “RTC” press the and hold the Manual Defrost
button for 5 seconds until “dh1” appears. Release the Manual Defrost
button and then press and hold for an additional 5 seconds until “dEF”
appears.
NOTE: Defrost will only terminate once a specific preset temperature or a
preset time duration is reached.
LAE Control
Manual Activation
Up Button
Info / Set Point
Button
Stand-By
Button
Manual Defrost /
Down Button
LAE ELECTRONIC TEMPERATURE CONTROLS
HOW TO INITIATE A MANUAL DEFROST:
38
TRUETEMPERATURE CONTROLS SEQUENCE OF OPERATION WWW.TRUEMFG.COM
1a
1c
1b
2
3
4
CHANGING “DEFROST INTERVALS”:
May need to unlock control.
This can only be changed if defrost mode parameter “DFM” is set for “TIM”.
WHY: The defrost interval is the time duration between defrost cycles. The
defrost interval time starts when the cabinet is supplied power or after a manual
defrost.
STEP 1 - To see the set point, press and hold the Info button and the
Stand-by button at the same time.
NOTE: Depending on the version of control, one of three parameters will
appear: “ScL” image 1a, “SPL” image 1b, “MdL” image 1c.
STEP 2 - Push the Up button until “dFt” appears. See image 2.
STEP 3 - Press and hold the Info button to see the defrost interval time.
See image 3
STEP 4 - While pressing and holding the Info button , press the
Up or Down button to change the defrost interval times (higher
the number the less frequent the cabinet will defrost).
STEP 5 - Once the defrost interval time has been changed, release the Info
button .
STEP 6 - Wait 30 seconds for the display to show temperature.
See image 4.
LAE Control
Manual Activation
Up Button
Info / Set Point
Button
Stand-By
Button
Manual Defrost /
Down Button
LAE ELECTRONIC TEMPERATURE CONTROLS
HOW TO CHANGE “DEFROST INTERVALS”:
39
TRUETEMPERATURE CONTROLS SEQUENCE OF OPERATION WWW.TRUEMFG.COM
CHANGE DISPLAY READOUT FROM FAHRENHEIT TO CELSIUS:
May need to unlock control.
This can NOT be changed with the LAE model AR2-28 version of the control.
See page 32 for more information.
WHY: Changing readout will assist with customer application.
STEP 1 - To change the display, press and hold the Info button and the
Stand-by button at the same time. “MdL” or “SPL” will appear.
See images 1a and 1b.
STEP 2 - Push the Down button until “ScL” appears. See image 2.
STEP 3 - Press and hold the Info button to see the “readout scale”. See
image 3.
STEP 4 - While pressing and holding the Info button , press the
up or down button to change the “readout scale".
See image 4.
STEP 5 - Once the “readout scale” has been changed, release the info button
.
STEP 6 - Wait 30 seconds for the display to show temperature.
See image 5.
1a
1b
2
3
4
5
LAE Control
Manual Activation
Up Button
Info / Set Point
Button
Stand-By
Button
Manual Defrost /
Down Button
LAE ELECTRONIC TEMPERATURE CONTROLS
HOW TO CHANGE DISPLAY READOUT FROM FAHRENHEIT TO CELSIUS:
40
TRUETEMPERATURE CONTROLS SEQUENCE OF OPERATION WWW.TRUEMFG.COM
2
1DISPLAYING TEMPERATURE PROBES, T1, T2, T3:
WHY: To display temperature probe readings in different locations of the
cabinet.
Also, display may show an average cabinet temperature and not a specific probe
temperature.
STEP 1 - To display T1 temperature, press and release the info button .
“t1” will appear. See image 1.
STEP 2 - Press and hold the info button . This is the temperature of the
T1 Probe. See image 2.
STEP 3 - By releasing the info button , “t2” will appear. Press and hold the
info button to display the temperature of the T2 probe.
STEP 4 - By releasing the info button again, “t3” will appear. Press and
hold the info button to display the temperature of
the T3 probe. (If probe T3 is not activated, “t3” will not appear of
the display.)
DISPLAY CODES
DISPLAY Defrost in progress Room high temperature alarm Controller in stand-by Room low temperature alarm Door open alarm Probe T1 failure Instant Probe 1 temperature Probe T2 failure Instant Probe 2 temperature Probe T3 failure
Instant Probe 3 temperature Maximum probe 1 temperature recorded Minutes of the Real Time Clock Minimum probe 1 temperature recorded Hours of the Real Time Clock Keypad state lock
LAE Control
Manual Activation
Up Button
Info / Set Point
Button
Stand-By
Button
Manual Defrost /
Down Button
LAE ELECTRONIC TEMPERATURE CONTROLS
HOW TO DISPLAY PROBE TEMPERATURES:
41
TRUETEMPERATURE CONTROLS SEQUENCE OF OPERATION WWW.TRUEMFG.COM
984823
STEP 2: With the display showing “t1”, press and release
the down button until “loc” appears. “loc” is the
parameter to lock and unlock.
HOW DO WE UNLOCK THE CONTROL?
STEP 1: With the display showing temperature, press and
release the info button until “t1” appears.
STEP 3: With the display showing “loc”, press and hold
the info button until “yes” appears. “yes” shows the
control is locked out.
Continue holding the info button.
NOTE: Holding the info button allows the param-
eter to be displayed and then changed.
STEP 4: With the display showing “yes”, and while still
holding the info button press and release the down
button until “no” appears. “no” shows the control is
unlocked.
Release all buttons.
THE CONTROL IS NOW UNLOCKED.
WHY DO WE LOCK THE CONTROL?
The control is locked to prevent unnecessary changes to
the program that may affect cabinet operation.
THE DISPLAY WILL READ AN INTERIOR
CABINET TEMPERATURE DURING NORMAL
OPERATION.
INFO BUTTON
DOWN BUTTON
UP BUTTON
POWER BUTTON
2
3
4
1
LAE ELECTRONIC TEMPERATURE CONTROLS
INSTRUCTIONS FOR SETTING THE OPTIONAL TEMPERATURE ALARM RANGES ON THE
ELECTRONIC CONTROL (CONTINUED)
42
TRUETEMPERATURE CONTROLS SEQUENCE OF OPERATION WWW.TRUEMFG.COM
WHY DO WE NEED TO SET THE ALARM ON
THE ELECTRONIC CONTROL?
The alarm will advise that a temperature has gone above
and/or below the cabinets Cut-in and/or Cut-out temper-
ature after a determined time has expired.
STOP: Prior to proceeding, please contact The
True Manufacturing tech service department as
they will provide assistance in verifying the cut in
and cut out settings of your electronic control.Control may need to be unlocked. See instructions on
how to unlock the electronic control.
STEP 2: With the display showing “ScL”, “SPL’ or “MDL”,
press and release the info button until “AtM”
appears.
“AtM” is the parameter to change alarm mode.
STEP 3: With the display showing “AtM”, press and hold
the info button until “non” appears. “non” shows
the alarm is not active. Continue holding the info button.
NOTE: Holding the info button allows the param-
eter to be displayed and then changed.
STEP 4: With the display showing “non”, and while still
holding the info button , press and release the down
button to change the setting to “AbS”. Release
both buttons.
“AbS” shows the alarm will be an absolute number.
NOTE: The procedure of holding the info button
while then pressing and releasing the up button or
the down button will allow the parameter setting to
be displayed and then changed. Releasing the buttons will
allow the control to scroll to the next parameter.
THIS PROCEDURE WILL BE REPEATED ON
THE FOLLOWING PARAMETERS.
HOW DO WE PROGRAM THE ALARM
SETTING ON THE ELECTRONIC CONTROL?
STEP 1: With the display showing temperature, press and
hold the info button and the power button
at the same time until either “ScL”, “SPL’ or “MDL” appears.
Release both buttons.
THE DISPLAY WILL READ AN INTERIOR
CABINET TEMPERATURE DURING NORMAL
OPERATION.
INFO BUTTON
DOWN BUTTON
UP BUTTON
POWER BUTTON
1
2
3
4
LAE ELECTRONIC TEMPERATURE CONTROLS
INSTRUCTIONS FOR SETTING THE OPTIONAL TEMPERATURE ALARM RANGES ON THE
ELECTRONIC CONTROL
43
TRUETEMPERATURE CONTROLS SEQUENCE OF OPERATION WWW.TRUEMFG.COM
STEP 5: The display will now show “ALA”. Press and hold
the info button until a temperature appears. “ALA”
is the parameter for the low alarm setting.
With the display showing a temperature, and while still
holding the info button , press and release the down
button to change the temperature below the
Cut-Out Temperature.
NOTE: True Manufacturing recommends this tempera-
ture to be at least 3 degrees colder than the Cut-Out
temperature to prevent a false alarm.
Release both buttons.
STEP 7: Press and release the info button until
“Atd” appears.
STEP 8: With the display showing “Atd”, and while
holding the info button press and release the up
button to change alarm delay in minutes. “Atd” is
the parameter for the delay alarm setting.
NOTE: True Manufacturing recommends this time delay
to be at least 30 minutes to prevent a false alarm.
Release both buttons.
THE ALARM AND TIME DELAY IS NOW SET.
STEP 6: The display will now show “AhA”. Press and hold
the info button until a temperature appears. “AhA”
is the parameter for the high alarm setting.
With the display showing a temperature, and while still
holding the info button press and release the up
button to change the temperature above the Cut-In
Temperature.
NOTE: True Manufacturing recommends this tempera-
ture to be at least 3 degrees warmer than the Cut-In
temperature to prevent a false alarm.
Release both buttons.
7
8
5
6
LAE ELECTRONIC TEMPERATURE CONTROLS
INSTRUCTIONS FOR SETTING THE OPTIONAL TEMPERATURE ALARM RANGES ON THE
ELECTRONIC CONTROL (CONTINUED)
44
TRUETEMPERATURE CONTROLS SEQUENCE OF OPERATION WWW.TRUEMFG.COM
WHY DO WE LOCK THE CONTROL?
The control is locked to prevent unnecessary changes to
the program that may affect cabinet operation.
STEP 2: With the display showing “t1”, press and release
the down button until “loc” appears. “loc” is the
parameter to lock and unlock..
HOW DO WE LOCK THE
ELECTRONIC CONTROL?
STEP 1: With the display showing temperature, press and
release the info button until “t1” appears.
STEP 3: With the display showing “loc”, press and hold
the info button until “no” appears. “no” shows the
control is unlocked.
Continue holding the info button.
NOTE: Holding the info button allows the param-
eter to be displayed and then changed.
STEP 4: With the display showing “no”, and while still
holding the info button , press and release the up
button until “yes” appears.
“yes” shows the control is locked out.
Release all buttons.
THE CONTROL IS NOW LOCKED.
THE DISPLAY WILL READ AN INTERIOR
CABINET TEMPERATURE DURING NORMAL
OPERATION.
INFO BUTTON
DOWN BUTTON
UP BUTTON
POWER BUTTON
2
1
4
3
LAE ELECTRONIC TEMPERATURE CONTROLS
INSTRUCTIONS FOR SETTING THE OPTIONAL TEMPERATURE ALARM RANGES ON THE
ELECTRONIC CONTROL
45
TRUETEMPERATURE CONTROLS SEQUENCE OF OPERATION WWW.TRUEMFG.COM
LAE CONTROL PARAMETER LIST ORDER
AR2-28-1TM and 2TM
SCL IISMSPL IISLSPH IISHSP IISP
C-H IIHYHYS IIFCCRT HDSCT1 IIDFCT2 SBCSD DSMDFM DI2DFT STTDH1 EDTDH2 LSMDH3 OA1DH4 OA2DH5 CDDH6 INPDLI OS1
DTO T2DTY OS2DPD T3DRN OS3DDM TLDDDY TDSFID AVG
FDD SIMFTO ADRFCMFDTFDHFT1FT2FT3ATMALAAHAALRAHRATI
ATDADOAHMAHTACC
BR1-28
MDL IISMSPL IISLSPH IISHSP IISP
C-H IIH0HY0 IIH1HY1 IIHTCRT IIDFCT1 IIFCCT2 ECSHRT EPTTIL SBHT DSM
DFM DADDFT CSDDFB D1ODH1 D1ADH2 D2ODH3 D2ADH4 LSMDH5 LSADH6 STTDLI EDT
DTO OA1DTY OA2DSO OA3SOD 2CD DPD OS1DRN T2DDM OS2DDY T3FID OS3
FDD T4FTO OS4FCM TLDFDT TDSFDH AVGFT1 SCLFT2 SIMFT3 ADRFMS BTEATM RFSALAAHAALRAHRATI
ATD
Per our design or control version, all
Parameters may or may not be displayed.
SUBJECT TO C
HANGE
SUSUSUSSUSUSUBJECT TOTOTOTOTOTOTOTOTTTT
UBUBUBUBUBUBUBUBUBUUUUU
TOTOTOTOT TTT TT T
CTCTCCCCCTCCCECECECECECECECECECECJE
CECECECECECEEJEEEEEEEEBJUBUBUU
ALSMLSMLSASTTTEDTED
O OODTYDSOSODDPDD
LAE ELECTRONIC TEMPERATURE CONTROLS
46
TRUETEMPERATURE CONTROLS SEQUENCE OF OPERATION WWW.TRUEMFG.COM
Per our design or control version, all
Parameters may or may not be displayed.
LAE CONTROL PARAMETER LIST ORDER
BIT25
SPL IISMSPH IISLSP IISH
HYS IISPCRT IIHYCT1 IIFCCT2 IIDFCSD SBDFM DI1DFT DI2DFB T3MDLI OS3
DTO PSLDTY PSRDPD POFDRN LSMDDM OA1DDY OA2FID OS1
FDD T2FTO OS2FCM TLDFDT SCLFDH SIMFT1 ADRFT2FT3ATMALAAHAALRAHRATI
ATDADOAHMAHTACC
BIT25-6TM and 7TM
SPL IISMSPH IISLSP IISH
HY0 IISPHY1 IIH0CRT IIH1CT1 IIHTCT2 IIFCCSD IIDFHT SB
DFM DI1DFT DI2DFB T3MLTD OS3DDS PSLDLI PSR
DTO POFDTY LSMDSO OA1SOD OA2DPD OS1DRN T2DDM OS2DDY TLDFID SCL
FDD SIMFTO ABEFCM ADRFDTFDHFT1FT2FT3FMSATMALAAHAALRAHRATI
ATDADOAHMAHTACC
BIT25 Heating
SPL SBSPH DI1SP DI2CM PSLHYS PSRTON POFTOF DSMPB LSMIT OA1DT OA2AR OS1CT TLDPF SCL
HSD SIMATM ADRALAAHAALRAHRATDADO
LAE ELECTRONIC TEMPERATURE CONTROLS
47
TRUETEMPERATURE CONTROLS SEQUENCE OF OPERATION WWW.TRUEMFG.COM
LAE CONTROLLER PARAMETER SETTINGS FOR CELSIUS
For LAE control model AR2-28 ONLY, ALL parameters with a formula
shown need to be converted for Celsius applications.
EXAMPLE:
If current SPL is set for 20 degrees F the formula is (X-32) / 1.8
(20-32) / 1.8 = -6.7 Celsius
AR2-28SCL 1C ADOSPL (X-32) / 1.8 AHMSPH (X-32) / 1.8 AHT (X-32) / 1.8SP (X-32) / 1.8 ACC
C-H IISMHYS (X) / 1.8 IISL (X-32) / 1.8CRT IISH (X-32) / 1.8CT1 IISP (X-32) / 1.8CT2 IIHY (X) / 1.8CSD IIFCDFM HDSDFT IIDFDH1 SBDH2 DSDH3 DSMDH4 DI2DH5 STTDH6 EDTDLI (X-32) / 1.8 LSM
DTO OA1DTY OA2DPD CDDRN INPDDM OS1 (X) / 1.8DDY T2FID OS2 (X) / 1.8
FDD (X-32) / 1.8 T3FTO OS3 (X) / 1.8FCM TLDFDT (X) / 1.8 TDSFDH (X) / 1.8 AVGFT1 SIMFT2 ADRFT3ATMALA (X-32) / 1.8AHA (X-32) / 1.8ALR (X) / 1.8AHR (X) / 1.8ATI
ATD
T TO CHANGE
TOOTOTTT T
EEEGEEGNGAAANAAANAHAAA
CHCHO
COOOOOTOTOOTOTOTOTOTOTTTT
SUBJECT
S
CTCECECECECECJE
CJEEJEBJ
UBUUBSUSUSUSSSS
TT
MMOA1OA1OA2OA2CDCDINPINPO
(X-32) / 1.8(X-32) /
TT (FDHFDHFT1FT1FT2FT2FTFTA
LAE ELECTRONIC TEMPERATURE CONTROLS
48
TRUETEMPERATURE CONTROLS SEQUENCE OF OPERATION WWW.TRUEMFG.COM
LAE ELECTRONIC TEMPERATURE CONTROLS
LAE Probe Temperature to Resistance Chart
Temperature Resistance
C F K-ohm
-40 -40 195.65-35 -31 148.17-30 -22 113.35-25 -13 87.56-20 -4 68.24-15 5 53.65-10 14 42.51-5 23 33.890 32 27.225 41 22.02
10 50 17.9315 59 14.6720 68 12.0825 77 10.0030 86 8.3235 95 6.9540 104 5.8345 113 4.9250 122 4.1655 131 3.5460 140 3.0165 149 2.5970 158 2.2375 167 1.9380 176 1.6785 185 1.4590 194 1.2795 203 1.15
100 212 0.97105 221 0.86110 230 0.76115 239 0.67120 248 0.60125 257 0.53
JECT TO C
HANGEEGEGNGAN
HHHHAHHHCHHHHCHCHCHCHCHCHCHCHCHCHO
COTO
T TCCCCTCCECCCCECEC
SUBJECECECECECECECECEC
JEBJUB
SUS
3.898927.2227.2222.0222.021717
777786869595
1
555560606565
Checking the probe resistance.
• Verify the probe resistance is accurate at the probe location.
• Use a calibrated thermometer to check the probe location
temperature (coil or air temperature).
• Disconnect the probe from the controller. The probe cannot
be plugged into the controller when measuring resistance.
• Use a calibrated Ohm meter to measure the resistance of the
probe
• The resistance of the probe should match the associated
temperature from the above table.
• Fill a cup full of ice water (use a lot of ice). Put the probe into
the ice bath, stir for 1 minute, then measure the resistance with a
calibrated Ohm meter. Make sure to keep the probe in the center
of the cup.
• The resistance of the probe should match the associated
temperature at 32°F / 0°C degrees as shown in the above
table.
Checking the controller display temperature accuracy.
• After verifying the probe resistance to the box temperature, plug
the probe into the controller and check the temperature display.
• The controller should display the associated temperature
from the above table
• Fill a cup full of ice water (use a lot of ice). Put the Ohm verified
probe in to the ice bath, stir for 1 minute. Make sure to keep the
probe in the center of the cup.
• The controller should display 32°F / 0°C.
Control version will vary with model and age of cabinet.
LAE:
t1 = Thermostat
t2 = Defrost
t3 = Display
49
TRUETEMPERATURE CONTROLS SEQUENCE OF OPERATION WWW.TRUEMFG.COM
DIAGNOSTIC FLOW CHART FOR DIXELL AND LAE ELECTRONIC CONTROLS
Concern: Electronic Control Display Temperature does not match the cabinet temperature
NOTE: The temperatures may reflect the refrigeration cycle determined by a set point and differential or it may show an average temperature.The temperatures are also effected by a defrost cycle and the open and closing of the door.The most accurate temperature on a cabinets operation is to verify the product temperature.
YES NO
NO YES
YES
NO
YES YES
NO NO YESNO
Change the control
NO YES
YESNO YES
NO
Replace the probe.
set point.
Check for a refrigeration issue, air flow blockage or ice on the evaporator coil.
Reposition the probe.Check for a bad compressor,
fans or wiring.
Is the probe touching the evaporator coil?
Is the cabinet cycling at a set pointand differential temperature?
Is the product at the correct temperature?
Is the controller calling for cooling?(The control's led indicator will be on next to the snowflake symbol)
Is the probe resistance correct?See checking probe resistance chart.
Replace the controller
Is there continuity across the controller compressor relay?
all the fans running?
Is the product at the correct temperature?
Is the control set at the correct set point?See changing / checking the set point.
Is the compressor and
working correctly!!!The cabinet is
LAE ELECTRONIC TEMPERATURE CONTROLS
50
TRUETEMPERATURE CONTROLS SEQUENCE OF OPERATION WWW.TRUEMFG.COM
PRODUCT ADVISEMENT
LAE ELECTRONIC CONTROL CHANGE FROM MODEL AR1 AND MODEL AR2 TO MODEL BR1.
REASON FOR ADVISEMENT: LAE Electronic Control model update will change the display, connecting cable, module,
wiring and programming*.
*Control is pre-programmed from the factory. New control is Universal voltage
BR1 DISPLAY, CABLE AND MODULE CONNECTIONSAR2 DISPLAY, CABLE AND MODULE CONNECTIONS
AR21 LINE IN
2 AUX 2
6 AUX 1
7 DEF
8 FAN
9 LINE IN
10 OR 11 COMP
14-19 NEUTRAL
26 T3
27 T1 (COMMON)
27 T3 (COMMON)
28 T1
29 T2 (common)
30 T2
31 DOOR (DI1)
32 DI1 (COMMON)
32 DI2 (COMMON)
33 DI2
BR11 LINE IN
2 AUX 2
4 AUX 1
5 OR 6 DEF
7 FAN
8 OR 9 LINE IN
10 OR 11 COMP
13-18 NEUTRAL
23 T3
21 T1 (COMMON)
24 T3 (COMMON)
20 T1
21 T2 (COMMON)
22 T225 DOOR (DI1)27 DI1
(COMMON)27 DI2
(COMMON)26 DI2
LAE ELECTRONIC TEMPERATURE CONTROLS