Technical data*: Combi T Thermo Hollow Floor Combi T Thermo …€¦ · The MERO Combi T Thermo is...

6
Innovative solutions from one source Development Consulting Planning Manufacturing Installation Access Floor Hollow Floor Floor covering and Installation Services EnEV-proved PBS Hollow Floor Thermo

Transcript of Technical data*: Combi T Thermo Hollow Floor Combi T Thermo …€¦ · The MERO Combi T Thermo is...

Page 1: Technical data*: Combi T Thermo Hollow Floor Combi T Thermo …€¦ · The MERO Combi T Thermo is a dry hollow floor with a floor heating and cooling system. Fields of application

Innovative solutions from one source

Development

Consulting

Planning

Manufacturing

Installation

AccessFloor

HollowFloor

Floorcoveringand

Installation

Services

EnEV-proved

06.1

3/C

ombi

TT

herm

oSu

bjec

tto

tech

nica

lcha

nges

with

outp

riorn

otic

e

Hollow Floor Combi T ThermoHeating Pipe grid 100 Pipe grid 150

HeatflowdensityqGacc.toDINEN1264-2(withoutcovering,Rλ=0,00m²K/W)

77W/m² 60W/m²

atstandardheatingliquidovertemperature∆θH 12K 12K

HeatflowdensityqGacc.toDINEN1264-2(withcovering,R=0,15m²K/W)

89W/m²

78W/m²

atstandardheatingliquidovertemperature∆θH 26K 29K

Rλ,Bcarpet 0,07–0,23m²K/W 0,07–0,23m²K/W

Rλ,Bceramictile/stone 0,02m²K/W 0,02m²K/W

Rλ,BPVC 0,01m²K/W 0,01m²K/W

Cooling

Specificcoolingcapacityacc.toDINEN1264-5

38,2W/m² 28,7W/m²

Coolingliquidtemperature∆θH 8K 8K

Heating and cooling

Anadequatetemperatureisimportantforacomfortableindoorclimateandagoodplacetowork.Afurtheradvan-tageinofficesistheinvisibleinstalla-tionofsupplylines.TheMEROhollowfloorCombiTTher-mocombinesthesetwocharacteris-tics.TheMEROCombiTThermocanbeusedinalmostallareas,whetherit

concernsnewbuildingsortherefur-bishmentofoldbuildings.Thesystemdoesnotrequireanyspecificheatingcircuitconnections.Allfloorcoveringssuitableforunderfloorheatingasstoneandceramictiles,textilefloorcover-ings,dimensionallystablefloorcover-ingsanddifferenttypesofparquetcanbeappliedonMEROCombiTThermo.

TÜVcertifiedsince1997

Ourco-operationpartner:

TheMEROhollowfloorCombiTThermoistestedacc.toDINEN1264-2/3/4no.7F249-Fand7F250-Fandcertifiedbyindependentinstitutes.

Technicaldata*: Combi T ThermoAccessories: Drillingisdoneatfactoryoronsitefor:Powersupplyandtwist-airoutletsExpansionjoints/constructionjoints/jointsRevisionopeningsAccessfloorductsCutoutsSpecialwallconnectionsFasciaBridgingAdditionalinsulation(heat,impactsound)Stairs,rampsFloorcoveringsasstone,parquetetc.

*For further detailed technical datapleaseaskforourproductdatasheets.

Bearing layer:

Dimensions: 600x600Systemweight: 56kg/m²to66kg/m²Panelmaterial: Calciumsulphatepanel(fiber-reinforcedcalciumsulphate)Adhesive: Highqualitysolvent-freeadhesiveforthe

adhesionofthetoothing

Substruction

Module: 600x600mmPedestalmaterial: GalvanizedsteelConstructionheight: From50mmPedestalbonding: Normallygluedwiththesubfloorandthe

panel;continuouslyadjustabletoheight

Floor coverings

Textileundelasticfloorcoverings,parquet,naturalstone,artificialstone,liquidcoating

Load values Pointload:Valuedacc.toDINEN13213:Ultimateload:

3.000–5.000NClass2–5>6.000–10.000N

Fire protection

BuildingmaterialclassbearingpanelAcc.toEN13501T1: A1Fireresistanceclassacc.toDIN4102T2: F30possible

Acoustic values

(dependingonsystemandfloorcovering)

SoundreductionindexRL,w,P 39–54dBNormalizedimpactsoundpressurelevelLn,w,P 42–91dBImprovementofsoundpressurelevel∆Lw,P 10–29dB

NewdenominationaccordingtoDINENNormalizedflankleveldifferenceDn,f,w,P

NormalizedflankimpactsoundpressureLn,f,w,P

ImprovementofsoundpressurelevelΔLw,P

Heat flow density of the FH at pipe grid galv. = 100 mm

Hea

t flo

w d

ensi

ty q

[W/m

]

Limiting curve living zone 9K

Limiting curve perimeter area 15K stone 18 mm

Heating liquid over temperature [K]

Heat flow density of the FH at pipe grid galv. = 150 mm

Limiting curve living zone 9K

Limiting curve living zone 15K stone 18 mm

Limiting curve living zone 9K

Stone 18 mm

Limiting curve living zone 15K stone 18 mm

Heating liquid over temperature [K]

Hea

t flo

w d

ensi

ty q

[W/m

]

Cooling capacity of the FH at pipe grid galv. = 100 mm

0

5

10

15

20

25

30

35

40

0 2 4 6 8 10Cooling liquid under temperature T [K]

Coo

ling

flow

den

sity

q [W

/m2 ]

0,000

0,050

0,100

0,150

Stone 18 mm

Nominal cooling capacity at 8K

Coo

ling

flow

den

sity

q [W

/m2 ]

Cooling capacity of the FH at pipe grid galv. = 150 mm

0

5

10

15

20

25

30

35

40

0 2 4 6 8 10

0,000

0,050

0,100

0,150

Stone18 mm

Nominal cooling capacity 8 K

Cooling liquid under temperature T [K]

Headoffice:

MERO-TSKInternational GmbH & Co. KG

Max-Mengeringhausen-Str.5

97084Würzburg,Germany

Postaladress:

MERO-TSKInternational GmbH & Co. KG

ProductDivisionFloorSystems

LauberStraße11

97357Prichsenstadt,Germany

Phone.:+49(0)9383203-603

Fax:+49(0)9383203-629

E-mail:[email protected]

Internet:www.mero.de

PBS Hollow Floor Thermo

Page 2: Technical data*: Combi T Thermo Hollow Floor Combi T Thermo …€¦ · The MERO Combi T Thermo is a dry hollow floor with a floor heating and cooling system. Fields of application

Fields of application

• stoneandceramictiles

• textilefloorcoverings

• dimensionallystableelasticfloorcoverings

• differenttypesofparquet

Advantages

• Especially suitable for low tem-perature plants according to EnEV

• Extremelyshortconstructiontime

• MaximumsystemsafetyduetotightnesstestaccordingtoDINUponorPE-Xatube

• Variousgridsandvariableconstructionheightsarepossible

• Verygoodstructural-physicalcha-racteristics

• Favourablecooling,especiallywithgroundwaterheatpumps

• Healthyindoorclimatethroughra-diantheat

TheMEROdryhollowfloorwithpre-fabricatedgroovesfortheheatingpipesisinstalledaccordingtothelayoutdrawing.

Theplasticpipeisplacedintothegrooves.

Thecutoutsareprefabricated(e.g.forelectricunderfloortankswhicharein-stalledonsite)

Priortothegroutingofthebodyfiller,allpipesaretestedforleaks.

Theprotrudingbodyfillerwillbere-movedfromthesupportingpanel.

AftertheoperationalheatingtheMEROCombiTThermoisreadyfortheappli-cationofthefloorcovering.

System floor

Planning instructions

Theplanningandsettingofthehea-tingandcoolingcircuitsiscarriedouttogetherwiththeTGAplanner.Onrequest,thecalculationofthepipenetworkcanbedonebyMERO.TheMEROCombiTThermocanalsobeoperatedalongthemethodofTi-chelmann.Withafewstandardpa-nelswemeetallstructuralrequire-ments.

Construction principle

Thesupportingpanelsconsistofin-combustiblefiber-reinforcedcalciumsulphate,whichguaranteeanopti-malheattransmission.Specialmilledgroovesfortheinstallationandfix-ingofthepipeworkintegratethefloorheatingintothefloorpanel.Aftertheinstallationoftheheatingpipe,thegroovesarefilledwithbodyfillerflushwiththesurface.Thermallyinsulatedconnectingpipesensureanoptimalenergysupply.Duetothedewpointcontroltheac-cumulationofcondensedwatercanbeavoided.

5

2

1

54

31.Supportingpanelwith groovesfortheheatingpipes2.Heatingpipe3.Bodyfiller4.Pedestal5.Perimeterstrip

Weuseplasticpipesconsistingofhigh-lycross-linkedpolyethylene.Thepipestructurehasanoxygenbarrierwhichexceedsbyfarthestandardrequire-mentsregardingoxygentightness.Thesubstructureconsistsofsteelpedes-tals.Theirheightcanbeexactlyadjus-ted.Allpedestalsareprotectedagainstcorrosionbygalvanizationandpassiva-tion.Thepedestalbaseplatesaregluedtotherawsubfloor.Dependingontherequirements,variouspaneltypesareavailable.

Construction process

2 4MERO-TSK International GmbH & Co. KG

For economic and ecological reasons, rooms today are more and more heated and cooled by activated spaces. The larger the heated part of the space, the lower the energy required. This reduces the cost of heating and cooling. The PBS Thermo is a dry hollow floor with a floor heating and cooling system.

The PBS Thermo can be used in almost all area’s, whether it concerns new buildings or the refurbishment of old buildings. In principle, all floor coverings suitable for floor heating can be installed on PBS Thermo:

• Thermo is proved as heating and cooling system acc. to DIN and certified

Page 3: Technical data*: Combi T Thermo Hollow Floor Combi T Thermo …€¦ · The MERO Combi T Thermo is a dry hollow floor with a floor heating and cooling system. Fields of application

Foreconomicandecologicalreasons,roomstodayaremoreandmoreheatedandcooledbyactivatedspaces.Thelargertheheatedpartofthespace,thelowertheenergyrequired.Thisredu-cesthecostofheatingandcooling.TheMEROCombiTThermoisadryhollowfloorwithafloorheatingandcoolingsystem.

Fields of application

TheMEROCombiTThermocanbeusedinalmostallareas,whetheritconcernsnewbuildingsortherefur-bishmentofoldbuildings.Inprinci-ple,allfloorcoveringssuitableforfloorheatingcanbeinstalledonMEROCombiTThermo:

• stoneandceramictiles

• textilefloorcoverings

• dimensionallystableelasticfloorcoverings

• differenttypesofparquet

Advantages

• Especially suitable for low tem-perature plants according to EnEV

• Extremelyshortconstructiontime

• MaximumsystemsafetyduetotightnesstestaccordingtoDINUponorPE-Xatube

• CombiTThermoisprovedashea-tingandcoolingsystemacc.toDINandcertifiedacc.toDINCertco

• Variousgridsandvariableconstructionheightsarepossible

• Verygoodstructural-physicalcha-racteristics

• Favourablecooling,especiallywithgroundwaterheatpumps

• Healthyindoorclimatethroughra-diantheat

TheMEROdryhollowfloorwithpre-fabricatedgroovesfortheheatingpipesisinstalledaccordingtothelayoutdrawing.

Theplasticpipeisplacedintothegrooves.

Thecutoutsareprefabricated(e.g.forelectricunderfloortankswhicharein-stalledonsite)

Priortothegroutingofthebodyfiller,allpipesaretestedforleaks.

Theprotrudingbodyfillerwillbere-movedfromthesupportingpanel.

AftertheoperationalheatingtheMEROCombiTThermoisreadyfortheappli-cationofthefloorcovering.

System floor

Planning instructions

Theplanningandsettingofthehea-tingandcoolingcircuitsiscarriedouttogetherwiththeTGAplanner.Onrequest,thecalculationofthepipenetworkcanbedonebyMERO.TheMEROCombiTThermocanalsobeoperatedalongthemethodofTi-chelmann.Withafewstandardpa-nelswemeetallstructuralrequire-ments.

Construction principle

Thesupportingpanelsconsistofin-combustiblefiber-reinforcedcalciumsulphate,whichguaranteeanopti-malheattransmission.Specialmilledgroovesfortheinstallationandfix-ingofthepipeworkintegratethefloorheatingintothefloorpanel.Aftertheinstallationoftheheatingpipe,thegroovesarefilledwithbodyfillerflushwiththesurface.Thermallyinsulatedconnectingpipesensureanoptimalenergysupply.Duetothedewpointcontroltheac-cumulationofcondensedwatercanbeavoided.

5

2

1

54

31.Supportingpanelwith groovesfortheheatingpipes2.Heatingpipe3.Bodyfiller4.Pedestal5.Perimeterstrip

Weuseplasticpipesconsistingofhigh-lycross-linkedpolyethylene.Thepipestructurehasanoxygenbarrierwhichexceedsbyfarthestandardrequire-mentsregardingoxygentightness.Thesubstructureconsistsofsteelpedes-tals.Theirheightcanbeexactlyadjus-ted.Allpedestalsareprotectedagainstcorrosionbygalvanizationandpassiva-tion.Thepedestalbaseplatesaregluedtotherawsubfloor.Dependingontherequirements,variouspaneltypesareavailable.

Construction process

2MERO-TSK International GmbH & Co. KG

4MERO-TSK International GmbH & Co. KG

Page 4: Technical data*: Combi T Thermo Hollow Floor Combi T Thermo …€¦ · The MERO Combi T Thermo is a dry hollow floor with a floor heating and cooling system. Fields of application

Foreconomicandecologicalreasons,roomstodayaremoreandmoreheatedandcooledbyactivatedspaces.Thelargertheheatedpartofthespace,thelowertheenergyrequired.Thisredu-cesthecostofheatingandcooling.TheMEROCombiTThermoisadryhollowfloorwithafloorheatingandcoolingsystem.

Fields of application

TheMEROCombiTThermocanbeusedinalmostallareas,whetheritconcernsnewbuildingsortherefur-bishmentofoldbuildings.Inprinci-ple,allfloorcoveringssuitableforfloorheatingcanbeinstalledonMEROCombiTThermo:

• stoneandceramictiles

• textilefloorcoverings

• dimensionallystableelasticfloorcoverings

• differenttypesofparquet

Advantages

• Especially suitable for low tem-perature plants according to EnEV

• Extremelyshortconstructiontime

• MaximumsystemsafetyduetotightnesstestaccordingtoDINUponorPE-Xatube

• CombiTThermoisprovedashea-tingandcoolingsystemacc.toDINandcertifiedacc.toDINCertco

• Variousgridsandvariableconstructionheightsarepossible

• Verygoodstructural-physicalcha-racteristics

• Favourablecooling,especiallywithgroundwaterheatpumps

• Healthyindoorclimatethroughra-diantheat

Theplasticpipeisplacedintothegrooves.

Thecutoutsareprefabricated(e.g.forelectricunderfloortankswhicharein-stalledonsite)

Priortothegroutingofthebodyfiller,allpipesaretestedforleaks.

System floor

Planning instructions

Construction principle

Thesupportingpanelsconsistofin-combustiblefiber-reinforcedcalciumsulphate,whichguaranteeanopti-malheattransmission.Specialmilledgroovesfortheinstallationandfix-ingofthepipeworkintegratethefloorheatingintothefloorpanel.Aftertheinstallationoftheheatingpipe,thegroovesarefilledwithbodyfillerflushwiththesurface.Thermallyinsulatedconnectingpipesensureanoptimalenergysupply.Duetothedewpointcontroltheac-cumulationofcondensedwatercanbeavoided.

5

2

1

54

31.Supportingpanelwith groovesfortheheatingpipes2.Heatingpipe3.Bodyfiller4.Pedestal5.Perimeterstrip

Weuseplasticpipesconsistingofhigh-lycross-linkedpolyethylene.Thepipestructurehasanoxygenbarrierwhichexceedsbyfarthestandardrequire-mentsregardingoxygentightness.Thesubstructureconsistsofsteelpedes-tals.Theirheightcanbeexactlyadjus-ted.Allpedestalsareprotectedagainstcorrosionbygalvanizationandpassiva-tion.Thepedestalbaseplatesaregluedtotherawsubfloor.Dependingontherequirements,variouspaneltypesareavailable.

Construction process

2MERO-TSK International GmbH & Co. KG

4MERO-TSK International GmbH & Co. KG

The PBS dry hollow floor with pre-fabricated grooves for the heating pipes is installed according to the layout drawing

Theprotrudingbodyfillerwillbere-movedfromthesupportingpanel.

After the operational heating the PBS Thermo is ready for the application of the floor covering

The planning and setting of the heating and cooling circuits is carried out together with the TGA planner. On request, the calculation of the pipe network can be done by PBS. The PBS Thermo can also be operated along the method of Tichelmann. With a few standard panels we meet all structural requirements.

Page 5: Technical data*: Combi T Thermo Hollow Floor Combi T Thermo …€¦ · The MERO Combi T Thermo is a dry hollow floor with a floor heating and cooling system. Fields of application

Floor Systems

MERO Hollow Floor Combi T ThermoInnovative solutions from one source

Development

Consulting

Planning

Manufacturing

Installation

AccessFloor

HollowFloor

Floorcoveringand

Installation

Services

EnEV-proved

06.1

3/C

ombi

TT

herm

oSu

bjec

tto

tech

nica

lcha

nges

with

outp

riorn

otic

e

Hollow Floor Combi T ThermoHeating Pipe grid 100 Pipe grid 150

HeatflowdensityqGacc.toDINEN1264-2(withoutcovering,Rλ=0,00m²K/W)

77W/m² 60W/m²

atstandardheatingliquidovertemperature∆θH 12K 12K

HeatflowdensityqGacc.toDINEN1264-2(withcovering,R=0,15m²K/W)

89W/m²

78W/m²

atstandardheatingliquidovertemperature∆θH 26K 29K

Rλ,Bcarpet 0,07–0,23m²K/W 0,07–0,23m²K/W

Rλ,Bceramictile/stone 0,02m²K/W 0,02m²K/W

Rλ,BPVC 0,01m²K/W 0,01m²K/W

Cooling

Specificcoolingcapacityacc.toDINEN1264-5

38,2W/m² 28,7W/m²

Coolingliquidtemperature∆θH 8K 8K

Heating and cooling

TÜVcertifiedsince1997

Ourco-operationpartner:

TheMEROhollowfloorCombiTThermoistestedacc.toDINEN1264-2/3/4no.7F249-Fand7F250-Fandcertifiedbyindependentinstitutes. MERO-TSK International GmbH & Co. KG

Accessories: Drillingisdoneatfactoryoronsitefor:Powersupplyandtwist-airoutletsExpansionjoints/constructionjoints/jointsRevisionopeningsAccessfloorductsCutoutsSpecialwallconnectionsFasciaBridgingAdditionalinsulation(heat,impactsound)Stairs,rampsFloorcoveringsasstone,parquetetc.

Bearing layer:

Dimensions: 600x600Systemweight: 56kg/m²to66kg/m²Panelmaterial: Calciumsulphatepanel(fiber-reinforcedcalciumsulphate)Adhesive: Highqualitysolvent-freeadhesiveforthe

adhesionofthetoothing

Substruction

Module: 600x600mmPedestalmaterial: GalvanizedsteelConstructionheight: From50mmPedestalbonding: Normallygluedwiththesubfloorandthe

panel;continuouslyadjustabletoheight

Floor coverings

Textileundelasticfloorcoverings,parquet,naturalstone,artificialstone,liquidcoating

Load values Pointload:Valuedacc.toDINEN13213:Ultimateload:

3.000–5.000NClass2–5>6.000–10.000N

Fire protection

BuildingmaterialclassbearingpanelAcc.toEN13501T1: A1Fireresistanceclassacc.toDIN4102T2: F30possible

Acoustic values

(dependingonsystemandfloorcovering)

SoundreductionindexRL,w,P 39–54dBNormalizedimpactsoundpressurelevelLn,w,P 42–91dBImprovementofsoundpressurelevel∆Lw,P 10–29dB

NewdenominationaccordingtoDINENNormalizedflankleveldifferenceDn,f,w,P

NormalizedflankimpactsoundpressureLn,f,w,P

ImprovementofsoundpressurelevelΔLw,P

Heat flow density of the FH at pipe grid galv. = 100 mm

Hea

t flo

w d

ensi

ty q

[W/m

]

Limiting curve living zone 9K

Limiting curve perimeter area 15K stone 18 mm

Heating liquid over temperature [K]

Heat flow density of the FH at pipe grid galv. = 150 mm

Limiting curve living zone 9K

Limiting curve living zone 15K stone 18 mm

Limiting curve living zone 9K

Stone 18 mm

Limiting curve living zone 15K stone 18 mm

Heating liquid over temperature [K]

Hea

t flo

w d

ensi

ty q

[W/m

]

Cooling capacity of the FH at pipe grid galv. = 100 mm

0

5

10

15

20

25

30

35

40

0 2 4 6 8 10Cooling liquid under temperature T [K]

Coo

ling

flow

den

sity

q [W

/m2 ]

0,000

0,050

0,100

0,150

Stone 18 mm

Nominal cooling capacity at 8K

Coo

ling

flow

den

sity

q [W

/m2 ]

Cooling capacity of the FH at pipe grid galv. = 150 mm

0

5

10

15

20

25

30

35

40

0 2 4 6 8 10

0,000

0,050

0,100

0,150

Stone18 mm

Nominal cooling capacity 8 K

Cooling liquid under temperature T [K]

Headoffice:

MERO-TSKInternational GmbH & Co. KG

Max-Mengeringhausen-Str.5

97084Würzburg,Germany

Postaladress:

MERO-TSKInternational GmbH & Co. KG

ProductDivisionFloorSystems

LauberStraße11

97357Prichsenstadt,Germany

Phone.:+49(0)9383203-603

Fax:+49(0)9383203-629

E-mail:[email protected]

Internet:www.mero.de

Technical data: Thermo

An adequate temperature is important for a comfortable indoor climate and a good place to work. A further advantage in offices is the invisible installation of supply lines. The PBS hollow floor Thermo combines these two characteristics. The PBS Thermo can be used in almost every area, whether is

concerns new buildings or the refurbishment of old buildings. The system does not require any specific heating circuit connections. All floor coverings suitable for under floor heating as stone and ceramic tiles, textile floor coverings, dimensionally stable floor coverings and different types of parquet can be applied on PBS Thermo

Page 6: Technical data*: Combi T Thermo Hollow Floor Combi T Thermo …€¦ · The MERO Combi T Thermo is a dry hollow floor with a floor heating and cooling system. Fields of application

Floor Systems

MERO Hollow Floor Combi T ThermoInnovative solutions from one source

Development

Consulting

Planning

Manufacturing

Installation

AccessFloor

HollowFloor

Floorcoveringand

Installation

Services

EnEV-proveHeating Pipe grid 100 Pipe grid 150

HeatflowdensityqGacc.toDINEN1264-2(withoutcovering,Rλ=0,00m²K/W)

77W/m² 60W/m²

atstandardheatingliquidovertemperature∆θH 12K 12K

HeatflowdensityqGacc.toDINEN1264-2(withcovering,R=0,15m²K/W)

89W/m²

78W/m²

atstandardheatingliquidovertemperature∆θH 26K 29K

Rλ,Bcarpet 0,07–0,23m²K/W 0,07–0,23m²K/W

Rλ,Bceramictile/stone 0,02m²K/W 0,02m²K/W

Rλ,BPVC 0,01m²K/W 0,01m²K/W

Cooling

Specificcoolingcapacityacc.toDINEN1264-5

38,2W/m² 28,7W/m²

Coolingliquidtemperature∆θH 8K 8K

Heating and cooling

Anadequatetemperatureisimportantforacomfortableindoorclimateandagoodplacetowork.Afurtheradvan-tageinofficesistheinvisibleinstalla-tionofsupplylines.TheMEROhollowfloorCombiTTher-mocombinesthesetwocharacteris-tics.TheMEROCombiTThermocanbeusedinalmostallareas,whetherit

concernsnewbuildingsortherefur-bishmentofoldbuildings.Thesystemdoesnotrequireanyspecificheatingcircuitconnections.Allfloorcoveringssuitableforunderfloorheatingasstoneandceramictiles,textilefloorcover-ings,dimensionallystablefloorcover-ingsanddifferenttypesofparquetcanbeappliedonMEROCombiTThermo.

TÜVcertifiedsince1997

Ourco-operationpartner:

MERO-TSK International GmbH & Co. KG

Technicaldata*: Combi T ThermoAccessories: Drillingisdoneatfactoryoronsitefor:Powersupplyandtwist-airoutletsExpansionjoints/constructionjoints/jointsRevisionopeningsAccessfloorductsCutoutsSpecialwallconnectionsFasciaBridgingAdditionalinsulation(heat,impactsound)Stairs,rampsFloorcoveringsasstone,parquetetc.

*For further detailed technical datapleaseaskforourproductdatasheets.

Bearing layer:

Dimensions: 600x600Systemweight: 56kg/m²to66kg/m²Panelmaterial: Calciumsulphatepanel(fiber-reinforcedcalciumsulphate)Adhesive: Highqualitysolvent-freeadhesiveforthe

adhesionofthetoothing

Substruction

Module: 600x600mmPedestalmaterial: GalvanizedsteelConstructionheight: From50mmPedestalbonding: Normallygluedwiththesubfloorandthe

panel;continuouslyadjustabletoheight

Floor coverings

Textileundelasticfloorcoverings,parquet,naturalstone,artificialstone,liquidcoating

Load values Pointload:Valuedacc.toDINEN13213:Ultimateload:

3.000–5.000NClass2–5>6.000–10.000N

Fire protection

BuildingmaterialclassbearingpanelAcc.toEN13501T1: A1Fireresistanceclassacc.toDIN4102T2: F30possible

Acoustic values

(dependingonsystemandfloorcovering)

SoundreductionindexRL,w,P 39–54dBNormalizedimpactsoundpressurelevelLn,w,P 42–91dBImprovementofsoundpressurelevel∆Lw,P 10–29dB

NewdenominationaccordingtoDINENNormalizedflankleveldifferenceDn,f,w,P

NormalizedflankimpactsoundpressureLn,f,w,P

ImprovementofsoundpressurelevelΔLw,P

Heat flow density of the FH at pipe grid galv. = 100 mm

Hea

t flo

w d

ensi

ty q

[W/m

]

Limiting curve living zone 9K

Limiting curve perimeter area 15K stone 18 mm

Heating liquid over temperature [K]

Heat flow density of the FH at pipe grid galv. = 150 mm

Limiting curve living zone 9K

Limiting curve living zone 15K stone 18 mm

Limiting curve living zone 9K

Stone 18 mm

Limiting curve living zone 15K stone 18 mm

Heating liquid over temperature [K]

Hea

t flo

w d

ensi

ty q

[W/m

]

Cooling capacity of the FH at pipe grid galv. = 100 mm

0

5

10

15

20

25

30

35

40

0 2 4 6 8 10Cooling liquid under temperature T [K]

Coo

ling

flow

den

sity

q [W

/m2 ]

0,000

0,050

0,100

0,150

Stone 18 mm

Nominal cooling capacity at 8K

Coo

ling

flow

den

sity

q [W

/m2 ]

Cooling capacity of the FH at pipe grid galv. = 150 mm

0

5

10

15

20

25

30

35

40

0 2 4 6 8 10

0,000

0,050

0,100

0,150

Stone18 mm

Nominal cooling capacity 8 K

Cooling liquid under temperature T [K]

Postaladress:

System floor

The PBS hollow foor Thermo is tested acc. toDIN EN 1264-2/3/4 no. 7F249-F and 7F250-F and certifed by independentinstitutes.

PBS HOLLAND BV

Product Division Floor Systems

Griekenweg 6-8,

5342 PZ, Oss

Phone.: +31 (0) 412 65 33 00

Fax: +31 (0) 412 63 25 95

E-mail: [email protected]

Internet: www.pbsholland.com