TENTATIVE TCS-NET AIR CONDITIONING CONTROL SYSTEM

104
FILE NO. A04-016 TCS-NET AIR CONDITIONING CONTROL SYSTEM (TOUCH SCREEN CONTROLLER) TENTATIVE

Transcript of TENTATIVE TCS-NET AIR CONDITIONING CONTROL SYSTEM

FILE NO. A04-016

TCS-NET AIR CONDITIONINGCONTROL SYSTEM(TOUCH SCREEN CONTROLLER)

TENTATIVE

2

CONTENTS1 OUTLINE

1-1 TCS-Net Air conditioning control system outline ...............................................................................................41-2 Component .......................................................................................................................................................5

1-2-1 TCS-Net Control system component ......................................................................................................51-2-2 Application control component ...............................................................................................................6

1-3 Basic system component .................................................................................................................................71-3-1 Apparatus component ............................................................................................................................71-3-2 The control system devices ...................................................................................................................81-3-3 The control system devices (Procured on site) .......................................................................................91-3-4 Software .................................................................................................................................................9

1-4 Touch screen controller function ...................................................................................................................... 101-5 Energy monitoring and billing function ............................................................................................................. 131-6 Input/Output .................................................................................................................................................... 15

2 SYSTEM CONFIGURATION2-1 Touch screen controller system configuration .................................................................................................... 18

3 INSTALLATION3-1 Installation work flow....................................................................................................................................... 243-2 Setup file data preparation .............................................................................................................................. 25

3-2-1 Control wiring diagram (Connection example) ....................................................................................... 253-2-2 Power meter wiring diagram (Connection example) ............................................................................... 263-2-3 Air conditioner address table ................................................................................................................ 273-2-4 Schedule table ..................................................................................................................................... 29

3-3 Setup file creation ........................................................................................................................................... 303-3-1 Setup file creation software (Excel macro) ........................................................................................... 303-3-2 Setup file contents ............................................................................................................................... 31

3-4 Control system installation .............................................................................................................................. 313-4-1 External view ....................................................................................................................................... 343-4-2 Installation method ............................................................................................................................... 383-4-3 Device specifications ........................................................................................................................... 42

3-5 Wiring ............................................................................................................................................................. 433-5-1 Wiring specifications ............................................................................................................................ 433-5-2 Wiring diagram ..................................................................................................................................... 44

3-6 Network connection ........................................................................................................................................ 533-7 Control system configulation ........................................................................................................................... 54

4 ADDRESS SETTING4-1 Address setting flow ....................................................................................................................................... 564-2 Definition of address ....................................................................................................................................... 574-3 Address setting for air conditioner ................................................................................................................... 62

4-3-1 Setting for VRF system ........................................................................................................................ 62(1) Check at main Power-ON .............................................................................................................. 63(2) Manual setting from wired remote controller .................................................................................. 64(3) Line (system) address setting ....................................................................................................... 66(4) Power reset ................................................................................................................................... 66(5) Indoor unit address check ............................................................................................................. 67(6) Trial operation ................................................................................................................................ 67(7) Setup of relay connector and terminator ........................................................................................ 68(8) Central control address setting ...................................................................................................... 71(9) Trial operation for central controller (TCB-SC642TLE) .................................................................... 73(10) Automatic address setting (for reference) .................................................................................... 74(11) Clearance of address .................................................................................................................. 77(12) Confirmation of indoor unit address and position by using the remote controller .......................... 78(13) Address change from remote controller ....................................................................................... 79(14) In case of increase the address-undefined indoor units (Extension, etc.) .................................... 81(15) Address setup example (VRF system) ........................................................................................ 82

4-3-2 Setting for 1 by 1 system ..................................................................................................................... 85(1) Address re-setup ........................................................................................................................... 85(2) Indoor address change example .................................................................................................... 89

4-4 Address setting for Control System devices ................................................................................................... 914-4-1 Address setting flow ............................................................................................................................. 914-4-2 Setting for Intelligent server ................................................................................................................. 924-4-3 Setting for TCS-Net relay interface ....................................................................................................... 934-4-4 Setting for Energy monitoring relay interface ........................................................................................ 944-4-5 Setting for Digital I/O relay interface ..................................................................................................... 95

5 TRIAL OPERATION5-1 Trial operation .................................................................................................................................................. 985-2 Air conditioning control system troubleshooting ............................................................................................ 101

5-2-1 Faults of air conditioner ...................................................................................................................... 1015-5-2 Faults of air conditioning control system ............................................................................................ 101

3

1

OUTLINE

1-1 TCS-Net Air conditioning control system outline1-2 Component

1-2-1 TCS-Net control system component1-2-2 Application control component

1-3 Basic system component1-3-1 Apparatus component1-3-2 The control system devices1-3-3 The control system devices (Procured on site)1-3-4 Software

1-4 Touch screen controller function1-5 Energy monitoring and billing function1-6 Input/Output

4

1-1 TCS-Net Air conditioning control system outlineThe TCS-Net Air conditioning control system has achieved easy-to-operate central air conditioningcontrol with the LCD Touch Screen Controller that integrates advanced functions. The system allowsoperation status monitoring, operation control, scheduled operation, and error code display of up to 512indoor units with one controller. It is also equipped with functions for energy monitoring and billing (foreach indoor unit) and for operation control using external input/output signals.

Operation status monitoringMonitors operation status of all air conditioners collectively.

Operation controlControls operation of devices easily with the LCD touch panel. Allows elaborate operation settings, suchas collective operation of entire building or each block/tenant/area, as well as individual operation of eachindoor unit.

Operation scheduleAllows elaborate operation schedule settings for each area.

Error code displayDisplays failure information and location real time when a failure occurs. Also displays fault loginformation.

Energy monitoring and billingDistributes power for each indoor unit, and outputs the calculation results as daily/monthly reports.

I/O functionProvides operation control using external input signals, and outputs emergency signals to externaldevices.

5

SM

MS

SH

RM

Sid

e re

mot

e co

ntro

ller

Mas

ter

rem

ote

cont

rolle

r

TC

S-N

et In

terf

ace BM

S-I

FLS

V1E

BM

S-T

P06

40A

CE

BM

S-T

P06

40P

WE

BM

S-T

P51

20A

CE

BM

S-T

P51

20P

WE

Touc

h sc

reen

co

ntro

ller

Pow

er m

eter

BM

S-I

FW

H3E

Ene

rgy

met

er

rela

y in

terf

ace

Dig

ita l/

O R

elay

In

terf

ace

BM

S-I

FD

D01

E

PC

for

Ene

rgy

mon

itorin

gan

d bi

lling

Sup

er D

igita

l Inv

erte

rD

igita

l Inv

erte

r

"1:1

mod

el"

conn

ectio

n in

terf

ace

TC

B-P

CN

T30

TLE

I/F I/F

HU

B

PC

BM

S-L

SV

2E

Inte

llige

ntse

rver

1-2

Co

mp

on

ent

1-2-

1 T

CS

-Net

co

ntr

ol s

yste

m c

om

po

nen

t

6

1-2-

2 A

pp

licat

ion

co

ntr

ol c

om

po

nen

tS

MM

SS

HR

M

Alarm status outputON/OFF command

Air

-co

nd

itio

nin

g

Man

agem

ent

on

sit

e

I/F I/FP

C

HUB

Term

inal

Scr

ew M

3 6

55.5

45.5

60

50

PJ17

TO

SH

IBA

NC

C-1

21

4T

CB

-PC

MO

1

TC

B-P

CM

O1

E

4-4ø

hol

e

5

4 1

ICI

41

D2

HEAT

COM

COM COOL

10

TB

1

8

Term

inal

Scr

ew M

3 6

71 61

Term

inal

Scr

ew M

4 8

4-4ø

hol

e

85

75

OFF

OFF ON

MS

10

MS

OFF

COM COMON

ONT82

T81

K100

PJ17

5

5ICI

41

8

OPERATION/

TO

SH

IBA

NC

C-1

21

2

TC

B-P

CO

M1

TC

B-P

CO

M1

E

Bat

ch d

rive,

err

or o

utpu

t

Mas

ter

ON

/OF

F s

igna

l

Power peak-cut control signal

Operation status outputOperation control command

Wire

d re

mot

e co

ntro

ller

RB

C-A

MT

21E

Sid

e re

mot

e co

ntro

ller

Mas

ter

rem

ote

cont

rolle

r

Wee

kly

timer

RB

C-E

XW

21E

Wee

kly

timer

RB

C-E

XW

21E

Sub

-rem

ote

cont

rolle

rR

BC

-AS

21E

Wire

less

rem

ote

cont

rolle

r

Cen

tral r

emot

e co

ntro

ller

TCB

-SC

642T

LE

Ext

erna

l mas

ter

ON

/OF

F b

oard

TC

B-P

CM

O2E

Pow

er p

eak-

cut

cont

rol b

oard

TC

B-P

CD

M2E

TC

S-N

et In

terf

ace

BM

S-L

SV

2EIn

telli

gent

serv

erB

MS

-IF

LSV

1E

BM

S-T

P06

40A

CE

BM

S-T

P06

40P

WE

BM

S-T

P51

20A

CE

BM

S-T

P51

20P

WE

Touc

h sc

reen

co

ntro

ller

Pow

er

met

er

BM

S-I

FW

H3E

Ene

rgy

met

er

rela

y in

terf

ace

Dig

ita l/

O R

elay

Inte

rfac

e B

MS

-IF

DD

01E

PC

for

Ene

rgy

mon

itorin

g an

d bi

lling

Sup

er D

igita

l Inv

erte

rD

igita

l Inv

erte

r

"1:1

mod

el"

conn

ectio

n in

terf

ace

TC

B-P

CN

T30

TLE

Net

wor

k ad

apte

rT

CB

-PC

NT

20E

AI-

NE

TW

OR

K

AI-

NE

T c

entr

al

cont

rol d

evic

es

Rem

ote

loca

tion

ON

/OF

F c

ontr

ol b

oxT

CB

-IF

CB

-4E

Master ON/OFF signal

7

System Configuration Table

Monitoring/Control/Scheduling/Error code display

Energy monitoring and billing

Indoor units connected

Digital I/O

Touch Screen Controller

Intelligent Server

Intelligent Server Software

TCS-NET Relay I/F

Energy Monitoring Relay I/F

Digital I/O Relay I/F

PC (for Energy monitoringand billing)

Switching HUB

× × × ×

× ×

Max. 64 units Max. 64 units Max. 512 units Max. 512 units

× × × ×

BMS-TP0640ACE BMS-TP0640PWE BMS-TP5120ACE BMS-TP5120PWE

× × × × × × × ×

× × × × × × × ×

× × × × × × × ×

× × × ×

× × × ×

× × × ×

×(*) ×(*) ×(*) ×(*) ×(*) ×(*) ×(*) ×(*)

Func

tion

BMS-LSV2E

BMS-STCC01E

BMS-IFLSV1E

BMS-IFWH3E

BMS-IFDD01E

Procured on site

Procured on site

Dev

ices

(*) A Switching HUB is required when using two or more Intelligent server or when connecting to a PC for Energy Monitoringand billing.

1-3 Basic system component1-3-1 Apparatus component

TCS-NETRelay I /F

(BMS-IFLSV1E)

Ethernet

Touch Screen Controller(BMS-TP0640/5120)

Switching HUB(Procured on site)

PC for Energy Monitoringand billimg

(Procured on site)

Intelligent server Software

(BMS-STCC01E)

InteIligent Server(BMS-LSV2E)

RS-485

Main BUS

Main BUS

TCS-NETRelay I /F

(BMS-IFLSV1E)

EnergyMonitoringRelay I /F

(BMS-IFWH3E)

Main BUS

EnergyMonitoringRelay I /F

(BMS-IFWH3E)

Digital I /ORelay I /F

(BMS-IFDD01E)

Digital I /ORelay I /F

(BMS-IFDD01E)

CompactFlash

Set up files

CompactFlash

Power meter 1

Power meter 8

Power meter 1

Power meter 8

Input 1

Input 8

Output 1

Output 4

Output 1

Output 4

Input 1

Input 8

(Procured on site)

(Procured on site)

(Procured on site)

(Procured on site)

8

Name

Tou

ch S

cree

n C

ontr

olle

r

Modelname

Appearance PerformanceB

MS

-TP

0640

AC

EB

MS

-TP

5120

AC

EB

MS

-TP

0640

PW

EB

MS

-TP

5120

PW

E

Inte

llige

nt S

erve

r

BM

S-L

SV

2E

Inte

llige

nt S

erve

rS

oftw

are

BM

S-S

TC

C01

E

TC

S-N

et R

elay

Inte

rfac

e

BM

S-I

FLS

V1E

Ene

rgy

Mon

itori

ngR

elay

Int

erfa

ce

BM

S-I

FW

H3E

Dig

ital I

/O R

elay

Inte

rfac

e

BM

S-I

FD

D01

E

Operation monitoringOperation controlOperation scheduleError code displayFire alarm inputEnergy monitoring data saving in CF card

Data collection

Data collection software(This software is used for Intelligent server)

Protocol transformation

Main BUS to RS-485

Power meter interface

Input and output interface

Fire alarm input Key input Error output

1-3-2 The control system devices

9

Name

Pow

er m

eter

Performance Specification

Pulse output typePulse generator constants: 1kWh/pulse or 10kWh/pulsePulse duration: 50 - 1000 msOutput terminal: ON/OFF contactor

1-3-3 The control system devices (Procured on site)

Mesurement of power consumption Outputdata by pulse signal

Sw

itchi

ng H

UB

and

Eth

erne

t w

ire

HUB:10BASE-T compliant (*)Number of ports: as required

Ethernet wire: Category5 UTP straight cable (with HUB)Category5 UTP cross cable (without HUB)

Network withTouch screen controllerIntelligent serverEnergy monitoring PC

PC

for

ene

rgy

mon

itorin

gan

d bi

lling

Microsoft Excel is required for the energy monitoring andbilling function

OS: Windows 2000 or laterExcel: Excel 2000 or later

Energy monitoring calculationElectricity billing calculationMonthly report creation

* 100BASE-T compliant HUB is required in using 5 or more servers, or 2 or more controllers.

Name

Mon

thly

rep

ort

crea

tion

softw

are

Performance Note

This software is provided by CD-ROM

1-3-4 Software

Monthly report creationPower distribution calculationBilling calculationDaily sum report creation

10

1-4 Touch screen controller function

All Indoor unit operation can be controled within user's selected division.

Monitoring Items Mode FAN mode FLAP setting Set Temperature Inlet air temperature R/C control prohibition

Controlable division Whole building All tenant All area Unit

Setting Items Mode FAN mode FLAP setting Set Temperature Inlet air temperature R/C control prohibition (7 combination)

MonitoringAll Indoor unit conditions can be monitored by the controller.

Control

1234567

ON/OFFprohibition

×––××–×

MODEprohibition

–×–×–××

SET TEMPprohibition

––×–×××

11

A basic operation schedule pattern is determined by setting weekly and monthly operation schedules.These schedules can be set for each area.

Weekly schedule settingUp to 20 patterns a day (including ON andOFF) can be set.

Scheduling

All Block Tenant Area RC Group/Unit

Indoor Unit (line address + indoor unit address)

Building A 1 - 1 (header unit)

1 - 2 (follower unit)

1 - 3 (header unit)

1 - 4 (follower unit)

1 - 5 (header unit)

1 - 6 (follower unit)

1 - 7 (follower unit)

1 - 8 (header unit)

1 - 9 (follower unit)

2 - 1 (header unit)

2 - 2 (follower unit)

2 - 3 (header unit)

2 - 4 (header unit)

2 - 5 (header unit)

2 - 6 (follower unit)

2 - 7 (follower unit)

2 - 8 (follower unit)

2 - 9 (follower unit)

3 - 1 (header unit)

1F 1 0 1

1 0 2

1 0 3

1 0 4

1 0 5

1 0 6

1 0 7

1 0 8

1 0 9

1 1 0

Shop A

Office A

Shop B

Office B

Shop C

Office C

Tenant A

Tenant B

Tenant C

Sharedspace

1F outdoorair conditioner

Management zone categories

12

Monthly schedule settingSchedule patterns except for weekly schedulepatterns can be set as special-day patterns.Up to four special-day patterns can be set.Non-operation dates can also be set.

When an error occurs in a device, an errorcode is displayed.

Error code display

Fault log display

13

PC operating environment

1-5 Energy monitoring and billing functionDistributes total power consumption for each indoor unit according to the billing schedule set by the TouchScreen Controller. Reads the system setup file and the operation result file saved in the CF card of theTouch Screen Controller into the PC, and calculates power distribution result using the dedicated reportcreation software (Excel macro) to create spreadsheets and monthly reports.

Excel

HUB

IF

Ethernet

Ethernet

RS-485

Main BUS

Setup file creation software

Setup file

Software under development

Setup file• Tenant name, etc.• Air conditioner information, etc.• Setting values for energy monitoring and billing Air conditioner specific characteristic values Tenant names for reports

File transfer (FTP)

Monthly meter-read fileSetup file

Report creation software (Excel macro)

Default data file

Air conditioner operation resultPower meter pulse counter value Record in

CF cardEvery 15 min

Touch Screen Controller

Monthly report, spreadsheet(Excel file)

Intelligent Server

Energy monitoring I/F

Power meter

Air conditioner

Energy monitoring and billing software

PC (procured on site)

Printer

Printer for monthly reports (procured on site)

Windows 2000 or later

Excel 2000 or later is required separately.

OS

ExcelA PC for energy monitoring and billing and a printer should be procured on site.

Touch Screen Controller sets a billing schedule for monthly reports.

Data flow

Specifications

Electricity billing schedule

14

The report creation software creates monthly reports in Excel file format.

FunctionMonthly reportcreation

Power distributioncalculationBilling calculation

Daily sum reportcreation

RemarksOperation result report type:• Display operation hours• Display operation hours, display by In/Out working hours• Display operation hours/consumption/billing• Display operation hours/consumption/billing, display by In/Out working hoursSpreadsheet type:• Operation result for all the units• Operation result without tenant, Area name• Operation result sum by tenant, block• Accoounts sum by tenant

DescriptionCreates operation result reportsfor each indoor unit groupaggregates by the touch screencontroller based on the setupfiles.Creates 4 types of spreadsheetsfor monthly report.

Aggregates daily reports in specified range to create a monthly report.

Monthly Report

Monthly report printout sample

Report creation software functions

Calculates power distribution for each indoor unit group

Calculates expenses for each indoor unit group

15

1-6 Input/OutputThis system controls air conditioners by interlocking them with electric lock signals and fire alarm signals,and transmits air conditioner emergency signals to other devices.

HUB

Intelligent Server

Ethernet

Ethernet

Air conditioner

Digital I/ORelay I/F Door-lock input

RS-485

Main BUS

TCS-Net Relay I/F

Fire alarm input

Error output

Touch ScreenController

• Controls Air conditioners by interlocking with input signals.

• Outputs Air conditioner error to external devices.

16

17

2

SYSTEM CONFIGURATION

2-1 Touch screen controller system configuration

18

2-1 Touch screen controller system configuration

CompactFlash

Ethernet

InteIligent Server(BMS-LSV2E)

Touch Screen Controller(BMS-TP0640/5120)

Intelligent Server Software(BMS-STCC01E)

(*) A Switching HUB is required when usingtwo or more Intelligent Servers or whenconnecting to a PC for energy monitoringand billing.

PC for EnergyMonitoring andbilling

Switching HUB

TCS-NETRelay I/F

(BMS-IFLSV1E)

TCS-NETRelay I/F

(BMS-IFLSV1E)

MAX 8 perIntelligent server

EnergyMonitoringRelay I/F

(BMS-IFWH3E)

EnergyMonitoringRelay I/F

(BMS-IFWH3E)

Digital I/ORelay I/F

(BMS-IFDD01E)

Digital I/ORelay I/F

(BMS-IFDD01E)

RS-485

Main Bus

Max. 64 air conditionersper relay I/F

Max. 64 air conditionersper relay I/F

Max. 8 powermeters per relay I/F

Max. 8 powermeters per relay I/F

Max. 8 inputcontacts perrelay I/F

Max. 4 devicesper relay I/F

Max. 8 inputcontacts perrelay I/F

Max. 4 devicesper relay I/F

Max. 512 indoorunits (64 units x 8)per IntelligentServer

Max. 32 (8 x 4)power meters perIntelligent Server

Max. 32 (8 x 4)digital inputs perIntelligent Server

Max. 16 (4 x 4)digital outputsper IntelligentServer

Power meter 1

Power meter 8

(with pulse generator)

Input contact 1

Input contact 8

Device 1

Device 4

Main Bus

(with pulse generator)

(with pulse generator)

(with pulse generator)

Power meter 1

Power meter 8

Input contact 1

Input contact 8

Device 1

Device 4

MAX 4 perIntelligent server

MAX 4 perIntelligent server

19

System Configuration Table

Air conditioning monitoring/control

Energy monitoring and billing

Indoor units connected

Intelligent Server

Intelligent Server Software

TCS-NET Relay I/F

Energy Monitoring Relay I/F

Digital I/O Relay I/F

Touch Screen Controller BMS-TP0640ACE BMS-TP0640PWE BMS-TP5120ACE BMS-TP5120PWE

×

– ×

Max. 64 units

1 unit

1 unit

Max. 8 units

– Max. 4 units

Max. 4 units

Func

tion

BMS-LSV2E

BMS-STCC01E

BMS-IFLSV1E

BMS-IFWH3E

BMS-IFDD01E

Co

mp

on

ent

×

– ×

Max. 512 units

Max. 4 units

1 unit per Intelligent Server(max. 4 units in total)

Up to 8 units per Intelligent Server(max. 32 units in total)

– Max. 4 units

Max. 4 units

(× ... available – ... not available)

Switching HUB

Ethernet wire

PC

Power meter

Procured on site

Procured on site

Procured on site

Procured on site

*1

*3

Category 5 UTP straight wire

OS: Windows 2000 or later, Excel 2000 or later

Pulse output typePulse generator constants:1 kWh/pulse or 10 kWh/pulsePulse duration: 50 - 1000 msOutput terminal: ON/OFF contactor

Comply with 10BASE-T*2

Number of ports: As required

*1:The number of ethernet wires and the number of switching HUB port vary with the number of Intelligent Server connected.*2:100 BASE-T compliant is required in using 5 or more server, or 2 or more controllers.*3:The number of power meters vary with power meter specifications.

• Two or more refirgerant system can be connected to one power meter.• For heat recovery VRF (SHRM) and “Super digital inverter”, “Digital inverter”, it is necessary to install the power meter

independently.• All power meters connected same controller must be set same pulse generator constants.

20

The following lists required component devices in each category.

1. Without energy monitoring(A) Up to 64 indoor units

Device

Touch Screen Controller

Intelligent Server

Intelligent Server Software

TCS-NET Relay Interface

Digital I/O Relay Interface

Ethernet wire

Remarks

Up to 8 units per Intelligent Server

Category5 UTP cross cable

Model

BMS-TP0640ACE

BMS-LSV2E

BMS-STCC01E

BMS-IFLSV1E

BMS-IFDD01E

Procured on site

Quantity

1

1

1

Max. 8

Max. 4

*1

(B) Up to 512 indoor units

Device

Touch Screen Controller

Intelligent Server

Intelligent Server Software

TCS-NET Relay Interface

Digital I/O Relay Interface

Ethernet wire

Switching HUB

Remarks

Same quantity as Intelligent Serverrequired

*2 Up to 8 units per Intelligent Server

*3 Up to 4 units per Intelligent Server

Category5 UTP straight cable

10 BASE-T compliant *4

number of ports: As required

Model

BMS-TP5120ACE

BMS-LSV2E

BMS-STCC01E

BMS-IFLSV1E

BMS-IFDD01E

Procured on site

Procured on site

Quantity

1

Max. 4

Max. 4

Max. 32*2

Max. 16*3

*1

1

2. With energy monitoring(A) Up to 64 indoor units

Device

Touch Screen Controller

Intelligent Server

Intelligent Server Software

TCS-NET Relay Interface

Energy Monitoring RelayInterface

Digital I/O Relay Interface

Ethernet wire

Switching HUB

PC

Power meter

Remarks

Up to 8 units per Intelligent Server

Category5 UTP straight cable

10 BASE-T compliant *4

number of ports: As required

OS: Windows 2000 or laterExcel: Excel 2000 or later

Pulse output typePulse generator constants:1kWh/pulse or 10kWh/pulsePulse duration: 50 - 1000 msOutput terminal: ON/OFF contactor

Model

BMS-TP0640PWE

BMS-LSV2E

BMS-STCC01E

BMS-IFLSV1E

BMS-IFWH3E

BMS-IFDD01E

Procured on site

Procured on site

Procured on site

Procured on site

Quantity

1

1

1

Max. 8

Max. 4

Max. 4

*1

1

1

*5

System configuration examples

21

(B) Up to 512 indoor units

Device

Touch Screen Controller

Intelligent Server

Intelligent Server Software

TCS-NET Relay Interface

Energy Monitoring RelayInterface

Digital I/O Relay Interface

Ethernet wire

Switching HUB

PC

Power meter

Remarks

Same quantity as Intelligent Serverrequired

*2 Up to 8 units per Intelligent Server

*3 Up to 4 units per Intelligent Server

*3 Up to 4 units per Intelligent Server

Category5 UTP straight cable

10 BASE-T compliant *4

number of ports: As required

OS: Windows 2000 or laterExcel: Excel 2000 or later

Pulse output typePulse generator constants:1kWh/pulse or 10kWh/pulsePulse duration: 50 - 1000 msOutput terminal: ON/OFFcontactor

Model

BMS-TP5120PWE

BMS-LSV2E

BMS-STCC01E

BMS-IFLSV1E

BMS-IFWH3E

BMS-IFDD01E

Procured on site

Procured on site

Procured on site

Procured on site

Quantity

1

Max. 4

Max. 4

Max. 32*2

Max. 16*3

Max. 16*3

*1

1

1

*5

*1 The number of ethernet wire and the number of switching HUB port vary with the number of Intelligent servers connected.*4 100BASE-T compliant HUB is required in using 5 or more servers, or 2 or more controllers.*5 The number of power meters vary with power meter specifications.

• Two or more refirgerant system can be connected to one power meter.• For heat recovery VRF (SHRM) and “Super digital inverter”, “Digital inverter”, it is necessary to install the power meter

independently.• All power meters connected same controller must be set same pulse generator constants.

22

23

3

INSTALLATION

3-1 Installation work flow3-2 Setup file data preparation

3-2-1 Control wiring diagram (Connection example)3-2-2 Power meter wiring diagram (Connection example)3-2-3 Air conditioner address table3-2-4 Schedule table

3-3 Setup file creation3-3-1 Setup file creation software (Excel macro)3-3-2 Setup file contents

3-4 Control system Installation3-4-1 External view3-4-2 Installation method3-4-3 Device specifications

3-5 Wiring3-5-1 Wiring specifications3-5-2 Wiring diagram

3-6 Network connection3-7 Control system configulation

24

3-1 Installation work flow

Work flow

0. System planning

Contents Reference No.

1. Setup file data preparation

2. Setup file creation

3. On site installation(Construction work)

4. On site installation(Wiring)

5. On site installation(Control system configuration)

6. On site installation(Address setting)

7. Trial operation and adjustment

8. Commissioning

Air conditioner equipmentsselectionControl system device selection

System wiring diagramPower meter wiring diagramAddress listSchedule list

Create setup files by excel macrosoftware

Control system installation

Wiring power cable/communication lineNetwork connection

Energy monitoring PCconfigurationIntellignet server configurationSetup file installation

Air conditioner address settingControl system device addresssetting

Chapter. 2

3-2

3-3

3-4

3-53-6

3-7

Chapter. 4

Chapter. 5

25

3-2 Setup file data preparationBefore implementation of installing, prepare the materials for creating the setting files.• Control wiring diagram• Power meter wiring diagram• Air conditioner addresstable• Schedule table

3-2-1 Control wiring diagram (Connection example)

U1,

U2

U1,

U2

U1,

U2

U1,

U2

U1,

U2

U1,

U2

U1,

U2

U1,

U2

U1,

U2

U1,

U2

U1,

U2

U1,

U2

U1,

U2

U1,

U2

U1,

U2

U1,

U2

U3,

U4

U3,

U4

U3,

U4

U3,

U4

U3,

U4

U3,

U4

U3,

U4

U3,

U4

16th

flo

or

Tou

ch S

cre

en

Con

trol

ler

Sw

itchi

ngH

UB

8 do

or-l

ock

cont

rol s

igna

l inp

uts

8 fir

e al

arm

inpu

ts

8 po

wer

met

er in

puts

1st

-8th

floor

9th

-16

thflo

or

1st

floor

2nd

floor

15th

flo

or Dig

ital I

nput

/Out

put

Re

lay

Inte

rfa

ceB

MS

-IF

DD

01

E

Ene

rgy

Mon

itori

ngR

ela

y In

terf

ace

BM

S-I

FW

H3E

Ene

rgy

Mon

itori

ngR

ela

y In

terf

ace

BM

S-I

FW

H3E

Inte

llige

ntS

erv

er

BM

S-L

SV

2E

PC

fo

r cr

ea

ting

mo

nth

ly r

ep

ort

s

Pri

nte

r

Mai

n B

US

TCS

-NE

T R

elay

Inte

rface

TCS

-NE

T R

elay

Inte

rface

TCS

-NE

T R

elay

Inte

rface

TCS

-NE

T R

elay

Inte

rface

Out

door

uni

t

Indo

or u

nit

Dig

ital I

nput

/Out

put

Re

lay

Inte

rfa

ceB

MS

-IF

DD

01

E

BM

S-

IFLS

V1E

Inte

llige

nt s

erve

rso

ftw

are

BM

S-S

TC

C

Inte

llige

ntS

erv

er

BM

S-L

SV

2E

Inte

llige

nt s

erve

rso

ftw

are

BM

S-S

TC

C

BM

S-

IFLS

V1E

BM

S-

IFLS

V1E

BM

S-

IFLS

V1E

8 po

wer

met

er in

puts

26

3-2-

2 P

ow

er m

eter

wir

ing

dia

gra

m (

Co

nn

ecti

on

exa

mp

le)

•Tw

o or

mor

e re

firge

rant

sys

tem

can

be

conn

ecte

d to

one

pow

er m

eter

.

•F

or h

eat

reco

very

VR

F (

SH

RM

) an

d “S

DI*

1 ” “

DI*

2 ” it

is n

eces

sary

to

inst

all t

he p

ower

met

er in

depe

nden

tly.

•A

ll po

wer

met

ers

conn

ecte

d sa

me

cont

rolle

r m

ust

be s

et s

ame

puls

e ge

nera

tor

cons

tant

s.

*1:

Sup

er d

igita

l inv

erte

r*2

: D

igita

l inv

erte

r

Pul

l box

Pul

l box

Pow

er m

eter

No.

1

SM

MS

SM

MS

Pow

er m

eter

No.

4

SD

I

Pul

l box

SD

IS

DI

DI

DI

DI

Pul

l box

Pul

l box

Pul

l box

Pul

l box

Pow

er m

eter

No.

3

SH

RM

Pul

l box

Pow

er m

eter

No.

2

SM

MS

27

3-2-3 Air conditioner address table• B

uild

ing

nam

e:

Key

inpu

tN

o.

Po

wer

met

er N

o.

and

Inp

ut/

Ou

tpu

t d

ata

No

.

Pow

erm

eter

No.

1 2 3 4 5 6 7 8 9 10 11 12 15 16 17 18 19 20

Ou

tdo

or

refr

iger

ant

syst

em

Out

door

uni

tm

odel

nam

eR

.C.

gro

up

/u

nit

Indo

or u

nit

mod

el n

ame

Hea

der

unit

Air

Co

nd

itio

ner

Lis

t

Blo

ckna

me

Ten

ant

nam

eA

rea

nam

e

Ad

dre

ss I

nfo

rmat

ion

Dis

pla

y n

ame

Int

ellig

ent

Ser

ver

addr

ess

TC

S-N

ET

rel

ay I

/F a

ddre

ss L

ine

addr

ess

Ind

oor

unit

addr

ess

Gro

up a

ddre

ss

Fire

ala

rmN

o.

Hea

der

indo

or u

nit

of g

roup

con

trol

Indo

or u

nit o

n in

divi

dual

con

trol

Fol

low

er in

door

uni

t of

gro

up c

ontr

ol

1 0

28

(Example)

• Bu

ildin

g n

ame:

XX

X B

uild

ing

Key

inpu

tN

o. 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2

Po

wer

met

er N

o.

and

Inp

ut/

Ou

tpu

t d

ata

No

.

Pow

erm

eter

No.

1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 3 3 3

Out

door

uni

tm

odel

nam

e

MM

Y-AP

1401

HT8

MM

Y-AP

1401

HT8

MM

Y-AP

1401

HT8

R.C

. g

rou

p/

un

it

PA

C-B

• 1F

-1

PA

C-B

• 1F

-1

PA

C-B

• 1F

-1

PA

C-B

• 1F

-1

PA

C-B

• 1F

-1

PA

C-B

• 1F

-2

PA

C-B

• 1F

-3

PA

C-B

• 1F

-4

PA

C-B

• 1F

-5

PAC

-M •

1F-1

PAC

-M •

1F-2

PAC

-M •

1F-3

PAC

-M •

1F-4

PAC

-M •

1F-5

PAC

-M •

1F-6

PAC

-M •

1F-7

PAC

-M •

1F-8

PA

C-S

• 2F

-1

PA

C-S

• 2F

-2

Indo

or u

nit

mod

el n

ame

MM

U-A

P00

91H

MM

U-A

P00

91H

MM

U-A

P00

91H

MM

U-A

P00

91H

MM

U-A

P00

91H

MM

K-A

P00

91H

MM

K-A

P00

91H

MM

K-A

P00

91H

MM

K-A

P00

91H

MM

K-A

P00

91H

MM

K-A

P00

91H

MM

K-A

P00

91H

MM

K-A

P00

91H

MM

K-A

P00

91H

MM

K-A

P00

91H

MM

K-A

P00

91H

MM

K-A

P00

91H

MM

K-A

P00

91H

MM

K-A

P00

91H

MM

K-A

P00

91H

Hea

der

unit 1 0 0 0 0 1 1 1 1 1 1 1 1 1 1 1 1 1 0 1

Air

Co

nd

itio

ner

Lis

t

Blo

ckna

me

1F

1F

1F

1F

1F

1F

1F

1F

1F

1F

1F

1F

1F

1F

1F

1F

1F

2F

2F

2F

Ten

ant

nam

e

Ten

ant

A

Ten

ant

A

Ten

ant

A

Ten

ant

A

Ten

ant

A

Ten

ant

B

Ten

ant

B

Ten

ant

B

Ten

ant

B

Ten

ant

C

Ten

ant

C

Ten

ant

C

Ten

ant

C

Off

ice

A

Off

ice

A

Off

ice

A

Off

ice

A

Sha

red

spac

e

Ten

ant

D

Are

ana

me

Sho

p A

Sho

p A

Sho

p A

Sho

p A

Sho

p A

Sho

p B

Sho

p C

Sho

p D

Sho

p E

Sho

p F

Sho

p F

Sho

p G

Sho

p G

Off

ice

Off

ice

Mee

ting

room

Mee

ting

room

A B

Sho

p H

Ad

dre

ss I

nfo

rmat

ion

Dis

pla

y n

ame

1 2 3

1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 1 2 3

1 2 2 2 2 0 0 0 0 0 0 0 0 0 0 0 0 1 2 0

1 1 1

1 1 1

Int

ellig

ent

Ser

ver

addr

ess

TC

S-N

ET

rel

ay I

/F a

ddre

ss L

ine

addr

ess

Ind

oor

unit

addr

ess

Gro

up a

ddre

ss

Fire

ala

rmN

o. 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Ou

tdo

or

refr

iger

ant

syst

em

PA

C-B

PA

C-M

PA

C-S

Hea

der

indo

or u

nit

of g

roup

con

trol

Indo

or u

nit o

n in

divi

dual

con

trol

Fol

low

er in

door

uni

t of

gro

up c

ontr

ol

1 0

29

3-2-4 Schedule tableS

ched

ule

Tab

le (

/

)

• Bu

ildin

g n

ame:

R.C

. gr

oup/

unit

Are

a

Ten

ant

Blo

ck

Day

of

the

wee

k

1 2 3 4 5 6 7 8

: : : : : : : :

: : : : : : : :

: : : : : : : :

Sch

edul

e Ta

ble

(Exa

mpl

e)

• Bu

ildin

g n

ame:

XX

X B

uild

ing

R.C

. gr

oup/

unit

Are

a

Ten

ant

Blo

ck

Day

of

the

wee

k

1 2 3 4 5 6 7 8

PA

C-B

, 1F

-1

Con

sulta

tion

room

XX

Den

tal C

linic

B1

Mon

day

to S

atur

day

8:00

19:0

0

21:0

0

: : : : :

Run

Sto

p

Sto

p

PA

C-B

, 1F

-3 t

o 1F

-5

War

ehou

se

XX

Ele

ctric

Co.

, Ltd

.

B1

Mon

day

to F

rida

y

8:00

12:0

0

13:0

0

19:0

0

21:0

0

: : :

Run

Sto

p

Run

Sto

p

Sto

p

PA

C-B

, 1F

-6

Nig

ht-d

uty

room

B1

Mon

day

to S

atur

day

8:00

9:30

10:0

0

16:3

0

22:0

0

23:5

8

: :

Run

Sto

p

Sto

p

Run

Sto

p

Sto

p

30

HUBEthernet Ethernet

RS-485

Main BUS

Excel

Setup file creation software for Touch Screen Controller

Default data fileProduct information file

Provided from installation company and building management company.

Setup fileSetup file• Tenant name, etc.• Air conditioner information, etc.• Setting values for energy monitoring and billing Air conditioner specific characteristic values Tenant names for reports Record in CF card

Touch Screen Controller

Intelligent Server

Energy monitoring I/F

Power meterAir conditioner

Air conditioner informationLocation, indoor unit group setting,

control address (I/F, indoor, outdoor), device type, product model, number of devices

Device information Power meter No., pulse constant, fire alarm/door-lock input No., emergency output No.

Control display information Block/area/tenant/R.C. Group, unit names

Building operation information Meter read date Schedule (operation, charging)

Set by scheduler function of Touch Screen Controller.

Power distribution software

Printer

TCS-NET Relay I/F

System Configuration

3-3 Setup file creationCreate setup files according to the control wiring system diagram and the address table.

3-3-1 Setup file creation software (Excel macro)• The setup file creation software is used to create setup files installed in the Touch Screen Controller.• In the air conditioning control system, setting values are defined in accordance with air conditioner

installation conditions in a building. If wrong value is set, a problem such as interruption incommunication with air conditioners will occur.

• Setting items: Air conditioner information, device information, Touch Screen Controller displayinformation.

• An operator enters information in Excel spreadsheets, and then creates 23 setup files using the enteredinformation.

Operating environment Windows 2000 or later

Excel 2000 or later is required separately.

OS

Excel

Operating environment and others

31

3-3-2 Setup file contents(1) Display setup file

• File name: DISP_FORM.DEF• Enter entire building display mode, number of block display buttons, number of tenant display buttons, number

of area display buttons, number of R.C. group/indoor display buttons, and schedule setting unit.• For the entire building display mode, specify display unit when the entire building button is pressed.

[0: block, 1: tenant, 2: area, 3: R.C. group/indoor]• For the number of buttons, enter the number of lateral buttons in each display mode. The number of

vertically arranged buttons is always 6.• Specify schedule setting unit. [0: area, 1: R.C. group/indoor]• Specify filter sign display mode. [0: not display, 1: display]

(2) Error code definition file• File name: ERROR_CODE.DEF• Enter reception code (hexadecimal), error code, error code name, display mode, and external

output.• Specify display mode [0: not display (normal), 1: display].• Specify external output [0: not output emergency, 1-64: emergency output No. (output to

corresponding number)].

(3) Touch Screen Controller IP address definition file• File name: CONT_IP.DEF• Enter the Touch Screen Controller IP address.

(4) Intelligent Server IP address definition file• File name: LSV_IP.DEF• Enter an Intelligent Server number and IP address.

(5) I/O Controller IP address definition file• File name: IO_IP.DEF• Enter the I/O Controller IP address.• Only one address can be entered. Do not enter any IP address when the I/O Controller is not used.

(6) Building name definition file• File name: BUILD_NAME.DEF• Enter a building name.

(7) Block name definition file• File name: BLOCK_NAME.DEF• Enter a block number/name, and font size.• Specify font size. [0 (small) -3 (large), 2: standard]

(8) Tenant name definition file• File name: TENANT_NAME.DEF• Enter tenant numbers/names (up to 512), and font size.• Specify font size. [0 (small) -3 (large), 2: standard]

(9) Area name definition file• File name: AREA_NAME.DEF• Enter area numbers/names (up to 512), and font size.• Specify font size. [0 (small) -3 (large), 2: standard].

(10) R.C. group/indoor name definition file• File name: AC_NAME.DEF• Enter R.C. group/indoor numbers/names (up to 512), and font size.• Specify font size. [0 (small) -3 (large), 2: standard]

32

(11) Door-lock input definition file• File name: KEY_CH.DEF• Enter door-lock input numbers (1-64), input device IDs, input channels, and signal logic (up to 64).• When no door-lock input is used, do not enter it.• An input device ID means the following:

0 to 7: I/O module device ID10: general-purpose input in the touch panel100 or more: digital I/O interface (Second digit: Intelligent Server No., first digit: Relay Interface No.)

• Specify signal logic. [0: negative logic, 1: positive logic]

(12) Fire alarm input definition file• File name: FIRE_CH.DEF• Enter fire alarm input numbers (1-64), input device IDs, input channels, and signal logic (up to 64).• When no fire alarm input is used, do not enter it.• An input device ID means the following:

0 to 7: I/O module device ID10: general-purpose input in the touch panel100 or more: digital I/O interface (Second digit: Intelligent Server No., first digit: Relay Interface No.)

• Specify signal logic. [0: negative logic, 1: positive logic]

(13) Emergency external output definition file• File name: EMGOUT_CH.DEF• Enter external emergency output numbers (1-64), output device IDs, and output channels (up to 64).• When no external emergency output is used, do not enter it.• An output device ID means the following:

0 to 7: I/O module device ID20: general-purpose output in the touch panel100 or more: digital I/O interface (Second digit: Intelligent Server No., first digit: Relay Interface No.)

(14) R.C. group/indoor setup file• File name: AC_MAP.DEF• R.C. group/indoor No., Intelligent Server No., Relay Interface No., outdoor system No., indoor unit

address, device type, block No., tenant No., area No., key No., fire alarm No.• Device type

0: SMMS, SHRM, 1: SDI, DI, 2: HA interface• Key No.

0: no door-lock interlocking, 1-64: When a signal is input from the number defined in (11), stopcommand is sent to the system.

• Fire alarm No.0: no fire alarm interlocking, 1-64: When a signal is input from the number defined in (12), stopcommand is sent to the system.

• Indoor unit set in this file is header unit only.

(15) Indoor unit group config file• File name: AC_GROUP.DEF• R.C. group/indoor No., Intelligent Server No., Relay Interface No., outdoor system No., indoor unit

address, device type, outdoor unit No., header/follower, tenant No.• Used for energy monitoring and billing. No data is provided when energy monitoring and billing is not

performed.

(16) Outdoor unit group config file• File name: OUT_GROUP.DEF• Outdoor unit No., Intelligent Server No., Relay Interface No., system No., outdoor unit address,

device type• Used for energy monitoring and billing. No data is provided when energy monitoring and billing is not

performed.

33

(17) Power meter input definition file• File name: WHM_CH.DEF• Power meter No. (1-64), interface address, channel No., pulse generator constants• Used for energy monitoring and billing. No data is provided when energy monitoring and billing is not

performed.• An interface address means the following:

1 to 31: energy monitoring interface100 or more: pulse counter interface (Second digit: Intelligent Server No., first digit: Relay InterfaceNo.)

• Pulse generator constants (kWh/pulse): Used by the energy monitoring and billing Excel macro, butnot used by the controller.

(18) Report setup file• File name: REPORT.DEF• Daily report limit time (meter-read time), Monthly report limit date

(19) Operation mode setup file• File name: RUN_MODE.DEF• Operation mode range, scheduled operation central setting, door-lock interlocking central setting• Operation mode range 0: all enabled, 16: cooling/dry/blowing, 32: heating/blowing• Scheduled operation central setting

Setting

0

1

2

3

Stop (10 minutes later)

Stop

Stop + “run/stop” changeoverprohibition reset

Stop + “run/stop” changeoverprohibition reset

Stop + “run/stop” changeoverprohibition reset

Stop (within 10 minutes)

Stop

Stop + “run/stop” changeoverprohibition reset

Stop + “run/stop” changeoverprohibited

Stop + “run/stop” changeoverprohibited

Run

Run

Run + “run/stop” changeoverprohibition reset

“Run/stop” changeoverprohibition reset

Run + “run/stop” changeoverprohibition reset

Setting

0

1

2

3

Lock (OFF to ON)

Stop

Stop

Stop + “run/stop” changeover prohibited

Stop

• Door-lock interlocking central setting

Unlock (ON to OFF)

No operation

“Run/stop” changeover prohibition reset

“Run/stop” changeover prohibition reset

No operation

* All these files must be included in “¥DEF” folder.

34

3-4 Control system installation3-4-1 External view

Model: BMS-TP0640ACEBMS-TP5120ACEBMS-TP0604PWEBMS-TP5120PWE

Touch Screen Controller

249

95.7

591

.75

256

193016

545 49

242

99.3

75

82.5302

55.548

7075

316

Function switch (F1, F2, F3)

PCI expansion unitconnector cover

Power inputterminal block

Power cable

Ethernet portIntelligentServer

USB mouse

CF (Compact Flash)card slot (CF card fordata files)

POWER LED

M4 Tap (×4 pcs.)(depth: 10 mm max.)

unit: mm

Universal Input/Output port

35

Model: BMS-LSV2E

Intelligent Server

CAUTIOND

o not remove.

WARNINGDo not decompose.

198

39 42

370

Not used

Touch Screen Controller(Ethernet)

Relay Interface(RS-485)

Power switch

CF (Compact Flash) card slot

Metal case type

unit: mm

36

Model: BMS-IFLSV1E

TCS-NET Relay Interface

200

22787822

22787822

66

63.6

146.

9

156

170

6- 5.5 mounting holes

1

2

3

4

5

1

2

3

4

5

Parts name

Case

Case lid

Grommet

Grommet

Grommet for power supply

Specifications

Galvanized sheet metal

Galvanized sheet metal

C30-SG20A

C30-SG20A

C30-SG20A

unit: mm

37

Model: BMS-IFWH3EBMS-IFDD01E

Energy monitoring R I/F • Digital I/O R I/F

234

1818

(193

)92

.564

.5

1818

53.5

103.

5

63.6

220

246

Grommet forpower input

Grommet forpower meter

Grommet forRS-485

Grommet for DO

unit: mm

38

3-4-2 Installation method

Touch Screen ControllerMake space for installation and service.Install the Touch Screen Controller in a wall (standard) or on the dedicated stand (when available on site).

In-wall installation■■■■■Conditions for installationSpace 30 mm or more between the controller andsurrounding objects as the ambient temperaturemust satisfy the installation space requirements.

■■■■■Attaching Fixture

Panel

30 mm or more (top)

30 mm or more (bottom)

30 mm or more (rear)

30 mm or more (side)Interface side

Panel

Top view

Bottom view

1. Insert the controller from outside of the panel.

2. Insert the fixtures from inside of the panel.

Tightening screws excessivelymay cause the screws to break.Optimum tightening torque forgood waterproofing effect is0.6N/m.

Panel

Touch ScreenController

Fixture

■Panel cut size303

+1-0

243

+1

-0

R1 or less

[mm]Panel thickness: 1.6 -1.7 mm

REQUIREMENT

Use a panel(procured on site) ofthickness 1.6-1.7 mm.

For reference

Display stand (not supplied with the controller)Use the CONTEC stand (model: IPC-SND-03).For details of the stand, visit the CONTEC web site.

Europe: http://www.contec-europe.com/China: http://www.contec.sh.cn/

• Check that the installation dimensions on the rear of theTouch Screen Controller equal the installationdimensions of the CONTEC stand.

• Use the screws supplied with the stand to install thecontroller.

REQUIREMENT

The angle adjustment lock screw.(Loosen the screw and adjust angle.)

75 m

m

75 mm

39

Do not install the unit in any of the following places.• Humid or wet place• Dusty place• Place exposed to direct sunlight• Place where there is a TV set or radio within one meter• Place exposed to rain (outdoors, under eaves, etc.)

REQUIREMENT

Intelligent Server Installation Method and Orientation

There are four ways to install the Intelligent Server as shown below: (1) rack mount (2) surface mount (3)wall mount A, and (4) wall mount B. The rack mount installation requires a support bracket for a 19-inchrack. Please contact us if you need the support bracket.Use the four bottom screw holes for the wall mount installation.

(4)Wall mount -BWall mount with the left side upward

(1)Rack mountA support bracket is required to befixed to the bottom (rear side) of theunit.

(2)Surface mountStandard installation

(3)Wall mount -AWall mount with the front side upward

308.4 30.830.8

3013

335

Screw hole for wallmount (M4 × 4 pcs.)

(Unit: mm)

AC inlet side LED side

40

■■■■■Installation Method and Orientation

■■■■■Installation Space and Maintenance Space

There are five installation methods for this relay interface as shown below: surface mount and wallmounts. Use the attached screws.

Do not install the unit in any of the following places.• Humid or wet place• Dusty place• Place exposed to direct sunlight• Place where there is a TV set or radio within one meter• Place exposed to rain (outdoors, under eaves, etc.)

REQUIREMENT

A side space for connecting through cable inlets and an upper space formaintenance must be reserved before installation.The other sides can be adjacent to surrounding objects.

100mm

100mm

No good

TCS-NET Relay Interface

■■■■■Installation Method and OrientationThere are five installation methods for this relay interface as shown below: surface mount and wall mounts.Use the attached screws.

Do not install the unit in any of the following places.• Humid or wet place• Dusty place• Place exposed to direct sunlight• Place where there is a TV set or radio within one meter• Place exposed to rain (outdoors, under eaves, etc.)

REQUIREMENT

■■■■■Installation Space and Maintenance Space

No good

100mm

100mm

100mm

A side space for connecting through cable inlets and an upper spacefor maintenance must be reserved before installation.The other sides can be adjacent to surrounding objects.

Energy monitoring R I/F • Digital I/O R I/F

41

3-4-3 Device specifications

Touch Screen ControllerDevice, model

Touch ScreenController

BMS-TP0640ACEBMS-TP5120ACEBMS-TP0640PWEBMS-TP5120PWE

Specification

100 - 240 V, AC 50/60 Hz

50 VA

316 (W) x 256 (H) x 54 (D) mm

3.5 kg

0 to 40 °C

20 to 85%RH

Item

Power supply

Power consumption

Outside dimensions

Weight

Ambient temperature

Ambient humidity

Intelligent ServerDevice, model

Intelligent Server

BMS-LSV2E

Specification

85 - 132 V, 180 - 264 V, AC 50/60 Hz

30 VA

370 (W) x 42 (H) x 198 (D) mm

2.5 kg

0 to 40 °C

10 to 90%RH

Item

Power supply

Power consumption

Outside dimensions

Weight

Ambient temperature

Ambient humidity

Relay InterfaceDevice, model

TCS-NETRelay Interface

BMS-IFLSV1E

Specification

220 - 240 V, AC 50/60 Hz

2.4 W

170 (W) x 66 (H) x 200 (D) mm

1 kg

0 to 40 °C

10 to 90%RH (no condensation)

Galvanized sheet metal 0.8t (no coating)

Item

Power supply

Power consumption

Outside dimensions

Weight

Ambient temperature

Ambient humidity

Chassis material

Energy Monitoring Interface

Device, model

Energy monitoringRelay Interface

BMS-IFWH3E

Specification

220 - 240 V, AC 50/60 Hz

2.8 W (Energy monitoring)

193 (W) x 66 (H) x 246 (D) mm

1.65 kg

0 to 40 °C

10 to 90%RH

Galvanized sheet metal 0.8t

Item

Power supply

Power consumption

Outside dimensions

Weight

Ambient temperature

Ambient humidity

Chassis material

Digital I/O Interface

Device, model

Digital I/O RelayInterface

BMS-IFDD01E

Specification

220 - 240 V, AC 50/60 Hz

6.5 W

193 (W) x 66 (H) x 246 (D) mm

1.65 kg

0 to 40 °C

10 to 90%RH

Galvanized sheet metal 0.8t (no coating)

Item

Power supply

Power consumption

Outside dimensions

Weight

Ambient temperature

Ambient humidity

Chassis material

42

3-5 Wiring3-5-1 Wiring specifications

Touch Screen Controller

Intelligent Server

TCS-NET Relay Interface

Energy Monitoring Relay Interface

Digital I/O Relay Interface

Device Input voltage

Power supply specifications

Powerconsumption

50 VA

30 VA

2.4 W

2.8 W

6.5 W

Power cablewire size

Remarks

Intelligent Server ↔ TCS-NETRelay Interface

Intelligent Server ↔ EnergyMonitoring Relay Interface

Intelligent Server ↔ Digital I/ORelay Interface

TCS-NET Relay Interface ↔ Airconditioner

Energy Monitoring Relay Interface↔ Power Meter

Digital I/O Relay Interface ↔ DigitalInput/Output

Inter-device connection Control wiringspecifications

D-sub (9-pin) wire *1

(If length is short) Use ashield wire

Shield wire

Shield wire

Shield wire

Shield wire

Number ofcores

4

2

2

2

2

2

2

2

Diameter(mm2)

1.25 mm2

1.25 mm2

1.25 mm2

1.25 mm2

2.0 mm2

0.3 mm2

0.3 mm2

Length(m)

Max. 500

Max. 500

Max. 500

Max.1000*2

Max.2000*2

Max. 100

Max. 100

Polarity

With polarity

With polarity

With polarity

No polarity

No polarity

No polarity

With polarity

Remarks

Supplied withIntelligentServer software

Procure on site

Procure on site

Procure on site

Procure on site

Procure on site

Procure on site

Procure on site

*1: Use the D-sub (9 pin) wire supplied with the Intelligent Server software. If its length is short, use a shield wire.*2: Total length per TCS-NET Relay Interface

Touch Screen Controller ↔ Intelligent Server

Inter-device connection Control wiringspecifications

Ethernet (cross)Category 5 UTP cross wire

Number ofcores

8

Diameter(mm2)

Length(m)

Max. 100

Polarity

Remarks

Procure on site

When Switching HUB is not used

100 - 240 V, AC 50/60 Hz

85 - 132 V, AC 50/60 Hz180 - 264 V, AC 50/60 Hz

220 - 240 V, AC 50/60 Hz

0.75 mm2 Procure on site

Touch Screen Controller ↔ Switching HUB

Switching HUB ↔ IntelligentServer

Inter-device connection Control wiringspecifications

Ethernet (straight)Category 5 UTP straight wire

Ethernet (straight)Category 5 UTP straight wire

Number ofcores

8

8

Diameter(mm2)

Length(m)

Max. 100

Max. 100

Polarity

Remarks

Procure on site

Procure on site

When Switching HUB is used

Ethernet wire specifications

Communication wiring specifications

43

3-5-2 Wiring diagramTO

UC

H S

CR

EE

N C

ON

TRO

LLE

R C

ON

NE

CTI

ON

DIA

GR

AM

AB

FGU

1U

2

TC

C-L

INK

RS

-485

SW6ON

1 2

U2 U1

U4 U3

U2 U1

U4 U3 U4 U3

ON

1

1

2

SW5

SW6ON

1 2

ON

1 2

SW5

SW

1

AD

DR

ES

S

8 SW

1

AD

DR

ES

S

AB

LN

LN

LN

LN

LN

LN

FGU

1U

2

TC

C-L

INK

RS

-485

+12VGNDDO4DO3DO2DO1

DI 8DI 7DI 6DI 5DI 4DI 3DI 2DI 1

DI 8DI 7DI 6DI 5DI 4DI 3DI 2DI 1

DI 8DI 7DI 6DI 5DI 4DI 3DI 2DI 1

4

SW1

ADDRESS

1

SW1

ADDRESS

AB

RS

-485

AB

RS

-485

AB

RS

-485

AB

RS

-485

+12VGNDDO4DO3DO2DO1

DI 8DI 7DI 6DI 5DI 4DI 3DI 2DI 1

4

SW1

ADDRESS

1

SW1

ADDRESS

U2 U1 U2 U1 U2 U1

U2 U1

U4 U3

U2 U1

U4 U3 U4 U3

U2 U1 U2 U1 U2 U1

TO

UC

H S

CR

EE

N C

ON

TR

OL

LE

R(B

MS

-TP

06

40

/51

20

)

INT

ELL

IGE

NT

SE

RV

ER

(BM

S-L

SV

2E)

Red

Ora

ng

eYe

llow

Bro

wn

Cri

mp

3 w

ires

with

a cl

osed

end

wir

e jo

int.

Re

d/O

ran

ge

Bro

wn/

Yello

w

Pow

er s

uppl

y

DIGITAL I/OINTERFACE(BMS-IFDD01E)

DIGITAL I/OINTERFACE(BMS-IFDD01E)

ENERGYMONITORINGINTERFACE

ENERGYMONITORINGINTERFACE

Power meter 1Power meter 2Power meter 3Power meter 4Power meter 5Power meter 6Power meter 7Power meter 8

Power meter 1Power meter 2Power meter 3Power meter 4Power meter 5Power meter 6Power meter 7Power meter 8

Input contact 1Input contact 2Input contact 3Input contact 4Input contact 5Input contact 6Input contact 7Input contact 8

Input contact 1Input contact 2Input contact 3Input contact 4Input contact 5Input contact 6Input contact 7Input contact 8

Load 1Load 2Load 3Load 4

Load 1Load 2Load 3Load 4

TCS-NET RELAYINTERFACE

TCS-NET RELAYINTERFACE

TCC-LINKTERMINATOR

RS-485TERMINATOR

TCC-LINKTERMINATOR

RS-485TERMINATOR

Out

door

unit

Indo

or u

nit

Indo

or u

nit

Rem

ote

cont

rolle

r

Out

door

unit

Indo

or u

nit

Rem

ote

cont

rolle

r

Cen

tral

rem

ote

cont

rolle

r

Out

door

unit

Indo

or u

nit

Indo

or u

nit

Rem

ote

cont

rolle

r

Out

door

unit

Indo

or u

nit

Rem

ote

cont

rolle

r Cen

tral

rem

ote

cont

rolle

r

A B

AB

Pow

er s

uppl

yP

ower

sup

ply

Pow

er s

uppl

yP

ower

sup

ply

Pow

er s

uppl

y

44

Con

nect

ions

(TC

S-N

ET

RE

LAY

INTE

RFA

CE

(BM

S-IF

LSV

1E)

Con

nect

pow

er c

able

s, e

arth

wire

s, a

nd s

igna

l cab

les

to th

e sp

ecifi

ed te

rmin

als

on th

e te

rmin

al b

lock

.

•T

he R

S-4

85 s

igna

l lin

es h

ave

pola

rity

. Con

nect

A to

A, a

nd B

toB

. If c

onne

cted

with

inco

rrec

tpo

larit

y, th

e un

it w

ill n

ot w

ork.

•T

he M

ain

BU

S s

igna

l lin

es h

ave

no p

olar

ity. C

AU

TIO

N1

O

SW

6

N

ON

ON

LED

5

3

12

12

LED

4

4

SW

5O

NO

NLE

D3

12

12

LED

2

SW

7LE

D1

U2U1TCC-LINK

BARS-485

2

SW1SW2SW3SW4

FG

3510

3510

L N

5510

L N

Sec

ure

each

cab

lew

ith a

cab

le c

lam

p.

Con

nect

the

shi

eld

wir

e of

the

Mai

n B

US

com

mun

icat

ion

wir

e to

the

eart

h on

the

air

con

ditio

ner

side

. D

o no

t co

nnec

t th

e sh

ield

wire

to th

e te

rmin

al b

lock

. It s

houl

dbe

ope

n an

d in

sula

ted.

Con

nect

the

shi

eld

wir

e of

the

RS

-485

com

mun

icat

ion

wir

e to

the

eart

h on

the

Int

ellig

ent

serv

er s

ide.

Do

not

conn

ect

the

shie

ld w

ire

toth

e te

rmin

al b

lock

. It

shou

ld b

eop

en a

nd in

sula

ted.

Air

con

ditio

ner

Inte

llige

nt s

erve

r

Pow

er s

uppl

y

Leng

th o

f st

ripp

ed p

ower

cab

leLe

ngth

of

stri

pped

RS

-485

com

mu

nic

atio

n w

ire

Inst

all a

bre

aker

at t

he p

rimar

y si

deof

the

pow

er s

uppl

y.

RE

QU

IRE

ME

NT

Con

nect

the

ear

thw

ire

to t

he e

arth

term

inal

on

the

chas

sis.

45

Con

nect

ion

diag

ram

(TC

S-N

ET

RE

LAY

INTE

RFA

CE

(BM

S-IF

LSV

1E))

A

A BFG U1 U2

TCC-LINKTCC-LINK

RS-485

SW

6O

N 12

U2

U1

U4

U3

U2

U1

U4

U3

U4

U3

ON 1

8

2

SW

5

SW1

ADDRESS

A BFG U1 U2

RS-485

SW

6O

N 12

ON 1

2

SW

5

B

1

SW1

ADDRESSU

2U

1U

2U

1U

2U

1

U2

U1

U4

U3

U2

U1

U4

U3

U4

U3

U2

U1

U2

U1

U2

U1

AB

L NL N

Con

nect

the

shi

eld

wir

es o

f th

e tw

ow

ires.

Mai

n B

US

U1

and

U2

have

no

pola

rity

.

The

shi

eld

of M

ain

BU

Sca

ble

sh

ou

ld b

e o

pe

nan

d in

sula

ted.

It is

not

conn

ecte

d to

the

term

inal

blo

ck.

Mai

n B

US

ter

min

ator

res

isto

r is

set

on

the

air

cond

ition

ersi

de. B

it 1

and

2 of

SW

6 sh

ould

be

OF

F.

Set

the

RS

-485

ter

min

ator

res

isto

r on

the

No.

1 (r

elay

inte

rfac

e ad

dres

s S

W1=

1) u

nit

and

for

Inte

llige

nt S

erve

ron

ly. D

o no

t set

it h

ere.

The

shi

eld

of R

S-4

85 c

able

sho

uld

be o

pen

and

insu

late

d. I

t is

not

con

nect

ed t

o th

e te

rmin

al b

lock

.

CA

UT

ION

: R

S-4

85 s

igna

ls A

and

B h

ave

pola

rity

. Be

care

ful w

hen

conn

ectin

g th

e R

S-4

85 w

ires

.

TO

UC

H S

CR

EE

N C

ON

TR

OLL

ER

(BM

S-T

P06

40/5

120)

INT

ELL

IGE

NT

SE

RV

ER

(BM

S-L

SV

2E)

Red

Ora

nge

Yello

wB

row

n

Cri

mp

3 w

ires

with

a cl

osed

end

wir

ejo

int.

Red

/Ora

nge

Bro

wn/

Yello

w

Pow

ersu

pply

Ou

tdo

or

unit R

em

ote

cont

rolle

rIndo

or u

nit

Ind

oo

run

it

Ou

tdo

or

unit

Re

mo

teco

ntro

ller

Ind

oo

run

it

Ce

ntr

al

rem

ote

cont

rolle

r

Set

the

RS

-485

ter

min

ator

res

isto

r on

the

No.

1 (r

elay

inte

rfac

e ad

dres

s S

W1=

1)un

it. S

et b

it 1

of S

W5

to O

N.

Set

the

TC

S-N

ET

Rel

ay I

nter

face

add

ress

with

SW

1. A

ssig

n 1

to 8

to

each

addr

ess

to a

void

dup

licat

ion.

CA

UT

ION

: The

SW

1 se

tting

is r

ead

whe

n th

e po

wer

is t

urne

d on

. Pus

h th

ere

set

switc

h S

W7

afte

r ch

angi

ng t

he a

ddre

ss.

Ou

tdo

or

unit R

em

ote

cont

rolle

rIndo

or u

nit

Ind

oo

run

it

Ou

tdo

or

unit

Re

mo

teco

ntro

ller

Ind

oo

run

it

Ce

ntr

al

rem

ote

cont

rolle

r

Pow

ersu

pply

46

Con

nect

ions

(EN

ER

GY

MO

NIT

OR

ING

RE

LAY

INTE

RFA

CE

(BM

S-IF

WH

3E))

Con

nect

pow

er c

able

s, e

arth

wire

s, a

nd s

igna

l wire

s to

the

spec

ified

term

inal

s on

the

term

inal

blo

ck.

The

RS

-485

sig

nal w

ire h

aspo

larit

y. C

onne

ct A

to A

, and

B to

B. I

f con

nect

ed w

ith in

corr

ect

pola

rity,

the

unit

will

not

wor

k.

CA

UT

ION

Inst

all a

bre

aker

an

the

prim

ary

side

of t

he p

ower

sup

ply.

RE

QU

IRE

ME

NT

3535

356

610

5510

ON

SW

1

DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 FG B A

SW

2S

W3

SW

4S

W7

12

34

N

RS-485

L

Sec

ure

each

cab

lew

ith a

cab

le c

lam

p.

Pow

er

cabl

e

Sec

ure

each

cabl

e w

ith a

cabl

e cl

amp.

Pow

er m

eter

Inte

llige

nt S

erve

r

Leng

th o

f st

ripp

edp

ow

er

cab

leLe

ngth

of

stri

pped

com

mu

nic

atio

n w

ire

Leng

th o

f st

ripp

edpo

wer

met

er w

ire

Inse

rt t

he w

ire

by p

ushi

ng t

hele

ver

with

a s

crew

driv

er. C

heck

that

the

wir

e is

inse

rted

secu

rely

.

Whe

n in

sert

ing

two

RS

-485

com

mun

icat

ion

wir

es in

to a

sin

gle

term

inal

for

con

nect

ion

to a

noth

erin

terf

ace,

cri

mp

them

usi

ng t

heat

tach

ed p

in t

erm

inal

.

Con

nect

the

ear

thw

ire

to t

he e

arth

term

inal

on

the

chas

sis.

47

The following describes wiring connections of the Energy Monitoring Relay Interface when it is used inthe air conditioner control system.

• Terminator resistor settingSet the RS-485 terminator resistor by the TCS-NET Relay Interface.Do not set it by the Energy Monitoring Relay Interface.

• Shield earthingThe shield earth of the RS-485 signal wires should be single-point earth. Earth the wires on theIntelligent server side.Other shield lines should be closed, and the terminal end should be open and insulated.

• Connection of power meterUse a power meter with a pulse generator.Connect the non-voltage contact output of the power meter to the Energy Monitoring Relay Interface.An external input circuit is shown below.Input signal is electrically isolated by photo-coupler.

12V

Wiring Connection

Energy Monitoring Relay Interface

Inputterminal

Power meter(with pulse generator)

ContactDI-1 to DI-8

48

Con

nect

ion

diag

ram

(EN

ER

GY

MO

NIT

OR

ING

RE

LAY

INTE

RFA

CE

(BM

S-IF

WH

3E))

A B

AB

AB

LN

FGU

1U

2 TC

C-L

INK

RS

-485

LN

LN

DI 8DI 7DI 6DI 5

DI 4DI 3DI 2DI 1

DI 2DI 1

DI 8DI 7DI 6DI 5

DI 4DI 3

1

SW1

SW1

ADDRESS

4

ADDRESS

AB

RS

-485

AB

RS

-485

Set

the

Ene

rgy

Mon

itori

ng R

elay

Inte

rfac

e ad

dres

s w

ith S

W1.

Ass

ign

1 to

4 to

eac

h ad

dres

s to

avo

id d

uplic

atio

n.E

ach

inte

rfac

e ha

s its

ow

n ad

dres

s an

dca

n be

set

inde

pend

ently

.C

AU

TIO

N: T

he S

W1

setti

ng is

rea

dw

hen

the

pow

er is

tur

ned

on.

Pus

h th

ere

set

switc

h af

ter

chan

ging

the

add

ress

.

Con

nect

the

resp

ectiv

esh

ield

wir

es o

ftw

o ca

bles

.

The

shi

eld

eart

h of

the

RS

-485

sig

nal

wir

es s

houl

d be

sing

le-p

oint

ear

th.

Ear

th t

he w

ires

on

the

Inte

llige

nt s

erve

rsi

de.

Do

not

eart

hhe

re.

CA

UT

ION

: RS

-485

sign

als

A a

nd B

have

pol

arity

. Be

care

ful w

hen

conn

ectin

g th

e R

S-

485

wir

e.C

AU

TIO

N: N

o te

rmin

ator

res

isto

rse

ttin

g sw

itch

is p

rovi

ded

on t

heE

nerg

y M

onito

ring

Rel

ay I

nter

face

.S

et t

he R

S-4

85 t

erm

inat

or r

esis

tor

on t

he T

CS

-NE

T R

elay

Int

erfa

ce.

TO

UC

H S

CR

EE

N C

ON

TR

OLL

ER

(BM

S-T

P06

40/5

120)

INT

ELL

IGE

NT

SE

RV

ER

(BM

S-L

SV

2E)

Re

d/O

ran

ge

Bro

wn

/Ye

llow

Pow

er s

uppl

y

Red

Ora

ng

eYe

llow

Bro

wn

Cri

mp

3 w

ires

with

a cl

ose

end

wir

e jo

int.

TCS-NET RELAYINTERFACE

ENERGYMONITORINGINTERFACE

ENERGY MONITORINGINTERFACE (BMS-IFWH3E)

CA

UT

ION

: RS

-485

sig

nals

Aan

d B

hav

e po

lari

ty. B

eca

refu

l whe

n co

nnec

ting

the

RS

-485

wir

e.

Power meter 1

Power meter 2

Power meter 3

Power meter 4

Power meter 5

Power meter 6

Power meter 7

Power meter 8

Power meter 1

Power meter 2

Power meter 3

Power meter 4

Power meter 5

Power meter 6

Power meter 7

Power meter 8

Pow

er s

uppl

yP

ower

sup

ply

49

Con

nect

ions

(DIG

ITA

L I/O

RE

LAY

INTE

RFA

CE

(BM

S-IF

DD

01E

))

Con

nect

pow

er c

able

s, e

arth

wire

s, a

nd s

igna

l wire

s to

the

spec

ified

term

inal

s on

the

term

inal

blo

ck.

The

RS

-485

sig

nal w

ire h

aspo

larit

y. C

onne

ct A

to A

, and

B to

B. I

f con

nect

ed w

ith in

corr

ect

pola

rity,

the

unit

will

not

wor

k.

CA

UT

ION

Inst

all a

bre

aker

at t

he p

rimar

y si

deof

the

pow

er s

uppl

y.

RE

QU

IRE

ME

NT

3535

356

610

5510

ON

SW

1

DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 FG B

DO

1

DO

2

DO

3

DO

4

GN

D

+12

VA

SW

2S

W3

SW

4S

W7

12

34

N

RS-485

L

Sec

ure

each

cabl

e w

ith a

cab

lecl

amp.

Pow

er

cabl

e

Se

cure

ea

chca

ble

with

aca

ble

clam

p.

Dig

ital i

nput

cont

acts

Inte

llige

ntS

erve

r

Dig

ital o

utpu

tlo

ad

Leng

th o

f st

ripp

edp

ow

er

cab

leLe

ngth

of

stri

pped

com

mu

nic

atio

n w

ire

Leng

th o

f st

ripp

ed d

igita

lIn

put/

Out

put

conn

ecto

r w

ire

Inse

rt t

he w

ire

by p

ushi

ng t

hele

ver

with

a s

crew

driv

er. C

heck

that

the

wire

is in

sert

ed s

ecur

ely.

Whe

n in

sert

ing

two

RS

-485

com

mun

icat

ion

cabl

es in

to a

sing

le t

erm

inal

for

con

nect

ion

toan

othe

r in

terf

ace,

cri

mp

them

usin

g th

e at

tach

ed p

in t

erm

inal

.

Con

nect

the

ear

thw

ire

to t

he e

arth

term

inal

on

the

chas

sis.

50

If an inductive load (relay coil) or a bulb is connected, a surge voltage or rush current will begenerated. Take adequate measures against surge voltage or rush current.

CAUTION

Wiring Connection

The following describes wiring connections of the Digital I/O Relay Interface when it is used in the airconditioner control system.

• Terminator resistor settingSet the RS-485 terminator resistor by the TCS-NET Relay Interface.Do not set it by the Digital I/O Relay Interface.

• Shield earthingThe shield earth of the RS-485 signal wires should be single-point earth. Earth the wires on theIntelligent Server.Other shield lines should be closed, and the terminal end should be open and insulated.

• Connection of external digital inputsInput circuit examples are shown below (electrically isolated using a photo-coupler).

(1) Example of contact input connection (2) Example of current sink connection

12V 12V

Contact

Input terminal

DI-1 to DI-8

Current sink

Input terminal

DI-1 to DI-8

• Connection of external digital outputsOutput circuit examples are shown below (open collector output electrically isolated using a photo-coupler).

(1) Example of load connection (2) Example of load connection

12V

GND

12V+12VOutput terminal

DO1 to DO4 Load

Externalpowersupply Output terminal

DO1 to DO4

51

Co

nnec

tion

dia

gram

(DIG

ITA

L I/O

RE

LA

Y IN

TER

FAC

E (B

MS

-IFD

D01

E))

A B

AB

AB

FGU

1U

2

TC

C-L

INK

RS

-485

4

SW1

ADDRESS

AB

RS

-485

AB

RS

-485

DI 8

+12VGNDDO4DO3DO2DO1

+12VGNDDO4DO3DO2DO1

DI 7

DI 6DI 5

DI 4

DI 3DI 2DI 1

DI 8DI 7

DI 6DI 5

DI 4

DI 3DI 2DI 1

1

SW1

ADDRESS

LN

LN

LN

The

shi

eld

eart

h of

the

RS

-485

sig

nal

wir

es s

houl

d be

sing

le-p

oint

ear

th.

Ear

th t

he w

ires

on

the

Inte

llige

ntS

erve

r.

Set

the

Dig

ital I

/O R

elay

Inte

rfac

ead

dres

s w

ith S

W1.

Ass

ign

1 to

4 to

each

add

ress

to

avoi

d du

plic

atio

n.Yo

u ca

n se

t th

e di

gita

l Inp

ut/O

utpu

tR

elay

Int

erfa

ce a

ddre

ssin

depe

nden

tly f

rom

the

Mai

n B

US

Rel

ay I

nter

face

add

ress

or

the

Ene

rgy

Mon

itori

ng R

elay

Int

erfa

cea

dd

ress

.C

AU

TIO

N: T

he S

W1

setti

ng is

rea

dw

hen

the

pow

er is

tur

ned

on.

Pus

hth

e re

set s

witc

h (S

W7)

afte

rch

angi

ng t

he a

ddre

ss.

DIGITAL I/OINTERFACE(BMS-IFDD01E)

DIGITAL I/OINTERFACE(BMS-IFDD01E)

TCS-NET RELAYINTERFACE

CA

UT

ION

: S

et th

eR

S-4

85 t

erm

inat

orre

sist

or o

n th

e T

CS

-N

ET

Rel

ayIn

terf

ace.

No

term

inat

or r

esis

tor

sett

ing

switc

h is

prov

ided

on

the

Dig

ital I

/O R

elay

Inte

rfac

e.

The

RS

-485

sig

nal w

ire

has

pola

rity

A a

nd B

. B

e ca

refu

l whe

nco

nnec

ting

the

wir

e.

TO

UC

H S

CR

EE

N C

ON

TR

OLL

ER

(BM

S-T

P06

40/5

120)

INT

ELL

IGE

NT

SE

RV

ER

(BM

S-L

SV

2E)

Re

d/O

ran

ge

Bro

wn

/Ye

llow

Pow

er s

uppl

y

Input contact 1

Input contact 2

Input contact 3

Input contact 4

Input contact 5

Input contact 6

Input contact 7

Input contact 8

Load 1

Load 2

Load 3

Load 4

Input contact 1

Input contact 2

Input contact 3

Input contact 4

Input contact 5

Input contact 6

Input contact 7

Input contact 8

Load 1

Load 2

Load 3

Load 4

Red

Ora

ng

eYe

llow

Bro

wn

Cri

mp

3 w

ires

with

a cl

osed

end

wir

e jo

int.

Con

nect

the

shie

ld w

ire

of t

hetw

o w

ires

Pow

er s

uppl

yP

ower

sup

ply

52

3-6 Network connection

Connecting the Network Wires

Connect the Touch Screen Controller to Intelligent Servers and to an optional PC for creating monthlyreports using network wires (category 5UTP straight wire), via a Switching HUB (procured on site).• Connect the Ethernet port of the controller to a port of the HUB with a network wire.• Connect the Ethernet port 1 of the Intelligent Server to a port of the HUB with a network wire.• Connect the PC’s Ethernet port to a port of the HUB with a network wire. (Not required if there is not

need to create reports.)

Ethernet

PC for creating monthly reports

Touch Screen Controller Switching HUB

Intelligent Server No.1

Intelligent Server No.2

Network wires(category 5UTP straight wire)

Ethernet port 1

Ethernet port 2

Ethernet port

53

3-7 Control system configuration

To connect the touch screen controller, intelligent server, and PC for energy monitoring and billing viaswitching HUB, All device IP address setting is necessary.

Device IP addressTouch screen controller: 192.168.2.69 (default address)

192.168.2.70••

Intelligent server: 192.168.2.100 (default address)192.168.2.101

••

PC for energy monitoring and billing: 192.168.2.** (**: Set number except from 69 to 149)

54

55

4

ADDRESS SETTING

4-1 Address setting flow4-2 Definition of address4-3 Address setting for air conditioner

4-3-1 Setting for VRF system(1) Check at main Power-ON(2) Manual setting from wired remote controller(3) Line (system) address setting(4) Power reset(5) Indoor unit address check(6) Trial operation(7) Setup of relay connector and terminator(8) Central control address setting(9) Trial operation for central controller (TCB-SC642TLE)(10) Automatic address setting (for reference)(11) Clearance of address(12) Confirmation of indoor unit address and position by using

the remote controller(13) Address change from remote controller(14) In case of increase the address-undefined indoor units

(Extension, etc.)(15) Address setup example (VRF system)

4-3-2 Setting for 1 by 1 system(1) Address re-setup(2) Indoor address change example

4-4 Address setting for control system devices4-4-1 Address setting flow4-4-2 Setting for Intelligent Server4-4-3 Setting for TCS-Net relay interface4-4-4 Setting for Energy monitoring relay interface4-4-5 Setting for Digital I/O relay interface

56

4-1 Address setting flowSetting flow

Power ON

Contents Reference No.

Manual address setting

Line address setting

Indoor units/Outdoor units

Setting from main wired remote controller(Line/Group/Indoor address setting)

Dip Switch setting on outdoor interfaceP.C.board

Power reset to activate line address

7 segment display on outdoor interfaceP.C.board check line/indoor address onremote controller

Test operation in each refrigerantsystem one by one

4-3-1 (1)

Power reset

Indoor unit address check

Trial operation (Refrigerant system)

Setup of relay connector and SW30-2

Central controller exist ?

Central control device setting

Trial operation (Central control device)

TCS-NET control system address settingLocal serverTCS-NET relay I/FEnergy monitoring relay I/FDigital I/O relay I/F

Central control wiring and terminatorsetting

Local central remote controller setting any(Central remote controller, ON/OFFcontroller, etc)

Test for local central control device

Switch settingCF (Compact Flash) card mounting

4-3-1 (2)

4-3-1 (3)

4-3-1 (4)

4-3-1 (5)

4-3-1 (6)

4-3-1 (7)

4-3-1 (8)

4-3-1 (9)

4-4

Chapter. 5Trial operation for Touch panel controller Operation from touch screen controller

57

4-2 Definition of addressIndoor unit address• “Indoor unit address” is to make outdoor unit recognize an individual indoor unit.This indoor unit address is allocated to every indoor unit one by one for every refrigerant system.(At shipment=99, Address unset)

Group address• “Group address” is the address to recognize group control and decide the header indoor unit and thefollower indoor unit.Group address and header indoor unit is decided automatically when automatic address setting isperformed.(Which indoor unit becomes the header unit is indefinite when automatic address setting is performed.)

Indoor unit on individual control : Group address = 0 (At shipment=99, Address unset)Header indoor unit of group control : Group address = 1Follower indoor unit of group control : Group address = 2

Indoor unit address

Header

Outdoor unit

Indoor unit

Remote controller

Follower

1 2 3 4

Header Follower

1 2 3 4

Indoor unit address

Header

Outdoor unit

Indoor unit

Remote controller

Follower

HeaderFollower FollowerHeader Follower

1 2 3 4

Header Follower

1 2 3 4

Group address

0 0 1 2 0 2 1 2

Individual control

Group control

Individual control

Group control

58

Line address (System address)• “Line address” is the address with which line (refrigerant system) indoor units are connected.This line address is set by switch setting on interface P.C. board of the header outdoor unit.

Header

Dip Switch setting

Central control device

Outdoor unit

Indoor unit

(At shipment=99, Address unset)

Remote controller

Follower

1 1

1

1 1Line address

Header Follower

2 2

2

2 2

Line address ( Outdoor)

Line 1 (Refrigerant system 1)

Line 2 (Refrigerant system 2)

59

Central control address• “Central control address” is to make central control devices recognize each indoor unit.This address can be set from central control devices automatically or manually.In case of group control on VRF system, one central control address is allocated to each indoor unit in agroup control.

HeaderCentral controldevice

Outdoor unit

Indoor unit

Remote controller

Follower

1 2

1

3 4Central control address

Header Follower

5 6

2

7

Line address ( Outdoor)

Line 1 (Refrigerant system 1)

Line 2 (Refrigerant system 2)

Individual control

Group control

(At shipment=99, Address unset)

60

Zone address (Zone No.)• “Zone address” is to be set when the central remote controller is used for each zone.Zone address is set by switch setting on central remote controller.

Central remote controller can divide all indoor units into max. 4 zone.The zone to which the indoor unit belongs is decided by its central control address.

Central control address1 to 1617 to 3233 to 4849 to 64

Zone 1Zone 2Zone 3Zone 4

HeaderCentral remote controller ("All" mode)Outdoor unit

Indoor unit

Remote controller

Follower

1 2 3 4

Header

20 21

Zone 1

Central Zone 1 RC*

Header Follower

17 18 19

Zone 2

Central Zone 2 RC*

1 2Zone address

Central control address

(At shipment=99, Address unset)

Zone No.

* RC: Remote controller

61

TCS-NET control system address

CompactFlash

CompactFlash

CompactFlash

CF card

TCS-NETrelay interface(BMS-IFLSV1E)

No.11-1 1-2 1-3 .....

.....

.....

.....

.....

.....

2-1 2-2 2-3

3-1 3-2 3-3

4-1 4-2 4-3

5-1 5-2 5-3

No.2

No.1

No.2

No.3

Outdoor units Indoor units

Intelligent server No. = 1

EthernetCF card

CF card

Touch Screen Controller(BMS-TP0640/5120)

Switching HUB(Procured on site)

PC for Energy Monitoringand billing

(Procured on site)

InteIligent Server(BMS-LSV2E)

Intelligent server No. = 2

RS-485

Line address=1

Line address=2

Line address=3

Line address=4

.....

.....

7-1 7-2 7-3

8-1 8-2 8-3

No.2 Line address=7

Line address=8

.....6-1 6-2 6-3No.1 Line address

=6

Line address=5

Power meterPower meter

Power meter

Power meterPower meter

Energy Monitoring relay interface(BMS-IFWH3E)

No.1Power meter

Power meterPower meter

Energy monitoring relay interface(BMS-IFWH3E)

No.1

No.2

InputInput

Output

InputInput

Output

Digital I /O relay interface(BMS-IFDD01E)

(Setup file)

TCS-NET control system addressTCS-NET relay interface No.Energy monitoring relay interface No.Digital I/O relay interface No.Interigent server No.

Number1 to 81 to 41 to 41 to 4

Setting methodSet by SW1 on P.C. board.Set by SW1 on P.C. board.Set by SW1 on P.C. board.Set based on setup data in CF card on touch panel controller.

62

4-3 Address setting for air conditioner4-3-1 Setting for VRF systemIn this air conditioner, it is required to set up address to the indoor unit before starting operation. Set upthe address according to the following setup procedure.

CAUTION

1. Set up address after wiring work.2. Be sure to turn on the power in order of indoor unit → outdoor unit. If turning on the power in the

reverse order, a check code [E19] (Error of No. of header units) is output.When a check code is output, turn on the power again.

3. To set up an address, it is unnecessary to operate the air conditioner.4. Manual address setting is recommended for TCS-NET control system

Manual address: Setup from the wired remote controller* It is temporarily necessary to set the indoor unit and wired to 1 by 1.

(In group operation and in time without remote controller)5. Automatic address setup is also available besides manual setup.

Automatic address: Setup from SW15 on the interface P.C. board of the header unitIt requires maximum 10 minutes (Usually, approx. 5 minutes) to set up automatically an address to1 line.

6. To set up an address automatically, the setup at outdoor side is necessary.(Address setup cannot be performed by power-ON only.)

63

Interface P.C. board7-segment display [A]

SW01 SW02 SW03

7-segment display [B]

4-3-1 (1) Check at main power-ON

After turning on the main power of the indoor units and outdoor unit in the refrigerant system to beexecuted with a test operation, check the following items in each outdoor and indoor unit.(After turning on the main power, be sure to check in order of indoor unit → outdoor unit.)

<Check on outdoor unit>1. Check that all the rotary switches, SW01, SW02, and SW03 on the interface P.C. board of the header

outdoor unit are set up to “1”.2. If other error code is displayed on 7-segment [B], remove the cause of trouble.3. Check that [L08] is displayed on 7-segment display [B] on the interface P.C. board of the header

outdoor unit. (L08: Indoor address unset up)(If the address setup operation has already finished in service time, etc, the above check code is notdisplayed, and only [U1] is displayed on 7-segment display [A].)

UNIT

SET CL

UNIT

SET CL

Normal status(Power and operation stop)

Abnormal status(Power is not normally turned on.)

If a frame is not displayed as shown in the above right figure, the power of the remote controller is notnormally turned on. Therefore check the following items.• Check power supply of indoor unit.• Check wiring between indoor unit and remote controller.• Check whether there is cutoff of cable around the indoor control P.C. board or not, and check

connection failure of connectors.• Check failure of transformer for the indoor microcomputer.• Check indoor control P.C. board failure.

<Check on indoor unit>1. Display check on remote controller (In case of wired remote controller)

Check that a frame as shown in the following left figure is displayed on LC display section of the remotecontroller.

64

4-3-1 (2) Manual setting from wired remote controller

CAUTIONBe sure to allocate Line (system) /Group/Indoor address one by one to match the address settingtable and setup file that is prepared beforehand.If wrong value is set, a problem such as error of communication with air conditioner will occur.

Indoor, group, line address are set manually for each refrigerant system one by one.

Line address (At shipment:1)

Header

Outdoor unit

Indoor unit

Indoor address 1 2 3 40 0 1 2Group address

1 1 1 1Line address

Remote controller

Follower

At shipment, all address are 0099 (Address unset status)

Dip Switch setting on interface P.C.board

(Step 1)Arrange one indoor unit and one remote controller (RBC-AMT21E) set to 1 by 1.

Note:Don’t use simple remote controller or wireless remote controller.(Address setting is not available.)

Connect wired remotecontroller individuallywhen manual addresssetting

65

UNIT

SET CL

UNIT No.

CODE No.SET DATA

R.C. No.

Operation procedure

1 → 2 → 3 → 4 → 5 → 6 → 7 → 8 → 9 → 10 → 11 End

2, 5, 8 3, 6, 9

14, 7, 10

11

DataItem code

system

Headerindoor

unit

#1

Indoor Indoor Indoor

Line address → 1Indoor address → 1Group address → 1

system

System System#2

Indoor Indoor

Followerindoor

unit

122

132

212

222

Remotecontroller

(Step 2)

Note)When setting the line address from the remote controller, do not use address 29 and 30.The address 29 and 30 cannot be set up in the outdoor unit. Therefore if they are incorrectly set up, acheck code [E04] (Indoor/outdoor communication circuit error) is output.

Turn on the power.

(Wiring example in 2 systems)

In the above example, under condition ofno inter-unit wire of the remote controller,set the address after individual connectingof the wired remote controller.

In case of group control

1 Push simultaneously SET + CL + but-tons for 4 seconds or more.LCD changes to flashing.

(Line address)

2 Using the setup temp. / buttons, set to the item code.

3 Using the timer time / buttons, setup the line address.(Match it with the line address on the interface P.C.board of the header unit in the identical refrigerantsystem.)

4 Push SET button.(OK when display goes on.)

(Indoor address)

5 Using the setup temp. / but-tons, set to the item code.

6 Using the timer time / buttons, setup the indoor address.

7 Push SET button.(OK when display goes on.)

(Group address)

8 Using the setup temp. / but-tons, set to the item code.

9 Using the timer time / buttons, setIndividual = , Header unit = , Followerunit = .

10 Push SET button.(OK when display goes on.)

11 Push button.Setup operation finished.(Status returns to normal stop status.)

Line (system) addressIndoor address

Group address

13

14

12Item code

Group addressIndividual : 0000Header unit : 0001Follower unit : 0002

66

4-3-1 (3) Line (System) address setting

CAUTIONBe sure to allocate different line address for each refrigerant system as much as possible even ifthere are two or more TCS-NET relay interfaces.

SW11

1ON

Header unit interface P.C. board

2 3 4

SW12

1ON

2 3 4

SW06

1ON

2 3 4

SW07

1ON ONON ON

2 3 4

SW09SW08

11 2 3 4

SW10

1 2 3 4

SW13

1ON

2 3 4

SW14

1ON

2 3 4

1. Using SW13 and 14 on the interface P.C.board of the header unit in each system, setup the system address for each system.(At shipment from factory: Set to Address 1)

Note) Be careful not to duplicate with otherrefrigerant line.

Systemaddress

123456789

1011121314

SW13 SW141 2 3 4 1 2 3 4

× × × × ×× × × ×× × × ×× × ×× × × ×× × ×× × ×× ×× × × ×× × ×× × ×× ×× × ×× ×

Systemaddress

1516171819202122232425262728

SW13 SW141 2 3 4 1 2 3 4

× ××

× × × ×× × ×

× × ×× ×

× × ×× ×

× ××

× × ×× ×

× ××

2. Check that the relay connectors between [U1U2] and [U3U4] terminals are come out in all the headerunits to which the central control is connected.(At shipment from factory: No connection of connector)

System address switch on outdoor interface P.C. board

: Is not used for setup of system address. (Do not change setup.)

( : Switch ON, × : Switch OFF)

4-3-1 (4) Power reset

• To activate line address on both outdoor and indoor unit side, power supply is temporarily reset.

• When power is supplied again, be sure to the power of indoor unit prior to the outdoor unit.

67

4-3-1 (5) Indoor unit address check

Step

1

2

3

4

Item

Power - on

Display check

Systeminformationcheck(Outdoor side)

Addressinformationcheck(indoor side)

Operation and check contents

Initial communication takes a couple of minutes.During initial communication, 7-segment display section is as follows as follows.Display [A] --- [U1], flashing Display [B] --- [ - - 0] --> [ - - i] flashing

After initial communications, [U1] are displayed in 7-segment display section.(If error code is displayed in display section [B], remove the cause reffering to “troubleshooting” of installation or service manual.)

<Procedure> (Operation while the airconditioner operates)

1 If it stops, push button.

2 Push UNIT button.

The unit NO is displayed on the LCD.(Disappears after several seconds) The dis-played unit No indicates the line address andindoor address. (If there is other indoor unitconnected to the same remote controller(Group control unit), other unit No is displayedevery pushing UNIT button.)

Operation procedure

1 → 2 → 3 End

Indoor addressLine address

End

UNIT

SET CL

UNIT No.

CODE No.SET DATA

R.C. No.

3

12

System capacity

No. of connectedoutdoor units

No. of connectedindoor units

Indoor addressNo. and capacity

SW01

1

1

1

6

SW02

2

3

4

1 to 16

[A]

[No. of HP]

[No. of indoor units]

[No. of outdoor units]

[Indoor unit address]

SW03

3

3

4

1 to 3

[B]

[HP]

[ ]

[ ]

[Capacity (HP)]

Rotary switch setup 7-segment display

SW02

1 to 16

1 to 16

1 to 16

SW03

1

2

3

Indoor address

SW02 setup number

SW02 setup number +16

SW02 setup number +32

7-segment [A]

[01] to [16]

[17] to [32]

[33] to [48]

Note) Indoor unit address No. is choosen by changing SW02 and SW03.

<On the header outdoor interface P.C.board>

4-3-1 (6) Trial operation

Please refre to the trial operation on the manual of air conditioner.

7-segment display A

2nd.place

1st.place

7-segment display B

Interlace P.C. board

3rd.place

2nd.place

1st.place

SW01 SW02

Display A Display B

D600 D601

CN30 CN31

SW06 SW07 SW09SW08

CN32 SW04

SW05 SW15

SW03

D602 D603 D604

SW01 SW02

Display A Display B

D600 D601

CN30 CN31

SW06 SW07 SW09SW08

CN32 SW04

SW05 SW15

SW03

D602 D603 D604

68

4-3-1 (7) Setup of relay connector and terminator

• After trial operation for each refrigerant system, set the relay connector and terminator resistor for allrefrigerant system which are connected from one TCS-NET relay interface.

<Procedure>

1 How to set up terminator resistor (SW30)When all the address setups have finished in the samerefrigerant system, put the terminator resistor (SW30) in thesame central control line into one.• Remain only SW30-2 of the header outdoor unit with the

least line address number as it is ON.(With terminal resistor)

• Set up SW30-2 of the other header outdoor units to OFF.(Without terminal resistor)

2 Connect the relay connector between [U1U2] and[U3U4] of the header outdoor unit for each refrigerantsystem.

Header outdoor unit interface P.C. board

SW11

1ON

2 3 4

SW12

1ON

2 3 4

SW06

1ON

2 3 4

SW07

1ON ONON ON

2 3 4

SW09SW08

11 2 3 4

SW10

1 2 3 4

SW13

1ON

2 3 4

SW14

1ON

2 3 4

SW30SW30

1ON

2

1

2

U1 U2For internal wiring between indoor and outdoor

U3 U4For wiring of central control system

U5 U6For internal wiring betweenoutdoor units

TCS-NETRelay I /F

(BMS-IFLSV1E)

No.1

Main BUS

Main BUS

Ethernet

Touch Screen Controller(BMS-TP0640/5120)

Switching HUB

PC for EnergyMonitoring

InteIligent Server(BMS-LSV2E)

InteIligent ServerSoftware

(BMS-STCC01E)

RS-485

Line address=1

Line address=2

TCS-NETRelay I /F

(BMS-IFLSV1E)

No.3

Main BUS

Main BUS

Line address=4

Line address=5

Main BUS

Line address=6

TCS-NETRelay I /F

(BMS-IFLSV1E)

No.2

Main BUS

Line address=3

CompactFlash

Range for eachsetting procedure

<System diagram (example)>

69

TCS-NETrelay

interface Header Header Header

U3 U4

ON1 2

OFFSW30

U1 U2 U5 U6

ON1 2

OFFSW30

ON1 2

OFFSW30

ON1 2

OFFSW30

ON1 2

OFFSW30

U3 U4

U1 U2 U5 U6

U3 U4

U1 U2 U5 U6

U3 U4

U1 U2 U5 U6

U3 U4

U1 U2 U5 U6

Refrigerant system 1

Refrigerant system 2

Refrigerant system

3

Check that relay connector are connected in all headeroutdoor units to which TCS-NET relay interface is connected.

TCS-NETrelay

interface Header Header Header

U3 U4

ON1 2

OFFSW30

U1 U2 U5 U6

ON1 2

OFFSW30

ON1 2

OFFSW30

ON1 2

OFFSW30

ON1 2

OFFSW30

U3 U4

U1 U2 U5 U6

U3 U4

U1 U2 U5 U6

U3 U4

U1 U2 U5 U6

U3 U4

U1 U2 U5 U6

SW30-2 should be OFF in all header outdoor unitsexcept the header unit with the smallest line address.

Refrigerant system 1

Refrigerant system 2

Rrefrigerant system

3

70

After this setting, if central control devices (central remote controller or ON/OFF controller) areconnected, set up the central control address.(For the central control address setup, refer to “4-3-1 (8) Central control address setting” the installationmanual of the central control devices.)

POINT

Never connect a relay connector until address setup for all the refrigerant system finishes;otherwise address cannot be correctly set up.

Before address setupDuring setup of address

After address setup

SW13, 14(Line address)

SW30-2Terminal-end resistance of indoor/outdoor communi cation line/central control communication line

Relay connector

Indoor sideLine addressIndoor unit addressGroup address

110

120

211

222

310

Connect shortafter

address setup

Connect shortafter

address setup

Connect shortafter

address setup

Setup at shipmentfrom factory

U3 U4

U1 U2 U5 U6

U1 U2

A B

Header unit

TCS-NETrelay interface

Individual Group

Remotecontroller

U3 U4

U1 U2 U5 U6

U1 U2

A B

Follower unit

Remotecontroller

Relayconnector

U3 U4

U1 U2 U5 U6

U1 U2

A B

Remotecontroller

U3 U4

U1 U2 U5 U6

U1 U2

A B

Follower unitU3 U4

U1 U2 U5 U6

U1 U2

A B

Header unit

Remotecontroller

Relayconnector

U3 U4

U1 U2 U5 U6

U1 U2

A B

Header unit

Header unit

Header unit Header unit

Individual Group

Remotecontroller

U3 U421

SW30ON

OFF

U1 U2 U5 U6

U1 U2

A B

Follower unit

Remotecontroller

Relayconnector

U3 U4

U1 U2 U5 U6

U1 U2

A B

Remotecontroller

U3 U4

U1 U2 U5 U6

U1 U2

A B

Follower unitU3 U4

U1 U2 U5 U6

U1 U2

A B

Remotecontroller

Relayconnector

Relayconnector

Open

ON

1 2

1 2 3

3 1

Header unit Follower unit Follower unitHeader unit Header unit

ON

Open Open

(Setup isunnecessary.)

(Setup isunnecessary.)

OFF afteraddress setup

OFF afteraddress setup

(Setup isunnecessary.)

(Setup isunnecessary.)

Outdoor interfaceP.C. board

21

SW30ON

OFF

21

SW30 SW30ON

OFF

21

SW30ON

OFF

21ON

OFF

TCS-NETrelay interface

71

U3U4

U1

A

U2

B

U1

A

U2

B

U1

A

U2

B

U1

A

U2

B

U1

A

U2

B

Remote controller Remote controller Remote controller

Headerunit

Central ControlDevice

Follower unitFollower unit

Headerunit

U1U3

U2U4

U1U2 U5U6

U3U4 U3U4 U3U4

U1U2 U5U6 U1U2 U1U2 U5U6

U3U4

U1U2 U5U6

4-3-1 (8) Central control address setting

(Note)1) Perform after the setting of indoor and outdoor unit address (Indoor/group/line address).2) Three setting address method can be selected.

1 Manual setting from wired main remote controller (RBC-AMT21E)2 Manual setting from central control remote controller (TCB-SC642TLE)3 Automatic setting from central remote controller (TCB-SC642TLE)

• Be sure to reconfirm the following status for all header outdoor units before the centralcontrol address setting.[1] Check that the relay connectors between [U1,U2] and [U3,U4] terminals are connected in

all header outdoor units to which the central control is connected.(At the shipment from factory : No connection of connector)

[2] SW30-2 should be OFF in all header unit except the header unit with the least line addressnumber. (At the shipment from factory : Set to ON)

• Correct address setting can’t be conducted without the setting status above mentioned.• The procedure above mentioned should be conducted after address setting of all indoor and

outdoor units.

REQUIREMENT

U1U2 U3U4

For inter-unitcable betweenindoor andoutdoor

For cabling ofcentral controlsystem

U5U6

For inter-unitcable betweenoutdoor units

Relay connector

Terminatorresistor(SW30)Left :SW30-1Right :SW30-2

CPU

Interface P.C. board on the outdoor unit.

72

Flow chart of setting central control address (digest)(In case of central remote controller TCB-SC642TLE)

Automatic setting?

Completion of indoor unit addresses

Set from wired remote controller?

Manual setting

Yes

YesMethod

Yes

No(No duplication)

Yes (Duplication is discovered.)

VRF* system?

Duplication?

*Super MMSSuper HRM

Automatic setting

Setting from central remote controller

Digital Inverter Super Digital Inverter

1 by 1 model

No

No

No

Central remote controller(TCB-SC642TLE)

End

Checking from central remote controller for duplication of central control address(1) Press the and buttons at the

same time for more than 4 sec.(2) Select CODE No. C3 using setup

temp. buttons.(3) Press the button.(4) indication flashes and central

control address duplicated error check starts.

(5) The check is completed when CODE No. C3 flashes and goes off.

(6) If any duplication is discovered, the GROUP No. will flash.

The central control address is cleared by selecting the data where GROUP No. is flashing and by pressing the button.

Set the correct central control address.

Checking duplication of central control address.(1) Press button three times. If any duplication is discovered, error code "L20" is displayed. Wired remote controller : Displayed promptly. Central remote controller : Max. 4 min. later.

Method

Method

Manual setting from wired remote controller (RBC-AMT21E)(1) Press the and buttons at the

same time for more than 4 sec. (Don't press button.)(2) Set CODE No. to 03 using setup

temp. buttons.(3) Set the central control address

using timer buttons.(4) Press the button to register

the address. ( indications changes from

flashing to ON state.)(5) Press the button.(6) indications changes from

ON state to flashing. (approx. 1 minute.)(7) End

Manual setting from central remote controller (TCB-SC642TLE)(1) Press the and buttons at

the same time for more than 4 sec.(2) Set CODE No. to C1 using

setup temp. buttons.(3) Press the button.(4) Select the zone and group No.

with and (Group) buttons.

(5) Set the Unit No. (Indoor and line address) with and buttons.

(6) Press the button.(7) Register the other Unit No. in

the same way following the steps (4) to (6).

(8) Press the button.(9) flashes for a few minutes,

then OFF.(10)End

Automatic setting from central remote controller (TCB-SC642TLE)(1) Press the and buttons at

the same time for more than 4 sec.(2) Select CODE No. C2 by

pressing setup temp. buttons.

(3) Press the button. ("C2" changes from flashing to

ON state and automatic setting will start.)

(4) Finishing automatic setting, changes from flashing to OFF.

(5) Press the button.(6) flashes for a few minutes,

then OFF.

Setting from wired remote controller

SET

SET

SET

UNIT

SET

SET

CL

(For detailed setting procedure, refer to installation manual attachedcentral control devices.)

73

4-3-1 (9) Trial operation for central controller (TCB-SC642TLE)

1 Test run of the central controller(1) Power on for all indoor units. Next, power on for central controller.

will flash, checking the indoor unit address automatically.

(2) If group No. displayed on central controllers is not same as indoor unit No.** In case of group control, main unit No. only.

2 How to perform an air conditioner test run(1) Hold down the button of the central controller for at least four seconds.

• During the test run, “TEST” appears on the LCD display.(2) Press the and buttons.

• The temperature cannot be adjusted at the “TEST” position.

Do not use this procedure except when performing a test run since it will strain the equipment.(3) Upon completion of the operation, press the button, and check that “TEST” on the LCD

display has gone off.

74

CAUTIONIn case to decide address (Line / Group / Indoor address) by automatic address setup, be sure tochange these address to match the address setting table for TCS-NET control system.

→→→→→ “4-3-1 (2) Manual setting from wired remote controllr”,→→→→→ “4-3-1 (13) Address change from remote controller”

If unmatched address is allocated, a problem such as error of communication with air conditionerwill occur.

4-3-1 (10) Automatic address setting (for reference)

Setting flow

Line addrss setting

Contents Reference No.

Power - ON

Automatic address setting

Line address settting

Check at Power-ON

Refer to this section “4-3-1 (10)

Trial operation

Manual setting from remote controller

Address change from remotecontroller

4-3-1

Trial operation

Manual address settingorAddress change from remote controller

Setup of relay connector and SW30-2

Central control device setting

Central controller exist ?

Trial operation (Central control device)

TCS-NET control system address settingIntelligent serverTCS-NET relay I/FEnergy monitoring I/FDigital I/O relay I/F

Setup of relay connector andterminator

Central control address setting

Test run for central controller

Address setting for TCS-NET controlsystem

4-3-1

4-3-1 (6)

4-3-1 (2)

4-3-1 (13)

4-3-1 (7)

4-3-1 (8)

4-3-1 (9)

4-4

Address setup flow (In case automatic address setup)

Chapter. 5Trial operation for Touch panel controller

75

Address setup procedure 1

1. Turn on power of indoor/outdoor units.(In order of indoor →→→→→ Outdoor)

2. After approx. 1 minute, check that U. 1. L08 (U. 1.flash) is displayed in 7-segment display section onthe interface P.C. board of the header outdoor unit.

3. Push SW15 and start setup the automatic address.(Max. 10 minutes for 1 refrigerant system (Usually,approx. 5 minutes))

4. When the count Auto 1 → Auto 2 → Auto 3 isdisplayed in 7-segment display section, and itchanges from U. 1. - - - (U. 1. flash) to U. 1. - - - (U. 1. light) ,the setup finished.

5. When perform a central control, connect a relayconnector between [U1, U2] and [U3, U4] termi-nals in the header unit.

SW04

SW011 1 1

SW05 SW15

D600 D601 D602 D603 D604

SW02 SW03

3

5

2, 4

Header unit interface P.C. board

U1 U2For internal wiring between indoor and outdoor

U3 U4For wiring of central control system

U5 U6For internal wiring betweenoutdoor units

Outdoor

Indoor Indoor

Remotecontroller

Remotecontroller

Central control remote controller

Outdoor

Indoor Indoor

Remotecontroller

Central control remote controller

Outdoor

Indoor Indoor

Remotecontroller

Remotecontroller

Outdoor

Indoor Indoor

Remotecontroller

Central control remote controller

(Example)

Address setupprocedure

Cable systematicdiagram

(Example)

Wiringsystematicdiagram

Outdoor

Indoor Indoor

Remotecontroller

Outdoor

Indoor Indoor

• When a group control is performed over themultiple refrigerant systems, be sure to turn onthe power supplies of all the indoor unitsconnected in a group in the time of addresssetup.

• If turning on the power for each refrigerantsystem to set up address, a header indoor unitis set for each line. Therefore, an alarm code“L03” (Duplicated indoor header units) is outputin operation after address setup. In this case,change the group address from the wiredremote controller so that only one headerindoor unit is set up.

Group control over multiplerefrigerant systems

• Automatic address setup procedureWithout central control : To the address setup procedure 1With central control : To the address setup procedure 2(However, go to the procedure 1 when the central control is performed in a single refrigerant system.)

REQUIREMENT

In case of central control in a singlerefrigerant system

To procedure 1

In case of central control overrefrigerant system

To procedure 2

76

Line (system) address switch on outdoor interface P.C. board ( : Switch ON, × : Switch OFF)

2. Check that the relay connectors between [U1U2] and[U3U4] terminals are disconnected in all the headeroutdoor units to which the central control is connected.(At shipment from factory: No connection of connector)

3. Turn on power of indoor/outdoor.(In order of indoor →→→→→ outdoor)

4. After approx. 1 minute, check that 7-segment display is U.1.L08 (U.1. flash) on the interface P.C. board of theheader outdoor unit.

5. Push SW15 and start setup the automatic address.(Max. 10 minutes for 1 refrigerant system(Usually, approx. 5 minutes))

6. When the count Auto 1 →→→→→ Auto 2 →→→→→ Auto 3 isdisplayed in 7-segment display section, and it changesfrom U. 1. - - - (U. 1. flash) to U. 1. - - - (U. 1. light) , thesetup finished.

7. Procedure 4. to 6. are repeated in other refrigerantsystems.

8. How to set up terminator resistor (SW30)

When all the address setups have finished in the samerefrigerant system, put the terminator resistor (SW30)in the same central control line into one.• Remain only SW30-2 of the header outdoor unit with

the least line address number as it is ON.(With terminator resistor)

• Set up SW30-2 of the other header outdoor units toOFF. (Without terminator resistor)

9. Connect the relay connector between [U1U2] and[U3U4] of the header outdoor unit for each refrigerantsystem.

: Is not used for setup of line address. (Do not change setup.)

Lineaddress

123456789

1011121314

SW13 SW141 2 3 4 1 2 3 4

× × × × ×× × × ×× × × ×× × ×× × × ×× × ×× × ×× ×× × × ×× × ×× × ×× ×× × ×× ×

Lineaddress

1516171819202122232425262728

SW13 SW141 2 3 4 1 2 3 4

× ××

× × × ×× × ×

× × ×× ×

× × ×× ×

× ××

× × ×× ×

× ××

U1 U2For internal wiring between indoor and outdoor

U3 U4For wiring of central control system

U5 U6For internal wiring betweenoutdoor units

2

Header outdoor unit interface P.C. board

SW11

1ON

2 3 4

SW12

1ON

2 3 4

SW06

1ON

2 3 4

SW07

1ON ONON ON

2 3 4

SW09SW08

11 2 3 4

SW10

1 2 3 4

SW13

1ON

2 3 4

SW14

1ON

2 3 4

SW30SW30

1ON

2

SW11

1ON

Header unit interface P.C. board

2 3 4

SW12

1ON

2 3 4

SW06

1ON

2 3 4

SW07

1ON ONON ON

2 3 4

SW09SW08

11 2 3 4

SW10

1 2 3 4

SW13

1ON

2 3 4

SW14

1ON

2 3 4

Address setup procedure 2

1. Using SW13 and 14 on the interface P.C. board of the headeroutdoor unit in each system, set up the line (system) addressfor each system.(At shipment from factory: Set to Address 1)

Note) Be careful not to duplicate with other refrigerant system.

77

4-3-1 (11) Clearance of address

Method 1An address is individually cleared from a wired remote controller.“0099” is set up to line address, indoor address, and group address data from the remote controller.(For the setup procedure, refer to the abovementioned address setup from the remote controller.)

Method 2Clear the indoor addresses in the same refrigerant line from the outdoor unit.1. Turn off the power of the refrigerant system to be returned to the status at shipment, and change the

header outdoor unit to the following status.

1) Remove the relay connector between [U1U2] and [U3U4].(If it has been already removed, leave it as it is.)

2) Turn on SW30-2 on the interface P.C. board of the header outdoor unit if it is ON.(If it has been already ON, leave it as it is.)

3. After “A.d. c.L.” has been displayed on 7-degment display, return SW01/SW02/SW03 to 1/1/1.4. When the address clearing has correctly finished, “U.1.L08” is displayed on 7-degment display after a

while. If “A.d. n.G.” is displayed on 7-degment display, there is a possibility which is connected with theother refrigerant system. Check again the relay connector between [U1U2] and [U3U4] terminals.Note) Be careful that the other line address may be also cleared if clearing operation is not correctly

executed.5. After clearing of the address, set up an address again.

2. Turn on the indoor/outdoor power of which address is to be cleared. After approx. 1 minute, check that“U.1. - - -” is displayed, and then execute the following operation on the interface P.C. board of theheader outdoor unit of which address is to be cleared in the refrigerant system.

U3 U4

U1 U2 U5 U6

U1 U2

A B

Header unit

Disconnect

Remote controller

U3 U4

U1 U2 U5 U6

U1 U2

A B

Follower unit

Remote controller

U3 U4

U1 U2 U5 U6

U1 U2

A B

Remote controller

U3 U4

U1 U2 U5 U6

U1 U2

A B

Follower unitU3 U4

U1 U2

U1U3

U2U4

U5 U6

U1 U2

A B

Remote controller

Center unitCenter unit Center unitCenter unitHeader unit Header unit

Central control device

Unit of which address is to be returned to the initial status

Address which can be cleared

Line + Indoor + Group address

Central control address

SW01 SW02 SW03

2 1 2

2 2 2

SW04

After checking that “A.d.buS” is displayed on7-degment display, and then push SW04 for 5seconds or more.

After checking that “A.d.nEt” is displayed on7-degment display, and then push SW04 for 5seconds or more.

78

Operation procedure

1 → 2

Operation procedure

1 → 2 → 3 End

Operate

End

UNIT

SET CL

UNIT No.

CODE No.

UNIT

SET CL

UNIT No.

CODE No.SET DATA

R.C. No.

2

3

1

1

2

4-3-1 (12) Confirmation of indoor unit address and position by using the remotecontroller

[Confirmation of indoor unit address and the position]1. When you want to know the indoor address though position of the indoor unit itself can be

recognized;<Procedure> (Operation while the air conditioner operates)

1 If it stops, push button.

2 Push UNIT button.The unit NO is displayed on the LCD.(Disappears after several seconds) Thedisplayed unit No indicates the line addressand indoor address. (If there is other indoorunit connected to the same remote controller(Group control unit), other unit No is dis-played every pushing UNIT button.)

2. When you want to know position of the indoor unit using the address• To confirm the unit numbers in a group control;<Procedure> (Operation while the air conditioner stops)

The indoor unit numbers in a group control are successively displayed, and the corresponding indoor fan isturned on. (Operation while the air conditioner stops)

1 Push + buttons simultaneouslyfor 4 seconds or more.

• Unit No is displayed.• The fans of all the indoor units in a group

control are turned on.

2 Every pushing UNIT button, the indoorunit numbers in the group control aresuccessively displayed.• The firstly displayed unit No indicates the

address of the header unit.• Only fan of the selected indoor unit is

turned on.

3 Push button to finish the procedure.All the indoor units in group control stop.

79

Operation procedure

1 → 2 → 3 → 4 → 5 → 6 End

16

5

4

3

2UNIT

SET CL

UNIT No.

CODE No.SET DATA

R.C. No.

• To confirm all the unit numbers from an arbitrary wired remote controller;<Procedure> (Operation while the air conditioner stops)

The indoor unit No and position in the same refrigerant piping can be confirmed. An outdoor unit is selected, theindoor unit numbers in the same refrigerant piping are successively displayed, and then its indoor unit fan isturned on.

1 Push the timer time + buttons simultaneously for 4 seconds or more.Firstly, the line 1, item code (Address Change) is displayed. (Select outdoor unit.)

3 Using the setup temp. / buttons,set to the item code.

4 Using the timer time / buttons, changethe displayed setup data to a data which youwant to change.

5 Push SET button.

6 Using the UNIT button, select the unit No. tobe changed at the next time. Repeat the proce-dure 4 to 6 and change the indoor address sothat it is not duplicated.

7 After the above change, push UNIT button toconfirm the changed contents.

8 If it is acceptable, push button to finishconfirmation.

2 Using UNIT + buttons, select the line address.

3 Using SET button, determine the selected line address.• The indoor unit address, which is connected to the refrig-

erant pipe of the selected outdoor unit is displayed and thefan is turned on.

4 Every pushing UNIT button, the indoor unit numbersin the identical pipe are successively displayed.• Only fan of the selected indoor unit operates.

[To select another line address]

5 Push CL button to return to procedure 2.• The indoor address of another line can be successively

confirmed.

6 Push button to finish the procedure.

4-3-1 (13) Address change from remote controller

Change of indoor address from wired remote controller

• To change the indoor address in individual operation (Wired remote controller : Indoor unit = 1 : 1) orgroup control (When the setup operation with automatic address has finished, this change is available.)

<Procedure> (Operation while air conditioner stops)

1 Push simultaneously SET + CL + buttons for 4 seconds or more.(The firstly displayed unit No indicates the header unit in group control.)

2 In group control, select an indoor unit No to be changed by UNIT button.(The fan of the selected indoor unit is turned on.)

Operation procedure

1 → 2 → 3 → 4 → 5 → 6 → 7 → 8 End

48

UNIT

SET CL

UNIT No.

CODE No.SET DATA

R.C. No.

15

2,6,73

80

Operation procedure

1 → 2 → 3 → 4 → 5 → 6 → 7 → 8 End

84 6

5, 7

UNIT

SET CL

UNIT No.

CODE No.SET DATA

R.C. No.

1

3

2UNIT

SET CL

UNIT No.

CODE No.SET DATA

R.C. No.

To finish the setup

Cancel of line selection

Here, if the unit No is not called up, the outdoor unitin this line does not exist.

Push CL button, and then select a line according toprocedure 2 .

• To change all the indoor addresses from an arbitrary wired remote controller;(When the setup operation with automatic address has finished, this change is available.)

Contents : Using an arbitrary wired remote controller, the indoor unit address can be changed for each samerefrigerant system

∗∗∗∗∗ Change the address in the address check/change mode.<Procedure> (Operation while air conditioner stops)

1 Push the timer time + buttons simultaneously for 4 seconds or more.Firstly, the line 1, item code (Address Change) is displayed.

2 Using UNIT + buttons, select the line address.

3 Push SET button.• The indoor unit address, which is connected to the refrigerant system of the selected outdoor unit is

displayed and the fan is turned on.First the current indoor address is displayed on the setup data. (Line address is not displayed.)

4 The indoor address of the setup data moves up/down by the timer time / buttons.Change the setup data to a new address.

5 Push SET button to determine the setup data.

6 Every pushing UNIT button, the indoor unit numbers in the identical pipe are successivelydisplayed. Only fan of the selected indoor unit operates.Repeat the procedure 4 to 6 and change all the indoor addresses so that they are not duplicated.

7 Push SET button.(All the displays on LCD go on.)

8 Push button to finish the procedure.

81

4-3-1 (14) In case of increase the address-undefined indoor units (Extension, etc.)

If set up the indoor address of which address is undefined accompanied with extension of indoor units,replacement of P.C. board, etc, follow to the methods below.

Method 1Set up an address individually from a wired remote controller.(Line address, Indoor address, Group address, Central control address)For the setup method, refer to the above “Manual address setup from remote controller”.

Method 2Set up an address from the outdoor unit.∗ Leave the address of the unit of which address has been already set up as it is.

Set up an address only to the unit of which address is undefined.

The addresses are allocated from the low number.

Setup procedureArrange the outdoor header units in the refrigerant line to which indoor units are added. (Figure below)1. Remove the relay connector between [U1U2] and [U3U4].2. Turn on SW30-2 on the interface P.C. board at outdoor header unit side if it is ON.

∗ Turn off the power, and then execute the operation.

“AUTO1” → “AUTO2” → “AUTO3” … is counted and displayed on 7-degment display.5. When “U.1. - - -” is displayed on 7-segment display, the setup operation finished.

Turn off the indoor/outdoor power.6. Return the following setup as before.

• Relay connector• SW30-2• SW01, 02, 03

U3 U4

U1 U2 U5 U6

U1 U2

A B

Header unit

Remote controller

U3 U4

U1 U2 U5 U6

U1 U2

A B

Follower unit

Remote controller

U3 U4

U1 U2 U5 U6

U1 U2

A B

Remote controller

U3 U4

U1 U2 U5 U6

U1 U2

A B

Follower unitU3 U4

U1 U2

U1U3

U2U4

U5 U6

U1 U2

A B

Remote controller

Center unitCenter unit Center unitCenter unitHeader unit Header unit

Central control device

Added indoor unit

Disconnect

3. Turn on the indoor/outdoor power of which address is to be set up. After approx. 1 minute, check that“U.1.---” is displayed on 7-segment display.

4. Execute the following operation on the interface P.C. board of the header outdoor unit.

SW04

After checking that “In.At” is displayed on 7-segmentdisplay, and then push SW04 for 5 seconds or more.

SW01 SW02 SW03

2 14 2

82

4-3-1 (15) Address setup example (VRF system)

[Automatic address / Manual address setup example]

Individual control

Automatic address setting Available Available

Outdoor Line address 1 1

Line address 1 1 1 1

Indoor Indoor unit address 1 2 1 2

Group address 0 0 0 0

Configuration

Outdoor

Indoor Indoor

RC

Master

RC

Master

Outdoor

Indoor

RC1

Master Side Master

* RC: Remote controller

Side

RC2

Indoor

RC3

RC4

Automatic address setting

Outdoor

Configuration

Line address 1 1 1

Line address 1 1 1 1 1 1

Indoor Indoor unit address 1 2 1 2 1 2

Group address 0 0 0 0 0 0

Outdoor

Indoor

RC

Master

Outdoor

Indoor Indoor

MasterReceiver unit

Wireless RC.

Receiver unit

Wireless RC.

Master

Outdoor

Indoor Indoor

Master

1 2 3 4

MasterSide

Indoor

RC

Master

Side

Available Available Available

83

Automatic address setting

Group control

Configuration

Outdoor Line address 1 1 1

Line address 1 1 1 1 1 1

Indoor Indoor unit address 1 2 1 2 1 2

Group address 1 2 1 2 1 2

Receiver unit(Side)

Wireless RC.

Receiver unit

Wireless RC.

Outdoor

Indoor

RC

Master

Indoor

Outdoor

Indoor Indoor

Outdoor

Indoor

RC

Master

Indoor

Available Available Available

Central control (Multiple refrigerant systems)

Automatic address setting

Configuration

Outdoor Line address 1 2 1 2

Line address 1 1 2 2 1 1 2 2

Indoor Indoor unit address 1 2 1 2 1 2 1 2

Group address 0 0 0 0 1 2 1 2

Outdoor

Indoor Indoor

RC

Master

RC

Master

Centralremote

controller

Individualcontrol

Outdoor

Indoor Indoor

RC

Master

RC

Master

Individualcontrol

Outdoor

Indoor Indoor

RC

Master

Centralremote

controller

Groupcontrol

Outdoor

Indoor Indoor

RC

Master

Groupcontrol

Available Available

84

Group control over other R.C. group/indoor names)

Outdoor

Indoor Indoor

RC

Master

Outdoor

Indoor Indoor Indoor Indoor

Outdoor

Indoor

Outdoor

Indoor Indoor

RC Master

Wireless RC.

Outdoor

Indoor Indoor Indoor Indoor

Outdoor

Indoor

*1In case of group control over refrigerant systems, automatic address setting is available only when all indoor units connected to a group control are turned on during address setting.

If an automatic address setting is conducted under condition of power-ON only in the refrigerant system in which address set up, it will cause the error code “L03” (Duplicated indoor header units) because indoor header units exit for each refrigerant system. In this case, change the group address by the wired remote controller so that only one indoor unit becomes the header unit in one group control.

It is necessary to change the group address as marked with * when an automatic address setting is conducted under condition of power-ON only in the refrigerant system in which address set up.

*1In case of group control over refrigerant systems, automatic address setting is available only when all indoor units connected to a group control are turned on during address setting.

If an automatic address setting is conducted under condition of power-ON only in the refrigerant system in which address set up, it will cause the error code “L03” (Duplicated indoor header units) because indoor header units exit for each refrigerant system. In this case, change the group address by the wired remote controller so that only one indoor unit becomes the header unit in one group control.

It is necessary to change the group address as marked with * when an automatic address setting is conducted under condition of power-ON only in the refrigerant system in which address set up.

Automatic address setting Available (*1)

Available (*1)

Outdoor

Configuration

Line address 1 2 1

Line address 1 1 2 2 2 3 3

Indoor Indoor unit address 1 2 1 2 3 1 2

Group address 1 2 2 2 2 2 2

Group address 1 2 2 21 2* 1 2* 2

Automatic address setting

Configuration

Outdoor Line address 1 2 1

Line address 1 1 2 2 2 3 3

Indoor Indoor unit address 1 2 1 2 3 1 2

Group address 1 2 2 2 2 2 2

Group address 1 2 1 2* 2 2 1 2* 2

85

4-3-2 Setting for 1 by 1 system4-3-2 (1) Address re-setup

POINT 1

When controlling the super-digital inverter and the digital inverter, the adaptor named “1:1 model”connection interface (TCB-PCNT30TLE) is necessary.

1. Cabling connection of control wiringAttach an adaptor per 1 group in group control operation (including individual control).Connect the adaptor to the header indoor unit in the group control. (For details, see POINT 3.)

2. Cabling connection diagram with indoor control P.C. board• For details, refer to Installation Manual.

• Parts included in the single-point chain line are optional accessories.• There is non-polarity on the cables connected to U3 and U4 terminals.

Centralcontrol devices

U3

TCB-PCNT 30TLE

(Adapter)

TCB-PCNT 30TLE

(Adapter).C. board

Remotecontroller

U4

Indoor unit

A B

Indoorcontrol

Indoorcontrol

PP .C. board

Indoor unit

A B

U3

Indoorcontrol

P.C. board

Remotecontroller

U4

Indoor unit

A B

Indoorcontrol

P.C. board

Indoor unit

A B

Indoorcontrol

P.C. board

Indoor unit

central control wiring

A B

U3 U4

1 2

1 1 1 1

BLU BLU

connecting terminal block for central control wiring

CN40 (BLU)

CN51 (RED)

“1:1 model”connection interface

CN50 (WHI)

Indoor controlP.C. board

WHI

2 2 2 2RED

3 3 3 3RED

4 4 4 4RED

5 5 5 5RED

1 2

86

POINT 2

After automatic address setup, it is necessary to change the line address from the wired remote controllerfor each system. (Manual re-setup)

Reason : After automatic address setup, all the line addresses become “1” except a group control andthen a duplicated address error “E08” is output.

• Set up a line address for each refrigerant system.• Set up a line address so that it is not duplicated with other systems.

(If the central control is conducted with VRF systems, set up a line address so that it is not alsoduplicated with line address of VRF systems.)

• When performing a central control over 30 systems, the address setup method is necessary to bechanged.(including VRF system)

*adapter *adapter *adapter

Centralcontrol devices

Central control wiring

System A System B System C

Outdoor

Indoor(Header)

Remotecontroller

* TCB-PCNT30TLE

Outdoor

Indoor(Follower)

Outdoor

Indoor(Header)

Remotecontroller

Outdoor

Indoor(Follower)

Outdoor

Indoor(Follower)

Outdoor

Indoor

Remotecontroller

After automatic address

After change of manual address

Line addressIndoor unit addressGroup address

111

212

* A wired remote controller is required for address change.

No change

Line addressIndoor unit addressGroup address

111

212

111

212

312

Need to change line address

311

412

512

110

Need to change line address

610

87

POINT 3

When the central control is performed for indoor units of twin control in a group control, it may be requiredto change the group address. (Adapter is attached to the header indoor unit.)

Reason : The central control device communicates with individual indoor unit, header indoor unit of thegroup control, and header indoor unit of twin control. However, as the address is automaticallyset up, which unit will become the header unit is indefinite. Therefore if the unit attached withadapter would not become the header indoor unit, a central control is unavailable.

How to check group address (Header/Follower indoor unit setup)* Check the group address after confirming which unit is attached with the adapter.

<Procedure> Operation while air conditioner stops.1 Push SET + CL + buttons simultaneously for 4 seconds or more.

2 The indoor unit in which the fan is turned on is the header indoor unit.

Indoor unit in which the fan is turned on = Indoor unit with the adapter : To Case 1Indoor unit in which the fan is turned on = Indoor unit with the adapter : To Case 2

*Adapter

Centralcontrol devices

Central control wiring

System A System B System C

Outdoor

*TCB-PCNT30TLE

Indoor(Header)

Remotecontroller

Outdoor

Indoor(Follower) *Adapter

Outdoor

Indoor(Follower Header)

Remotecontroller

Outdoor

Indoor(Follower)

Outdoor

Indoor(Header Follower)

*Adapter

Outdoor

Indoor

Remotecontroller

Line addressIndoor unit address

Group address

111

212

312

4121 2

511

610

Central control is possible. Central control is possible.Central control is impossible.

* A wired remote controller (RBC-AMT21E) is required for address change.

88

Case 1(In case that the indoor unit in which the fan is turned on and the unit with the adapter are same)

3 As the central control is available, push button. (Setup is determined.)When pushing the button, the display disappears and the status returns to the normal stop status.(The operation on the remote controller is not accepted for approx. 1 minute after the button has been pushed.)If the operation on the remote controller is not accepted for 1 minute or more after button has been pushed, anincorrect address setup is considered.In this case, automatic address is performed again. After approx. 5 minutes or more, and set up again the groupaddress from <procedure 1>.

Case 2(In case that the indoor unit in which the fan is turned on and the unit from <procedure 1> with theadapter are different)As the central control is unavailable, change the address in the following procedure.

<Indoor unit without the adapter : Header indoor unit →→→→→ Follower indoor unit.>3 Using the setup temp + buttons, select Item code 14.

4 Check the setup data is and change the setup data from to using the timer +

buttons.

5 Push the SET button. In this time, the setup has finished if the display changes from flashing to

lighting.

<Indoor unit with the adapter : Follower indoor unit →→→→→ Header indoor unit.>6 Push the UNIT button to turn on the fan of the indoor unit attached with the adaptor.

7 Using the setup temp + buttons, select Item code 14.

8 Check the setup data is and change the setup data from to using the timer +

buttons.

9 Push the SET button.

<Reconfirmation of re-set up>In this time, the setup has finished if the display changes from flashing to lighting.10 When the above setup operation has finished, push the UNIT button to select the indoor unit

of which setup has been changed. Using the setup temp + buttons, specify theItem code 14 and check the changed contents.Pushing the CL button enables to clear the setup contents until now.(In this case, repeat the procedure from 1.)

11 Push button. (Setup is determined.)When pushing the button, the display disappears and the status returns to the normal stop status.(The operation on the remote controller is not accepted for approx. 1 minute after the button has beenpushed.)

If the operation on the remote controller is not accepted for 1 minute or more after button has been pushed,an incorrect address setup is considered.In this case, automatic address is performed again. After approx. 5 minutes or more set up again the groupaddress from <procedure 1>.

89

1 In case of central control up to 29 refrigerant systems (including No. of VRF systems)

Line address

: adapter (“1:1 model” connection interface

TCB-PCNT30TLE)

1 1 2 1 3 1 3 1 4 2 5 1 6 2 6 2 7 2 7 3 8

Indoor unit address 1 1 1 2 1 1 1 3 2 1 2 1 2

2Group address 0 0 1 2 1 2 1 2 2 2

Automatic address is impossible.Set up again an address manuallyon wired remote controller.

Change the line address on wired remote controller after automatic address setting.

POINT 1) Change the line address for each refrigerant system.

Centralcontrol device

Outdoor

Indoor

1Refrigerant system

RC

Outdoor

Indoor

2

RC

Outdoor

Indoor

3

RC

Indoor

Outdoor

Indoor

4

RC

Outdoor

Indoor

5

Outdoor

Indoor

6

RC

Indoor

Outdoor

Indoor

7

Indoor

Outdoor

Indoor

8

*RC : Remote controller

4-3-2 (2) Indoor address change example

90

2 In case of central control over 30 refrigerant systems (including No. of VRF systems if any)* Change operation is same to the above 1 up to 29th refrigerant system.

Line address 1 30 1 30 1 30 1 30 1 30 2

1

1 30 2 30 2

1

2

2

3

Indoor unit address 1 1 2

Group address 0 0 1 2 1 2 1 2 2 2

Automatic address is impossible.Set up again an address manuallyon wired remote controller.

Change the line address on wired remote controller after automatic address setting.

POINT 1) Set all the line addresses to 30 for all indoor units attached with the adapter.

POINT 2) Change the indoor address so that the indoor unit address numbers are not duplicated.

POINT 3) When the indoor unit with adaptor is in twin or triple control, change also the lineaddress of the follower indoor unit to 30.

Centralcontrol device

Outdoor

Indoor

1Refrigerant system

RC

Outdoor

Indoor

2

RC

Outdoor

Indoor

3

RC

Indoor

Outdoor

Indoor

4

RC

Outdoor

Indoor

5

Outdoor

Indoor

6

RC

Indoor

Outdoor

Indoor

7

Indoor

Outdoor

Indoor

8

: adapter (“1:1 model” connection interface

TCB-PCNT30TLE)

1 5 1 6 3 7 1 2

2

1 3 1 4

*RC : Remote controller

91

Before setting for TCS-NET air conditioning system, be sure to complete address setting and trialoperation of each air conditioning system.(Address setting --- Line/Group/indoor unit address, central control address if central controller existsTrial operation --- Test operation should be performed in each refrigerant system one by one.)

CAUTION

4-4 Address setting for Control System devices4-4-1 address setting flow

Setting flow

Intelligent Server setting

Contents Reference No.

TCS-Net relay I/F setting

Energy monitoring exist ?

CF card mounting, Dip switch setting

Address setting (SW01 on P.C. Board,address 1 to 8)Terminator Resistor setting (SW06 on P.C.Board)

Address setting (SW01 on P.C. Board,address 1 to 4)

Address setting (SW01 on P.C. Board,address 1 to 4)

4-4-2

Energy monitoring relay I/F setting

Digital I/O relay I/F exist ?

Digital I/O Relay I/F setting

Power ON (Trial Operation)

4-4-3

4-4-4

4-4-5

Chapter. 5

92

4-4-2 Setting for Intelligent server

Installing CF (Compact Flash) card

RS-485 operation mode setting

• Do not insert or remove the CF (Compact Flash) card during power on of the Intelligent Server.Doing so may cause a failure.

• If the CF (Compact Flash) card is not inserted properly, the Intelligent Server will not work.

REQUIREMENT

Insert the attached CF (Compact Flash) card fully into the CF (Compact Flash) card slot on the side ofthe Intelligent Server.

CF (Compact Flash) cardCF (Compact Flash) card slot

1

ON

2 3 4

1 2 3 4

OFF ON ON OFF

1 2 3 4

RS-485 mode setswitch

AC inlet side LED indicator side

The RS-485 mode set switch is provided on the bottom board of the Intelligent Server.Set the switch as follows:

If the RS-485 mode set switch is setincorrectly, the Intelligent Server willnot work.

NOTE

1

2

3

4 Not used

(Note 1) Transmit data sent from the Intelligent Server is not received bythe same server during transmission.

(Note 2) Transmit data sent from the Intelligent Server is also receivedby the same server during transmission.

ON

OFF

ON

OFF

ON

OFF

A terminator resistor is connected between TX(+) and TX(-).

No terminator resistor is connected between TX(+) and TX(-).

A terminator resistor is connected between RX(+) and RX(-).

No terminator resistor is connected between RX(+) and RX(-).

Half-duplex mode (Note 1)

Full-duplex mode (Note 2)

Intelligent ServerSoftware(BMS-STCC01E) Intelligent Server

(BMS-LSV2E)

93

4-4-3 Setting for TCS-NET relay interface

1

ON SW5

2

1

ON SW6

SW7

2

1 ON

SW

3S

W4

SW

2S

W1

23

4LED

4

FG

U1

U2

AB

LN

RS

-485

TC

C-L

INK

LED

2

LED

5LE

D3

LED

1

• SW2 Test switch• SW3 Test switch• SW4 Test switch

Not used during operation.Set these switches to zero (0) or “all OFF”.

• SW5 RS-485 terminator resistor select switchSet “120 ohm" only when the relayinterface address SW=1, and set “open”for other relay interfaces.

CAUTION• Set relay interface addresses according to the air conditioner address table.

For the relay interface whose address SW1=1, perform terminator resistor setting.

• When the SW1 setting has been changed, push the reset switch SW7. The new addresssetting is read.

The following settings are necessary to use TCS-NET Relay Interfaces.

• SW1 TCS-NET Relay Interface address set switchWhen two or more TCS-NET Relay Interfaces are used, set a different address for SW1 to avoidaddress duplication.Assign addresses in an ascending order.

• RS-485 terminator resistor select switch SW5.Set “120 ohm” only when the TCS-NET Relay Interface address SW=1, and set “open” for otherrelay interfaces.

• The Main BUS terminator resistor is set on the air conditioner side. Set SW6 to “open”.

REQUIREMENT

• SW6 Main BUS terminator resistor selectswitchThe Main BUS terminator resistor is seton the air conditioner side. Set SW6 to“open”.

• SW7 Reset switchWhen performing an address setting withSW1, push this reset switch after theaddress setting to read the set value.

SW1

SW2

SW3

SW4

SW5

SW6

SW7

LED1

LED2

LED3

LED4

LED5

Relay interface address set switch

1-8

0, 9-F

Test switch (0 usually)

Test switch (all OFF usually)

Test switch

RS-485 terminator resistor select switch

Main BUS Terminator resistor select switch

Reset switch

Power indicator

RS-485 communication status indicator

Main BUS Communication status indicator

Main BUS Communication error indicator

Test indicator

Relay interface address

Not used

Note:Bit 2 is not used.

60 ohm 120 ohm 120 ohm Open

100 ohm Open

1

ON

2 1

ON

2 1

ON

2 1

ON

2

1

ON

2 1

ON

2

94

4-4-4 Setting for Energy monitoring relay interface

ON

SW1 SW2SW3

LED

2

LED

3

LED

4

LED

5

LED

1

SW4 SW71 2 3 4

DI1

DI2

DI3

DI4

DI5

DI6

DI7

DI8

NL

BARS

-485

• SW2 Operation mode set switch• SW3 Test switch• SW4 Test switch

• SW7 Reset switchWhen performing a address setting with SW1, push this reset switch after the address setting toread the set value.

CAUTION

• Set relay interface addresses according to the air conditioner address table.• When the SW1 setting has been changed, push reset switch SW7. The new address

setting is read.• You can set the Energy Monitoring Relay Interface address independently from the TCS-

NET Relay Interface address or the Digital I/O Relay Interface address.

The following settings are necessary to use Energy Monitoring Relay Interfaces.

• SW1 Address set switchWhen two or more Energy Monitoring Relay Interfaces are used, set a different address for eachunit to avoid address duplication.Assign addresses in an ascending order. (from 1, 2, 3 . . . n)

These switches are not used during normaloperation. Set zero (0) or "all OFF".

SW1

SW2

SW3

SW4

SW7

LED1

LED2

LED3

LED4

LED5

Address set switch

1 - 4 Address

0,5 - F Not used

Operating mode set switch (0 usually)

Test switch (all OFF usually)

Test switch

Reset switch

Power indicator

RS-485 communication status indicator

Not used

Test indicator

Test indicator

95

4-4-5 Setting for Digital I/O relay interface

ON

SW1 SW2SW3

LED

2

LED

3

LED

4

LED

5

LED

1

LED17

LED16

LED15

LED14

SW4 SW71 2 3 4

DI1

DI2

DI3

DI4

DI5

DI6

DI7

DI8

NL

B

DO1

DO2

DO3

DO4

GND

+12V

ARS

-485

SW1

SW2

SW3

SW4

SW7

LED1

LED2

LED3

LED4

LED5

LED14 -LED17

Address set switch

1 - 4 Address

0,5 - F Not used

Operating mode set switch (0 usually)

Test switch (all OFF usually)

Test switch

Reset switch

Power indicator

RS-485 communication status indicator

Not used

Test indicator

Test indicator

Digital output indicator

• Set relay interface addresses according to the air conditioner address table.• When the SW1 setting has been changed, push the reset switch SW7. The new address

setting is read.

CAUTION

The following settings are necessary to use Digital I/O Relay Interfaces.

• SW1 Address set switchWhen two or more Digital I/O Relay Interfaces are used, set a different address for each unit toavoid address duplication.Assign addresses in ascending order.

• SW2 Operation mode set switch• SW3 Test switch• SW4 Test switch• SW7 Reset switch

When performing address setting with SW1, push this reset switch after address setting to readthe set value.

These switches are not used during normaloperation. Set zero (0) or “all OFF”.

96

97

5

TRIAL OPERATION

5-1 Trial operation5-2 Air conditioning control system troubleshooting

5-2-1 Faults of air conditioner5-2-2 Faults of air conditioning control system

98

5-1 Trial operation

Preparation

Entering names

Checks before trialoperation (controlwiring)

Trial operationstartup

Item Description

Preparation of necessarydocuments

Entry of setting conditions

Checking installation work

Checking control wiringusing the before-trialoperation check list.Checking block/tenant/areanamesChecking schedules

Power onInitial screenSystem initialization

Check point

● Meeting with the customer on setting informationCreation of control wiring system diagramCreation of air conditioner address tableCreation of schedule table for each R.C. group/indoor

● Create a setting file including setting data.● Set the setting data in the Touch Screen Controller by

overwriting (copy) the data on its CF (Compact Flash) card.

● Power supply wiring● Control wiring● Grounding of units

● Check control wiring specifications and wire sizes.● Check block/tenant/area names using the air conditioner

address table.● Check schedules using the schedule table for each R.C.

group/indoor.

● Turn on the Touch Screen Controller with the IntelligentServer and the relay interface turned on.

● The controller software starts automatically, and the totalbuilding control screen appears.

● Select “System Initialize” from the option to initialize thesystem.

When “System Initialize” is selected, a message “Will youre-cold start all intelligent server?” appears. Select “Yes”.The setting file is transmitted from the Intelligent Server tothe relay interface.The L1 or L2 LED of the Intelligent Server blinks during thestartup process. When the startup processing endssuccessfully, the L1 and L2 LEDs turn off. If the startupprocessing fails, the L1 LED lights up. Retry “SystemInitialize” from the Touch Screen Controller in this case. Orselect “TPC-CON” on the hidden Windows task bar at thebottom of the LCD screen. You can see a message on thescreen during the system reset. The “Access Start”message appears at the end of several message lines. Ittakes several minutes for system initialization.

Trial operation Checking communicationstatus (referring to thecontrol wiring systemdiagram)

Checking operation statususing the before-trialoperation check list.

● Select air conditioning screen after System Initialize to checkcommunication status and connection of air conditioners.

Check that there is no orange frame on the command buttonof the air conditioner, which indicates a communicationerror. If an orange frame is present, check power on (or off),control line wiring, and address setting of the air conditioner.

● Check operation status for each block, tenant, area, andR.C. group/indoor.- ON/OFF- Operation mode- Set temperatures

Check all indoor units whether controls can be changed fromthe Touch Screen Controller and whether the settingchanged by the remote controller is reflected on the TouchScreen Controller on both the Touch Screen Controller sideand the on-site remote controller side.

99

Trial Operation Check list

• Bu

ildin

g n

ame:

• A

......

......

.ON

• B

....O

N/O

FF

• C

......

.....

OF

F

• D

......

......

..C

OO

L•

E...

CO

OL

/HE

AT

• F

......

......

....H

EAT

Set

tem

pera

ture

Tena

ntB

lock

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

R.C

. g

rou

p/i

nd

oo

r

Blo

ck n

ame

Ten

ant

nam

eA

rea

nam

e

R.C.

grou

p/ind

oor

Are

a

Dis

pla

y n

ame

Tena

ntB

lock

R.C.

grou

p/ind

oor

Are

aTe

nant

Blo

ckR.

C. gr

oup/

indoo

r

ON

/OF

FO

pera

tion

mod

e

Are

a

Ch

eck

list

100

Trial Operation Check list (Example)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

R.C

. g

rou

p/i

nd

oo

r

PA

C-B

•1F

-1

PA

C-B

•1F

-1

PA

C-B

•1F

-1

PA

C-B

•1F

-1

PA

C-B

•1F

-1

PA

C-B

•1F

-2

PA

C-B

•1F

-3

PA

C-B

•1F

-4

PA

C-B

•1F

-5

PA

C-M

•1F

-1

PA

C-M

•1F

-2

PA

C-M

•1F

-3

PA

C-M

•1F

-4

PA

C-M

•1F

-5

PA

C-M

•1F

-6

PA

C-M

•1F

-7

PA

C-M

•1F

-8

PA

C-S

•2F

-1

PA

C-S

•2F

-2

PA

C-S

•2F

-3

Blo

ck n

ame

1F

1F

1F

1F

1F

1F

1F

1F

1F

1F

1F

1F

1F

1F

1F

1F

1F

2F

2F

2F

Ten

ant

nam

e

Ten

ant

A

Ten

ant

A

Ten

ant

A

Ten

ant

A

Ten

ant

A

Ten

ant

B

Ten

ant

B

Ten

ant

B

Ten

ant

B

Ten

ant

C

Ten

ant

C

Ten

ant

C

Ten

ant

C

Off

ice

A

Off

ice

A

Off

ice

A

Off

ice

A

Sha

red

spac

e

Ten

ant

D

Are

a na

me

Sho

p A

Sho

p A

Sho

p A

Sho

p A

Sho

p A

Sho

p B

Sho

p C

Sho

p D

Sho

p E

Sho

p F

Sho

p F

Sho

p G

Sho

p G

Off

ice

Off

ice

Mee

ting

room

Mee

ting

room

A B

Sho

p H

R.C.

grou

p/ind

oor

B B B B B B B B B B B B B B B B B B B B

Are

a

B B B B B B B B B B B B B B B B B B B B

Tena

nt

B B B B B B B B B B B B B B B B B B B B

Blo

ck B B B B B B B B B B B B B B B B B B B B

R.C.

grou

p/ind

oor

E E E E E E E E E E E E E E E E E E E E

Are

a

E E E E E E E E E E E E E E E E E E E E

Tena

nt

E E E E E E E E E E E E E E E E E E E E

Blo

ck E E E E E E E E E E E E E E E E E E E E

R.C.

grou

p/ind

oor

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

Are

a

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

Tena

nt

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

Blo

ck

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

• A

......

......

.ON

• B

....O

N/O

FF

• C

......

.....

OF

F

• D

......

......

..C

OO

L•

E...

CO

OL

/HE

AT

• F

......

......

....H

EAT

• Bu

ildin

g n

ame:

Dis

pla

y n

ame

Ch

eck

list

ON

/OF

FO

pera

tion

mod

eS

et t

empe

ratu

re

101

5-2 Air conditioning control system troubleshooting<Regarding faults that may occur after installation, trial operation, and adjustments of Air conditioningcontrol system and their remedies>

5-2-1 Faults of air conditioner• The Touch Screen Controller displays an error code and description that are the same as those

displayed on the remote controller.• Check the faulty air conditioner according to the check points of each error code of the air conditioner.

5-2-2. Faults of air conditioning control system

Faults detected by Touch Screen Controller

• Touch Screen Controller displays an error code and description. (Not displayed on the remotecontroller)

• Take remedial action according to the description and possible causes of each error code in the tablebelow.

S00

S01

S06

S07

Errorcode Description

Intelligent servercommunicationerror.

Communicationerror betweenIndoor and BMS.

BMS-IFWHcommunicationerror.

BMS-IFDDcommunicationerror.

Possible causes

Intelligent Server is not powered on.Switching HUB is not powered on.Improper connection of network cable.Malfunction of Intelligent Server.

Air conditioner is not powered on.Improper TCC-LINK connection.Malfunction of Intelligent Server.Malfunction of Relay Interface.

Energy Monitoring Relay Interface is not poweredon.Improper RS-485 cable connection.Malfunction of Energy Monitoring Relay Interface.Malfunction of Intelligent Server.

Digital I/O Relay Interface is not powered on.Improper RS-485 cable connection.Malfunction of Digital I/O Relay Interface.Malfunction of Intelligent Server.

Remedy

Remove the cause and thenpower on the Intelligent Server,Switching HUB, and TouchScreen Controller.

Remove the cause and thenpower on the air conditioner,Intelligent Server, and RelayInterface.

Remove the cause and thenpower on the Energy MonitoringRelay Interface and IntelligentServer.

Remove the cause and thenpower on the Digital I/O RelayInterface and Intelligent Server.

102

1

2

3

4

5

6

No. DescriptionNothing is displayed onthe Touch ScreenController screen.

Remote controller doesnot work. (Centralcontrol in progress)

Remote controller doesnot work. (Operationswitchover control inprogress)

Scheduled operation ofair conditioners isdisabled.

Air conditioner stops(out of control).

Energy monitoring andbilling result isincorrect.

Possible causesTouch Screen Controller is not powered on.

Backlight turns off automatically due to notouch-screen operation for 10 minutes.

Malfunction of Touch Screen Controller.

Air Conditioning Control Systemmalfunctioned or stopped after localprohibition is set by the system.

Operation mode range selection is set bythe Air Conditioning Control System.

Air Conditioning Control System is notworking.

Scheduled operation is not set or non-operation date/special day setting is notupdated. (The setting must be updatedevery year.)

Scheduled operation is not set correctly.

Incorrect input of door-lock signal.

Improper connection between power meterand BMS-IFWH3E.

Charging schedule is not set correctly.Non-operation date/special day setting isnot updated. (The setting must be updatedevery year.)

RemedyPower on the Touch Screen Controller.

Touch the Touch ScreenController screen.

Power off and on the TouchScreen Controller.

Power off and on the airconditioner.

Check the operation mode rangeselection setting, and correct it ifwrong.

Power on the equipment of thesystem.

Perform setting for scheduledoperation.

Check the scheduled operationsetting, and correct it if wrong.

Correct the signal connection.

Correct the connection.

Check the charging schedulesetting, and correct it if wrong.

Other faults

1No. Indication

An LED other than“RN” LED at the upperleft is lighting orflashing after 10minutes passed frompower on of IntelligentServer.

Possible causesNo Relay Interface is powered on.

Communication with any Relay Interfacefails due to improper RS-485 connection ordisconnection of connector.

Malfunction of Intelligent Server.

RemedyCheck whether every RelayInterface is powered on (shown byLED1 lighting red), and turn onthem if powered off.

Correct the connection.

Power off and on the IntelligentServer.

Fault judgment by Intelligent Server

1

2

No. IndicationLED2 (green) does notlight.(RS-485 communicationerror)

LED3 (orange) doesnot light.

Possible causesIntelligent Server is not powered on.

Improper RS-485 connection ordisconnection of connector.

Improper connection of Main BUS due todisconnection or lack of terminatingresistors, etc.

RemedyPower on the Intelligent Server.

Correct the connection.

Correct the connection.

Faults of TCS-Net Relay Interface

103