TECHNICAL DETAILS Firefly® & Firefly® BB...˜ UL864 listed for releasing devices for fire alarm...

2
Model Specific Features Firefly Standby current draw: 100-240 VAC = .15-.1A, 24 VAC = .6A or 24 VDC = .2A Max current draw: 100-240 VAC = .5-.25A, 24 VAC = 1.5A or 24 VDC = 1.6A Optional R-BBU power available – 10 hours Requires a 4 wire connection for local detectors Firefly BB Standby current draw: 100-240 VAC = .15-.1A, 24 VAC = .5A or 24 VDC = .2A Max current draw: 100-240 VAC = .5-.25A, 24 VAC = 1.0A or 24 VDC = .6A Battery backup power – 7 days May utilize 4 wire or 2 wire connection for local detectors Diagnostic indicator LED lights Requirements For indoor dry location use only All wiring must satisfy the most current version of NFPA 72- National Fire Alarm Code and the National Electric Code Firefly® AR-D is a multi-voltage fail-safe release device that is available with or without battery backup. It is an energized solenoid mechanism designed to be used in conjunction with FireGard™ operators. Standard Features Input voltage is 100-240 VAC, 1 phase, 50/60Hz or 24 VAC/ VDC The release device has a 10 second delay upon power failure and alarm Contact relays receive the alarm signal from the local detectors or fire alarm control panel Normally closed dry contact is required for alarm signal Provisions to power a 24 VDC door closing warning device upon alarm signal Down limit detection to prevent release of a closed door upon alarm signal: requires a closed door signal Maximum rated pull: 50 lbs Alarm test button UL864 listed for releasing devices for fire alarm systems 800.294.4358 | cooksondoor.com CornellCookson, Inc. is an ISO 9001:2015 registered company 3.2019 AR-D RELEASE DEVICE F irefly® & F irefly® BB TECHNICAL DETAILS

Transcript of TECHNICAL DETAILS Firefly® & Firefly® BB...˜ UL864 listed for releasing devices for fire alarm...

Page 1: TECHNICAL DETAILS Firefly® & Firefly® BB...˜ UL864 listed for releasing devices for fire alarm systems 800.294.4358 | cooksondoor.c om CornellCookson, Inc. is an ISO 9001:2015 registered

Model Specific Features Firefly ▶ Standby current draw: 100-240 VAC = .15-.1A, 24 VAC = .6A or 24 VDC = .2A ▶ Max current draw: 100-240 VAC = .5-.25A, 24 VAC = 1.5A or 24 VDC = 1.6A ▶ Optional R-BBU power available – 10 hours

▶ Requires a 4 wire connection for local detectors

Firefly BB ▶ Standby current draw: 100-240 VAC = .15-.1A, 24 VAC = .5A or 24 VDC = .2A

▶ Max current draw: 100-240 VAC = .5-.25A, 24 VAC = 1.0A or 24 VDC = .6A

▶ Battery backup power – 7 days

▶ May utilize 4 wire or 2 wire connection for local detectors

▶ Diagnostic indicator LED lights

Requirements ▶ For indoor dry location use only

▶ All wiring must satisfy the most current version of NFPA 72- National Fire Alarm Code and the National Electric Code

Firefly® AR-D is a multi-voltage fail-safe release device that is available with or without battery backup. It is an energized solenoid mechanism designed to be used in conjunction with FireGard™ operators.

Standard Features▶ Input voltage is 100-240 VAC, 1 phase, 50/60Hz or 24 VAC/ VDC

▶ The release device has a 10 second delay upon power failure and alarm

▶ Contact relays receive the alarm signal from the local detectors or fire alarm control panel

▶ Normally closed dry contact is required for alarm signal

▶ Provisions to power a 24 VDC door closing warning device upon alarm signal

▶ Down limit detection to prevent release of a closed door upon alarm signal: requires a closed door signal

▶ Maximum rated pull: 50 lbs

▶ Alarm test button

▶ UL864 listed for releasing devices for fire alarm systems

800.294.4358 | cooksondoor.comCornellCookson, Inc. is an ISO 9001:2015 registered company3.2019

A R - D R E L E A S E D E V I C EFirefly® & Firefly® BB

T E C H N I C A L D E T A I L S

Page 2: TECHNICAL DETAILS Firefly® & Firefly® BB...˜ UL864 listed for releasing devices for fire alarm systems 800.294.4358 | cooksondoor.c om CornellCookson, Inc. is an ISO 9001:2015 registered

FireflyAR-D

Smokedetector

Sash chain or cable

Release Device Arrangement

10.827”

9.961”

9.581” 7.874”

Front View

11.102”

5.941”

Side View

Outside Dimensions

3.2019

800.294.4358 | cooksondoor.comCornellCookson, Inc. is an ISO 9001:2015 registered company3.2019

Firefly® & Firefly® BB AR-D Release Device