Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The...

58
MCAC-UTSM-2010-15 T1 Condition Rooftop Package I Content 1. MODEL LIST .................................................................................................................................................................... 1 2. EXTERNAL APPEARANCE ........................................................................................................................................... 2 3. MODEL NUMBER NOMENCLATURE .......................................................................................................................... 3 4. FEATURE & BENEFITS ................................................................................................................................................. 4 5. SPECIFICATIONS ........................................................................................................................................................... 5 6. DIMENSIONAL DRAWINGS ........................................................................................................................................ 17 6.1. MRA................................................................................................................................................................................... 17 6.2. MRC .................................................................................................................................................................................. 18 7. WIRING DIAGRAMS ..................................................................................................................................................... 19 7.1. 50HZ (MRA/MRC) ........................................................................................................................................................... 19 7.2. 60HZ (MRA/MRC) ........................................................................................................................................................... 23 8. PERFORMANCE DATA................................................................................................................................................ 30 8.1. 50HZ (MRA/MRC) ........................................................................................................................................................... 30 8.2. 60HZ (MRA/MRC) ........................................................................................................................................................... 38 9. ELECTRICAL DATA ..................................................................................................................................................... 43 9.1. EVAPORATOR PART ............................................................................................................................................................ 43 9.2. COMPRESSOR & CONDENSER PART.................................................................................................................................. 44 10. REFRIGERANT CYCLE DIAGRAM AND SOUND LEVEL.................................................................................... 45 10.1. COOLING ONLY .............................................................................................................................................................. 45 10.2. HEAT PUMP.................................................................................................................................................................... 45 11. OPERATION LIMIT ................................................................................................................................................... 46 11.1. COOLING ONLY............................................................................................................................................................... 46 11.2. HEAT PUMP .................................................................................................................................................................... 46 12. INSTALLATION.......................................................................................................................................................... 47 12.1. ACCESSORIES................................................................................................................................................................ 47 12.2. GENERAL INFORMATION ................................................................................................................................................ 47 12.3. DIMENSIONAL DATA....................................................................................................................................................... 48 12.4. LOCATIONS AND RECOMMENDATIONS .......................................................................................................................... 49 12.5. INSTALLATION ................................................................................................................................................................ 50 12.6. ELECTRICAL WIRING ..................................................................................................................................................... 52 12.7. STARTUP ..................................................................................................................................................................... 53 12.8. MAINTENANCE ............................................................................................................................................................... 54 13. SYSTEM OPERATION.............................................................................................................................................. 56 14. WIRED CONTROLLER ............................................................................................................................................. 57 Technical Manual (2 - 5 TR)

Transcript of Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The...

Page 1: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

I

Content 1. MODEL LIST .................................................................................................................................................................... 1

2. EXTERNAL APPEARANCE ........................................................................................................................................... 2

3. MODEL NUMBER NOMENCLATURE .......................................................................................................................... 3

4. FEATURE & BENEFITS ................................................................................................................................................. 4

5. SPECIFICATIONS ........................................................................................................................................................... 5

6. DIMENSIONAL DRAWINGS ........................................................................................................................................ 17

6.1. MRA ................................................................................................................................................................................... 17 6.2. MRC .................................................................................................................................................................................. 18

7. WIRING DIAGRAMS ..................................................................................................................................................... 19

7.1. 50HZ (MRA/MRC) ........................................................................................................................................................... 19 7.2. 60HZ (MRA/MRC) ........................................................................................................................................................... 23

8. PERFORMANCE DATA ................................................................................................................................................ 30

8.1. 50HZ (MRA/MRC) ........................................................................................................................................................... 30 8.2. 60HZ (MRA/MRC) ........................................................................................................................................................... 38

9. ELECTRICAL DATA ..................................................................................................................................................... 43

9.1. EVAPORATOR PART ............................................................................................................................................................ 43 9.2. COMPRESSOR & CONDENSER PART .................................................................................................................................. 44

10. REFRIGERANT CYCLE DIAGRAM AND SOUND LEVEL .................................................................................... 45

10.1. COOLING ONLY .............................................................................................................................................................. 45 10.2. HEAT PUMP .................................................................................................................................................................... 45

11. OPERATION LIMIT ................................................................................................................................................... 46

11.1. COOLING ONLY ............................................................................................................................................................... 46 11.2. HEAT PUMP .................................................................................................................................................................... 46

12. INSTALLATION .......................................................................................................................................................... 47

12.1. ACCESSORIES ................................................................................................................................................................ 47 12.2. GENERAL INFORMATION ................................................................................................................................................ 47 12.3. DIMENSIONAL DATA ....................................................................................................................................................... 48 12.4. LOCATIONS AND RECOMMENDATIONS .......................................................................................................................... 49 12.5. INSTALLATION ................................................................................................................................................................ 50 12.6. ELECTRICAL WIRING ..................................................................................................................................................... 52 12.7. START–UP ..................................................................................................................................................................... 53 12.8. MAINTENANCE ............................................................................................................................................................... 54

13. SYSTEM OPERATION .............................................................................................................................................. 56

14. WIRED CONTROLLER ............................................................................................................................................. 57

Technical Manual (2 - 5 TR)

Page 2: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

1

1. Model List (50Hz)

Nominal Capacity Model Power Supply Ton Refrigerant Model Name Function V, ph, Hz

2

R22

MRA-24CW

Two way air outlet option

Cooling Only

220~240V, 1Ph~, 50Hz 3 MRA-36CW 3 MRA-36CW

380~415V, 3Ph~, 50Hz 4 MRA-48CW 5 MRA-60CW 2

R22

MRA-24HW-Q

Two way air outlet option

Heat Pump

220~240V, 1Ph~, 50Hz 3 MRA-36HW-Q 3 MRA-36HW-R

380~415V, 3Ph~, 50Hz 4 MRA-48HW-R 5 MRA-60HW-R 3

R22

MRC-36HW

One way air outlet

Heat Pump

220~240V, 1Ph~, 50Hz 3 MRC-36HW-R

380~415V, 3Ph~, 50Hz 4 MRC-48HW-R 5 MRC-60HW-R

(60Hz)

Nominal Capacity Model Power Supply Ton Refrigerant Model Name Function V, ph, Hz

2

R22

MRA-24CW

Two way air outlet option

Cooling Only 208-230V~, 1Ph, 60Hz

3 MRA-36CW 4 MRA-48CW 5 MRA-60CW 5 MRA-60CW-D 208-230V~, 3Ph, 60Hz 5 MRA-60HW-V Heat Pump 208-230V~, 1Ph, 60Hz 3

R22

MRA-36CW-V Two way air outlet option (Copeland

Compressor)

Cooling Only 208-230V~, 1Ph, 60Hz 4 MRA-48CW-V

5 MRA-60CW-V 5 MRA-60CW-D 208-230V~, 3N, 60Hz, 5 MRA-60HW-V Heat Pump 208-230V~, 1Ph, 60Hz 3

R22

MRC-36CW-V

One way air outlet

Cooling Only 208-230V~, 1Ph, 60Hz 4 MRC-48CW-V

5 MRC-60CW-V 5 MRC-60CW-X 208-230V~, 3N, 60Hz,

Page 3: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

2

2. External Appearance

MRA

MRC

Page 4: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

3

3. Model Number Nomenclature

M R A 24 C W Q

Power Supply: Q: 220~240V, 1Ph, 50Hz R: 380~415V, 3Ph, 50Hz V: 208~230V, 1Ph, 60Hz D: 208~230V, 3Ph, 60Hz X: 208~230V, 3Ph, 60Hz

W: Wired Controller

Function Code: C: Cooling Only; E: Electric Heater and Cooling H: Cooling and Heating

Cooling Capacity (*1000Btu/h):

Design Code: A: The first design B: The second design C: The third design

Rooftop Package Unit

Page 5: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

4

4. Feature & Benefits 4.1. The adoption of anticorrosive-box

The reinforced anticorrosion by using galvanization armor plate and coated with man-composed paint. The appearance is stylish and be easy for maintenance. (Has been 1000 hours salt spray test)

4.2. The adoption of credible protection system 4.2.1. The protection of compressor

High-pressure protection, low-pressure protection, compressor current protection and so on the series’ protectors can ensure compressor operating normally. Adopts independent system, except for protections of sequence and wire control output, any protection relate to its corresponding compressor. Once a compressor protection energized, the corresponding compressor will stop, as others working still.

4.2.2. Fan motor The fan motors for evaporator have over-heat protection and over-current protection function. The fan motors for condenser have the temperature controller protection function.

4.3. Energy saving design 4.3.1. High Efficiency Compressor

Using professional compressor, heat exchanger and optimum connection pipe, the compressor can startup under low power input.

4.3.2. Condenser By using high-efficient thin wing, the condenser has high-efficient heat exchanger, the energy waste decreases greatly.

4.3.3. Evaporator By using the high-efficient, super thin wing and inner-whorl copper pipe, the evaporators get the higher capacity and the lower noise level.

4.3.4. The Heat Insulation of indoor unit The heat insulation of indoor unit can availably decrease heat loss.

4.4. Optional collocation 4.4.1. Strong Air Flow

The wind is sent off by exterior high static pressure produced by condenser fan. 4.4.2. Minimum Installation Arrangement

The installation is fast and low cost with the easy installation and ready operation 4.4.3. Pre-Drilled Duct Flange

Flanges are prepared at the supply and return duct connections so that they can reduce duct connection work at site.

4.4.4. Quiet Operation Noise and vibration have been effectively reduced by adopting new style hermetic compressor. The centrifugal fan and fan casing are optimum shaped for efficient and low noise operation.

4.5. Cabinet 4.5.1. Sloped drain pan and drain pipe 4.5.2. Cabinets have forklift and lifting holes for easy transportation 4.5.3. Cabinets have fresh air function, and the filter can be washable. 4.6. Optional supply/return airflow design, from side or bottom, It could be flexibly applied to

multi-position.

Page 6: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

5

5. Specifications Table 1 Model MRA-24CW MRA-36CW Power supply V-Ph-Hz 220~240V-1-50 220~240V-1-50

Cooling Capacity Btu/h 24000 36000 Input W 3100 4600 Rated current A 14.7 21.9

Max. input consumption W 3900 5800 Max. current A 18 27 Starting current A 30 45

Compressor

Model PH440X3CS-4KUS1 C-SB301H5A Type Rotary Scroll Brand Midea Toshiba SANYO Capacity W 7557/7608±5% 12000/11800±7% Input W 2488/2670±5% 3800/4000±7% Rated current(RLA) A 11.98/13.21±5% 18.5/19.6±7% Locked rotor Amp(LRA) A 62.37±10% 122 Thermal protector INTERNAL INTERNAL Capacitor uF/V 60uF/450V 60uF/450V Refrigerant oil ml 950 1700

Evaporator fan motor

Model YDK270-4V YDK270-4V Type Centrifugal Centrifugal Brand YongAn YongAn Input(hi) W 650±10% 650±10% Capacitor uF 12uF/450V 12uF/450V Number of motors Pieces 1 1 Speed(hi/lo) r/min 1000/850 1000/850

Evaporator coil

a.Number of rows 2 3 b.Tube pitch(a) × row pitch(b) mm 25.4×22 25.4×22 c.Fin spacing mm 1.7 1.7 d.Fin type (code) Hydrophilic aluminium Hydrophilic aluminium

e.Tube outside dia. and type mm Φ9.53 Φ9.53 Inner groove tube Inner groove tube

f.Coil length × height × width mm 547×44×508 547×66×508 g.Number of circuits 5 5

Evaporator part air flow (Hi) m3/h 1700 1700 Evaporator part external static pressure (Hi) Pa 40 40

Condenser fan motor

Model YDK165-6N YDK165-6N Type Axial Axial Brand Weiling Weiling Input W 270±10% 270±10% Capacitor uF 12uF/450V 12uF/450V Number of motors Pieces 1 1 Speed r/min 850±30 850±30

Condenser coil

Number of rows 1 1 Tube pitch(a) ×row pitch(b) mm 25.4 25.4 Fin spacing mm 1.7 1.7 Fin type (code) Non-hydrophilic aluminium Non-hydrophilic aluminium

Tube outside dia.and type mm Φ9.53 Φ9.53 Inner groove tube Inner groove tube

Coil length×height× width mm 1492×22×558.8 1492×22×558.8 Number of circuits 2 2

Condenser part air flow m3/h 4900 4900 Package noise level(Sound pressure) dB(A) 65.4 64.3 Package net dimension(W×H×D) mm 1290×630×1030 1290×630×1030 Package packing dimension (W×H×D) mm 1325×665×1085 1325×665×1085 Package net/gross weight kg 144/147 154/157 Refrigerant type g R22/1800 R22/1400 Throttle type Orifice Orifice Design pressure MPa 2.8/1.2 2.8/1.2 Power wiring mm2 3×4.0 3×4.0 Controller Thermostat controller Thermostat controller Operation temp °C 17-30 17-30 Ambient temp °C 18-43 18-43 Application area m2 23-35 38-56

Notes: 1. Nominal cooling capacities are based on the following conditions:

Indoor temp: 26.7°C DB, 19.4°C WB; Outdoor temp: 35°C DB, 23.9°C WB 2. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Page 7: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

6

Table 2 Model MRA-36CW MRA-48CW MRA-60CW Power supply V-Ph-Hz 380~415V-3-50 380~415V-3-50 380~415V-3-50

Cooling Capacity Btu/h 36000 48000 60000 Input W 4400 5600 6500 Rated current A 7.6 9.3 11

Max. input consumption W 5500 6600 8400 Max. current A 9 11 14 Starting current A 17 25 25

Compressor

Model C-SB303H8A C-SB373H8A C-SB453H8A Type Scroll Scroll Scroll Brand SANYO SANYO SANYO Capacity W 11600±7% 14500±7% 17700±7% Input W 3800±7% 4540±7% 5450±7% Rated current(RLA) A 6.8±7% 7.9±7% 9.3±7% Locked rotor Amp(LRA) A 42-45 52 63-69 Thermal protector INTERNAL INTERNAL INTERNAL Capacitor uF/V 12 uF/450V 12 uF/450V 12 uF/450V Refrigerant oil ml 1700 1700 1700

Evaporator fan motor

Model YDK270-4V YDK350-4V YDK350-4V Type Centrifugal Centrifugal Centrifugal Brand YongAn YongAn YongAn Input W 650±10% 860±10% 860±10% Capacitor uF 12uF/450V 15uF/370-450V 15uF/370-450V Number of motors Pieces 1 1 1 Speed(Hi/Lo) r/min 1000/850 980/810 980/810

Evaporator coil

a.Number of rows 3 3 3 b.Tube pitch(a)×row pitch(b) mm 25.4×22 25.4×22 25.4×22 c.Fin spacing mm 1.7 1.7 1.7 d.Fin type (code) Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium

e.Tube outside dia.and type mm Φ9.53 Φ9.53 Φ9.53 Inner groove tube Inner groove tube Inner groove tube

f.Coil length ×height × width mm 547×66×508 547×66×711.2 547×66×711.2 g.Number of circuits 5 8 8

Evaporator part air flow (Hi) m3/h 1700 2900 2900 Evaporator part external static pressure (Hi) Pa 40 50 50

Condenser fan motor

Model YDK165-6N YDK165-6N YDK165-6N Type Axial Axial Axial Brand Weiling Weiling Weiling Input W 270±10% 270±10% 270±10% Capacitor uF 12uF/450V 12uF/450V 12uF/450V Number of motors Pieces 1 1 1 Speed r/min 850±30 850±30 850±30

Condenser coil

Number of rows 1 1 1 Tube pitch(a) × row pitch(b) mm 25.4 25.4 25.4 Fin spacing mm 1.7 1.7 1.7

Fin type (code) Non-hydrophilic aluminium

Non-hydrophilic aluminium

Non-hydrophilic aluminium

Tube outside dia.and type mm Φ9.53 Φ9.53 Φ9.53 Inner groove tube Inner groove tube Inner groove tube

Coil length×height ×width mm 1492×22×812.8 1476×22×1270 1476×22×762 Number of circuits 2 3 8

Condenser part air flow m3/h 4900 5800 5800 Package noise level (Sound pressure) dB(A) 64.4 65.1 64.3 Package net dimension(W×H×D) mm 1290×630×1030 1290×830×1030 1290×830×1030 Package packing dimension (W×H×D) mm 1325×665×1085 1325×865×1085 1325×865×1085 Package net/gross weight kg 154/157 192/195 192/195 Refrigerant type g R22/1700 R22/2300 R22/2600 Throttle type Orifice Orifice Orifice Design pressure MPa 2.8/1.2 2.8/1.2 2.8/1.2 Connection wiring Power wiring mm2 5×2.5 5×2.5 5×2.5 Controller Thermostat controller Thermostat controller Thermostat controller Operation temp °C 17-30 17-30 17-30 Ambient temp °C 18-43 18-43 18-43 Application area m2 32-48 40-60 46-70 Notes: 1. Nominal cooling capacities are based on the following conditions:

Indoor temp: 26.7°C DB, 19.4°C WB; Outdoor temp: 35°C DB, 23.9°C WB 2. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Page 8: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

7

Table 3 Sale Model MRA-24HW-Q MRA-36HW-Q MRA-36HW-R Power supply V-Ph-Hz 220-240~1-50 220-240~1-50 380-415~3-50

Cooling Capacity Btu/h 24000 36000 36000 Input W 3000 4500 4400 Rated current A 14.5 21.5 7.7

Heating Capacity Btu/h 26400 39600 39600 Input W 2700 4000 3700 Rated current A 13.0 19.3 6.8

Max. input consumption W 4300 5600 5500 Max. current A 21.1 29.2 9.2 Starting current A 30 40 15

Compressor

Model PH440X3CS-4KUS1 C-SB301H5A C-SB303H8A Type ROTARY Scroll Scroll Brand MEIZHI Sanyo Sanyo Supplier Guangdong MEIZHI Dalian Sanyo Dalian Sanyo Capacity Btu/h 25784 39579 39579 Input W 2488 3750 3800 Rated current(RLA) A 11.98 17.4 6.8 Locked rotor Amp(LRA) A 55 122 48 Thermal protector inner inner inner Capacitor uF 60 60 —— Refrigerant oil ml ATOMOS NM56EP ·950 SAY56T.1700 1700

Indoor fan motor

Model YDK270-4V YDK270-4V YDK270-4V Type AC Motor AC Motor AC Motor Brand YongAn YongAn YongAn Input W 650 650 650 Capacitor uF 12 12 12 Speed(hi/lo) r/min 1000/850 1000/850 1000/850

Indoor coil

a.Number of rows 2 3 3 b.Tube pitch(a)x row pitch(b) mm 25.4X22 25.4X22 25.4X22 c.Fin spacing mm 1.7 1.7 1.7 d.Fin type (code) Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium

e.Tube outside dia.and type mm Ф9.53 Ф9.53 Ф9.53 innergroove tube innergroove tube innergroove tube

f.Coil length x height x width mm 547X508X44 547X508X66 547X508X66 g.Number of circuits 5 5 5

Indoor air flow (Hi/Mi/Lo) m3/h 1400 1700 1700 Indoor external static pressure (Hi) Pa 25 40 40 Indoor noise level (Hi/Lo) dB(A) 62.1 61.5 63.2

Indoor unit Dimension (WXHXD) mm 1290X630X1030 1290X630X1030 1290X630X1030 Packing (WXHXD) mm 1325X665X1085 1325X665X1085 1325X665X1085 Net/Gross weight Kg 150/152 160/162 160/162

Outdoor fan motor

Model YDK165-6N YDK165-6N YDK165-6N Brand YongAn/Welling YongAn/Welling YongAn/Welling Input W 270 270 270 Capacitor uF 12 12 12 Speed r/min 850 850 850

Outdoor coil

Number of rows 1 2 2 Tube pitch(a)x row pitch(b) mm 25.4X22 25.4X22 25.4X22 Fin spacing mm 1.7 1.7 1.7 Fin type (code) Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium

Tube outside dia.and type mm Ф9.53 Ф9.53 Ф9.53 innergroove tube innergroove tube innergroove tube

Coil length x height x width mm 1492X558.8X22 1476X558.8X44 1476X558.8X44 Number of circuits 2 2 2

Outdoor air flow m3/h 5400 5400 5400 Outdoor noise level dB(A) 62.1 61.5 63.2

Outdoor unit Dimension(WXHXD) mm 1290X630X1030 1290X630X1030 1290X630X1030 Packing (WXHXD) mm 1325X665X1085 1325X665X1085 1325X665X1085 Net/Gross weight Kg 150/152 160/162 160/162

Refrigerant type g 1800 2900 2700 Throttle type Eva. orifice(060+054) Eva. orifice(077+074) Eva. orifice(080+076) Design pressure MPa 2.8 2.8 2.8

Connection wiring Power wiring mm2 2.5X3 3.3X3 2.0X5 Signal wiring mm2 1.0X4/1.0X5 1.0X4/1.0X5 1.0X4/1.0X5

Controller Honeywell Honeywell Honeywell Operation temp ℃ 17-30 17-30 17-30 Ambient temp ℃ -8-43 -8-43 -8-43 Application area m2 28-47 42-70 42-70 Notes: 1. Nominal cooling capacities are based on the following conditions:

Indoor temp: 26.7°C DB, 19.4°C WB; Outdoor temp: 35°C DB, 23.9°C WB 2. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Page 9: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

8

Table 4 Sale Model MRA-48HW-R MRA-60HW-R Power supply V-Ph-Hz 380-415~3-50 380-415~3-50

Cooling Capacity Btu/h 48000 60000 Input W 5500 6500 Rated current A 9.4 11

Heating Capacity Btu/h 52800 66000 Input W 4500 5700 Rated current A 8.1 9.8

Max. input consumption W 7000 8200 Max. current A 12 14.6 Starting current A 18 20

Compressor

Model C-SB373H8A C-SB453H8A Type Scroll Scroll Brand Sanyo Sanyo Supplier Dalian Sanyo Dalian Sanyo Capacity Btu/h 49474 60392 Input W 4450 5450 Rated current(RLA) A 7.9 9.3 Locked rotor Amp(LRA) A 52 66 Thermal protector inner inner Capacitor uF —— —— Refrigerant oil ml 1700 SAY56T.1700

Indoor fan motor

Model YDK350-4V YDK350-4V Type AC Motor AC Motor Brand YongAn YongAn Input W 860 860 Capacitor uF 15 15 Speed(hi/lo) r/min 980/810 980/810

Indoor coil

a.Number of rows 3 3 b.Tube pitch(a)x row pitch(b) mm 25.4X22 25.4X22 c.Fin spacing mm 1.7 1.7 d.Fin type (code) Hydrophilic aluminium Hydrophilic aluminium

e.Tube outside dia.and type mm Ф9.53 Ф9.53 innergroove tube innergroove tube

f.Coil length x height x width mm 547X711.2X66 547X711.2X66 g.Number of circuits 8 8

Indoor air flow (Hi/Mi/Lo) m3/h 2900 2900 Indoor external static pressure (Hi) Pa 50 50 Indoor noise level (Hi/Lo) dB(A) 62.4 63.3

Indoor unit Dimension (WXHXD) mm 1290X830X1030 1290X830X1030 Packing (WXHXD) mm 1325X865X1085 1325X865X1085 Net/Gross weight Kg 197/200 197/200

Outdoor fan motor

Model YDK165-6N YDK180-6A Brand YongAn/Welling Welling Input W 270 255 Capacitor uF 12 12 Speed r/min 850 930

Outdoor coil

Number of rows 2 2 Tube pitch(a)x row pitch(b) mm 25.4X22 25.4X22 Fin spacing mm 1.7 1.7 Fin type (code) Hydrophilic aluminium Hydrophilic aluminium

Tube outside dia.and type mm Ф9.53 Ф9.53 innergroove tube innergroove tube

Coil length x height x width mm 1476X762X44 1476X762X44 Number of circuits 8 8

Outdoor air flow m3/h 5400 5700 Outdoor noise level dB(A) 62.4 63.3

Outdoor unit Dimension(WXHXD) mm 1290X830X1030 1290X830X1030 Packing (WXHXD) mm 1325X865X1085 1325X865X1085 Net/Gross weight Kg 197/200 197/200

Refrigerant type g 3300 3600 Throttle type Eva. orifice Eva. orifice(112+102) Design pressure MPa 2.8 2.8

Connection wiring Power wiring mm2 2.0X5 2.0X5 Signal wiring mm2 1.0X4/1.0X5 1.0X4/1.0X5

Controller Honeywell Honeywell Operation temp ℃ 17-30 17-30 Ambient temp ℃ -8-43 -8-43 Application area m2 56-93 64-106 Notes: 1. Nominal cooling capacities are based on the following conditions:

Indoor temp: 26.7°C DB, 19.4°C WB; Outdoor temp: 35°C DB, 23.9°C WB 2. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Page 10: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

9

Table 5 Sale Model MRC-36HW MRC-36HW-R Power supply V-Ph-Hz 220-240~, 1, 50 380-415~, 3, 50

Cooling Capacity Btu/h 36000 36000 Input W 4200 4140 Rated current A 20 7.2

Heating Capacity Btu/h 39600 39600 Input W 3350 3455 Rated current A 17.2 6.3

Max. input consumption W 5585 5300 Max. current A 25.6 9.2 Starting current A 108 42

Compressor

Model C-SB301H5A C-SB303H8A Type scroll Scroll Brand SANYO SANYO Supplier Dalian Sanyo Dalian Sanyo Capacity Btu/h 39579 39579 Input W 3750 3800 Rated current(RLA) A 17.4 6.8 Locked rotor Amp(LRA) A 122 48 Thermal protector inner inner Capacitor uF 60 —— Refrigerant oil ml 1700 1700

Indoor fan motor

Model YDK250-6X YDK250-6X Type AcMotor AcMotor Brand YongAn YongAn Input W 370 370 Capacitor uF 12 12 Speed(hi/lo) r/min 770/720 770/720

Indoor coil

a.Number of rows 3 3 b.Tube pitch(a)x row pitch(b) mm 25.4×22 25.4×22 c.Fin spacing mm 1.7 1.7 d.Fin type (code) Hydrophilic aluminium Hydrophilic aluminium

e.Tube outside dia.and type mm Ф9.53 Ф9.53 innergroove tube innergroove tube

f.Coil length x height x width mm 420×711.2×66 420×711.2×66 g.Number of circuits 8 8

Indoor air flow (Hi/Mi/Lo) m3/h 1962 1972 Indoor external static pressure (Hi) Pa 40 40

Outdoor fan motor

Model YDK180-6A YDK180-6A Brand Welling Welling Input W 246 246 Capacitor uF 12 12 Speed r/min 940 940

Outdoor coil

Number of rows 1 1 Tube pitch(a)x row pitch(b) mm 25.4 25.4 Fin spacing mm 1.7 1.7 Fin type (code) Hydrophilic aluminium Hydrophilic aluminium

Tube outside dia.and type mm Ф9.53 Ф9.53 innergroove tube innergroove tube

Coil length x height x width mm 1492×762×22 1492×762×22 Number of circuits 4 4

Outdoor air flow m3/h 6015 6028 Outdoor noise level dB(A) 63.5 64.1

Outdoor unit Dimension(WXHXD) mm 730×830×1102 730×830×1102 Packing (WXHXD) mm 765×855×1152 765×855×1152 Net/Gross weight Kg 158/161 158/161

Refrigerant type g R22: 2200 R22: 2600 Throttle type orifice(095+090) orifice(080+085) Design pressure MPa 2.8 2.8

Connection wiring Power wiring mm2 3.3x 3 2.0x 5 Signal wiring mm2 1.0x 4/1.0x 5 1.0x 4/1.0x 5

Controller Honeywell Honeywell Operation temp ℃ Cooling: 17~32; Heating: 10~27 Cooling: 17~32; Heating: 10~27 Ambient temp ℃ Cooling: 18~43; Heating: -7~24 Cooling: 18~43; Heating: -7~24 Application area m2 42-70 42-70 Notes: 1. Nominal cooling capacities are based on the following conditions:

Indoor temp: 26.7°C DB, 19.4°C WB; Outdoor temp: 35°C DB, 23.9°C WB 2. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Page 11: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

10

Table 6 Sale Model MRC-48HW-R MRC-60HW-R Power supply V-Ph-Hz 380-415~, 3, 50 380-415~, 3, 50

Cooling Capacity Btu/h 48000 60000 Input W 5460 6715 Rated current A 9.2 11.2

Heating Capacity Btu/h 52800 66000 Input W 4500 5450 Rated current A 7.8 9.3

Max. input consumption W 6380 8435 Max. current A 11.8 14.6 Starting current A 48 60

Compressor

Model C-SB373H8A C-SB453H8A Type Scroll Scroll Brand Sanyo Sanyo Supplier Dalian Sanyo Dalian Sanyo Capacity Btu/h 49474 60392 Input W 4450 5450 Rated current(RLA) A 7.2 9.3 Locked rotor Amp(LRA) A 52 66 Thermal protector inner inner Capacitor uF —— —— Refrigerant oil ml 1700 1700

Indoor fan motor

Model YDK400-4 YDK400-4 Type AcMotor AcMotor Brand YongAn YongAn Input W 990 990 Capacitor uF 25 25 Speed(hi/lo) r/min 970/750 970/750

Indoor coil

a.Number of rows 4 4 b.Tube pitch(a)x row pitch(b) mm 25.4×22 25.4×22 c.Fin spacing mm 1.3 1.3 d.Fin type (code) Hydrophilic aluminum Hydrophilic aluminum

e.Tube outside dia.and type mm Ф9.53 Ф9.53 innergroove tube innergroove tube

f.Coil length x height x width mm 420×711.2×88 420×711.2×88 g.Number of circuits 7 7

Indoor air flow (Hi/Mi/Lo) m3/h 2637 2637 Indoor external static pressure (Hi) Pa 50 50

Outdoor fan motor

Model YDK180-6A YDK180-6A Brand Welling Welling Input W 246 246 Capacitor uF 12 12 Speed r/min 940 940

Outdoor coil

Number of rows 2 2 Tube pitch(a)x row pitch(b) mm 25.4×22 25.4×22 Fin spacing mm 1.7 1.7 Fin type (code) Hydrophilic aluminum Hydrophilic aluminum

Tube outside dia.and type mm Ф9.53 Ф9.53 innergroove tube innergroove tube

Coil length x height x width mm (1473+1404)×762×22 (1473+1404)×762×22 Number of circuits 4 4

Outdoor air flow m3/h 5780 5805 Outdoor noise level dB(A) 66.1 66.1

Outdoor unit Dimension(WXHXD) 730×830×1102 730×830×1102 730×830×1102 Packing (WXHXD) 765×855×1152 765×855×1152 765×855×1152 Net/Gross weight 169/172 169/172 171/174

Refrigerant type g R22: 3400 R22: 3600 Throttle type orifice(098+092) orifice(098+092) Design pressure MPa 2.6 2.6

Connection wiring Power wiring mm2 2.0x 5 2.0x 5 Signal wiring mm2 1.0x 4/1.0x 5 1.0x 4/1.0x 5

Controller / / Operation temp ℃ Cooling: 17~32; Heating: 10~27 Cooling: 17~32;Heating: 10~27 Ambient temp ℃ Cooling: 18~43; Heating: -7~24 Cooling: 18~43; Heating: -7~24 Application area m2 56-93 64-106

Notes: 1. Nominal cooling capacities are based on the following conditions:

Indoor temp: 26.7°C DB, 19.4°C WB; Outdoor temp: 35°C DB, 23.9°C WB 2. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Page 12: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

11

Table 7 Model MRA-24CW MRA-36C MRA-48CW MRA-60CW

Power supply V-Ph-Hz 208~230-1-60 208~230-1-60 208~230-1-60 208~230-1-60

Cooling Capacity Btu/h 24000 36000 48000 60000 Input W 3100 4200 5600 6100 Rated current A 13.8 18.1 25.6 29.1

Max. input consumption W 3700 4900 6700 7900 Max. current A 18 21 33 39 Starting current A 27 36 54 60

Compressor

Model PH360X3CS-3KUU1 THK73XC6-U C-SB301H6B C-SB351H6A

Type Rotary Rotary Scroll Scroll Brand Toshiba Shanghai Hitachi Sanyo Sanyo Capacity W 7520/7600±5% 9300 14500±7% 16800~16700±5% Input W 2430/2470±5% 3050 4450±7% 5250~5450±5% Rated current(RLA) A 11.8/10.8±5% 15.3 21.9±7% 26~26.3±5% Locked rotor Amp(LRA) A 44.2/48.9±10% 62A (208V/50Hz) 130 151

Thermal protector Internal over load protector

Internal over load protector

Internal over load protector

Internal over load protector

Capacitor uF 50μF/400 V 60μF/400 V 50μF/440 V 70μF/440 V Crankcase input W -- -- 35 35 Refrigerant oil ml 850 875±20(Initial) 1700 1700

Evaporator fan motor

Model YDK270-6W YDK270-6W YDK350-6W YDK350-6W Drive type Direct Direct Direct Direct Input W 515±10% 515±10% 615±10% 615±10% Capacitor uF 12uF/450V 12uF/450V 12uF/450V 12uF/450V Number of motors Pieces 1 1 1 1 Speed(Hi) r/min 960 960 1000 1000

Evaporator coil

a.Number of rows 2 3 3 3 b.Tube pitch(a)x row pitch(b) mm 25.4×22 25.4×22 25.4×22 25.4×22

c.Fin spacing mm 1.7 1.7 1.7 1.7

d.Fin type (code) Hydrophilic aluminum

Hydrophilic aluminum

Hydrophilic aluminum

Hydrophilic aluminum

e.Tube outside dia.and type mm Ф9.53 Ф9.53 Ф9.53 Ф9.53

Inner groove tube Inner groove tube Inner groove tube Inner groove tube f.Coil length x height x width mm 547×508×44 547×508×66 547×711.2×66 547×711.2×66

g.Number of circuits 5 5 8 8 Evaporator part air flow m3/h 1700 1700 2900 2900 Evaporator part external static pressure Pa 40 40 50 50

Condenser fan motor

Model YDK165-6M YDK165-6M YDK165-6M YDK165-6M Type Centrifugal Centrifugal Centrifugal Centrifugal Drive type Direct Direct Direct Direct Input W 330±10% 330±10% 330±10% 330±10% Capacitor uF 12uF/450V 12uF/450V 12uF/450V 12uF/450V Number of motors Pieces 1 1 1 2 Speed r/min 1040 1040 980 980

Condenser coil

Number of rows 1 1 1 2 Tube pitch(a)x row pitch(b) mm 25.4 25.4 25.4 25.4×22

Fin spacing mm 1.7 1.7 1.7 1.7

Fin type (code) Unhydrophilic aluminum

Unhydrophilic aluminum

Unhydrophilic aluminum

Unhydrophilic aluminum

Tube outside dia.and type mm Ф9.53 Ф9.53 Ф9.53 Ф9.53

Inner groove tube Inner groove tube Inner groove tube Inner groove tube Coil length x height x width mm 1492×558.8×22 1492×558.8×22 1476×1270×22 1476×762×44

Number of circuits 2 2 3 3 Condenser part air flow m3/h 4910 4910 5880 5880 Package noise level (Sound pressure) dB(A) 63.3 65.2 65.8 65.4 Package net dimension(W x H x D) mm 1290×630×1030 1290×630×1030 1290×830×1030 1290×830×1030 Package packing dimension (W x H x D) mm 1325×665×1085 1325×665×1085 1325×865×1085 1325×865×1085 Package Net/Gross weight kg 144/147 154/157 192/195 192/195 Refrigerant type g R22/1600 R22/1800 R22/2900 R22/3000 Throttle type Eva. orifice Eva. orifice Eva. orifice Eva. orifice Design pressure MPa 2.8/1.2 2.8/1.2 2.8/1.2 2.8/1.2 Power wiring mm2 3×4 3×4 3×4 3×6 Drainage pipe diameter mm 20 20 20 20

Controller Thermostat controller

Thermostat controller

Thermostat controller

Thermostat controller

Operation temp ℃ 17—30 17—30 17—30 17—30 Ambient temp ℃ 18—43 18—43 18—43 18—43 Application area m2 23—35 31—46 40—60 46—70

Notes: 1. Nominal cooling capacities are based on the following conditions:

Indoor temp: 26.7°C DB, 19.4°C WB; Outdoor temp: 35°C DB, 23.9°C WB 2. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Page 13: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

12

Table 8 Sale Model MRA-60CW-D MRA-60HW-V

Power supply V-Ph-Hz 208-230~ 3 60 208-230~ 1 60

Cooling Capacity Btu/h 60000 60000 Input W 6007 6300 Rated current A 18.4 29

Heating Capacity Btu/h - 66000 Input W - 5200 Rated current A - 24

Max. input consumption W 7459 7800 Max. current A 23.6 42 Starting current A 40

Compressor

Model C-SB353H6B C-SB351H6A Type Scroll Scroll Brand Sanyo Sanyo Supplier Dalian Sanyo Dalian Sanyo Capacity Btu/h 57322 57322 Input W 5100 5250 Rated current(RLA) A 16.4 26 Locked rotor Amp(LRA) A 135 141 Thermal protector outer Inner Refrigerant oil ml 1700 1700

Indoor fan motor

Model YDK350-6W YDK350-6W Type AC Motor AC Motor Brand YongAn YongAn Input W 615 615 Capacitor uF 12 12 Speed(hi/mi/lo) r/min 980/810 980/810

Indoor coil

a.Number of rows 3 3 b.Tube pitch(a)x row pitch(b) mm 25.4X22 25.4X22 c.Fin spacing mm 1.7 1.7 d.Fin type (code) Hydrophilic aluminium Hydrophilic aluminium

e.Tube outside dia.and type mm Ф9.53 Ф9.53 innergroove tube innergroove tube

f.Coil length x height x width mm 547X711.2X66 547X711.2X66 g.Number of circuits 8 8

Indoor air flow (Hi/Mi/Lo) m3/h 2900/2350 2783 Indoor external static pressure (Hi) Pa 50 50 Indoor noise level (Sound pressure)(Hi/Mi/Lo) dB(A) 62.4 621

Indoor unit Dimension (WxHxD) mm 1290X830X1030 1290X830X1030 Packing (WxHxD) mm 1325X865X1085 1325X865X1085 Net/Gross weight Kg 192/195 197/200

Outdoor fan motor

Model YDK165-6M YDK165-6M Brand YongAn/Welling YongAn/Welling Input W 363 363 Capacitor uF 12 12 Speed r/min 880 880

Outdoor coil

Number of rows 2 2 Tube pitch(a)x row pitch(b) mm 25.4X22 25.4X22 Fin spacing mm 1.7 1.7 Fin type (code) Unhydrophilic aluminium Hydrophilic aluminium

Tube outside dia.and type mm Ф9.53 Ф9.53 innergroove tube innergroove tube

Coil length x height x width mm 1476X762X44 1476X762X44 Number of circuits 8 8

Outdoor air flow m3/h 5880 5980 Outdoor noise level(Sound pressure) dB(A) 62.4 62.1

Outdoor unit Dimension(WxHxD) mm 1290X830X1030 1290X830X1030 Packing (WxHxD) mm 1325X865X1085 1325X865X1085 Net/Gross weight Kg 192/195 197/200

Refrigerant type g R22(2900 ) R22(3500 ) Throttle type Eva. orifice Eva. orifice Design pressure MPa 2.8 2.8

Connection wiring Power wiring mm2 2.5x3 3x10.0 Signal wiring mm2 1.0x3/1.0x4 1.0x4/1.0x5

Controller Honeywell Honeywell Operation temp ℃ 17-30 17-30 Ambient temp ℃ 17-43 17-43 Application area m2 45-68 45-68

Notes: 1. Nominal cooling capacities are based on the following conditions:

Indoor temp: 26.7°C DB, 19.4°C WB; Outdoor temp: 35°C DB, 23.9°C WB 2. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Page 14: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

13

Table 9 Sale Model MRA-36CW-V MRA-48CW-V MRA-60CW-V Power supply V-Ph-Hz 208~230-1-60 208~230-1-60 208~230-1-60

Cooling Capacity Btu/h 36000 48000 60000 Input W 3900 5300 6100 Current A 17.6 24 28

Max. input consumption W 4700 6400 7700 Max. current A 24 34 39.2

Compressor

Model ZR36KC-PFV-522 ZR48KC-PFV-522 ZR57KC-PFV-522 Type Scroll Scroll Scroll Brand Copelond Copelond Copelond Capacity Btu/h 36900 49500 57500 Input W 3350 4400 5200 Rated current(RLA) A 17.9 23.6 28 Locked rotor Amp(LRA) A 100.0 132.0 150 Thermal protector yes yes yes Capacitor uF 40 40 60 Refrigerant oil ml 1200 1200 1824

Indoor fan motor

Model YDK270-6W YDK350-6W YDK350-6W Type Ac Motor Ac Motor Ac Motor Brand YongAn YongAn YongAn Input W 515/425 615/480 615/480 Rated current A 2.23/1.92 2.69/2.17 2.69/2.17 Capacitor uF 12 12 12 Speed(hi/mi/lo) r/min 1040/790 980/810 980/810

Indoor coil

a.Number of rows 3 3 3 b.Tube pitch(a)x row pitch(b) mm 25.4X22 25.4X22 25.4X22 c.Fin spacing mm 1.7 1.7 1.7 d.Fin type (code) Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium

e.Tube outside dia.and type mm Ф9.5 Ф9.5 Ф9.5

innergroove tube innergroove tube innergroove tube f.Coil length x height mm 547X508X66 547X711.2X66 547X711.2X66 g.Number of circuits 5 8 8

Indoor static pressure Pa 50 50 50 Indoor air flow CFM 1100 1800 1800

Outdoor fan motor

Model YDK180-6B YDK180-6B YDK180-6B Type Ac Motor Ac Motor Ac Motor Brand Welling Welling Welling Input W 470 470 470 Rated current A 2 2 2 Capacitor uF 12 12 12 Speed r/min 1000 1000 1000

Outdoor coil

Number of rows 2 2 2 Tube pitch(a)x row pitch(b) mm 25.4X22 25.4X22 25.4X22 Fin spacing mm 1.7 1.7 1.7 Fin type (code) Unhydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium

Tube outside dia.and type mm Ф9.5 Ф9.5 Ф9.5

innergroove tube innergroove tube innergroove tube Coil length x height mm 1492X558.8X44 1476X762X44 1476X762X44 Number of circuits 2 3 5

Outdoor air flow CFM 2900 3500 3500

Unit Dimension(W×H×D) mm 1290X630X1030 1290X830X1030 1290X830X1030 Packing (W×H×D) mm 1325X665X1085 1325X865X1085 1325X865X1085 Net/Gross weight kg 154/157 192/195 192/195

Charged refrigerant type g R22(2100g) R22(2500g) R22(3500g) Throttle type Orifice Orifice Orifice Design pressure MPa 2.8/1.2 2.8/1.2 2.8/1.2

Connection wiring

Power wiring mm2 3×4.0 3×4.0 3×6.0 Signal wiring mm2 3×1.0 3×1.0 3×1.0

Controller Wired controller Wired controller Wired controller Ambient temp ℃ Cooling:21~43 Cooling:21~43 Cooling:21~43

Notes: 1. Nominal cooling capacities are based on the following conditions:

Indoor temp: 26.7°C DB, 19.4°C WB; Outdoor temp: 35°C DB, 23.9°C WB 2. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Page 15: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

14

Table 10 Sale Model MRA-60CW-D MRA-60HW-V Power supply V-Ph-Hz 208~230-3-60 208~230-1-60

Cooling Capacity Btu/h 60000 60000 Input W 6400 6300 Current A 17 29

Heating Capacity Btu/h -- 66000 Input W -- 5600 Current A -- 26

Max. input consumption W 8200 8300 Max. current A 25 43

Compressor

Model 503DH-80B2 ZR57KC-PFV-522 Brand / Type HITICHI / Scroll Copelond / Scroll Capacity Btu/h 61074 57500 Input W 5300 5200 Rated current(RLA) A 15.8 28 Locked rotor Amp(LRA) A 100.0 150 Thermal protector yes yes Capacitor uF -- 60 Refrigerant oil ml 1400 1824

Indoor fan motor

Model YDK350-6W YDK350-6W Type Ac Motor Ac Motor Brand YongAn YongAn Input W 615/480 615/480 Rated current A 2.69/2.17 2.69/2.17 Capacitor uF 12 12 Speed(hi/mi/lo) r/min 980/810 980/810

Indoor coil

a.Number of rows 3 3 b.Tube pitch(a)x row pitch(b) mm 25.4X22 25.4X22 c.Fin spacing mm 1.7 1.7 d.Fin type (code) Hydrophilic aluminium Hydrophilic aluminium

e.Tube outside dia.and type mm Ф9.5 Ф9.5

innergroove tube innergroove tube f.Coil length x height mm 547X711.2X66 547X711.2X66 g.Number of circuits 8 8

Indoor static pressure Pa 50 50 Indoor air flow CFM 1800 1800

Outdoor fan motor

Model YDK180-6B YDK180-6B Type Ac Motor Ac Motor Brand Welling Welling Input W 470 470 Rated current A 2 2 Capacitor uF 12 12 Speed r/min 1000 1000

Outdoor coil

Number of rows 2 2 Tube pitch(a)x row pitch(b) mm 25.4X22 25.4X22 Fin spacing mm 1.7 1.7 Fin type (code) Hydrophilic aluminium Hydrophilic aluminium

Tube outside dia.and type mm Ф9.5 Ф9.5

innergroove tube innergroove tube Coil length x height mm 1476X762X44 1476X762X44 Number of circuits 5 5

Outdoor air flow CFM 3500 3500

Unit Dimension(W×H×D) mm 1290X830X1030 1290X830X1030 Packing (W×H×D) mm 1325X865X1085 1325X865X1085 Net/Gross weight kg 192/195 197/200

Charged refrigerant type g R22(3700g) R22(4000g) Throttle type Orifice Orifice Design pressure MPa 2.8/1.2 2.8/1.2

Connection wiring Power wiring mm2 5×4.0 3×10.0 Signal wiring mm2 3×1.0 4×1.0

Controller Wired controller Wired controller Ambient temp ℃ Cooling:21~43 Cooling:21~43 Heating:-5~24

Notes: 1. Nominal cooling capacities are based on the following conditions:

Indoor temp: 26.7°C DB, 19.4°C WB; Outdoor temp: 35°C DB, 23.9°C WB 2. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Page 16: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

15

Table 11 Sale Model MRC-36CW-V MRC-48CW-V Power supply V-Ph-Hz 208~230-1-60 208~230-1-60

Cooling Capacity Btu/h 36000 48000 Input W 3976 5000 Current A 18 22.7

Max. input consumption W 5000 6200 Max. current A 24 31

Compressor

Model ZR36KC-PFV-522 ZR48KC-PFV-522 Type Scroll Scroll Brand Copelond Copelond Capacity Btu/h 36900 49500 Input W 3350 4400 Rated current(RLA) A 17.9 23.6 Locked rotor Amp(LRA) A 100.0 132.0 Thermal protector yes yes Capacitor uF 40 40 Refrigerant oil ml 1200 1200

Indoor fan motor

Model YDK250-6X YDK300-6X Type Ac Motor Ac Motor Brand YongAn YongAn Input W 500/420 655/450 Rated current A 2.15/1.81 2.85/2.2 Capacitor uF 12 12 Speed(hi/mi/lo) r/min 800/720 980/750

Indoor coil

a.Number of rows 3 4 b.Tube pitch(a)x row pitch(b) mm 25.4×22 25.4×22 c.Fin spacing mm 1.7 1.3 d.Fin type (code) Hydrophilic aluminium Hydrophilic aluminium

e.Tube outside dia.and type mm Ф9.5 Ф9.5 innergroove tube innergroove tube

f.Coil length x height mm 420×711.2×66 420×711.2×88 g.Number of circuits 8 7

Indoor static pressure Pa 50 50 Indoor air flow CFM 1200 1700

Outdoor fan motor

Model YDK180-6B YDK180-6B Type Ac Motor Ac Motor Brand Welling Welling Input W 470 470 Rated current A 2 2 Capacitor uF 12 12 Speed r/min 1000 1000

Outdoor coil

Number of rows 1 2 Tube pitch(a)x row pitch(b) mm 25.4×22 25.4×22 Fin spacing mm 1.7 1.7 Fin type (code) Non-hydrophilic aluminium Non-hydrophilic aluminium

Tube outside dia.and type mm Ф9.5 Ф9.5 innergroove tube innergroove tube

Coil length x height mm 1492×762×22 (1473+1404)×762×44 Number of circuits 4 4

Outdoor air flow CFM 3500 3400

Unit Dimension(W×H×D) mm 1116×830×744 1116×830×744 Packing (W×H×D) mm 1152×870×765 1152×870×765 Net/Gross weight kg 144/147 155/158

Charged refrigerant type g R22 / 1600 R22 / 3000 Throttle type Orifice Orifice Design pressure MPa 2.8/1.2 2.8/1.2

Connection wiring Power wiring mm2 3×4.0 3×4.0 Signal wiring mm2 3×1.0 3×1.0

Controller Wired controller Wired controller Ambient temp ℃ Cooling:21~43 Cooling:21~43

Notes: 1. Nominal cooling capacities are based on the following conditions:

Indoor temp: 26.7°C DB, 19.4°C WB; Outdoor temp: 35°C DB, 23.9°C WB 2. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Page 17: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

16

Table 12 Sale Model MRC-60CW-V MRC-60CW-X Power supply V-Ph-Hz 208~230-1-60 208~230-3-60

Cooling Capacity Btu/h 60000 60000 Input W 6060 6100 Current A 28.3 16.5

Max. input consumption W 7700 7800 Max. current A 40 24.5

Compressor

Model ZR57KC-PFV-522 503DH-80B2 Type Scroll Scroll Brand Copelond HITICHI Capacity Btu/h 57500 61074 Input W 5200 5300 Rated current(RLA) A 28 15.8 Locked rotor Amp(LRA) A 150 100.0 Thermal protector yes yes Capacitor uF 60 / Refrigerant oil ml 1800 1400

Indoor fan motor

Model YDK500-6B YDK500-6B Type Ac Motor Ac Motor Brand YongAn YongAn Input W 620 620 Rated current A 2.8 2.8 Capacitor uF 20 20 Speed(hi/mi/lo) r/min 1080 1080

Indoor coil

a.Number of rows 4 4 b.Tube pitch(a)x row pitch(b) mm 25.4×22 25.4×22 c.Fin spacing mm 1.3 1.3 d.Fin type (code) Hydrophilic aluminium Hydrophilic aluminium

e.Tube outside dia.and type mm Ф9.5 Ф9.5 innergroove tube innergroove tube

f.Coil length x height mm 420×711.2×88 420×711.2×88 g.Number of circuits 7 7

Indoor static pressure Pa 50 50 Indoor air flow CFM 1700 1700

Outdoor fan motor

Model YDK180-6B YDK180-6B Type Ac Motor Ac Motor Brand Welling Welling Input W 470 470 Rated current A 2 2 Capacitor uF 12 12 Speed r/min 1000 1000

Outdoor coil

Number of rows 2 2 Tube pitch(a)x row pitch(b) mm 25.4×22 25.4×22 Fin spacing mm 1.7 1.7 Fin type (code) Non-hydrophilic aluminium Non-hydrophilic aluminium

Tube outside dia.and type mm Ф9.5 Ф9.5 innergroove tube innergroove tube

Coil length x height mm (1473+1404)×762×44 (1473+1404)×762×44 Number of circuits 4 4

Outdoor air flow CFM 3400 3400

Unit Dimension(W×H×D) mm 1116×830×744 1116×830×744 Packing (W×H×D) mm 1152×870×765 1152×870×765 Net/Gross weight kg 166/169 167/170

Charged refrigerant type g R22 / 3400 R22 / 3400 Throttle type Orifice Orifice Design pressure MPa 2.8/1.2 2.8/1.2

Connection wiring Power wiring mm2 3×6.0 5×3.3 Signal wiring mm2 3×1.0 3×1.0

Controller Wired controller Wired controller Ambient temp ℃ Cooling:21~43 Cooling:21~43

Notes: 1. Nominal cooling capacities are based on the following conditions:

Indoor temp: 26.7°C DB, 19.4°C WB; Outdoor temp: 35°C DB, 23.9°C WB 2. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Page 18: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

17

6. Dimensional Drawings 6.1. MRA

Package net dimensions: Width 1290mm; Depth 1030mm; Height as the following chart:

Capacity(Btu/h) A(Height)

24000~36000 630 mm

48000~60000 830 mm

Page 19: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

18

6.2. MRC

Page 20: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

19

7. Wiring Diagrams 7.1. 50HZ (MRA/MRC)

7.1.1. MRA-24CW (220~240V-1ph-50Hz)

7.1.2. MRA-36CW (220~240V-1ph-50Hz)

Page 21: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

20

7.1.3. MRA- 36CW/MRA-48CW/MRA-60CW (380~415V-3ph-50Hz)

7.1.4. MRA-24HW-Q (220~240V-1ph-50Hz)

Page 22: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

21

7.1.5. MRA-36HW-Q (220~240V-1ph-50Hz)

7.1.6. MRA-36HW-R (380~415V-3ph-50Hz)

Page 23: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

22

7.1.7. MRA-48HW-R, MRA-60HW-R (380~415V-3ph-50Hz)

7.1.8. MRC-36HW (220~240V-1ph-50Hz)

MAIN CONTROL BOARD

L-PRO

T6

CN4

CN2

T5

CN3CN13

21 22

KM 1A1

31

5

A2246

COMPRED

FAN2

CAP2

FAN1

CAP1

WHIT

E

WHI

TE

Y/G

L N

XT1

CN32 CN34 CN35 CN36 CN6CN15

XP5XS5

XP6XS6

RT3 RT4

CN8

CN7

Y/G

S

CY/G

R

CAP3

REDRED

REDRED

RED

WHITE

BLACK

RED

BLAC

K

BLACK

BLUE

RED BLACK

BLUE

BROWN

CN1

RED

BLAC

K

B C RY G

XT2

BLACK

BLAC

K

BLACK

202096090024

BLACK

1 2

45

CAP4

RELAY

RES

BLACK

BLACK

BLACK

BLACK

WHITERED

24V

RT2

XS1

XP1

XS2XP2

K1 K2

XS3XP3

TRAN SFORME R(24V~)

2-WAY TERMINAL

LOW PRESS SWITCH

AC CON TACT OR

COMP RESSORCOMP

FAN1

RT2~4

XP1~6

XS1~6

CAP1

T5

XT2

WIRING DIAGRAM

CONNECTORS

TEMP.SENSOR

CODE

INDOOR FAN

PART NAME

CONNECTORS

FAN2

CAP2

T6

OUTDOOR FANINDOOR FAN CAP

OUTDOOR FAN CAP

TRAN SFORME R

XT1

L-PR O

KM1

MIDDLE TERMINAL

K2 COMP.TEMP. SWITH

K1 HIGH PRESS SWITCH

CAP5

CAP3 COMP RUNNI NG CAP

CAP4,CAP5 COMP CAP

RELAY RELAY

TO TH E WIRE CO N TROLLER

CTCN49N

CN30

CN33 CN48

4-WAY

VAL

VE

BLUE BLUE

BROWN

BROW

N

BLAC

K

RED

BLU

E

YELL

OW

GREE

N

BROWN

Page 24: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

23

7.1.9. MRC-36HW-R, MRC-48HW-R, MRC-60HW-R (380~415V-3ph-50Hz)

7.2. 60HZ (MRA/MRC)

7.2.1. MRA-24CW, MRA-36CW, MRA-48CW (208~230V-1ph-60Hz)

Page 25: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

24

7.2.2. MRA-60CW (208~230V-1ph-60Hz)

7.2.3. MRA-60CW-D (208~230V-3ph-60Hz)

Page 26: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

25

7.2.4. MRA-60HW-V (208~230V-1ph-60Hz)

7.2.5. MRA-36CW-V

Page 27: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

26

7.2.6. MRA-48CW-V MRA-60CW-V

7.2.7. MRA-60CW-D

Page 28: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

27

7.2.8. MRA-60HW-V

7.2.9. MRC-36CW-V

Page 29: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

28

7.2.10. MRC-48CW-V

7.2.11. MRC-60CW-V

Page 30: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

29

7.2.12. MRC-60CW-X

Page 31: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

30

8. Performance Data 8.1. 50HZ (MRA/MRC) 8.1.1. MRA-24CW (220~240V-1ph-50Hz)

Indoor air entering Temp

Outdoor air entering Temp(DB) 70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC

70 0F/21ºC DB

59 0F/15ºC WB

Tcc(kW) 7.31 6.96 6.60 6.32 Scc(kW) 5.41 5.36 5.28 5.31

S/T 0.74 0.77 0.80 0.84 PW(kW) 2.57 2.79 2.91 3.01

75 0F/24ºC DB

63 0F/17ºC WB

Tcc(kW) 7.53 7.17 6.82 6.39 Scc(kW) 5.64 5.59 5.52 5.37

S/T 0.75 0.78 0.81 0.84 PW(kW) 2.73 2.91 3.04 3.19

80 0F/26.7ºC DB

66.92 0F/19.4ºC WB

Tcc(kW) 7.67 7.31 7.10 6.60 Scc(kW) 5.67 5.63 5.54 5.41

S/T 0.74 0.77 0.78 0.82 PW(kW) 2.79 2.95 3.10 3.26

84 0F/29ºC DB

66 0F/19ºC WB

Tcc(kW) 7.74 7.38 7.24 6.67 Scc(kW) 6.50 6.28 6.23 6.07

S/T 0.84 0.85 0.86 0.91 PW(kW) 2.85 3.01 3.13 3.32

90 0F/32ºC DB

73 0F/23ºC WB

Tcc(kW) 7.81 7.53 7.38 6.82 Scc(kW) 6.64 6.55 6.50 6.34

S/T 0.85 0.87 0.88 0.93 PW(kW) 2.91 3.04 3.26 3.38

8.1.2. MRA-36CW (220~240V-1ph-50Hz) Indoor air entering

Temp Outdoor air entering Temp(DB)

70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC

70 0F/21ºC DB

59 0F/15ºC WB

Tcc(kW) 10.82 10.29 9.77 9.35 Scc(kW) 8.00 7.92 7.81 7.85

S/T 0.74 0.77 0.80 0.84 PW(kW) 3.82 4.14 4.32 4.46

75 0F/24ºC DB

63 0F/17ºC WB

Tcc(kW) 11.13 10.61 10.08 9.45 Scc(kW) 8.35 8.27 8.16 7.94

S/T 0.75 0.78 0.81 0.84 PW(kW) 4.05 4.32 4.51 4.74

80 0F/26.7ºC DB

66.92 0F/19.4ºC WB

Tcc(kW) 11.34 10.82 10.50 9.77 Scc(kW) 8.39 8.33 8.19 8.01

S/T 0.74 0.77 0.78 0.82 PW(kW) 4.14 4.37 4.60 4.83

84 0F/29ºC DB

66 0F/19ºC WB

Tcc(kW) 11.45 10.92 10.71 9.87 Scc(kW) 9.61 9.28 9.21 8.98

S/T 0.84 0.85 0.86 0.91 PW(kW) 4.23 4.46 4.65 4.92

90 0F/32ºC DB

73 0F/23ºC WB

Tcc(kW) 11.55 11.13 10.92 10.08 Scc(kW) 9.82 9.68 9.61 9.37

S/T 0.85 0.87 0.88 0.93 PW(kW) 4.32 4.51 4.83 5.01

8.1.3. MRA-36CW (380~415V-3ph-50Hz) Indoor air entering

Temp Outdoor air entering Temp(DB)

70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC 70 0F/21ºC DB

59 0F/15ºC WB

Tcc(kW) 10.82 10.29 9.77 9.35 Scc(kW) 8.00 7.92 7.81 7.85

S/T 0.74 0.77 0.80 0.84 PW(kW) 3.65 3.96 4.14 4.27

75 0F/24ºC DB

63 0F/17ºC WB

Tcc(kW) 11.13 10.61 10.08 9.45 Scc(kW) 8.35 8.27 8.16 7.94

S/T 0.75 0.78 0.81 0.84 PW(kW) 3.87 4.14 4.31 4.53

80 0F/26.7ºC DB

66.92 0F/19.4ºC WB

Tcc(kW) 11.34 10.82 10.50 9.77 Scc(kW) 8.39 8.33 8.19 8.01

S/T 0.74 0.77 0.78 0.82 PW(kW) 3.96 4.18 4.40 4.62

84 0F/29ºC DB

66 0F/19ºC WB

Tcc(kW) 11.45 10.92 10.71 9.87 Scc(kW) 9.61 9.28 9.21 8.98

S/T 0.84 0.85 0.86 0.91 PW(kW) 4.05 4.27 4.44 4.71

90 0F/32ºC DB

73 0F/23ºC WB

Tcc(kW) 11.55 11.13 10.92 10.08 Scc(kW) 9.82 9.68 9.61 9.37

S/T 0.85 0.87 0.88 0.93 PW(kW) 4.14 4.31 4.62 4.80

Page 32: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

31

8.1.4. MRA-48CW (380~415V-3ph-50Hz) Indoor air entering

Temp Outdoor air entering Temp(DB)

70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC

70 0F/21ºC DB

59 0F/15ºC WB

Tcc(kW) 14.42 13.72 13.02 12.46 Scc(kW) 10.67 10.56 10.42 10.47

S/T 0.74 0.77 0.80 0.84 PW(kW) 4.65 5.04 5.26 5.43

75 0F/24ºC DB

63 0F/17ºC WB

Tcc(kW) 14.84 14.14 13.44 12.60 Scc(kW) 11.13 11.03 10.89 10.58

S/T 0.75 0.78 0.81 0.84 PW(kW) 4.93 5.26 5.49 5.77

80 0F/26.7ºC DB

66.92 0F/19.4ºC WB

Tcc(kW) 15.12 14.42 14.00 13.02 Scc(kW) 11.19 11.10 10.92 10.68

S/T 0.74 0.77 0.78 0.82 PW(kW) 5.04 5.32 5.60 5.88

84 0F/29ºC DB

66 0F/19ºC WB

Tcc(kW) 15.26 14.56 14.28 13.16 Scc(kW) 12.82 12.38 12.28 11.98

S/T 0.84 0.85 0.86 0.91 PW(kW) 5.15 5.43 5.66 5.99

90 0F/32ºC DB

73 0F/23ºC WB

Tcc(kW) 15.40 14.84 14.56 13.44 Scc(kW) 13.09 12.91 12.81 12.50

S/T 0.85 0.87 0.88 0.93 PW(kW) 5.26 5.49 5.88 6.10

8.1.5. MRA-60CW (380~415V-3ph-50Hz) Indoor air entering

Temp Outdoor air entering Temp(DB)

70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC

70 0F/21ºC DB

59 0F/15ºC WB

Tcc(kW) 16.48 15.68 14.88 14.24 Scc(kW) 12.20 12.07 11.90 11.96

S/T 0.74 0.77 0.80 0.84 PW(kW) 5.40 5.85 6.11 6.31

75 0F/24ºC DB

63 0F/17ºC WB

Tcc(kW) 16.96 16.16 15.36 14.40 Scc(kW) 12.72 12.60 12.44 12.10

S/T 0.75 0.78 0.81 0.84 PW(kW) 5.72 6.11 6.37 6.70

80 0F/26.7ºC DB

66.92 0F/19.4ºC WB

Tcc(kW) 17.28 16.48 16.00 14.88 Scc(kW) 12.79 12.69 12.48 12.20

S/T 0.74 0.77 0.78 0.82 PW(kW) 5.85 6.18 6.50 6.83

84 0F/29ºC DB

66 0F/19ºC WB

Tcc(kW) 17.44 16.64 16.32 15.04 Scc(kW) 14.65 14.14 14.04 13.69

S/T 0.84 0.85 0.86 0.91 PW(kW) 5.98 6.31 6.57 6.96

90 0F/32ºC DB

73 0F/23ºC WB

Tcc(kW) 17.60 16.96 16.64 15.36 Scc(kW) 14.96 14.76 14.64 14.28

S/T 0.85 0.87 0.88 0.93 PW(kW) 6.11 6.37 6.83 7.09

8.1.6. MRA-24HW-Q (220~240V-1ph-50Hz) Cooling

Indoor air entering Temp

Outdoor air entering Temp(DB) 70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC 115 0F/46ºC

70 0F/21ºC DB

59 0F/15ºC WB

Tcc(kW) 7.31 6.96 6.60 6.32 6.11 Scc(kW) 5.41 5.36 5.28 5.31 5.19

S/T 0.74 0.77 0.80 0.84 0.85 PW(kW) 2.49 2.70 2.82 2.91 3.03

75 0F/24ºC DB

63 0F/17ºC WB

Tcc(kW) 7.53 7.17 6.82 6.39 6.25 Scc(kW) 5.64 5.59 5.52 5.37 5.31

S/T 0.75 0.78 0.81 0.84 0.85 PW(kW) 2.64 2.82 2.94 3.09 3.21

80 0F/27ºC DB

66 0F/19ºC WB

Tcc(kW) 7.67 7.31 7.10 6.60 6.46 Scc(kW) 5.67 5.63 5.54 5.41 5.36

S/T 0.74 0.77 0.78 0.82 0.83 PW(kW) 2.70 2.85 3.00 3.15 3.27

84 0F/29ºC DB

66 0F/19ºC WB

Tcc(kW) 7.74 7.38 7.24 6.67 6.50 Scc(kW) 6.50 6.28 6.23 6.07 6.11

S/T 0.84 0.85 0.86 0.91 0.94 PW(kW) 2.76 2.91 3.03 3.21 3.39

90 0F/32ºC DB

73 0F/23ºC WB

Tcc(kW) 7.81 7.53 7.38 6.82 6.60 Scc(kW) 6.64 6.55 6.50 6.34 6.34

S/T 0.85 0.87 0.88 0.93 0.96 PW(kW) 2.82 2.94 3.15 3.27 3.45

Page 33: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

32

Heating Outdoor DB (°C) 24 7 2 -5 -7 outdoor WB (°C) 18 6 1 -6 -8

Evap. Entering Air DB TC KW TC KW TC KW TC KW TC KW (°C) Capacity (kW) 15 10.05 2.80 8.12 2.41 6.65 2.07 6.03 1.94 5.64 1.84 20 9.74 3.06 7.73 2.59 6.26 2.28 5.87 2.10 5.41 1.97 27 9.12 3.24 7.27 2.80 5.87 2.46 5.72 2.28 5.10 2.12

8.1.7. MRA-36HW-Q (220~240V-1ph-50Hz) Cooling

Indoor air entering Temp

Outdoor air entering Temp(DB) 70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC 115 0F/46ºC

70 0F/21ºC DB

59 0F/15ºC WB

Tcc(kW) 10.82 10.29 9.77 9.35 9.03 Scc(kW) 8.00 7.92 7.81 7.85 7.68

S/T 0.74 0.77 0.80 0.84 0.85 PW(kW) 3.74 4.05 4.23 4.37 4.55

75 0F/24ºC DB

63 0F/17ºC WB

Tcc(kW) 11.13 10.61 10.08 9.45 9.24 Scc(kW) 8.35 8.27 8.16 7.94 7.85

S/T 0.75 0.78 0.81 0.84 0.85 PW(kW) 3.96 4.23 4.41 4.64 4.82

80 0F/27ºC DB

66 0F/19ºC WB

Tcc(kW) 11.34 10.82 10.50 9.77 9.56 Scc(kW) 8.39 8.33 8.19 8.01 7.93

S/T 0.74 0.77 0.78 0.82 0.83 PW(kW) 4.05 4.28 4.50 4.73 4.91

84 0F/29ºC DB

66 0F/19ºC WB

Tcc(kW) 11.45 10.92 10.71 9.87 9.61 Scc(kW) 9.61 9.28 9.21 8.98 9.03

S/T 0.84 0.85 0.86 0.91 0.94 PW(kW) 4.14 4.37 4.55 4.82 5.09

90 0F/32ºC DB

73 0F/23ºC WB

Tcc(kW) 11.55 11.13 10.92 10.08 9.77 Scc(kW) 9.82 9.68 9.61 9.37 9.37

S/T 0.85 0.87 0.88 0.93 0.96 PW(kW) 4.23 4.41 4.73 4.91 5.18

Heating Outdoor DB (°C) 24 7 2 -5 -7 outdoor WB (°C) 18 6 1 -6 -8

Evap. Entering Air DB TC KW TC KW TC KW TC KW TC KW (°C) Capacity (kW) 15 15.08 4.32 12.18 3.72 9.98 3.20 9.05 3.00 8.47 2.84 20 14.62 4.72 11.60 4.00 9.40 3.52 8.82 3.24 8.12 3.04 27 13.69 5.00 10.90 4.32 8.82 3.80 8.58 3.52 7.66 3.28

8.1.8. MRA-36HW-R (380~415V-3ph-50Hz) Cooling

Indoor air entering Temp

Outdoor air entering Temp(DB) 70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC 115 0F/46ºC

70 0F/21ºC DB

59 0F/15ºC WB

Tcc(kW) 10.82 10.29 9.77 9.35 9.03 Scc(kW) 8.00 7.92 7.81 7.85 7.68

S/T 0.74 0.77 0.80 0.84 0.85 PW(kW) 3.65 3.96 4.14 4.27 4.44

75 0F/24ºC DB

63 0F/17ºC WB

Tcc(kW) 11.13 10.61 10.08 9.45 9.24 Scc(kW) 8.35 8.27 8.16 7.94 7.85

S/T 0.75 0.78 0.81 0.84 0.85 PW(kW) 3.87 4.14 4.31 4.53 4.71

80 0F/27ºC DB

66 0F/19ºC WB

Tcc(kW) 11.34 10.82 10.50 9.77 9.56 Scc(kW) 8.39 8.33 8.19 8.01 7.93

S/T 0.74 0.77 0.78 0.82 0.83 PW(kW) 3.96 4.18 4.40 4.62 4.80

84 0F/29ºC DB

66 0F/19ºC WB

Tcc(kW) 11.45 10.92 10.71 9.87 9.61 Scc(kW) 9.61 9.28 9.21 8.98 9.03

S/T 0.84 0.85 0.86 0.91 0.94 PW(kW) 4.05 4.27 4.44 4.71 4.97

90 0F/32ºC DB

73 0F/23ºC WB

Tcc(kW) 11.55 11.13 10.92 10.08 9.77 Scc(kW) 9.82 9.68 9.61 9.37 9.37

S/T 0.85 0.87 0.88 0.93 0.96 PW(kW) 4.14 4.31 4.62 4.80 5.06

Heating Outdoor DB (°C) 24 7 2 -5 -7 outdoor WB (°C) 18 6 1 -6 -8

Evap. Entering Air DB TC KW TC KW TC KW TC KW TC KW (°C) Capacity (kW) 15 15.08 4.00 12.18 3.44 9.98 2.96 9.05 2.78 8.47 2.63 20 14.62 4.37 11.60 3.70 9.40 3.26 8.82 3.00 8.12 2.81 27 13.69 4.63 10.90 4.00 8.82 3.52 8.58 3.26 7.66 3.03

Page 34: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

33

8.1.9. MRA-48HW-R (380~415V-3ph-50Hz) Cooling

Indoor air entering Temp Outdoor air entering Temp(DB)

70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC 115 0F/46ºC

70 0F/21ºC DB

59 0F/15ºC WB

Tcc(kW) 14.42 13.72 13.02 12.46 12.04 Scc(kW) 10.67 10.56 10.42 10.47 10.23

S/T 0.74 0.77 0.80 0.84 0.85 PW(kW) 4.57 4.95 5.17 5.34 5.56

75 0F/24ºC DB

63 0F/17ºC WB

Tcc(kW) 14.84 14.14 13.44 12.60 12.32 Scc(kW) 11.13 11.03 10.89 10.58 10.47

S/T 0.75 0.78 0.81 0.84 0.85 PW(kW) 4.84 5.17 5.39 5.67 5.89

80 0F/27ºC DB

66 0F/19ºC WB

Tcc(kW) 15.12 14.42 14.00 13.02 12.74 Scc(kW) 11.19 11.10 10.92 10.68 10.57

S/T 0.74 0.77 0.78 0.82 0.83 PW(kW) 4.95 5.23 5.50 5.78 6.00

84 0F/29ºC DB

66 0F/19ºC WB

Tcc(kW) 15.26 14.56 14.28 13.16 12.81 Scc(kW) 12.82 12.38 12.28 11.98 12.04

S/T 0.84 0.85 0.86 0.91 0.94 PW(kW) 5.06 5.34 5.56 5.89 6.22

90 0F/32ºC DB

73 0F/23ºC WB

Tcc(kW) 15.40 14.84 14.56 13.44 13.02 Scc(kW) 13.09 12.91 12.81 12.50 12.50

S/T 0.85 0.87 0.88 0.93 0.96 PW(kW) 5.17 5.39 5.78 6.00 6.33

Heating Outdoor DB (°C) 24 7 2 -5 -7 outdoor WB (°C) 18 6 1 -6 -8

Evap. Entering Air DB TC KW TC KW TC KW TC KW TC KW (°C) Capacity (kW) 15 20.11 4.86 16.24 4.19 13.30 3.60 12.07 3.38 11.29 3.20 20 19.49 5.31 15.47 4.50 12.53 3.96 11.76 3.65 10.83 3.42 27 18.25 5.63 14.54 4.86 11.76 4.28 11.45 3.96 10.21 3.69

8.1.10. MRA-60HW-R (380~415V-3ph-50Hz) Cooling

Indoor air entering Temp Outdoor air entering Temp(DB)

70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC 115 0F/46ºC

70 0F/21ºC DB

59 0F/15ºC WB

Tcc(kW) 16.48 15.68 14.88 14.24 13.76 Scc(kW) 12.20 12.07 11.90 11.96 11.70

S/T 0.74 0.77 0.80 0.84 0.85 PW(kW) 5.40 5.85 6.11 6.31 6.57

75 0F/24ºC DB

63 0F/17ºC WB

Tcc(kW) 16.96 16.16 15.36 14.40 14.08 Scc(kW) 12.72 12.60 12.44 12.10 11.97

S/T 0.75 0.78 0.81 0.84 0.85 PW(kW) 5.72 6.11 6.37 6.70 6.96

80 0F/27ºC DB

66 0F/19ºC WB

Tcc(kW) 17.28 16.48 16.00 14.88 14.56 Scc(kW) 12.79 12.69 12.48 12.20 12.08

S/T 0.74 0.77 0.78 0.82 0.83 PW(kW) 5.85 6.18 6.50 6.83 7.09

84 0F/29ºC DB

66 0F/19ºC WB

Tcc(kW) 17.44 16.64 16.32 15.04 14.64 Scc(kW) 14.65 14.14 14.04 13.69 13.76

S/T 0.84 0.85 0.86 0.91 0.94 PW(kW) 5.98 6.31 6.57 6.96 7.35

90 0F/32ºC DB

73 0F/23ºC WB

Tcc(kW) 17.60 16.96 16.64 15.36 14.88 Scc(kW) 14.96 14.76 14.64 14.28 14.28

S/T 0.85 0.87 0.88 0.93 0.96 PW(kW) 6.11 6.37 6.83 7.09 7.48

Heating Outdoor DB (°C) 24 7 2 -5 -7 outdoor WB (°C) 18 6 1 -6 -8

Evap. Entering Air DB TC KW TC KW TC KW TC KW TC KW (°C) Capacity (kW) 15 21.33 6.16 17.23 5.30 14.11 4.56 12.80 4.28 11.98 4.05 20 20.68 6.73 16.41 5.70 13.29 5.02 12.47 4.62 11.49 4.33 27 19.36 7.13 15.43 6.16 12.47 5.42 12.14 5.02 10.83 4.67

Page 35: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

34

8.1.11. MRC-36HW (220~240V-1ph-50Hz) Cooling

Heating

Page 36: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

35

8.1.12. MRC-36HW-R (380~415V-3ph-50Hz) Cooling

Heating

Page 37: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

36

8.1.13. MRC-48HW-R (380~415V-3ph-50Hz) Cooling

Heating

Page 38: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

37

8.1.14. MRC-60HW-R (380~415V-3ph-50Hz) Cooling

Heating

Page 39: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

38

8.2. 60HZ (MRA/MRC) 8.2.1. MRA-24CW (208~230V-1Ph-60Hz)

Indoor air entering Temp Outdoor air entering Temp(DB)

70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC

70 0F/21ºC DB 59 0F/15ºC WB

Tcc(kW) 7.31 6.96 6.6 6.32 Scc(kW) 5.41 5.36 5.28 5.31

S/T 0.74 0.77 0.8 0.84 PW(kW) 2.57 2.79 2.91 3.01

75 0F/24ºC DB 630F/17ºC WB

Tcc(kW) 7.53 7.17 6.82 6.39 Scc(kW) 5.64 5.59 5.52 5.37

S/T 0.75 0.78 0.81 0.84 PW(kW) 2.73 2.91 3.04 3.19

80 0F/26.7ºC DB 66.920F/19.4ºC WB

Tcc(kW) 7.67 7.31 7.1 6.6 Scc(kW) 5.67 5.63 5.54 5.41

S/T 0.74 0.77 0.78 0.82 PW(kW) 2.79 2.95 3.1 3.26

84 0F/29ºC DB 660F/19ºC WB

Tcc(kW) 7.74 7.38 7.24 6.67 Scc(kW) 6.5 6.28 6.23 6.07

S/T 0.84 0.85 0.86 0.91 PW(kW) 2.85 3.01 3.13 3.32

8.2.2. MRA-36CW (208~230V-1Ph-60Hz) Indoor air entering Temp

Outdoor air entering Temp(DB) 70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC

70 0F/21ºC DB 59 0F/15ºC WB

Tcc(kW) 10.82 10.29 9.77 9.35 Scc(kW) 8 7.92 7.81 7.85

S/T 0.74 0.77 0.8 0.84 PW(kW) 3.49 3.78 3.95 4.07

75 0F/24ºC DB 63 0F/17ºC WB

Tcc(kW) 11.13 10.61 10.08 9.45 Scc(kW) 8.35 8.27 8.16 7.94

S/T 0.75 0.78 0.81 0.84 PW(kW) 3.7 3.95 4.12 4.33

80 0F/26.7ºC DB 66.920F/19.4ºC WB

Tcc(kW) 11.34 10.82 10.5 9.77 Scc(kW) 8.39 8.33 8.19 8.01

S/T 0.74 0.77 0.78 0.82 PW(kW) 3.78 3.99 4.2 4.41

84 0F/29ºC DB 66 0F/19ºC WB

Tcc(kW) 11.45 10.92 10.71 9.87 Scc(kW) 9.61 9.28 9.21 8.98

S/T 0.84 0.85 0.86 0.91 PW(kW) 3.86 4.07 4.24 4.49

8.2.3. MRA-48CW (208~230V-1Ph-60Hz) Indoor air entering Temp

Outdoor air entering Temp(DB) 70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC

70 0F/21ºC DB 59 0F/15ºC WB

Tcc(kW) 14.42 13.72 13.02 12.46 Scc(kW) 10.67 10.56 10.42 10.47

S/T 0.74 0.77 0.8 0.84 PW(kW) 4.65 5.04 5.26 5.43

75 0F/24ºC DB 63 0F/17ºC WB

Tcc(kW) 14.84 14.14 13.44 12.6 Scc(kW) 11.13 11.03 10.89 10.58

S/T 0.75 0.78 0.81 0.84 PW(kW) 4.93 5.26 5.49 5.77

80 0F/26.7ºC DB 66.920F/19.4ºC WB

Tcc(kW) 15.12 14.42 14 13.02 Scc(kW) 11.19 11.1 10.92 10.68

S/T 0.74 0.77 0.78 0.82 PW(kW) 5.04 5.32 5.6 5.88

84 0F/29ºC DB 66 0F/19ºC WB

Tcc(kW) 15.26 14.56 14.28 13.16 Scc(kW) 12.82 12.38 12.28 11.98

S/T 0.84 0.85 0.86 0.91 PW(kW) 5.15 5.43 5.66 5.99

Page 40: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

39

8.2.4. MRA-60CW (208~230V-1Ph-60Hz)

Indoor air entering Temp Outdoor air entering Temp(DB)

70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC

70 0F/21ºC DB 59 0F/15ºC WB

Tcc(kW) 16.48 15.68 14.88 14.24 Scc(kW) 12.2 12.07 11.9 11.96

S/T 0.74 0.77 0.8 0.84 PW(kW) 5.06 5.49 5.73 5.92

75 0F/24ºC DB 63 0F/17ºC WB

Tcc(kW) 16.96 16.16 15.36 14.4 Scc(kW) 12.72 12.6 12.44 12.1

S/T 0.75 0.78 0.81 0.84 PW(kW) 5.37 5.73 5.98 6.28

80 0F/26.7ºC DB 66.920F/19.4ºC WB

Tcc(kW) 17.28 16.48 16 14.88 Scc(kW) 12.79 12.69 12.48 12.2

S/T 0.74 0.77 0.78 0.82 PW(kW) 5.49 5.8 6.1 6.41

84 0F/29ºC DB 66 0F/19ºC WB

Tcc(kW) 17.44 16.64 16.32 15.04 Scc(kW) 14.65 14.14 14.04 13.69

S/T 0.84 0.85 0.86 0.91 PW(kW) 5.61 5.92 6.16 6.53

8.2.5. MRA-60CW-D (208~230V-3Ph-60Hz) Indoor air

entering Temp

Outdoor air entering Temp(DB) 70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC 115 0F/46ºC

70 0F/21ºC DB 59 0F/15ºC WB

Tcc(kW) 16.48 15.68 14.88 14.24 13.76 Scc(kW) 12.20 12.07 11.90 11.96 11.70

S/T 0.74 0.77 0.80 0.84 0.85 PW(kW) 4.92 5.34 5.57 5.75 5.99

75 0F/24ºC DB 63 0F/17ºC WB

Tcc(kW) 16.96 16.16 15.36 14.40 14.08 Scc(kW) 12.72 12.60 12.44 12.10 11.97

S/T 0.75 0.78 0.81 0.84 0.85 PW(kW) 5.22 5.57 5.81 6.11 6.35

80 0F/27ºC DB 66 0F/19ºC WB

Tcc(kW) 17.28 16.48 16.00 14.88 14.56 Scc(kW) 12.79 12.69 12.48 12.20 12.08

S/T 0.74 0.77 0.78 0.82 0.83 PW(kW) 5.34 5.63 5.93 6.23 6.46

84 0F/29ºC DB 66 0F/19ºC WB

Tcc(kW) 17.44 16.64 16.32 15.04 14.64 Scc(kW) 14.65 14.14 14.04 13.69 13.76

S/T 0.84 0.85 0.86 0.91 0.94 PW(kW) 5.46 5.75 5.99 6.35 6.70

90 0F/32ºC DB 73 0F/23ºC WB

Tcc(kW) 17.60 16.96 16.64 15.36 14.88 Scc(kW) 14.96 14.76 14.64 14.28 14.28

S/T 0.85 0.87 0.88 0.93 0.96 PW(kW) 5.57 5.81 6.23 6.46 6.82

8.2.6. MRA-60HW-V (208~230V-1Ph-60Hz) Cooling

Indoor air entering Temp

Outdoor air entering Temp(DB) 70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC 115 0F/46ºC 126 0F/52ºC 1290F/54ºC

70 0F/21ºC DB 59 0F/15ºC WB

Tcc(kW) 16.48 15.68 14.88 14.24 13.76 12.96 12.00 Scc(kW) 12.20 12.07 11.90 11.96 11.70 11.40 10.80

S/T 0.74 0.77 0.80 0.84 0.85 0.88 0.90 PW(kW) 5.23 5.67 5.92 6.11 6.36 6.80 7.12

75 0F/24ºC DB 63 0F/17ºC

Tcc(kW) 16.96 16.16 15.36 14.40 14.08 13.28 12.48 Scc(kW) 12.72 12.60 12.44 12.10 11.97 11.69 11.23

S/T 0.75 0.78 0.81 0.84 0.85 0.88 0.90 PW(kW) 5.54 5.92 6.17 6.49 6.74 7.12 7.43

80 0F/27ºC DB 66 0F/19ºC WB

Tcc(kW) 17.28 16.48 16.00 14.88 14.56 13.76 12.96 Scc(kW) 12.79 12.69 12.48 12.20 12.08 11.83 11.28

S/T 0.74 0.77 0.78 0.82 0.83 0.86 0.87 PW(kW) 5.67 5.99 6.30 6.62 6.87 7.06 7.56

84 0F/29ºC DB 66 0F/19ºC WB

Tcc(kW) 17.44 16.64 16.32 15.04 14.64 13.92 13.12 Scc(kW) 14.65 14.14 14.04 13.69 13.76 13.36 12.73

S/T 0.84 0.85 0.86 0.91 0.94 0.96 0.97 PW(kW) 5.80 6.11 6.36 6.74 7.12 7.43 7.75

90 0F/32ºC DB 73 0F/23ºC WB

Tcc(kW) 17.60 16.96 16.64 15.36 14.88 14.40 13.44 Scc(kW) 14.96 14.76 14.64 14.28 14.28 13.97 13.31

S/T 0.85 0.87 0.88 0.93 0.96 0.97 0.99 PW(kW) 5.92 6.17 16.00 6.87 7.25 7.75 7.94

Page 41: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

40

Heating Outdoor DB (°C) 24 7 2 -5 -7 outdoor WB (°C) 18 6 1 -6 -8

MODEL Evap. Entering Air DB TC KW TC KW TC KW TC KW TC KW (°C) Capacity (kW)

MKH25 15 25.09 5.62 20.27 4.84 16.60 4.16 15.05 3.90 14.09 3.69 20 24.32 6.14 19.30 5.20 15.63 4.58 14.67 4.21 13.51 3.95 27 22.77 6.50 18.14 5.62 14.67 4.94 14.28 4.58 12.74 4.26

8.2.7. MRA-36CW-V (208~230V-1Ph-60Hz) Outdoor Temperature (DB)

21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC

Indoor Conditions

21ºC DB 15ºC WB

Total capacity[kW] 10.82 10.50 10.08 9.77 9.56 9.14 8.72 Sensitive capacity[kW] 8.00 7.98 7.86 7.81 7.84 7.67 7.58 Input[kW] 3.24 3.39 3.59 3.67 3.71 3.86 4.10

24ºC DB 17ºC WB

Total capacity[kW] 11.13 10.82 10.40 10.08 9.62 9.66 8.93 Sensitive capacity[kW] 8.35 8.33 8.21 8.16 7.98 8.21 7.76 Input[kW] 3.43 3.57 3.73 3.82 3.94 4.10 4.29

27ºC DB 19ºC WB

Total capacity[kW] 11.34 11.03 10.71 10.50 10.08 9.66 9.24 Sensitive capacity[kW] 8.39 8.38 8.25 8.19 8.06 7.92 7.85 Input[kW] 3.51 3.62 3.78 3.90 4.02 4.17 4.29

32ºC DB 23ºC WB

Total capacity[kW] 11.55 11.34 11.03 10.92 10.40 9.87 9.56 Sensitive capacity[kW] 9.82 9.75 9.59 9.61 9.46 9.38 9.17 Input[kW] 3.67 3.74 3.94 4.10 4.17 4.40 4.68

8.2.8. MRA-48CW-V (208~230V-1Ph-60Hz) Outdoor Temperature (DB)

21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC

Indoor Conditions

21ºC DB 15ºC WB

Total capacity[kW] 14.42 14.00 13.44 13.02 12.74 12.18 11.62 Sensitive capacity[kW] 10.67 10.64 10.48 10.42 10.45 10.23 10.11 Input[kW] 4.40 4.61 4.88 4.98 5.04 5.25 5.57

24ºC DB 17ºC WB

Total capacity[kW] 14.84 14.42 13.86 13.44 12.82 12.88 11.90 Sensitive capacity[kW] 11.13 11.10 10.95 10.89 10.64 10.95 10.35 Input[kW] 4.66 4.85 5.07 5.19 5.35 5.57 5.83

27ºC DB 19ºC WB

Total capacity[kW] 15.12 14.70 14.28 14.00 13.44 12.88 12.32 Sensitive capacity[kW] 11.19 11.17 11.00 10.92 10.75 10.56 10.47 Input[kW] 4.77 4.91 5.14 5.30 5.46 5.67 5.83

32ºC DB 23ºC WB

Total capacity[kW] 15.40 15.12 14.70 14.56 13.86 13.16 12.74 Sensitive capacity[kW] 13.09 13.00 12.79 12.81 12.61 12.50 12.23 Input[kW] 4.98 5.09 5.35 5.57 5.67 5.98 6.36

8.2.9. MRA-60CW-V (208~230V-1Ph-60Hz) Outdoor Temperature (DB)

21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC

Indoor Conditions

21ºC DB 15ºC WB

Total capacity[kW] 18.11 17.58 16.88 16.35 16.00 15.29 14.59 Sensitive capacity[kW] 13.40 13.36 13.16 13.08 13.12 12.85 12.69 Input[kW] 5.06 5.31 5.61 5.73 5.80 6.04 6.41

24ºC DB 17ºC WB

Total capacity[kW] 18.63 18.11 17.40 16.88 16.10 16.17 14.94 Sensitive capacity[kW] 13.98 13.94 13.75 13.67 13.37 13.75 13.00 Input[kW] 5.37 5.58 5.84 5.98 6.16 6.41 6.71

27ºC DB 19ºC WB

Total capacity[kW] 18.99 18.46 17.93 17.58 16.88 16.17 15.47 Sensitive capacity[kW] 14.05 14.03 13.81 13.71 13.50 13.26 13.15 Input[kW] 5.49 5.65 5.92 6.10 6.28 6.53 6.71

32ºC DB 23ºC WB

Total capacity[kW] 19.34 18.99 18.46 18.28 17.40 16.53 16.00 Sensitive capacity[kW] 16.44 16.33 16.06 16.09 15.84 15.70 15.36 Input[kW] 5.73 5.86 6.16 6.41 6.53 6.88 7.32

8.2.10. MRA-60CW-D (208~230V-3Ph-60Hz) Outdoor Temperature (DB)

21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC

Indoor Conditions

21ºC DB 15ºC WB

Total capacity[kW] 18.11 17.58 16.88 16.35 16.00 15.29 14.59 Sensitive capacity[kW] 13.40 13.36 13.16 13.08 13.12 12.85 12.69 Input[kW] 5.31 5.57 5.89 6.02 6.08 6.34 6.72

24ºC DB 17ºC WB

Total capacity[kW] 18.63 18.11 17.40 16.88 16.10 16.17 14.94 Sensitive capacity[kW] 13.98 13.94 13.75 13.67 13.37 13.75 13.00 Input[kW] 5.63 5.86 6.12 6.27 6.46 6.72 7.04

27ºC DB 19ºC WB

Total capacity[kW] 18.99 18.46 17.93 17.58 16.88 16.17 15.47 Sensitive capacity[kW] 14.05 14.03 13.81 13.71 13.50 13.26 13.15 Input[kW] 5.76 5.93 6.21 6.40 6.59 6.85 7.04

32ºC DB 23ºC WB

Total capacity[kW] 19.34 18.99 18.46 18.28 17.40 16.53 16.00 Sensitive capacity[kW] 16.44 16.33 16.06 16.09 15.84 15.70 15.36 Input[kW] 6.02 6.14 6.46 6.72 6.85 7.22 7.68

Page 42: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

41

8.2.11. MRA-60HW-V (208~230V-1Ph-60Hz) Cooling

Outdoor Temperature (DB) 21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC

Indoor Conditions

21ºC DB 15ºC WB

Total capacity[kW] 18.11 17.58 16.88 16.35 16.00 15.29 14.59 Sensitive capacity[kW] 13.40 13.36 13.16 13.08 13.12 12.85 12.69 Input[kW] 5.23 5.48 5.80 5.92 5.99 6.24 6.62

24ºC DB 17ºC WB

Total capacity[kW] 18.63 18.11 17.40 16.88 16.10 16.17 14.94 Sensitive capacity[kW] 13.98 13.94 13.75 13.67 13.37 13.75 13.00 Input[kW] 5.54 5.76 6.03 6.17 6.36 6.62 6.93

27ºC DB 19ºC WB

Total capacity[kW] 18.99 18.46 17.93 17.58 16.88 16.17 15.47 Sensitive capacity[kW] 14.05 14.03 13.81 13.71 13.50 13.26 13.15 Input[kW] 5.67 5.84 6.11 6.30 6.49 6.74 6.93

32ºC DB 23ºC WB

Total capacity[kW] 19.34 18.99 18.46 18.28 17.40 16.53 16.00 Sensitive capacity[kW] 16.44 16.33 16.06 16.09 15.84 15.70 15.36 Input[kW] 5.92 6.05 6.36 6.62 6.74 7.11 7.56

Heating Outdoor DB (°C) 24 7 2 -5 Outdoor WB (°C) 18 6 1 -6

Evap. Entering Air DB TC KW TC KW TC KW TC KW (°C) Capacity (kW) 15 25.09 6.05 20.27 5.21 16.60 4.48 15.05 4.20 20 24.32 6.61 19.30 5.60 15.63 4.93 14.67 4.54 27 22.77 7.00 18.14 6.05 14.67 5.32 14.28 4.93

8.2.12. MRC-36CW-V (208~230V-1Ph-60Hz) Outdoor Temperature (DB)

21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC

Indoor Conditions

21ºC DB 15ºC WB

Total capacity[kW] 9.91 9.62 9.24 8.95 8.75 8.37 7.98 Sensitive capacity[kW] 7.33 7.31 7.20 7.16 7.18 7.03 6.95 Input[kW] 3.30 3.46 3.66 3.74 3.78 3.94 4.18

24ºC DB 17ºC WB

Total capacity[kW] 10.20 9.91 9.52 9.24 8.81 8.85 8.18 Sensitive capacity[kW] 7.65 7.63 7.52 7.48 7.31 7.52 7.11 Input[kW] 3.50 3.64 3.81 3.90 4.02 4.18 4.38

27ºC DB 19ºC WB

Total capacity[kW] 10.39 10.10 9.81 9.62 9.24 8.85 8.47 Sensitive capacity[kW] 7.69 7.68 7.56 7.50 7.39 7.26 7.20 Input[kW] 3.58 3.69 3.86 3.98 4.10 4.26 4.38

32ºC DB 23ºC WB

Total capacity[kW] 10.58 10.39 10.10 10.00 9.52 9.04 8.75 Sensitive capacity[kW] 8.99 8.94 8.79 8.80 8.67 8.59 8.40 Input[kW] 3.74 3.82 4.02 4.18 4.26 4.49 4.78

8.2.13. MRC-48CW-V (208~230V-1Ph-60Hz) Outdoor Temperature (DB)

21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC

Indoor Conditions

21ºC DB 15ºC WB

Total capacity[kW] 12.97 12.59 12.09 11.71 11.46 10.95 10.45 Sensitive capacity[kW] 9.60 9.57 9.43 9.37 9.39 9.20 9.09 Input[kW] 4.15 4.35 4.60 4.70 4.75 4.95 5.25

24ºC DB 17ºC WB

Total capacity[kW] 13.35 12.97 12.46 12.09 11.53 11.58 10.70 Sensitive capacity[kW] 10.01 9.99 9.85 9.79 9.57 9.85 9.31 Input[kW] 4.40 4.58 4.79 4.90 5.05 5.25 5.50

27ºC DB 19ºC WB

Total capacity[kW] 13.60 13.22 12.84 12.59 12.09 11.58 11.08 Sensitive capacity[kW] 10.06 10.05 9.89 9.82 9.67 9.50 9.42 Input[kW] 4.50 4.64 4.85 5.00 5.15 5.35 5.50

32ºC DB 23ºC WB

Total capacity[kW] 13.85 13.60 13.22 13.09 12.46 11.83 11.46 Sensitive capacity[kW] 11.77 11.69 11.50 11.52 11.34 11.24 11.00 Input[kW] 4.70 4.80 5.05 5.25 5.35 5.64 6.00

8.2.14. MRC-60CW-V (208~230V-1Ph-60Hz) Outdoor Temperature (DB)

21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC

Indoor Conditions

21ºC DB 15ºC WB

Total capacity[kW] 14.16 13.75 13.20 12.79 12.51 11.96 11.41 Sensitive capacity[kW] 10.48 10.45 10.30 10.23 10.26 10.05 9.93 Input[kW] 5.03 5.27 5.58 5.70 5.76 6.00 6.36

24ºC DB 17ºC WB

Total capacity[kW] 14.58 14.16 13.61 13.20 12.60 12.65 11.69 Sensitive capacity[kW] 10.93 10.91 10.75 10.69 10.45 10.75 10.17 Input[kW] 5.33 5.54 5.80 5.94 6.12 6.36 6.67

27ºC DB 19ºC WB

Total capacity[kW] 14.85 14.44 14.03 13.75 13.20 12.65 12.10 Sensitive capacity[kW] 10.99 10.97 10.80 10.73 10.56 10.37 10.29 Input[kW] 5.45 5.62 5.88 6.06 6.24 6.48 6.67

32ºC DB 23ºC WB

Total capacity[kW] 15.13 14.85 14.44 14.30 13.61 12.93 12.51 Sensitive capacity[kW] 12.86 12.77 12.56 12.58 12.39 12.28 12.01 Input[kW] 5.70 5.82 6.12 6.36 6.48 6.84 7.27

Page 43: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

42

8.2.15. MRC-60CW-X (208~230V-3Ph-60Hz)

Outdoor Temperature (DB)

21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC

Indoor Conditions

21ºC DB 15ºC WB

Total capacity[kW] 14.81 14.38 13.80 13.37 13.09 12.51 11.94

Sensitive capacity[kW] 10.96 10.93 10.77 10.70 10.73 10.51 10.38

Input[kW] 5.06 5.31 5.61 5.73 5.80 6.04 6.41

24ºC DB 17ºC WB

Total capacity[kW] 15.24 14.81 14.24 13.80 13.17 13.23 12.22

Sensitive capacity[kW] 11.43 11.40 11.25 11.18 10.93 11.25 10.63

Input[kW] 5.37 5.58 5.84 5.98 6.16 6.41 6.71

27ºC DB 19ºC WB

Total capacity[kW] 15.53 15.10 14.67 14.38 13.80 13.23 12.65

Sensitive capacity[kW] 11.49 11.48 11.29 11.22 11.04 10.85 10.76

Input[kW] 5.49 5.65 5.92 6.10 6.28 6.53 6.71

32ºC DB 23ºC WB

Total capacity[kW] 15.82 15.53 15.10 14.96 14.24 13.52 13.09

Sensitive capacity[kW] 13.45 13.36 13.14 13.16 12.95 12.84 12.56

Input[kW] 5.73 5.86 6.16 6.41 6.53 6.88 7.32

Page 44: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

43

9. Electrical Data 9.1. Evaporator part

Model Indoor Unit Power Supply IFM Hz Voltage Min. Max. MCA MFA KW FLA

MRA-24CW 50 220-240 198 242 3.5 5 0.27 2.8 MRA-36CW 50 220-240 198 242 3.5 5 0.27 2.8 MRA-36CW 50 380-415 342 418 3.5 5 0.27 2.8 MRA-48CW 50 380-415 342 418 4.8 15 0.35 3.8 MRA-60CW 50 380-415 342 418 4.8 15 0.35 3.8

MRA-24HW-Q 50 220-240 198 264 3.5 35 0.65 2.8 MRA-36HW-Q 50 220-240 198 264 3.5 45 0.65 2.8 MRA-36HW-R 50 380-415 342 456 3.5 30 0.65 2.8 MRA-48HW-R 50 380-415 342 456 4.75 30 0.86 3.8 MRA-60HW-R 50 380-415 342 456 4.75 30 0.86 3.8 MRC-36HW 50 220-240 198 242 1.88 45 0.33 1.5

MRC-36HW-R 50 380-415 342 418 1.88 30 0.33 1.5 MRC-48HW-R 50 380-415 342 418 4.5 30 0.79 3.6 MRC-60HW-R 50 380-415 342 418 4.5 30 0.79 3.6

MRA-24CW 60 208-230 198 242 2.4 5 0.17 1.63 MRA-36CW 60 208-230 198 242 2.4 5 0.17 1.63 MRA-48CW 60 208-230 198 242 3.37 5 0.17 1.63 MRA-60CW 60 208-230 198 242 3.37 5 0.17 1.63

MRA-60CW-D 60 208-230 187 253 3.37 4 0.62 2.69 MRA-60HW-V 60 208-230 188 253 3.37 54 0.62 2.69 MRA-36CW-V 60 208-230 198 242 2.79 35.7 0.27 2.23 MRA-48CW-V 60 208-230 198 242 3.37 48.9 0.35 2.69 MRA-60CW-V 60 208-230 198 242 3.37 57.6 0.35 2.69 MRA-60CW-D 60 208-230 198 242 3.37 37.7 0.35 2.69 MRA-60HW-V 60 208-230 198 242 3.37 64.4 0.35 2.69 MRC-36CW-V 60 208-230 188 253 2.63 34 0.25 2.15 MRC-48CW-V 60 208-230 188 253 3.23 42 0.3 2.85 MRC-60CW-X 60 208-230 188 253 3.5 50 0.5 2.8 MRC-60CW-V 60 208-230 188 253 3.5 30 0.5 2.8

Remark: MCA: Min. Current Amps. (A) MFA: Max. Fuse Amps. (A) KW: Fan Motor Rated Output (kW) FLA: Full Load Amps. (A) IFM: Indoor Fan Motor

Page 45: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

44

9.2. Compressor & condenser part Model Outdoor Unit Power Supply Compressor OFM

Hz Voltage Min. Max MCA TOCA MFA MSC RLA kW FLA MRA-24CW 50 220-240 198 242 18 14.7 40 69 12 0.17 1.2 MRA-36CW 50 220-240 198 242 30 21.9 70 122 19.8 0.17 1.2 MRA-36CW 50 380-415 342 418 10 7.6 25 45 7.3 0.17 1.2 MRA-48CW 50 380-415 342 418 11 9.3 30 52 8.5 0.17 1.2 MRA-60CW 50 380-415 342 418 14 11.1 40 69 9.5 0.17 1.2

MRA-24HW-Q 50 220-240 198 264 18 14.7 40 55 12 0.28 1.24 MRA-36HW-Q 50 220-240 198 264 30 21.9 70 122 17.4 0.28 1.24 MRA-36HW-R 50 380-415 342 456 10 7.6 25 48 6.8 0.28 1.24 MRA-48HW-R 50 380-415 342 456 11 9.3 30 52 7.9 0.28 1.24 MRA-60HW-R 50 380-415 342 456 14 11.1 40 66 9.3 0.26 1.17 MRC-36HW 50 220-240 198 242 25 28 35 19.3 112 0.25 1.2

MRC-36HW-R 50 380-415 342 418 9 10 15 6.9 45 0.25 1.2 MRC-48HW-R 50 380-415 342 418 12 13 18 8.2 55 0.25 1.2 MRC-60HW-R 50 380-415 342 418 14 15 20 9.7 69 0.25 1.2

MRA-24CW 60 208-230 198 242 18 13.4 40 54 12.4 0.27 2.23 MRA-36CW 60 208-230 198 242 22 17.9 50 62 15.3 0.27 2.23 MRA-48CW 60 208-230 198 242 31 25.6 70 130 23 0.35 2.69 MRA-60CW 60 208-230 198 242 39 29.1 90 151 27 0.35 2.69

MRA-60CW-D 60 208-230 187 253 20.5 42.2 50 135 16.4 0.33 1.49 MRA-60HW-V 60 208-230 188 253 39 29.1 90 161 26 0.33 1.5 MRA-36CW-V 60 208-230 198 242 22 23.8 35.7 100 17.9 0.18 2.0 MRA-48CW-V 60 208-230 198 242 30 32.6 48.9 132 23.6 0.18 2.0 MRA-60CW-V 60 208-230 198 242 35 39.1 58.7 150 28.0 0.18 2.0 MRA-60CW-D 60 208-230 198 242 21.4 25.1 37.7 100 15.8 0.18 2.0 MRA-60HW-V 60 208-230 198 242 36 42.9 64.4 150 28.0 0.18 2.0 MRC-36CW-V 60 208-230 188 253 22.5 23.8 35.7 100 17.9 0.18 2.0 MRC-48CW-V 60 208-230 188 253 28.4 30.9 46.3 132 23.6 0.18 2.0 MRC-60CW-X 60 208-230 188 253 35.4 39.7 59.5 150 28.0 0.18 2.0 MRC-60CW-V 60 208-230 188 253 20.6 24.2 36.3 100 15.8 0.18 2.0

Remark: MCA: Min. Current Amps. (A) TOCA: Total Over-current Amps. (A) MFA: Max. Fuse Amps. (A) MSC: Max. Starting Amps. (A) RLA: Rated Locked Amps. (A) OFM: Outdoor Fan Motor. FLA: Full Load Amps. (A) kW: Rated Motor Output (kW)

Page 46: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

45

10. Refrigerant Cycle Diagram and Sound Level 10.1. Cooling Only

Comp

High Pressure Switch

Low Pressure Switch

Condenser

Evaporator

Capillary

10.2. Heat Pump

Comp

High Pressure Switch

Condenser

Evaporator

Capillary

Low Pressure Switch

4-way Valve

Page 47: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

46

11. Operation Limit 11.1. Cooling only

StandardOperation

17°C

43°C

17°C 30°C

Out

door

tem

pera

ture

(°C

DB

)

Indoor temperature(°C WB)

11.2. Heat pump

17 3

-8

24

Out

door

air

tem

pera

ture

Indoor air temperature ℃

Heating

Standard operation

17 30

17

43

Out

door

air

tem

pera

ture

Indoor air temperature ℃

Cooling

Standard operation

Page 48: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

47

12. Installation 12.1. Accessories Standard accessories:

Name of accessories Quantity Outline

Manual 1 ――

Drain outlet 1

Snap ring 1

Drain pipe 1

12.2. General Information Important: read this entire manual before beginning installation procedures. Caution: Bodily injury can result from high voltage electrical components, fast moving fans. For protection from these inherent hazards during installation and servicing, the electrical supply must be is connected.

If operating checks must be performed with the unit operating, it is the technician’s responsibility to recognize these hazards and proceed safely.

Read this manual carefully before attempting to install, operate, or perform maintenance on this unit. Installation and maintenance should be performed by qualified service technicians only.

Inspection 1. Check for damage after the unit is unloaded. Report promptly, to the carrier, any damage found to the unit.

Do not drop the unit.

2. Check the unit's nameplate to determine if the unit is correct for the intended application. The power supply must be adequate for both the unit and all accessories.

Important: Reconnect all grounding devices. All parts of this product capable of conducting electrical current are grounded. If grounding wires, screws, straps, clips nuts or washers used to complete a path to ground are removed for service, they must be returned to their original position and properly fastened.

Page 49: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

48

Notice: Warnings and cautions appear at appropriate locations throughout this manual. Read these carefully.

Warning: Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

Caution: Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices and where property-damage-only accidents could occur.

12.3. Dimensional Data Capacity(Btu/h) A (Height)

24000~36000 630 mm

48000~60000 830 mm

Page 50: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

49

12.4. Locations and Recommendations 12.4.1. Horizontal Airflow Application

These units are designed certified for outdoor installations. These units may be installed directly on wood flooring or on Class A, Class B, or Class C roof covering material.

Location of the unit must allow service clearance around it. Clearance of the unit must be given careful consideration.

Check the handling facilities to ensure the safety of personnel and the unit(s).

Caution must be taken at all times to avoid Personal injuries and/or damage to equipment.

The unit must be mounted level for proper drainage of water through the holes in the base pan.

The unit must not be exposed to direct roof water runoff.

Flexible duct connectors must be of a flame retardant material. All duct work outside of the structure must be insulated and weatherproofed in accordance with local codes.

Holes through exterior walls must be sealed in accordance with local codes.

All fabricated outdoor ducts should be as short as possible. 12.4.2. Downflow Application -- Curb Mounting

The Roof Mounting Curb, or a field fabricated curb must be in place before the unit is hoisted to the roof top.

The Roof Mounting Curb (frame) must be installed on a flat, level section of the roof and provide a level mounting surface for the unit. In addition, be sure to provide sufficient height above the roof to prevent water from entering the unit. Remove covers from the downflow supply and return air openings and place them over the horizontal supply return air openings and secure with sheet metal screws.

Be sure the mounting curb spans structural members (trusses) of the roof, thereby providing sufficient support for the weight of the unit, the curb, the duct(s), and any factory or field installed accessories.

Be sure the hole in the structure for the ducts is large enough to accommodate the fabricated ducts and the insulation surrounding them.

These units are designed certified for outdoor installation. These units may be installed directly on wood flooring or on Class A, Class B, or Class C roof covering material.

Location of the unit must allow for service clearance around it. Clearance of the unit must be given careful consideration.

Check the handling facilities to ensure the safety of personnel and the unit(s).

Caution must be taken at all times to avoid personal injuries and/or damage to the equipment.

The unit must be mounted level for proper drainage of water through the holes in the base pan.

The unit must not be exposed to direct roof water runoff.

Flexible duct connectors must be of a flame retardant material. All duct work outside of the structure must be insulated and weatherproofed in accordance with local codes.

Roof flashing must be installed to seal the roof curb cavity and must conform to local building codes.

All fabricated outdoor ducts should be as short as possible.

12.4.3. Clearances The recommended clearances for single-unit installations are illustrated in Figure 1. These minimum requirements are not only an important consideration when determining unit placement, but they are also essential to ensure adequate serviceability, maximum capacity, and peak operating efficiency.

Any reduction of the unit clearances indicated in these illustrations may result in condenser coil starvation or the recirculation of warm condenser air. Actual clearances which appear to be inadequate should be reviewed with a local engineer.

Page 51: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

50

See the unit's nameplate for the absolute minimum clearance between the unit and any combustible surface(s).

12.5. Installation 12.5.1. Rooftop Units

For roof top applications using a field fabricated frame and ducts, use the following procedure:

The frame must be located and secured by bolting or welding to the roof. Flashing is required.

The hole in the roof must be prepared in advance of installing the unit.

Secure the ducts to the roof.

Place the unit on the frame or roof curb.

Secure the unit to the frame or roof curb.

Insulate any ductwork outside of the structure with at least two (2) inches of insulation and then weatherproof. There must be a weatherproof seal where the duct enters the structure.

Complete the installation according to the instructions in the following sections of this manual.

Figure 2 Typical rooftop application with frame

Typical rooftop application with frame:

Remove covers from the downflow supply and return air openings and place them over the horizontal supply return air openings and secure with sheet metal screws.

Figure 3 Typical rooftop application with frame

Page 52: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

51

12.5.2. Ground Level -- Horizontal Units For ground level installations, the unit should be positioned on a pad the size of the unit or larger. The unit must be level on the pad. The pad must not come in contact with the structure. Be sure the outdoor portion of the supply and return air ducts are as short as possible.

Proceed with the installation as follows:

Place the unit on the pad.

Attach the supply and return air ducts to the unit.

Insulate any ductwork outside of the structure with at least 2 inches of insulation and weatherproof. There must be a weatherproof seal where the duct enters the structure.

Complete the installation according to the instructions in the following sections of this manual.

Figure 4 Typical ground level application

12.5.3. Condensate Drain Piping Twist drain outlet into drain connection hole, sheathe drain pipe, lock in the snap ring.

Figure 5 Condensate drain piping

12.5.4. Ductwork 12.5.4.1. Attaching Horizontal Ductwork to Unit

All conditioned air ductwork should be insulated to minimize heating and cooling duct losses. Use a minimum of two (2) inches of insulation with a vapor barrier. The outside ductwork must be weatherproofed between the unit and the building. When attaching ductwork to a horizontal unit, provide a flexible watertight connection to prevent noise transmission from the unit to the ducts. The flexible connection must be indoors and made out of heavy canvas. Note: Do not draw the canvas taut between the solid ducts.

Page 53: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

52

12.5.4.2. Attaching Downflow Ductwork to Roof Curb

Supply and return air flanges are provided on the roof curb for easy duct installation. All ductwork must be run and attached to the curb before the unit is set into place.

Follow these guidelines for ductwork construction:

Connections to the unit should be made with three-inch canvas connectors to minimize noise and vibration transmission.

Elbows with turning vanes or splitters are recommended to minimize air noise and resistance.

The first elbow in the ductwork leaving the unit should be no closer than two feet from the unit, to minimize noise and resistance.

12.6. Electrical Wiring Electrical Power It is important that proper electrical power be available for the unit. Voltage variation should remain within the limits stamped on the unit nameplate. Disconnect Switch Provide an approved weatherproof disconnect either on the side of the unit or within close proximity and within sight of the unit. Over Current Protection The branch circuit feeding the unit must be protected as shown on the unit rating plate. Power Wiring The power supply lines must be run in weather tight conduit to the disconnect and into the bottom of the unit control box. Provide strain relief for all conduits with suitable connectors. Provide flexible conduit supports whenever vibration transmission may cause a noise problem within the building structure. Be sure all connections are made tight. Control Wiring (Class II) Low voltage control wiring should not be run in conduit with power wiring unless Class 1 wire of proper voltage rating is used. Make connections as shown on the unit wiring diagram. Do not short thermostat wires since this will damage the control transformer. Important: Upon completion of wiring check all electrical connections, including factory wiring within the unit, make sure all connections are tight. Replace and secure all electrical box covers and access doors before leaving the unit or turning on the power to the unit.

Page 54: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

53

Note

Knock down the control box access panel, first twist off screws and then up it, the control box access panel is getting out.

12.7. Start–Up Packaging and Components n Is the unit properly located and level with the proper clearance?

n Is the duct work correctly sized, run, taped, insulated , and weatherproofed with proper unit arrangement? See Ductwork Installation section.

n Is the wiring properly sized and run according to the unit wiring diagram?

n Are all the wiring connections, including those in the unit, tight?

n Has the unit been properly grounded and fused with the recommended fuse size? See Wiring Data.

n Have the air conditioning systems been checked at the service ports for charge and leak tested if necessary?

n Does the condenser fan and indoor blower turn free without rubbing, and are they tight on the shafts?

n Has the indoor blower speed been determined and the proper speed been set? See the Unit Wiring Diagram.

n Are all covers and access panels in place to prevent air loss and safety hazards?

Starting the Unit in the Cooling Mode Caution:

Before starting the system on the cooling cycle, turn the thermostat switch to OFF and close the unit disconnect switch. This procedure energizes the compressor crankcase heater, vaporizing any liquid refrigerant in the crankcase. This is a precaution against foaming at startup which could damage the compressor bearings.

Allow the heater to operate a minimum of eight (8) hours.

To start the unit in the cooling mode, set the thermostat system switch to COOL and move the thermostat COOL indicator to a setting below room temperature. The condenser (outdoor) fan motor compressor and evaporator (indoor) fan motor will operate automatically.

Voltage

With the compressor operating, check the line voltage at the unit. The voltage should be within the range shown on the unit nameplate.

If low voltage is encountered, check the size and length of the supply line from the main disconnect to the unit. The line may be undersized for the length of the run.

Cooling Shut Down

Place the system selector in the OFF position or reset thermostat at a setting above room temperature.

Do not de-energize the main power disconnect except when unit is to be serviced. Power is required to keep the heat pump compressor warm and boil off refrigerant in the compressor.

Page 55: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

54

12.8. Maintenance Routine Maintenance by Owner You can do some of the periodic maintenance functions for your unit yourself; this includes cleaning the permanent air filters, cleaning the unit cabinet, cleaning the condenser coil, and conducting a general unit inspection on a regular basis

Cleaning the Air Filter 1. Dismantle the air filter.

● Twist of screws and up the plate that is gets out.

● Make the Clasp of air filter from horizontal to vertical.

● The air filter turns 30 degree to out.

Figure 9

2. Clean the air filter (Vacuum cleaner or pure water may be used to clean the air filter. If the dust accumulation is too heavy, please use soft brush and mild detergent to clean it and dry out in cool place).

Figure 10

Page 56: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

55

● The air-in side should face up when using vacuum cleaner.

● The air-in side should face down when using water.

Caution: Do not dry out the air filter under direct sunshine or with fire.

3. Re-install the air filter

Condenser Coil

Unfiltered air circulates through the unit's condenser coil and can cause the coil's surface to become clogged with dust, dirt, etc. To clean the coil, vertically (i.e., with the fins) stroke the coil surface with a soft-bristled brush. Be sure to keep all vegetation away from the condenser coil area.

MAINTENANCE PERFORMED BY SERVICEMAN--COOLING SEASON

To keep your unit operating safely and efficiently, the manufacturer recommends that a qualified serviceman check the entire system at least once each year and any other time that you feel one is needed. Your serviceman should examine these areas of your unit:

● filters

● motors and drive system components

● economizer gaskets (for possible replacement)

● safety controls (for mechanical cleaning)

● electrical components and wiring (for possible replacement and connection tightness)

● condensate drain (for cleaning)

● unit duct connections (to see that they are physically sound and sealed to the unit casing)

● unit mounting support (for structural integrity)

● the unit (for obvious unit deterioration)

Caution

Do not operate the unit without the evaporator fan access panel in place. Reinstall the access panel after performing any maintenance procedures on the fan. Operating the unit without the access panel properly installed may result in severe personal injury or death.

Page 57: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

56

13. System Operation 13.1. LED Display The control would display any fault code that is currently active using the LED. The control will display the fault code, when the LEDS are flashing quickly; there is something wrong with the system. Refer to below table for detail fault code. Function: 1. the compressor and indoor fan will start when the system is energized, outdoor fan starts with compressor 2. When the system is de-energized, the outdoor fan and compressor would close soon, but the indoor fan

would close later. 13.2. Operational Codes:

No. Code LED1(Red) LED2(Yellow) LED3(Green) 1 Standby OFF OFF ON

2 Function ON ON ON

3 Lack of phase

Flash Flash Flash Phase-error

4

T1 sensor failure

Flash Flash Flash High pressure protection

Vent protection

5 T2 sensor failure Flash OFF Flash

6 T3 sensor failure OFF Flash Flash

7 T4 sensor failure ON Flash Flash

8 T2 Evaporator low temp, protection OFF Flash OFF

9 T2 Evaporator high temp, protection Flash ON ON

10 T3 Condenser high temp, protection Flash OFF OFF

11 Wired controller input failure Flash Flash ON

12 Compressor current protection OFF OFF Flash

13 Compressor-inhaling low pressure protection Flash ON Flash

14 Defrost ON Flash Flash

13.3. Low pressure switch The control will detect the status of low pressure switch, which is normally close. If the low pressure switch is open during the first time of power supply, the control will de-energized the compressor. If low pressure switch protection appears 3 times in 20 minutes, the control should be restored by switch off the power supply. The control will ignore the low pressure switch input during the following conditions: defrost operation, 4 minutes following the completion of a defrost cycle, first5minuteofcompressor operation during the heat mode. 13.4. High pressure switch The Unit is equipped with a high-pressure switch that is connected to the mainboard, If the high-pressure switch opens for more than 40 milliseconds, the control will de-energize the compressor and store and display the appropriate fault code. If the pressure switch closes and a thermostat call for compressor operation is present, the control will apply the three-minute anti-short cycle delay timer and start the compressor when the timer expires. 13.5. Temperature sensor The unit has two temperature sensors, which are called T3 and T4, T3 means pipe temperature sensor, T4 means outdoor unit circumstance temperature sensor. When the temperature sensor was damaged, the system would close and the LED would flash. 13.6. Indications of proper operation When the LEDS in lighting states, no matter which one, it is means the system runs properly.

Page 58: Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The protection of compressor High-pressure protection, low-pressure protection, compressor

MCAC-UTSM-2010-15 T1 Condition Rooftop Package

57

14. Wired Controller 14.1. Optional Midea’s wired controller: KJR-12B/DP (T)-E / KJR-25B

KJR-12B/DP (T)-E KJR-25B 14.2. Optional well-known brand thermostat controller: KJR-23B

KJR-23B