Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The...
Transcript of Technical Manualmail4.ansal.com.ar/Documentacion/pdfs/MTBR2.pdf · 2011-03-14 · 4.2.1. The...
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
I
Content 1. MODEL LIST .................................................................................................................................................................... 1
2. EXTERNAL APPEARANCE ........................................................................................................................................... 2
3. MODEL NUMBER NOMENCLATURE .......................................................................................................................... 3
4. FEATURE & BENEFITS ................................................................................................................................................. 4
5. SPECIFICATIONS ........................................................................................................................................................... 5
6. DIMENSIONAL DRAWINGS ........................................................................................................................................ 17
6.1. MRA ................................................................................................................................................................................... 17 6.2. MRC .................................................................................................................................................................................. 18
7. WIRING DIAGRAMS ..................................................................................................................................................... 19
7.1. 50HZ (MRA/MRC) ........................................................................................................................................................... 19 7.2. 60HZ (MRA/MRC) ........................................................................................................................................................... 23
8. PERFORMANCE DATA ................................................................................................................................................ 30
8.1. 50HZ (MRA/MRC) ........................................................................................................................................................... 30 8.2. 60HZ (MRA/MRC) ........................................................................................................................................................... 38
9. ELECTRICAL DATA ..................................................................................................................................................... 43
9.1. EVAPORATOR PART ............................................................................................................................................................ 43 9.2. COMPRESSOR & CONDENSER PART .................................................................................................................................. 44
10. REFRIGERANT CYCLE DIAGRAM AND SOUND LEVEL .................................................................................... 45
10.1. COOLING ONLY .............................................................................................................................................................. 45 10.2. HEAT PUMP .................................................................................................................................................................... 45
11. OPERATION LIMIT ................................................................................................................................................... 46
11.1. COOLING ONLY ............................................................................................................................................................... 46 11.2. HEAT PUMP .................................................................................................................................................................... 46
12. INSTALLATION .......................................................................................................................................................... 47
12.1. ACCESSORIES ................................................................................................................................................................ 47 12.2. GENERAL INFORMATION ................................................................................................................................................ 47 12.3. DIMENSIONAL DATA ....................................................................................................................................................... 48 12.4. LOCATIONS AND RECOMMENDATIONS .......................................................................................................................... 49 12.5. INSTALLATION ................................................................................................................................................................ 50 12.6. ELECTRICAL WIRING ..................................................................................................................................................... 52 12.7. START–UP ..................................................................................................................................................................... 53 12.8. MAINTENANCE ............................................................................................................................................................... 54
13. SYSTEM OPERATION .............................................................................................................................................. 56
14. WIRED CONTROLLER ............................................................................................................................................. 57
Technical Manual (2 - 5 TR)
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
1
1. Model List (50Hz)
Nominal Capacity Model Power Supply Ton Refrigerant Model Name Function V, ph, Hz
2
R22
MRA-24CW
Two way air outlet option
Cooling Only
220~240V, 1Ph~, 50Hz 3 MRA-36CW 3 MRA-36CW
380~415V, 3Ph~, 50Hz 4 MRA-48CW 5 MRA-60CW 2
R22
MRA-24HW-Q
Two way air outlet option
Heat Pump
220~240V, 1Ph~, 50Hz 3 MRA-36HW-Q 3 MRA-36HW-R
380~415V, 3Ph~, 50Hz 4 MRA-48HW-R 5 MRA-60HW-R 3
R22
MRC-36HW
One way air outlet
Heat Pump
220~240V, 1Ph~, 50Hz 3 MRC-36HW-R
380~415V, 3Ph~, 50Hz 4 MRC-48HW-R 5 MRC-60HW-R
(60Hz)
Nominal Capacity Model Power Supply Ton Refrigerant Model Name Function V, ph, Hz
2
R22
MRA-24CW
Two way air outlet option
Cooling Only 208-230V~, 1Ph, 60Hz
3 MRA-36CW 4 MRA-48CW 5 MRA-60CW 5 MRA-60CW-D 208-230V~, 3Ph, 60Hz 5 MRA-60HW-V Heat Pump 208-230V~, 1Ph, 60Hz 3
R22
MRA-36CW-V Two way air outlet option (Copeland
Compressor)
Cooling Only 208-230V~, 1Ph, 60Hz 4 MRA-48CW-V
5 MRA-60CW-V 5 MRA-60CW-D 208-230V~, 3N, 60Hz, 5 MRA-60HW-V Heat Pump 208-230V~, 1Ph, 60Hz 3
R22
MRC-36CW-V
One way air outlet
Cooling Only 208-230V~, 1Ph, 60Hz 4 MRC-48CW-V
5 MRC-60CW-V 5 MRC-60CW-X 208-230V~, 3N, 60Hz,
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
2
2. External Appearance
MRA
MRC
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
3
3. Model Number Nomenclature
M R A 24 C W Q
Power Supply: Q: 220~240V, 1Ph, 50Hz R: 380~415V, 3Ph, 50Hz V: 208~230V, 1Ph, 60Hz D: 208~230V, 3Ph, 60Hz X: 208~230V, 3Ph, 60Hz
W: Wired Controller
Function Code: C: Cooling Only; E: Electric Heater and Cooling H: Cooling and Heating
Cooling Capacity (*1000Btu/h):
Design Code: A: The first design B: The second design C: The third design
Rooftop Package Unit
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
4
4. Feature & Benefits 4.1. The adoption of anticorrosive-box
The reinforced anticorrosion by using galvanization armor plate and coated with man-composed paint. The appearance is stylish and be easy for maintenance. (Has been 1000 hours salt spray test)
4.2. The adoption of credible protection system 4.2.1. The protection of compressor
High-pressure protection, low-pressure protection, compressor current protection and so on the series’ protectors can ensure compressor operating normally. Adopts independent system, except for protections of sequence and wire control output, any protection relate to its corresponding compressor. Once a compressor protection energized, the corresponding compressor will stop, as others working still.
4.2.2. Fan motor The fan motors for evaporator have over-heat protection and over-current protection function. The fan motors for condenser have the temperature controller protection function.
4.3. Energy saving design 4.3.1. High Efficiency Compressor
Using professional compressor, heat exchanger and optimum connection pipe, the compressor can startup under low power input.
4.3.2. Condenser By using high-efficient thin wing, the condenser has high-efficient heat exchanger, the energy waste decreases greatly.
4.3.3. Evaporator By using the high-efficient, super thin wing and inner-whorl copper pipe, the evaporators get the higher capacity and the lower noise level.
4.3.4. The Heat Insulation of indoor unit The heat insulation of indoor unit can availably decrease heat loss.
4.4. Optional collocation 4.4.1. Strong Air Flow
The wind is sent off by exterior high static pressure produced by condenser fan. 4.4.2. Minimum Installation Arrangement
The installation is fast and low cost with the easy installation and ready operation 4.4.3. Pre-Drilled Duct Flange
Flanges are prepared at the supply and return duct connections so that they can reduce duct connection work at site.
4.4.4. Quiet Operation Noise and vibration have been effectively reduced by adopting new style hermetic compressor. The centrifugal fan and fan casing are optimum shaped for efficient and low noise operation.
4.5. Cabinet 4.5.1. Sloped drain pan and drain pipe 4.5.2. Cabinets have forklift and lifting holes for easy transportation 4.5.3. Cabinets have fresh air function, and the filter can be washable. 4.6. Optional supply/return airflow design, from side or bottom, It could be flexibly applied to
multi-position.
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
5
5. Specifications Table 1 Model MRA-24CW MRA-36CW Power supply V-Ph-Hz 220~240V-1-50 220~240V-1-50
Cooling Capacity Btu/h 24000 36000 Input W 3100 4600 Rated current A 14.7 21.9
Max. input consumption W 3900 5800 Max. current A 18 27 Starting current A 30 45
Compressor
Model PH440X3CS-4KUS1 C-SB301H5A Type Rotary Scroll Brand Midea Toshiba SANYO Capacity W 7557/7608±5% 12000/11800±7% Input W 2488/2670±5% 3800/4000±7% Rated current(RLA) A 11.98/13.21±5% 18.5/19.6±7% Locked rotor Amp(LRA) A 62.37±10% 122 Thermal protector INTERNAL INTERNAL Capacitor uF/V 60uF/450V 60uF/450V Refrigerant oil ml 950 1700
Evaporator fan motor
Model YDK270-4V YDK270-4V Type Centrifugal Centrifugal Brand YongAn YongAn Input(hi) W 650±10% 650±10% Capacitor uF 12uF/450V 12uF/450V Number of motors Pieces 1 1 Speed(hi/lo) r/min 1000/850 1000/850
Evaporator coil
a.Number of rows 2 3 b.Tube pitch(a) × row pitch(b) mm 25.4×22 25.4×22 c.Fin spacing mm 1.7 1.7 d.Fin type (code) Hydrophilic aluminium Hydrophilic aluminium
e.Tube outside dia. and type mm Φ9.53 Φ9.53 Inner groove tube Inner groove tube
f.Coil length × height × width mm 547×44×508 547×66×508 g.Number of circuits 5 5
Evaporator part air flow (Hi) m3/h 1700 1700 Evaporator part external static pressure (Hi) Pa 40 40
Condenser fan motor
Model YDK165-6N YDK165-6N Type Axial Axial Brand Weiling Weiling Input W 270±10% 270±10% Capacitor uF 12uF/450V 12uF/450V Number of motors Pieces 1 1 Speed r/min 850±30 850±30
Condenser coil
Number of rows 1 1 Tube pitch(a) ×row pitch(b) mm 25.4 25.4 Fin spacing mm 1.7 1.7 Fin type (code) Non-hydrophilic aluminium Non-hydrophilic aluminium
Tube outside dia.and type mm Φ9.53 Φ9.53 Inner groove tube Inner groove tube
Coil length×height× width mm 1492×22×558.8 1492×22×558.8 Number of circuits 2 2
Condenser part air flow m3/h 4900 4900 Package noise level(Sound pressure) dB(A) 65.4 64.3 Package net dimension(W×H×D) mm 1290×630×1030 1290×630×1030 Package packing dimension (W×H×D) mm 1325×665×1085 1325×665×1085 Package net/gross weight kg 144/147 154/157 Refrigerant type g R22/1800 R22/1400 Throttle type Orifice Orifice Design pressure MPa 2.8/1.2 2.8/1.2 Power wiring mm2 3×4.0 3×4.0 Controller Thermostat controller Thermostat controller Operation temp °C 17-30 17-30 Ambient temp °C 18-43 18-43 Application area m2 23-35 38-56
Notes: 1. Nominal cooling capacities are based on the following conditions:
Indoor temp: 26.7°C DB, 19.4°C WB; Outdoor temp: 35°C DB, 23.9°C WB 2. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
6
Table 2 Model MRA-36CW MRA-48CW MRA-60CW Power supply V-Ph-Hz 380~415V-3-50 380~415V-3-50 380~415V-3-50
Cooling Capacity Btu/h 36000 48000 60000 Input W 4400 5600 6500 Rated current A 7.6 9.3 11
Max. input consumption W 5500 6600 8400 Max. current A 9 11 14 Starting current A 17 25 25
Compressor
Model C-SB303H8A C-SB373H8A C-SB453H8A Type Scroll Scroll Scroll Brand SANYO SANYO SANYO Capacity W 11600±7% 14500±7% 17700±7% Input W 3800±7% 4540±7% 5450±7% Rated current(RLA) A 6.8±7% 7.9±7% 9.3±7% Locked rotor Amp(LRA) A 42-45 52 63-69 Thermal protector INTERNAL INTERNAL INTERNAL Capacitor uF/V 12 uF/450V 12 uF/450V 12 uF/450V Refrigerant oil ml 1700 1700 1700
Evaporator fan motor
Model YDK270-4V YDK350-4V YDK350-4V Type Centrifugal Centrifugal Centrifugal Brand YongAn YongAn YongAn Input W 650±10% 860±10% 860±10% Capacitor uF 12uF/450V 15uF/370-450V 15uF/370-450V Number of motors Pieces 1 1 1 Speed(Hi/Lo) r/min 1000/850 980/810 980/810
Evaporator coil
a.Number of rows 3 3 3 b.Tube pitch(a)×row pitch(b) mm 25.4×22 25.4×22 25.4×22 c.Fin spacing mm 1.7 1.7 1.7 d.Fin type (code) Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium
e.Tube outside dia.and type mm Φ9.53 Φ9.53 Φ9.53 Inner groove tube Inner groove tube Inner groove tube
f.Coil length ×height × width mm 547×66×508 547×66×711.2 547×66×711.2 g.Number of circuits 5 8 8
Evaporator part air flow (Hi) m3/h 1700 2900 2900 Evaporator part external static pressure (Hi) Pa 40 50 50
Condenser fan motor
Model YDK165-6N YDK165-6N YDK165-6N Type Axial Axial Axial Brand Weiling Weiling Weiling Input W 270±10% 270±10% 270±10% Capacitor uF 12uF/450V 12uF/450V 12uF/450V Number of motors Pieces 1 1 1 Speed r/min 850±30 850±30 850±30
Condenser coil
Number of rows 1 1 1 Tube pitch(a) × row pitch(b) mm 25.4 25.4 25.4 Fin spacing mm 1.7 1.7 1.7
Fin type (code) Non-hydrophilic aluminium
Non-hydrophilic aluminium
Non-hydrophilic aluminium
Tube outside dia.and type mm Φ9.53 Φ9.53 Φ9.53 Inner groove tube Inner groove tube Inner groove tube
Coil length×height ×width mm 1492×22×812.8 1476×22×1270 1476×22×762 Number of circuits 2 3 8
Condenser part air flow m3/h 4900 5800 5800 Package noise level (Sound pressure) dB(A) 64.4 65.1 64.3 Package net dimension(W×H×D) mm 1290×630×1030 1290×830×1030 1290×830×1030 Package packing dimension (W×H×D) mm 1325×665×1085 1325×865×1085 1325×865×1085 Package net/gross weight kg 154/157 192/195 192/195 Refrigerant type g R22/1700 R22/2300 R22/2600 Throttle type Orifice Orifice Orifice Design pressure MPa 2.8/1.2 2.8/1.2 2.8/1.2 Connection wiring Power wiring mm2 5×2.5 5×2.5 5×2.5 Controller Thermostat controller Thermostat controller Thermostat controller Operation temp °C 17-30 17-30 17-30 Ambient temp °C 18-43 18-43 18-43 Application area m2 32-48 40-60 46-70 Notes: 1. Nominal cooling capacities are based on the following conditions:
Indoor temp: 26.7°C DB, 19.4°C WB; Outdoor temp: 35°C DB, 23.9°C WB 2. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
7
Table 3 Sale Model MRA-24HW-Q MRA-36HW-Q MRA-36HW-R Power supply V-Ph-Hz 220-240~1-50 220-240~1-50 380-415~3-50
Cooling Capacity Btu/h 24000 36000 36000 Input W 3000 4500 4400 Rated current A 14.5 21.5 7.7
Heating Capacity Btu/h 26400 39600 39600 Input W 2700 4000 3700 Rated current A 13.0 19.3 6.8
Max. input consumption W 4300 5600 5500 Max. current A 21.1 29.2 9.2 Starting current A 30 40 15
Compressor
Model PH440X3CS-4KUS1 C-SB301H5A C-SB303H8A Type ROTARY Scroll Scroll Brand MEIZHI Sanyo Sanyo Supplier Guangdong MEIZHI Dalian Sanyo Dalian Sanyo Capacity Btu/h 25784 39579 39579 Input W 2488 3750 3800 Rated current(RLA) A 11.98 17.4 6.8 Locked rotor Amp(LRA) A 55 122 48 Thermal protector inner inner inner Capacitor uF 60 60 —— Refrigerant oil ml ATOMOS NM56EP ·950 SAY56T.1700 1700
Indoor fan motor
Model YDK270-4V YDK270-4V YDK270-4V Type AC Motor AC Motor AC Motor Brand YongAn YongAn YongAn Input W 650 650 650 Capacitor uF 12 12 12 Speed(hi/lo) r/min 1000/850 1000/850 1000/850
Indoor coil
a.Number of rows 2 3 3 b.Tube pitch(a)x row pitch(b) mm 25.4X22 25.4X22 25.4X22 c.Fin spacing mm 1.7 1.7 1.7 d.Fin type (code) Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium
e.Tube outside dia.and type mm Ф9.53 Ф9.53 Ф9.53 innergroove tube innergroove tube innergroove tube
f.Coil length x height x width mm 547X508X44 547X508X66 547X508X66 g.Number of circuits 5 5 5
Indoor air flow (Hi/Mi/Lo) m3/h 1400 1700 1700 Indoor external static pressure (Hi) Pa 25 40 40 Indoor noise level (Hi/Lo) dB(A) 62.1 61.5 63.2
Indoor unit Dimension (WXHXD) mm 1290X630X1030 1290X630X1030 1290X630X1030 Packing (WXHXD) mm 1325X665X1085 1325X665X1085 1325X665X1085 Net/Gross weight Kg 150/152 160/162 160/162
Outdoor fan motor
Model YDK165-6N YDK165-6N YDK165-6N Brand YongAn/Welling YongAn/Welling YongAn/Welling Input W 270 270 270 Capacitor uF 12 12 12 Speed r/min 850 850 850
Outdoor coil
Number of rows 1 2 2 Tube pitch(a)x row pitch(b) mm 25.4X22 25.4X22 25.4X22 Fin spacing mm 1.7 1.7 1.7 Fin type (code) Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium
Tube outside dia.and type mm Ф9.53 Ф9.53 Ф9.53 innergroove tube innergroove tube innergroove tube
Coil length x height x width mm 1492X558.8X22 1476X558.8X44 1476X558.8X44 Number of circuits 2 2 2
Outdoor air flow m3/h 5400 5400 5400 Outdoor noise level dB(A) 62.1 61.5 63.2
Outdoor unit Dimension(WXHXD) mm 1290X630X1030 1290X630X1030 1290X630X1030 Packing (WXHXD) mm 1325X665X1085 1325X665X1085 1325X665X1085 Net/Gross weight Kg 150/152 160/162 160/162
Refrigerant type g 1800 2900 2700 Throttle type Eva. orifice(060+054) Eva. orifice(077+074) Eva. orifice(080+076) Design pressure MPa 2.8 2.8 2.8
Connection wiring Power wiring mm2 2.5X3 3.3X3 2.0X5 Signal wiring mm2 1.0X4/1.0X5 1.0X4/1.0X5 1.0X4/1.0X5
Controller Honeywell Honeywell Honeywell Operation temp ℃ 17-30 17-30 17-30 Ambient temp ℃ -8-43 -8-43 -8-43 Application area m2 28-47 42-70 42-70 Notes: 1. Nominal cooling capacities are based on the following conditions:
Indoor temp: 26.7°C DB, 19.4°C WB; Outdoor temp: 35°C DB, 23.9°C WB 2. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
8
Table 4 Sale Model MRA-48HW-R MRA-60HW-R Power supply V-Ph-Hz 380-415~3-50 380-415~3-50
Cooling Capacity Btu/h 48000 60000 Input W 5500 6500 Rated current A 9.4 11
Heating Capacity Btu/h 52800 66000 Input W 4500 5700 Rated current A 8.1 9.8
Max. input consumption W 7000 8200 Max. current A 12 14.6 Starting current A 18 20
Compressor
Model C-SB373H8A C-SB453H8A Type Scroll Scroll Brand Sanyo Sanyo Supplier Dalian Sanyo Dalian Sanyo Capacity Btu/h 49474 60392 Input W 4450 5450 Rated current(RLA) A 7.9 9.3 Locked rotor Amp(LRA) A 52 66 Thermal protector inner inner Capacitor uF —— —— Refrigerant oil ml 1700 SAY56T.1700
Indoor fan motor
Model YDK350-4V YDK350-4V Type AC Motor AC Motor Brand YongAn YongAn Input W 860 860 Capacitor uF 15 15 Speed(hi/lo) r/min 980/810 980/810
Indoor coil
a.Number of rows 3 3 b.Tube pitch(a)x row pitch(b) mm 25.4X22 25.4X22 c.Fin spacing mm 1.7 1.7 d.Fin type (code) Hydrophilic aluminium Hydrophilic aluminium
e.Tube outside dia.and type mm Ф9.53 Ф9.53 innergroove tube innergroove tube
f.Coil length x height x width mm 547X711.2X66 547X711.2X66 g.Number of circuits 8 8
Indoor air flow (Hi/Mi/Lo) m3/h 2900 2900 Indoor external static pressure (Hi) Pa 50 50 Indoor noise level (Hi/Lo) dB(A) 62.4 63.3
Indoor unit Dimension (WXHXD) mm 1290X830X1030 1290X830X1030 Packing (WXHXD) mm 1325X865X1085 1325X865X1085 Net/Gross weight Kg 197/200 197/200
Outdoor fan motor
Model YDK165-6N YDK180-6A Brand YongAn/Welling Welling Input W 270 255 Capacitor uF 12 12 Speed r/min 850 930
Outdoor coil
Number of rows 2 2 Tube pitch(a)x row pitch(b) mm 25.4X22 25.4X22 Fin spacing mm 1.7 1.7 Fin type (code) Hydrophilic aluminium Hydrophilic aluminium
Tube outside dia.and type mm Ф9.53 Ф9.53 innergroove tube innergroove tube
Coil length x height x width mm 1476X762X44 1476X762X44 Number of circuits 8 8
Outdoor air flow m3/h 5400 5700 Outdoor noise level dB(A) 62.4 63.3
Outdoor unit Dimension(WXHXD) mm 1290X830X1030 1290X830X1030 Packing (WXHXD) mm 1325X865X1085 1325X865X1085 Net/Gross weight Kg 197/200 197/200
Refrigerant type g 3300 3600 Throttle type Eva. orifice Eva. orifice(112+102) Design pressure MPa 2.8 2.8
Connection wiring Power wiring mm2 2.0X5 2.0X5 Signal wiring mm2 1.0X4/1.0X5 1.0X4/1.0X5
Controller Honeywell Honeywell Operation temp ℃ 17-30 17-30 Ambient temp ℃ -8-43 -8-43 Application area m2 56-93 64-106 Notes: 1. Nominal cooling capacities are based on the following conditions:
Indoor temp: 26.7°C DB, 19.4°C WB; Outdoor temp: 35°C DB, 23.9°C WB 2. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
9
Table 5 Sale Model MRC-36HW MRC-36HW-R Power supply V-Ph-Hz 220-240~, 1, 50 380-415~, 3, 50
Cooling Capacity Btu/h 36000 36000 Input W 4200 4140 Rated current A 20 7.2
Heating Capacity Btu/h 39600 39600 Input W 3350 3455 Rated current A 17.2 6.3
Max. input consumption W 5585 5300 Max. current A 25.6 9.2 Starting current A 108 42
Compressor
Model C-SB301H5A C-SB303H8A Type scroll Scroll Brand SANYO SANYO Supplier Dalian Sanyo Dalian Sanyo Capacity Btu/h 39579 39579 Input W 3750 3800 Rated current(RLA) A 17.4 6.8 Locked rotor Amp(LRA) A 122 48 Thermal protector inner inner Capacitor uF 60 —— Refrigerant oil ml 1700 1700
Indoor fan motor
Model YDK250-6X YDK250-6X Type AcMotor AcMotor Brand YongAn YongAn Input W 370 370 Capacitor uF 12 12 Speed(hi/lo) r/min 770/720 770/720
Indoor coil
a.Number of rows 3 3 b.Tube pitch(a)x row pitch(b) mm 25.4×22 25.4×22 c.Fin spacing mm 1.7 1.7 d.Fin type (code) Hydrophilic aluminium Hydrophilic aluminium
e.Tube outside dia.and type mm Ф9.53 Ф9.53 innergroove tube innergroove tube
f.Coil length x height x width mm 420×711.2×66 420×711.2×66 g.Number of circuits 8 8
Indoor air flow (Hi/Mi/Lo) m3/h 1962 1972 Indoor external static pressure (Hi) Pa 40 40
Outdoor fan motor
Model YDK180-6A YDK180-6A Brand Welling Welling Input W 246 246 Capacitor uF 12 12 Speed r/min 940 940
Outdoor coil
Number of rows 1 1 Tube pitch(a)x row pitch(b) mm 25.4 25.4 Fin spacing mm 1.7 1.7 Fin type (code) Hydrophilic aluminium Hydrophilic aluminium
Tube outside dia.and type mm Ф9.53 Ф9.53 innergroove tube innergroove tube
Coil length x height x width mm 1492×762×22 1492×762×22 Number of circuits 4 4
Outdoor air flow m3/h 6015 6028 Outdoor noise level dB(A) 63.5 64.1
Outdoor unit Dimension(WXHXD) mm 730×830×1102 730×830×1102 Packing (WXHXD) mm 765×855×1152 765×855×1152 Net/Gross weight Kg 158/161 158/161
Refrigerant type g R22: 2200 R22: 2600 Throttle type orifice(095+090) orifice(080+085) Design pressure MPa 2.8 2.8
Connection wiring Power wiring mm2 3.3x 3 2.0x 5 Signal wiring mm2 1.0x 4/1.0x 5 1.0x 4/1.0x 5
Controller Honeywell Honeywell Operation temp ℃ Cooling: 17~32; Heating: 10~27 Cooling: 17~32; Heating: 10~27 Ambient temp ℃ Cooling: 18~43; Heating: -7~24 Cooling: 18~43; Heating: -7~24 Application area m2 42-70 42-70 Notes: 1. Nominal cooling capacities are based on the following conditions:
Indoor temp: 26.7°C DB, 19.4°C WB; Outdoor temp: 35°C DB, 23.9°C WB 2. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
10
Table 6 Sale Model MRC-48HW-R MRC-60HW-R Power supply V-Ph-Hz 380-415~, 3, 50 380-415~, 3, 50
Cooling Capacity Btu/h 48000 60000 Input W 5460 6715 Rated current A 9.2 11.2
Heating Capacity Btu/h 52800 66000 Input W 4500 5450 Rated current A 7.8 9.3
Max. input consumption W 6380 8435 Max. current A 11.8 14.6 Starting current A 48 60
Compressor
Model C-SB373H8A C-SB453H8A Type Scroll Scroll Brand Sanyo Sanyo Supplier Dalian Sanyo Dalian Sanyo Capacity Btu/h 49474 60392 Input W 4450 5450 Rated current(RLA) A 7.2 9.3 Locked rotor Amp(LRA) A 52 66 Thermal protector inner inner Capacitor uF —— —— Refrigerant oil ml 1700 1700
Indoor fan motor
Model YDK400-4 YDK400-4 Type AcMotor AcMotor Brand YongAn YongAn Input W 990 990 Capacitor uF 25 25 Speed(hi/lo) r/min 970/750 970/750
Indoor coil
a.Number of rows 4 4 b.Tube pitch(a)x row pitch(b) mm 25.4×22 25.4×22 c.Fin spacing mm 1.3 1.3 d.Fin type (code) Hydrophilic aluminum Hydrophilic aluminum
e.Tube outside dia.and type mm Ф9.53 Ф9.53 innergroove tube innergroove tube
f.Coil length x height x width mm 420×711.2×88 420×711.2×88 g.Number of circuits 7 7
Indoor air flow (Hi/Mi/Lo) m3/h 2637 2637 Indoor external static pressure (Hi) Pa 50 50
Outdoor fan motor
Model YDK180-6A YDK180-6A Brand Welling Welling Input W 246 246 Capacitor uF 12 12 Speed r/min 940 940
Outdoor coil
Number of rows 2 2 Tube pitch(a)x row pitch(b) mm 25.4×22 25.4×22 Fin spacing mm 1.7 1.7 Fin type (code) Hydrophilic aluminum Hydrophilic aluminum
Tube outside dia.and type mm Ф9.53 Ф9.53 innergroove tube innergroove tube
Coil length x height x width mm (1473+1404)×762×22 (1473+1404)×762×22 Number of circuits 4 4
Outdoor air flow m3/h 5780 5805 Outdoor noise level dB(A) 66.1 66.1
Outdoor unit Dimension(WXHXD) 730×830×1102 730×830×1102 730×830×1102 Packing (WXHXD) 765×855×1152 765×855×1152 765×855×1152 Net/Gross weight 169/172 169/172 171/174
Refrigerant type g R22: 3400 R22: 3600 Throttle type orifice(098+092) orifice(098+092) Design pressure MPa 2.6 2.6
Connection wiring Power wiring mm2 2.0x 5 2.0x 5 Signal wiring mm2 1.0x 4/1.0x 5 1.0x 4/1.0x 5
Controller / / Operation temp ℃ Cooling: 17~32; Heating: 10~27 Cooling: 17~32;Heating: 10~27 Ambient temp ℃ Cooling: 18~43; Heating: -7~24 Cooling: 18~43; Heating: -7~24 Application area m2 56-93 64-106
Notes: 1. Nominal cooling capacities are based on the following conditions:
Indoor temp: 26.7°C DB, 19.4°C WB; Outdoor temp: 35°C DB, 23.9°C WB 2. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
11
Table 7 Model MRA-24CW MRA-36C MRA-48CW MRA-60CW
Power supply V-Ph-Hz 208~230-1-60 208~230-1-60 208~230-1-60 208~230-1-60
Cooling Capacity Btu/h 24000 36000 48000 60000 Input W 3100 4200 5600 6100 Rated current A 13.8 18.1 25.6 29.1
Max. input consumption W 3700 4900 6700 7900 Max. current A 18 21 33 39 Starting current A 27 36 54 60
Compressor
Model PH360X3CS-3KUU1 THK73XC6-U C-SB301H6B C-SB351H6A
Type Rotary Rotary Scroll Scroll Brand Toshiba Shanghai Hitachi Sanyo Sanyo Capacity W 7520/7600±5% 9300 14500±7% 16800~16700±5% Input W 2430/2470±5% 3050 4450±7% 5250~5450±5% Rated current(RLA) A 11.8/10.8±5% 15.3 21.9±7% 26~26.3±5% Locked rotor Amp(LRA) A 44.2/48.9±10% 62A (208V/50Hz) 130 151
Thermal protector Internal over load protector
Internal over load protector
Internal over load protector
Internal over load protector
Capacitor uF 50μF/400 V 60μF/400 V 50μF/440 V 70μF/440 V Crankcase input W -- -- 35 35 Refrigerant oil ml 850 875±20(Initial) 1700 1700
Evaporator fan motor
Model YDK270-6W YDK270-6W YDK350-6W YDK350-6W Drive type Direct Direct Direct Direct Input W 515±10% 515±10% 615±10% 615±10% Capacitor uF 12uF/450V 12uF/450V 12uF/450V 12uF/450V Number of motors Pieces 1 1 1 1 Speed(Hi) r/min 960 960 1000 1000
Evaporator coil
a.Number of rows 2 3 3 3 b.Tube pitch(a)x row pitch(b) mm 25.4×22 25.4×22 25.4×22 25.4×22
c.Fin spacing mm 1.7 1.7 1.7 1.7
d.Fin type (code) Hydrophilic aluminum
Hydrophilic aluminum
Hydrophilic aluminum
Hydrophilic aluminum
e.Tube outside dia.and type mm Ф9.53 Ф9.53 Ф9.53 Ф9.53
Inner groove tube Inner groove tube Inner groove tube Inner groove tube f.Coil length x height x width mm 547×508×44 547×508×66 547×711.2×66 547×711.2×66
g.Number of circuits 5 5 8 8 Evaporator part air flow m3/h 1700 1700 2900 2900 Evaporator part external static pressure Pa 40 40 50 50
Condenser fan motor
Model YDK165-6M YDK165-6M YDK165-6M YDK165-6M Type Centrifugal Centrifugal Centrifugal Centrifugal Drive type Direct Direct Direct Direct Input W 330±10% 330±10% 330±10% 330±10% Capacitor uF 12uF/450V 12uF/450V 12uF/450V 12uF/450V Number of motors Pieces 1 1 1 2 Speed r/min 1040 1040 980 980
Condenser coil
Number of rows 1 1 1 2 Tube pitch(a)x row pitch(b) mm 25.4 25.4 25.4 25.4×22
Fin spacing mm 1.7 1.7 1.7 1.7
Fin type (code) Unhydrophilic aluminum
Unhydrophilic aluminum
Unhydrophilic aluminum
Unhydrophilic aluminum
Tube outside dia.and type mm Ф9.53 Ф9.53 Ф9.53 Ф9.53
Inner groove tube Inner groove tube Inner groove tube Inner groove tube Coil length x height x width mm 1492×558.8×22 1492×558.8×22 1476×1270×22 1476×762×44
Number of circuits 2 2 3 3 Condenser part air flow m3/h 4910 4910 5880 5880 Package noise level (Sound pressure) dB(A) 63.3 65.2 65.8 65.4 Package net dimension(W x H x D) mm 1290×630×1030 1290×630×1030 1290×830×1030 1290×830×1030 Package packing dimension (W x H x D) mm 1325×665×1085 1325×665×1085 1325×865×1085 1325×865×1085 Package Net/Gross weight kg 144/147 154/157 192/195 192/195 Refrigerant type g R22/1600 R22/1800 R22/2900 R22/3000 Throttle type Eva. orifice Eva. orifice Eva. orifice Eva. orifice Design pressure MPa 2.8/1.2 2.8/1.2 2.8/1.2 2.8/1.2 Power wiring mm2 3×4 3×4 3×4 3×6 Drainage pipe diameter mm 20 20 20 20
Controller Thermostat controller
Thermostat controller
Thermostat controller
Thermostat controller
Operation temp ℃ 17—30 17—30 17—30 17—30 Ambient temp ℃ 18—43 18—43 18—43 18—43 Application area m2 23—35 31—46 40—60 46—70
Notes: 1. Nominal cooling capacities are based on the following conditions:
Indoor temp: 26.7°C DB, 19.4°C WB; Outdoor temp: 35°C DB, 23.9°C WB 2. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
12
Table 8 Sale Model MRA-60CW-D MRA-60HW-V
Power supply V-Ph-Hz 208-230~ 3 60 208-230~ 1 60
Cooling Capacity Btu/h 60000 60000 Input W 6007 6300 Rated current A 18.4 29
Heating Capacity Btu/h - 66000 Input W - 5200 Rated current A - 24
Max. input consumption W 7459 7800 Max. current A 23.6 42 Starting current A 40
Compressor
Model C-SB353H6B C-SB351H6A Type Scroll Scroll Brand Sanyo Sanyo Supplier Dalian Sanyo Dalian Sanyo Capacity Btu/h 57322 57322 Input W 5100 5250 Rated current(RLA) A 16.4 26 Locked rotor Amp(LRA) A 135 141 Thermal protector outer Inner Refrigerant oil ml 1700 1700
Indoor fan motor
Model YDK350-6W YDK350-6W Type AC Motor AC Motor Brand YongAn YongAn Input W 615 615 Capacitor uF 12 12 Speed(hi/mi/lo) r/min 980/810 980/810
Indoor coil
a.Number of rows 3 3 b.Tube pitch(a)x row pitch(b) mm 25.4X22 25.4X22 c.Fin spacing mm 1.7 1.7 d.Fin type (code) Hydrophilic aluminium Hydrophilic aluminium
e.Tube outside dia.and type mm Ф9.53 Ф9.53 innergroove tube innergroove tube
f.Coil length x height x width mm 547X711.2X66 547X711.2X66 g.Number of circuits 8 8
Indoor air flow (Hi/Mi/Lo) m3/h 2900/2350 2783 Indoor external static pressure (Hi) Pa 50 50 Indoor noise level (Sound pressure)(Hi/Mi/Lo) dB(A) 62.4 621
Indoor unit Dimension (WxHxD) mm 1290X830X1030 1290X830X1030 Packing (WxHxD) mm 1325X865X1085 1325X865X1085 Net/Gross weight Kg 192/195 197/200
Outdoor fan motor
Model YDK165-6M YDK165-6M Brand YongAn/Welling YongAn/Welling Input W 363 363 Capacitor uF 12 12 Speed r/min 880 880
Outdoor coil
Number of rows 2 2 Tube pitch(a)x row pitch(b) mm 25.4X22 25.4X22 Fin spacing mm 1.7 1.7 Fin type (code) Unhydrophilic aluminium Hydrophilic aluminium
Tube outside dia.and type mm Ф9.53 Ф9.53 innergroove tube innergroove tube
Coil length x height x width mm 1476X762X44 1476X762X44 Number of circuits 8 8
Outdoor air flow m3/h 5880 5980 Outdoor noise level(Sound pressure) dB(A) 62.4 62.1
Outdoor unit Dimension(WxHxD) mm 1290X830X1030 1290X830X1030 Packing (WxHxD) mm 1325X865X1085 1325X865X1085 Net/Gross weight Kg 192/195 197/200
Refrigerant type g R22(2900 ) R22(3500 ) Throttle type Eva. orifice Eva. orifice Design pressure MPa 2.8 2.8
Connection wiring Power wiring mm2 2.5x3 3x10.0 Signal wiring mm2 1.0x3/1.0x4 1.0x4/1.0x5
Controller Honeywell Honeywell Operation temp ℃ 17-30 17-30 Ambient temp ℃ 17-43 17-43 Application area m2 45-68 45-68
Notes: 1. Nominal cooling capacities are based on the following conditions:
Indoor temp: 26.7°C DB, 19.4°C WB; Outdoor temp: 35°C DB, 23.9°C WB 2. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
13
Table 9 Sale Model MRA-36CW-V MRA-48CW-V MRA-60CW-V Power supply V-Ph-Hz 208~230-1-60 208~230-1-60 208~230-1-60
Cooling Capacity Btu/h 36000 48000 60000 Input W 3900 5300 6100 Current A 17.6 24 28
Max. input consumption W 4700 6400 7700 Max. current A 24 34 39.2
Compressor
Model ZR36KC-PFV-522 ZR48KC-PFV-522 ZR57KC-PFV-522 Type Scroll Scroll Scroll Brand Copelond Copelond Copelond Capacity Btu/h 36900 49500 57500 Input W 3350 4400 5200 Rated current(RLA) A 17.9 23.6 28 Locked rotor Amp(LRA) A 100.0 132.0 150 Thermal protector yes yes yes Capacitor uF 40 40 60 Refrigerant oil ml 1200 1200 1824
Indoor fan motor
Model YDK270-6W YDK350-6W YDK350-6W Type Ac Motor Ac Motor Ac Motor Brand YongAn YongAn YongAn Input W 515/425 615/480 615/480 Rated current A 2.23/1.92 2.69/2.17 2.69/2.17 Capacitor uF 12 12 12 Speed(hi/mi/lo) r/min 1040/790 980/810 980/810
Indoor coil
a.Number of rows 3 3 3 b.Tube pitch(a)x row pitch(b) mm 25.4X22 25.4X22 25.4X22 c.Fin spacing mm 1.7 1.7 1.7 d.Fin type (code) Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium
e.Tube outside dia.and type mm Ф9.5 Ф9.5 Ф9.5
innergroove tube innergroove tube innergroove tube f.Coil length x height mm 547X508X66 547X711.2X66 547X711.2X66 g.Number of circuits 5 8 8
Indoor static pressure Pa 50 50 50 Indoor air flow CFM 1100 1800 1800
Outdoor fan motor
Model YDK180-6B YDK180-6B YDK180-6B Type Ac Motor Ac Motor Ac Motor Brand Welling Welling Welling Input W 470 470 470 Rated current A 2 2 2 Capacitor uF 12 12 12 Speed r/min 1000 1000 1000
Outdoor coil
Number of rows 2 2 2 Tube pitch(a)x row pitch(b) mm 25.4X22 25.4X22 25.4X22 Fin spacing mm 1.7 1.7 1.7 Fin type (code) Unhydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium
Tube outside dia.and type mm Ф9.5 Ф9.5 Ф9.5
innergroove tube innergroove tube innergroove tube Coil length x height mm 1492X558.8X44 1476X762X44 1476X762X44 Number of circuits 2 3 5
Outdoor air flow CFM 2900 3500 3500
Unit Dimension(W×H×D) mm 1290X630X1030 1290X830X1030 1290X830X1030 Packing (W×H×D) mm 1325X665X1085 1325X865X1085 1325X865X1085 Net/Gross weight kg 154/157 192/195 192/195
Charged refrigerant type g R22(2100g) R22(2500g) R22(3500g) Throttle type Orifice Orifice Orifice Design pressure MPa 2.8/1.2 2.8/1.2 2.8/1.2
Connection wiring
Power wiring mm2 3×4.0 3×4.0 3×6.0 Signal wiring mm2 3×1.0 3×1.0 3×1.0
Controller Wired controller Wired controller Wired controller Ambient temp ℃ Cooling:21~43 Cooling:21~43 Cooling:21~43
Notes: 1. Nominal cooling capacities are based on the following conditions:
Indoor temp: 26.7°C DB, 19.4°C WB; Outdoor temp: 35°C DB, 23.9°C WB 2. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
14
Table 10 Sale Model MRA-60CW-D MRA-60HW-V Power supply V-Ph-Hz 208~230-3-60 208~230-1-60
Cooling Capacity Btu/h 60000 60000 Input W 6400 6300 Current A 17 29
Heating Capacity Btu/h -- 66000 Input W -- 5600 Current A -- 26
Max. input consumption W 8200 8300 Max. current A 25 43
Compressor
Model 503DH-80B2 ZR57KC-PFV-522 Brand / Type HITICHI / Scroll Copelond / Scroll Capacity Btu/h 61074 57500 Input W 5300 5200 Rated current(RLA) A 15.8 28 Locked rotor Amp(LRA) A 100.0 150 Thermal protector yes yes Capacitor uF -- 60 Refrigerant oil ml 1400 1824
Indoor fan motor
Model YDK350-6W YDK350-6W Type Ac Motor Ac Motor Brand YongAn YongAn Input W 615/480 615/480 Rated current A 2.69/2.17 2.69/2.17 Capacitor uF 12 12 Speed(hi/mi/lo) r/min 980/810 980/810
Indoor coil
a.Number of rows 3 3 b.Tube pitch(a)x row pitch(b) mm 25.4X22 25.4X22 c.Fin spacing mm 1.7 1.7 d.Fin type (code) Hydrophilic aluminium Hydrophilic aluminium
e.Tube outside dia.and type mm Ф9.5 Ф9.5
innergroove tube innergroove tube f.Coil length x height mm 547X711.2X66 547X711.2X66 g.Number of circuits 8 8
Indoor static pressure Pa 50 50 Indoor air flow CFM 1800 1800
Outdoor fan motor
Model YDK180-6B YDK180-6B Type Ac Motor Ac Motor Brand Welling Welling Input W 470 470 Rated current A 2 2 Capacitor uF 12 12 Speed r/min 1000 1000
Outdoor coil
Number of rows 2 2 Tube pitch(a)x row pitch(b) mm 25.4X22 25.4X22 Fin spacing mm 1.7 1.7 Fin type (code) Hydrophilic aluminium Hydrophilic aluminium
Tube outside dia.and type mm Ф9.5 Ф9.5
innergroove tube innergroove tube Coil length x height mm 1476X762X44 1476X762X44 Number of circuits 5 5
Outdoor air flow CFM 3500 3500
Unit Dimension(W×H×D) mm 1290X830X1030 1290X830X1030 Packing (W×H×D) mm 1325X865X1085 1325X865X1085 Net/Gross weight kg 192/195 197/200
Charged refrigerant type g R22(3700g) R22(4000g) Throttle type Orifice Orifice Design pressure MPa 2.8/1.2 2.8/1.2
Connection wiring Power wiring mm2 5×4.0 3×10.0 Signal wiring mm2 3×1.0 4×1.0
Controller Wired controller Wired controller Ambient temp ℃ Cooling:21~43 Cooling:21~43 Heating:-5~24
Notes: 1. Nominal cooling capacities are based on the following conditions:
Indoor temp: 26.7°C DB, 19.4°C WB; Outdoor temp: 35°C DB, 23.9°C WB 2. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
15
Table 11 Sale Model MRC-36CW-V MRC-48CW-V Power supply V-Ph-Hz 208~230-1-60 208~230-1-60
Cooling Capacity Btu/h 36000 48000 Input W 3976 5000 Current A 18 22.7
Max. input consumption W 5000 6200 Max. current A 24 31
Compressor
Model ZR36KC-PFV-522 ZR48KC-PFV-522 Type Scroll Scroll Brand Copelond Copelond Capacity Btu/h 36900 49500 Input W 3350 4400 Rated current(RLA) A 17.9 23.6 Locked rotor Amp(LRA) A 100.0 132.0 Thermal protector yes yes Capacitor uF 40 40 Refrigerant oil ml 1200 1200
Indoor fan motor
Model YDK250-6X YDK300-6X Type Ac Motor Ac Motor Brand YongAn YongAn Input W 500/420 655/450 Rated current A 2.15/1.81 2.85/2.2 Capacitor uF 12 12 Speed(hi/mi/lo) r/min 800/720 980/750
Indoor coil
a.Number of rows 3 4 b.Tube pitch(a)x row pitch(b) mm 25.4×22 25.4×22 c.Fin spacing mm 1.7 1.3 d.Fin type (code) Hydrophilic aluminium Hydrophilic aluminium
e.Tube outside dia.and type mm Ф9.5 Ф9.5 innergroove tube innergroove tube
f.Coil length x height mm 420×711.2×66 420×711.2×88 g.Number of circuits 8 7
Indoor static pressure Pa 50 50 Indoor air flow CFM 1200 1700
Outdoor fan motor
Model YDK180-6B YDK180-6B Type Ac Motor Ac Motor Brand Welling Welling Input W 470 470 Rated current A 2 2 Capacitor uF 12 12 Speed r/min 1000 1000
Outdoor coil
Number of rows 1 2 Tube pitch(a)x row pitch(b) mm 25.4×22 25.4×22 Fin spacing mm 1.7 1.7 Fin type (code) Non-hydrophilic aluminium Non-hydrophilic aluminium
Tube outside dia.and type mm Ф9.5 Ф9.5 innergroove tube innergroove tube
Coil length x height mm 1492×762×22 (1473+1404)×762×44 Number of circuits 4 4
Outdoor air flow CFM 3500 3400
Unit Dimension(W×H×D) mm 1116×830×744 1116×830×744 Packing (W×H×D) mm 1152×870×765 1152×870×765 Net/Gross weight kg 144/147 155/158
Charged refrigerant type g R22 / 1600 R22 / 3000 Throttle type Orifice Orifice Design pressure MPa 2.8/1.2 2.8/1.2
Connection wiring Power wiring mm2 3×4.0 3×4.0 Signal wiring mm2 3×1.0 3×1.0
Controller Wired controller Wired controller Ambient temp ℃ Cooling:21~43 Cooling:21~43
Notes: 1. Nominal cooling capacities are based on the following conditions:
Indoor temp: 26.7°C DB, 19.4°C WB; Outdoor temp: 35°C DB, 23.9°C WB 2. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
16
Table 12 Sale Model MRC-60CW-V MRC-60CW-X Power supply V-Ph-Hz 208~230-1-60 208~230-3-60
Cooling Capacity Btu/h 60000 60000 Input W 6060 6100 Current A 28.3 16.5
Max. input consumption W 7700 7800 Max. current A 40 24.5
Compressor
Model ZR57KC-PFV-522 503DH-80B2 Type Scroll Scroll Brand Copelond HITICHI Capacity Btu/h 57500 61074 Input W 5200 5300 Rated current(RLA) A 28 15.8 Locked rotor Amp(LRA) A 150 100.0 Thermal protector yes yes Capacitor uF 60 / Refrigerant oil ml 1800 1400
Indoor fan motor
Model YDK500-6B YDK500-6B Type Ac Motor Ac Motor Brand YongAn YongAn Input W 620 620 Rated current A 2.8 2.8 Capacitor uF 20 20 Speed(hi/mi/lo) r/min 1080 1080
Indoor coil
a.Number of rows 4 4 b.Tube pitch(a)x row pitch(b) mm 25.4×22 25.4×22 c.Fin spacing mm 1.3 1.3 d.Fin type (code) Hydrophilic aluminium Hydrophilic aluminium
e.Tube outside dia.and type mm Ф9.5 Ф9.5 innergroove tube innergroove tube
f.Coil length x height mm 420×711.2×88 420×711.2×88 g.Number of circuits 7 7
Indoor static pressure Pa 50 50 Indoor air flow CFM 1700 1700
Outdoor fan motor
Model YDK180-6B YDK180-6B Type Ac Motor Ac Motor Brand Welling Welling Input W 470 470 Rated current A 2 2 Capacitor uF 12 12 Speed r/min 1000 1000
Outdoor coil
Number of rows 2 2 Tube pitch(a)x row pitch(b) mm 25.4×22 25.4×22 Fin spacing mm 1.7 1.7 Fin type (code) Non-hydrophilic aluminium Non-hydrophilic aluminium
Tube outside dia.and type mm Ф9.5 Ф9.5 innergroove tube innergroove tube
Coil length x height mm (1473+1404)×762×44 (1473+1404)×762×44 Number of circuits 4 4
Outdoor air flow CFM 3400 3400
Unit Dimension(W×H×D) mm 1116×830×744 1116×830×744 Packing (W×H×D) mm 1152×870×765 1152×870×765 Net/Gross weight kg 166/169 167/170
Charged refrigerant type g R22 / 3400 R22 / 3400 Throttle type Orifice Orifice Design pressure MPa 2.8/1.2 2.8/1.2
Connection wiring Power wiring mm2 3×6.0 5×3.3 Signal wiring mm2 3×1.0 3×1.0
Controller Wired controller Wired controller Ambient temp ℃ Cooling:21~43 Cooling:21~43
Notes: 1. Nominal cooling capacities are based on the following conditions:
Indoor temp: 26.7°C DB, 19.4°C WB; Outdoor temp: 35°C DB, 23.9°C WB 2. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
17
6. Dimensional Drawings 6.1. MRA
Package net dimensions: Width 1290mm; Depth 1030mm; Height as the following chart:
Capacity(Btu/h) A(Height)
24000~36000 630 mm
48000~60000 830 mm
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
18
6.2. MRC
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
19
7. Wiring Diagrams 7.1. 50HZ (MRA/MRC)
7.1.1. MRA-24CW (220~240V-1ph-50Hz)
7.1.2. MRA-36CW (220~240V-1ph-50Hz)
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
20
7.1.3. MRA- 36CW/MRA-48CW/MRA-60CW (380~415V-3ph-50Hz)
7.1.4. MRA-24HW-Q (220~240V-1ph-50Hz)
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
21
7.1.5. MRA-36HW-Q (220~240V-1ph-50Hz)
7.1.6. MRA-36HW-R (380~415V-3ph-50Hz)
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
22
7.1.7. MRA-48HW-R, MRA-60HW-R (380~415V-3ph-50Hz)
7.1.8. MRC-36HW (220~240V-1ph-50Hz)
MAIN CONTROL BOARD
L-PRO
T6
CN4
CN2
T5
CN3CN13
21 22
KM 1A1
31
5
A2246
COMPRED
FAN2
CAP2
FAN1
CAP1
WHIT
E
WHI
TE
Y/G
L N
XT1
CN32 CN34 CN35 CN36 CN6CN15
XP5XS5
XP6XS6
RT3 RT4
CN8
CN7
Y/G
S
CY/G
R
CAP3
REDRED
REDRED
RED
WHITE
BLACK
RED
BLAC
K
BLACK
BLUE
RED BLACK
BLUE
BROWN
CN1
RED
BLAC
K
B C RY G
XT2
BLACK
BLAC
K
BLACK
202096090024
BLACK
1 2
45
CAP4
RELAY
RES
BLACK
BLACK
BLACK
BLACK
WHITERED
24V
RT2
XS1
XP1
XS2XP2
K1 K2
XS3XP3
TRAN SFORME R(24V~)
2-WAY TERMINAL
LOW PRESS SWITCH
AC CON TACT OR
COMP RESSORCOMP
FAN1
RT2~4
XP1~6
XS1~6
CAP1
T5
XT2
WIRING DIAGRAM
CONNECTORS
TEMP.SENSOR
CODE
INDOOR FAN
PART NAME
CONNECTORS
FAN2
CAP2
T6
OUTDOOR FANINDOOR FAN CAP
OUTDOOR FAN CAP
TRAN SFORME R
XT1
L-PR O
KM1
MIDDLE TERMINAL
K2 COMP.TEMP. SWITH
K1 HIGH PRESS SWITCH
CAP5
CAP3 COMP RUNNI NG CAP
CAP4,CAP5 COMP CAP
RELAY RELAY
TO TH E WIRE CO N TROLLER
CTCN49N
CN30
CN33 CN48
4-WAY
VAL
VE
BLUE BLUE
BROWN
BROW
N
BLAC
K
RED
BLU
E
YELL
OW
GREE
N
BROWN
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
23
7.1.9. MRC-36HW-R, MRC-48HW-R, MRC-60HW-R (380~415V-3ph-50Hz)
7.2. 60HZ (MRA/MRC)
7.2.1. MRA-24CW, MRA-36CW, MRA-48CW (208~230V-1ph-60Hz)
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
24
7.2.2. MRA-60CW (208~230V-1ph-60Hz)
7.2.3. MRA-60CW-D (208~230V-3ph-60Hz)
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
25
7.2.4. MRA-60HW-V (208~230V-1ph-60Hz)
7.2.5. MRA-36CW-V
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
26
7.2.6. MRA-48CW-V MRA-60CW-V
7.2.7. MRA-60CW-D
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
27
7.2.8. MRA-60HW-V
7.2.9. MRC-36CW-V
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
28
7.2.10. MRC-48CW-V
7.2.11. MRC-60CW-V
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
29
7.2.12. MRC-60CW-X
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
30
8. Performance Data 8.1. 50HZ (MRA/MRC) 8.1.1. MRA-24CW (220~240V-1ph-50Hz)
Indoor air entering Temp
Outdoor air entering Temp(DB) 70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC
70 0F/21ºC DB
59 0F/15ºC WB
Tcc(kW) 7.31 6.96 6.60 6.32 Scc(kW) 5.41 5.36 5.28 5.31
S/T 0.74 0.77 0.80 0.84 PW(kW) 2.57 2.79 2.91 3.01
75 0F/24ºC DB
63 0F/17ºC WB
Tcc(kW) 7.53 7.17 6.82 6.39 Scc(kW) 5.64 5.59 5.52 5.37
S/T 0.75 0.78 0.81 0.84 PW(kW) 2.73 2.91 3.04 3.19
80 0F/26.7ºC DB
66.92 0F/19.4ºC WB
Tcc(kW) 7.67 7.31 7.10 6.60 Scc(kW) 5.67 5.63 5.54 5.41
S/T 0.74 0.77 0.78 0.82 PW(kW) 2.79 2.95 3.10 3.26
84 0F/29ºC DB
66 0F/19ºC WB
Tcc(kW) 7.74 7.38 7.24 6.67 Scc(kW) 6.50 6.28 6.23 6.07
S/T 0.84 0.85 0.86 0.91 PW(kW) 2.85 3.01 3.13 3.32
90 0F/32ºC DB
73 0F/23ºC WB
Tcc(kW) 7.81 7.53 7.38 6.82 Scc(kW) 6.64 6.55 6.50 6.34
S/T 0.85 0.87 0.88 0.93 PW(kW) 2.91 3.04 3.26 3.38
8.1.2. MRA-36CW (220~240V-1ph-50Hz) Indoor air entering
Temp Outdoor air entering Temp(DB)
70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC
70 0F/21ºC DB
59 0F/15ºC WB
Tcc(kW) 10.82 10.29 9.77 9.35 Scc(kW) 8.00 7.92 7.81 7.85
S/T 0.74 0.77 0.80 0.84 PW(kW) 3.82 4.14 4.32 4.46
75 0F/24ºC DB
63 0F/17ºC WB
Tcc(kW) 11.13 10.61 10.08 9.45 Scc(kW) 8.35 8.27 8.16 7.94
S/T 0.75 0.78 0.81 0.84 PW(kW) 4.05 4.32 4.51 4.74
80 0F/26.7ºC DB
66.92 0F/19.4ºC WB
Tcc(kW) 11.34 10.82 10.50 9.77 Scc(kW) 8.39 8.33 8.19 8.01
S/T 0.74 0.77 0.78 0.82 PW(kW) 4.14 4.37 4.60 4.83
84 0F/29ºC DB
66 0F/19ºC WB
Tcc(kW) 11.45 10.92 10.71 9.87 Scc(kW) 9.61 9.28 9.21 8.98
S/T 0.84 0.85 0.86 0.91 PW(kW) 4.23 4.46 4.65 4.92
90 0F/32ºC DB
73 0F/23ºC WB
Tcc(kW) 11.55 11.13 10.92 10.08 Scc(kW) 9.82 9.68 9.61 9.37
S/T 0.85 0.87 0.88 0.93 PW(kW) 4.32 4.51 4.83 5.01
8.1.3. MRA-36CW (380~415V-3ph-50Hz) Indoor air entering
Temp Outdoor air entering Temp(DB)
70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC 70 0F/21ºC DB
59 0F/15ºC WB
Tcc(kW) 10.82 10.29 9.77 9.35 Scc(kW) 8.00 7.92 7.81 7.85
S/T 0.74 0.77 0.80 0.84 PW(kW) 3.65 3.96 4.14 4.27
75 0F/24ºC DB
63 0F/17ºC WB
Tcc(kW) 11.13 10.61 10.08 9.45 Scc(kW) 8.35 8.27 8.16 7.94
S/T 0.75 0.78 0.81 0.84 PW(kW) 3.87 4.14 4.31 4.53
80 0F/26.7ºC DB
66.92 0F/19.4ºC WB
Tcc(kW) 11.34 10.82 10.50 9.77 Scc(kW) 8.39 8.33 8.19 8.01
S/T 0.74 0.77 0.78 0.82 PW(kW) 3.96 4.18 4.40 4.62
84 0F/29ºC DB
66 0F/19ºC WB
Tcc(kW) 11.45 10.92 10.71 9.87 Scc(kW) 9.61 9.28 9.21 8.98
S/T 0.84 0.85 0.86 0.91 PW(kW) 4.05 4.27 4.44 4.71
90 0F/32ºC DB
73 0F/23ºC WB
Tcc(kW) 11.55 11.13 10.92 10.08 Scc(kW) 9.82 9.68 9.61 9.37
S/T 0.85 0.87 0.88 0.93 PW(kW) 4.14 4.31 4.62 4.80
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
31
8.1.4. MRA-48CW (380~415V-3ph-50Hz) Indoor air entering
Temp Outdoor air entering Temp(DB)
70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC
70 0F/21ºC DB
59 0F/15ºC WB
Tcc(kW) 14.42 13.72 13.02 12.46 Scc(kW) 10.67 10.56 10.42 10.47
S/T 0.74 0.77 0.80 0.84 PW(kW) 4.65 5.04 5.26 5.43
75 0F/24ºC DB
63 0F/17ºC WB
Tcc(kW) 14.84 14.14 13.44 12.60 Scc(kW) 11.13 11.03 10.89 10.58
S/T 0.75 0.78 0.81 0.84 PW(kW) 4.93 5.26 5.49 5.77
80 0F/26.7ºC DB
66.92 0F/19.4ºC WB
Tcc(kW) 15.12 14.42 14.00 13.02 Scc(kW) 11.19 11.10 10.92 10.68
S/T 0.74 0.77 0.78 0.82 PW(kW) 5.04 5.32 5.60 5.88
84 0F/29ºC DB
66 0F/19ºC WB
Tcc(kW) 15.26 14.56 14.28 13.16 Scc(kW) 12.82 12.38 12.28 11.98
S/T 0.84 0.85 0.86 0.91 PW(kW) 5.15 5.43 5.66 5.99
90 0F/32ºC DB
73 0F/23ºC WB
Tcc(kW) 15.40 14.84 14.56 13.44 Scc(kW) 13.09 12.91 12.81 12.50
S/T 0.85 0.87 0.88 0.93 PW(kW) 5.26 5.49 5.88 6.10
8.1.5. MRA-60CW (380~415V-3ph-50Hz) Indoor air entering
Temp Outdoor air entering Temp(DB)
70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC
70 0F/21ºC DB
59 0F/15ºC WB
Tcc(kW) 16.48 15.68 14.88 14.24 Scc(kW) 12.20 12.07 11.90 11.96
S/T 0.74 0.77 0.80 0.84 PW(kW) 5.40 5.85 6.11 6.31
75 0F/24ºC DB
63 0F/17ºC WB
Tcc(kW) 16.96 16.16 15.36 14.40 Scc(kW) 12.72 12.60 12.44 12.10
S/T 0.75 0.78 0.81 0.84 PW(kW) 5.72 6.11 6.37 6.70
80 0F/26.7ºC DB
66.92 0F/19.4ºC WB
Tcc(kW) 17.28 16.48 16.00 14.88 Scc(kW) 12.79 12.69 12.48 12.20
S/T 0.74 0.77 0.78 0.82 PW(kW) 5.85 6.18 6.50 6.83
84 0F/29ºC DB
66 0F/19ºC WB
Tcc(kW) 17.44 16.64 16.32 15.04 Scc(kW) 14.65 14.14 14.04 13.69
S/T 0.84 0.85 0.86 0.91 PW(kW) 5.98 6.31 6.57 6.96
90 0F/32ºC DB
73 0F/23ºC WB
Tcc(kW) 17.60 16.96 16.64 15.36 Scc(kW) 14.96 14.76 14.64 14.28
S/T 0.85 0.87 0.88 0.93 PW(kW) 6.11 6.37 6.83 7.09
8.1.6. MRA-24HW-Q (220~240V-1ph-50Hz) Cooling
Indoor air entering Temp
Outdoor air entering Temp(DB) 70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC 115 0F/46ºC
70 0F/21ºC DB
59 0F/15ºC WB
Tcc(kW) 7.31 6.96 6.60 6.32 6.11 Scc(kW) 5.41 5.36 5.28 5.31 5.19
S/T 0.74 0.77 0.80 0.84 0.85 PW(kW) 2.49 2.70 2.82 2.91 3.03
75 0F/24ºC DB
63 0F/17ºC WB
Tcc(kW) 7.53 7.17 6.82 6.39 6.25 Scc(kW) 5.64 5.59 5.52 5.37 5.31
S/T 0.75 0.78 0.81 0.84 0.85 PW(kW) 2.64 2.82 2.94 3.09 3.21
80 0F/27ºC DB
66 0F/19ºC WB
Tcc(kW) 7.67 7.31 7.10 6.60 6.46 Scc(kW) 5.67 5.63 5.54 5.41 5.36
S/T 0.74 0.77 0.78 0.82 0.83 PW(kW) 2.70 2.85 3.00 3.15 3.27
84 0F/29ºC DB
66 0F/19ºC WB
Tcc(kW) 7.74 7.38 7.24 6.67 6.50 Scc(kW) 6.50 6.28 6.23 6.07 6.11
S/T 0.84 0.85 0.86 0.91 0.94 PW(kW) 2.76 2.91 3.03 3.21 3.39
90 0F/32ºC DB
73 0F/23ºC WB
Tcc(kW) 7.81 7.53 7.38 6.82 6.60 Scc(kW) 6.64 6.55 6.50 6.34 6.34
S/T 0.85 0.87 0.88 0.93 0.96 PW(kW) 2.82 2.94 3.15 3.27 3.45
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
32
Heating Outdoor DB (°C) 24 7 2 -5 -7 outdoor WB (°C) 18 6 1 -6 -8
Evap. Entering Air DB TC KW TC KW TC KW TC KW TC KW (°C) Capacity (kW) 15 10.05 2.80 8.12 2.41 6.65 2.07 6.03 1.94 5.64 1.84 20 9.74 3.06 7.73 2.59 6.26 2.28 5.87 2.10 5.41 1.97 27 9.12 3.24 7.27 2.80 5.87 2.46 5.72 2.28 5.10 2.12
8.1.7. MRA-36HW-Q (220~240V-1ph-50Hz) Cooling
Indoor air entering Temp
Outdoor air entering Temp(DB) 70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC 115 0F/46ºC
70 0F/21ºC DB
59 0F/15ºC WB
Tcc(kW) 10.82 10.29 9.77 9.35 9.03 Scc(kW) 8.00 7.92 7.81 7.85 7.68
S/T 0.74 0.77 0.80 0.84 0.85 PW(kW) 3.74 4.05 4.23 4.37 4.55
75 0F/24ºC DB
63 0F/17ºC WB
Tcc(kW) 11.13 10.61 10.08 9.45 9.24 Scc(kW) 8.35 8.27 8.16 7.94 7.85
S/T 0.75 0.78 0.81 0.84 0.85 PW(kW) 3.96 4.23 4.41 4.64 4.82
80 0F/27ºC DB
66 0F/19ºC WB
Tcc(kW) 11.34 10.82 10.50 9.77 9.56 Scc(kW) 8.39 8.33 8.19 8.01 7.93
S/T 0.74 0.77 0.78 0.82 0.83 PW(kW) 4.05 4.28 4.50 4.73 4.91
84 0F/29ºC DB
66 0F/19ºC WB
Tcc(kW) 11.45 10.92 10.71 9.87 9.61 Scc(kW) 9.61 9.28 9.21 8.98 9.03
S/T 0.84 0.85 0.86 0.91 0.94 PW(kW) 4.14 4.37 4.55 4.82 5.09
90 0F/32ºC DB
73 0F/23ºC WB
Tcc(kW) 11.55 11.13 10.92 10.08 9.77 Scc(kW) 9.82 9.68 9.61 9.37 9.37
S/T 0.85 0.87 0.88 0.93 0.96 PW(kW) 4.23 4.41 4.73 4.91 5.18
Heating Outdoor DB (°C) 24 7 2 -5 -7 outdoor WB (°C) 18 6 1 -6 -8
Evap. Entering Air DB TC KW TC KW TC KW TC KW TC KW (°C) Capacity (kW) 15 15.08 4.32 12.18 3.72 9.98 3.20 9.05 3.00 8.47 2.84 20 14.62 4.72 11.60 4.00 9.40 3.52 8.82 3.24 8.12 3.04 27 13.69 5.00 10.90 4.32 8.82 3.80 8.58 3.52 7.66 3.28
8.1.8. MRA-36HW-R (380~415V-3ph-50Hz) Cooling
Indoor air entering Temp
Outdoor air entering Temp(DB) 70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC 115 0F/46ºC
70 0F/21ºC DB
59 0F/15ºC WB
Tcc(kW) 10.82 10.29 9.77 9.35 9.03 Scc(kW) 8.00 7.92 7.81 7.85 7.68
S/T 0.74 0.77 0.80 0.84 0.85 PW(kW) 3.65 3.96 4.14 4.27 4.44
75 0F/24ºC DB
63 0F/17ºC WB
Tcc(kW) 11.13 10.61 10.08 9.45 9.24 Scc(kW) 8.35 8.27 8.16 7.94 7.85
S/T 0.75 0.78 0.81 0.84 0.85 PW(kW) 3.87 4.14 4.31 4.53 4.71
80 0F/27ºC DB
66 0F/19ºC WB
Tcc(kW) 11.34 10.82 10.50 9.77 9.56 Scc(kW) 8.39 8.33 8.19 8.01 7.93
S/T 0.74 0.77 0.78 0.82 0.83 PW(kW) 3.96 4.18 4.40 4.62 4.80
84 0F/29ºC DB
66 0F/19ºC WB
Tcc(kW) 11.45 10.92 10.71 9.87 9.61 Scc(kW) 9.61 9.28 9.21 8.98 9.03
S/T 0.84 0.85 0.86 0.91 0.94 PW(kW) 4.05 4.27 4.44 4.71 4.97
90 0F/32ºC DB
73 0F/23ºC WB
Tcc(kW) 11.55 11.13 10.92 10.08 9.77 Scc(kW) 9.82 9.68 9.61 9.37 9.37
S/T 0.85 0.87 0.88 0.93 0.96 PW(kW) 4.14 4.31 4.62 4.80 5.06
Heating Outdoor DB (°C) 24 7 2 -5 -7 outdoor WB (°C) 18 6 1 -6 -8
Evap. Entering Air DB TC KW TC KW TC KW TC KW TC KW (°C) Capacity (kW) 15 15.08 4.00 12.18 3.44 9.98 2.96 9.05 2.78 8.47 2.63 20 14.62 4.37 11.60 3.70 9.40 3.26 8.82 3.00 8.12 2.81 27 13.69 4.63 10.90 4.00 8.82 3.52 8.58 3.26 7.66 3.03
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
33
8.1.9. MRA-48HW-R (380~415V-3ph-50Hz) Cooling
Indoor air entering Temp Outdoor air entering Temp(DB)
70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC 115 0F/46ºC
70 0F/21ºC DB
59 0F/15ºC WB
Tcc(kW) 14.42 13.72 13.02 12.46 12.04 Scc(kW) 10.67 10.56 10.42 10.47 10.23
S/T 0.74 0.77 0.80 0.84 0.85 PW(kW) 4.57 4.95 5.17 5.34 5.56
75 0F/24ºC DB
63 0F/17ºC WB
Tcc(kW) 14.84 14.14 13.44 12.60 12.32 Scc(kW) 11.13 11.03 10.89 10.58 10.47
S/T 0.75 0.78 0.81 0.84 0.85 PW(kW) 4.84 5.17 5.39 5.67 5.89
80 0F/27ºC DB
66 0F/19ºC WB
Tcc(kW) 15.12 14.42 14.00 13.02 12.74 Scc(kW) 11.19 11.10 10.92 10.68 10.57
S/T 0.74 0.77 0.78 0.82 0.83 PW(kW) 4.95 5.23 5.50 5.78 6.00
84 0F/29ºC DB
66 0F/19ºC WB
Tcc(kW) 15.26 14.56 14.28 13.16 12.81 Scc(kW) 12.82 12.38 12.28 11.98 12.04
S/T 0.84 0.85 0.86 0.91 0.94 PW(kW) 5.06 5.34 5.56 5.89 6.22
90 0F/32ºC DB
73 0F/23ºC WB
Tcc(kW) 15.40 14.84 14.56 13.44 13.02 Scc(kW) 13.09 12.91 12.81 12.50 12.50
S/T 0.85 0.87 0.88 0.93 0.96 PW(kW) 5.17 5.39 5.78 6.00 6.33
Heating Outdoor DB (°C) 24 7 2 -5 -7 outdoor WB (°C) 18 6 1 -6 -8
Evap. Entering Air DB TC KW TC KW TC KW TC KW TC KW (°C) Capacity (kW) 15 20.11 4.86 16.24 4.19 13.30 3.60 12.07 3.38 11.29 3.20 20 19.49 5.31 15.47 4.50 12.53 3.96 11.76 3.65 10.83 3.42 27 18.25 5.63 14.54 4.86 11.76 4.28 11.45 3.96 10.21 3.69
8.1.10. MRA-60HW-R (380~415V-3ph-50Hz) Cooling
Indoor air entering Temp Outdoor air entering Temp(DB)
70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC 115 0F/46ºC
70 0F/21ºC DB
59 0F/15ºC WB
Tcc(kW) 16.48 15.68 14.88 14.24 13.76 Scc(kW) 12.20 12.07 11.90 11.96 11.70
S/T 0.74 0.77 0.80 0.84 0.85 PW(kW) 5.40 5.85 6.11 6.31 6.57
75 0F/24ºC DB
63 0F/17ºC WB
Tcc(kW) 16.96 16.16 15.36 14.40 14.08 Scc(kW) 12.72 12.60 12.44 12.10 11.97
S/T 0.75 0.78 0.81 0.84 0.85 PW(kW) 5.72 6.11 6.37 6.70 6.96
80 0F/27ºC DB
66 0F/19ºC WB
Tcc(kW) 17.28 16.48 16.00 14.88 14.56 Scc(kW) 12.79 12.69 12.48 12.20 12.08
S/T 0.74 0.77 0.78 0.82 0.83 PW(kW) 5.85 6.18 6.50 6.83 7.09
84 0F/29ºC DB
66 0F/19ºC WB
Tcc(kW) 17.44 16.64 16.32 15.04 14.64 Scc(kW) 14.65 14.14 14.04 13.69 13.76
S/T 0.84 0.85 0.86 0.91 0.94 PW(kW) 5.98 6.31 6.57 6.96 7.35
90 0F/32ºC DB
73 0F/23ºC WB
Tcc(kW) 17.60 16.96 16.64 15.36 14.88 Scc(kW) 14.96 14.76 14.64 14.28 14.28
S/T 0.85 0.87 0.88 0.93 0.96 PW(kW) 6.11 6.37 6.83 7.09 7.48
Heating Outdoor DB (°C) 24 7 2 -5 -7 outdoor WB (°C) 18 6 1 -6 -8
Evap. Entering Air DB TC KW TC KW TC KW TC KW TC KW (°C) Capacity (kW) 15 21.33 6.16 17.23 5.30 14.11 4.56 12.80 4.28 11.98 4.05 20 20.68 6.73 16.41 5.70 13.29 5.02 12.47 4.62 11.49 4.33 27 19.36 7.13 15.43 6.16 12.47 5.42 12.14 5.02 10.83 4.67
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
34
8.1.11. MRC-36HW (220~240V-1ph-50Hz) Cooling
Heating
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
35
8.1.12. MRC-36HW-R (380~415V-3ph-50Hz) Cooling
Heating
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
36
8.1.13. MRC-48HW-R (380~415V-3ph-50Hz) Cooling
Heating
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
37
8.1.14. MRC-60HW-R (380~415V-3ph-50Hz) Cooling
Heating
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
38
8.2. 60HZ (MRA/MRC) 8.2.1. MRA-24CW (208~230V-1Ph-60Hz)
Indoor air entering Temp Outdoor air entering Temp(DB)
70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC
70 0F/21ºC DB 59 0F/15ºC WB
Tcc(kW) 7.31 6.96 6.6 6.32 Scc(kW) 5.41 5.36 5.28 5.31
S/T 0.74 0.77 0.8 0.84 PW(kW) 2.57 2.79 2.91 3.01
75 0F/24ºC DB 630F/17ºC WB
Tcc(kW) 7.53 7.17 6.82 6.39 Scc(kW) 5.64 5.59 5.52 5.37
S/T 0.75 0.78 0.81 0.84 PW(kW) 2.73 2.91 3.04 3.19
80 0F/26.7ºC DB 66.920F/19.4ºC WB
Tcc(kW) 7.67 7.31 7.1 6.6 Scc(kW) 5.67 5.63 5.54 5.41
S/T 0.74 0.77 0.78 0.82 PW(kW) 2.79 2.95 3.1 3.26
84 0F/29ºC DB 660F/19ºC WB
Tcc(kW) 7.74 7.38 7.24 6.67 Scc(kW) 6.5 6.28 6.23 6.07
S/T 0.84 0.85 0.86 0.91 PW(kW) 2.85 3.01 3.13 3.32
8.2.2. MRA-36CW (208~230V-1Ph-60Hz) Indoor air entering Temp
Outdoor air entering Temp(DB) 70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC
70 0F/21ºC DB 59 0F/15ºC WB
Tcc(kW) 10.82 10.29 9.77 9.35 Scc(kW) 8 7.92 7.81 7.85
S/T 0.74 0.77 0.8 0.84 PW(kW) 3.49 3.78 3.95 4.07
75 0F/24ºC DB 63 0F/17ºC WB
Tcc(kW) 11.13 10.61 10.08 9.45 Scc(kW) 8.35 8.27 8.16 7.94
S/T 0.75 0.78 0.81 0.84 PW(kW) 3.7 3.95 4.12 4.33
80 0F/26.7ºC DB 66.920F/19.4ºC WB
Tcc(kW) 11.34 10.82 10.5 9.77 Scc(kW) 8.39 8.33 8.19 8.01
S/T 0.74 0.77 0.78 0.82 PW(kW) 3.78 3.99 4.2 4.41
84 0F/29ºC DB 66 0F/19ºC WB
Tcc(kW) 11.45 10.92 10.71 9.87 Scc(kW) 9.61 9.28 9.21 8.98
S/T 0.84 0.85 0.86 0.91 PW(kW) 3.86 4.07 4.24 4.49
8.2.3. MRA-48CW (208~230V-1Ph-60Hz) Indoor air entering Temp
Outdoor air entering Temp(DB) 70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC
70 0F/21ºC DB 59 0F/15ºC WB
Tcc(kW) 14.42 13.72 13.02 12.46 Scc(kW) 10.67 10.56 10.42 10.47
S/T 0.74 0.77 0.8 0.84 PW(kW) 4.65 5.04 5.26 5.43
75 0F/24ºC DB 63 0F/17ºC WB
Tcc(kW) 14.84 14.14 13.44 12.6 Scc(kW) 11.13 11.03 10.89 10.58
S/T 0.75 0.78 0.81 0.84 PW(kW) 4.93 5.26 5.49 5.77
80 0F/26.7ºC DB 66.920F/19.4ºC WB
Tcc(kW) 15.12 14.42 14 13.02 Scc(kW) 11.19 11.1 10.92 10.68
S/T 0.74 0.77 0.78 0.82 PW(kW) 5.04 5.32 5.6 5.88
84 0F/29ºC DB 66 0F/19ºC WB
Tcc(kW) 15.26 14.56 14.28 13.16 Scc(kW) 12.82 12.38 12.28 11.98
S/T 0.84 0.85 0.86 0.91 PW(kW) 5.15 5.43 5.66 5.99
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
39
8.2.4. MRA-60CW (208~230V-1Ph-60Hz)
Indoor air entering Temp Outdoor air entering Temp(DB)
70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC
70 0F/21ºC DB 59 0F/15ºC WB
Tcc(kW) 16.48 15.68 14.88 14.24 Scc(kW) 12.2 12.07 11.9 11.96
S/T 0.74 0.77 0.8 0.84 PW(kW) 5.06 5.49 5.73 5.92
75 0F/24ºC DB 63 0F/17ºC WB
Tcc(kW) 16.96 16.16 15.36 14.4 Scc(kW) 12.72 12.6 12.44 12.1
S/T 0.75 0.78 0.81 0.84 PW(kW) 5.37 5.73 5.98 6.28
80 0F/26.7ºC DB 66.920F/19.4ºC WB
Tcc(kW) 17.28 16.48 16 14.88 Scc(kW) 12.79 12.69 12.48 12.2
S/T 0.74 0.77 0.78 0.82 PW(kW) 5.49 5.8 6.1 6.41
84 0F/29ºC DB 66 0F/19ºC WB
Tcc(kW) 17.44 16.64 16.32 15.04 Scc(kW) 14.65 14.14 14.04 13.69
S/T 0.84 0.85 0.86 0.91 PW(kW) 5.61 5.92 6.16 6.53
8.2.5. MRA-60CW-D (208~230V-3Ph-60Hz) Indoor air
entering Temp
Outdoor air entering Temp(DB) 70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC 115 0F/46ºC
70 0F/21ºC DB 59 0F/15ºC WB
Tcc(kW) 16.48 15.68 14.88 14.24 13.76 Scc(kW) 12.20 12.07 11.90 11.96 11.70
S/T 0.74 0.77 0.80 0.84 0.85 PW(kW) 4.92 5.34 5.57 5.75 5.99
75 0F/24ºC DB 63 0F/17ºC WB
Tcc(kW) 16.96 16.16 15.36 14.40 14.08 Scc(kW) 12.72 12.60 12.44 12.10 11.97
S/T 0.75 0.78 0.81 0.84 0.85 PW(kW) 5.22 5.57 5.81 6.11 6.35
80 0F/27ºC DB 66 0F/19ºC WB
Tcc(kW) 17.28 16.48 16.00 14.88 14.56 Scc(kW) 12.79 12.69 12.48 12.20 12.08
S/T 0.74 0.77 0.78 0.82 0.83 PW(kW) 5.34 5.63 5.93 6.23 6.46
84 0F/29ºC DB 66 0F/19ºC WB
Tcc(kW) 17.44 16.64 16.32 15.04 14.64 Scc(kW) 14.65 14.14 14.04 13.69 13.76
S/T 0.84 0.85 0.86 0.91 0.94 PW(kW) 5.46 5.75 5.99 6.35 6.70
90 0F/32ºC DB 73 0F/23ºC WB
Tcc(kW) 17.60 16.96 16.64 15.36 14.88 Scc(kW) 14.96 14.76 14.64 14.28 14.28
S/T 0.85 0.87 0.88 0.93 0.96 PW(kW) 5.57 5.81 6.23 6.46 6.82
8.2.6. MRA-60HW-V (208~230V-1Ph-60Hz) Cooling
Indoor air entering Temp
Outdoor air entering Temp(DB) 70 0F/21ºC 82 0F/28ºC 95 0F/35ºC 109 0F/43ºC 115 0F/46ºC 126 0F/52ºC 1290F/54ºC
70 0F/21ºC DB 59 0F/15ºC WB
Tcc(kW) 16.48 15.68 14.88 14.24 13.76 12.96 12.00 Scc(kW) 12.20 12.07 11.90 11.96 11.70 11.40 10.80
S/T 0.74 0.77 0.80 0.84 0.85 0.88 0.90 PW(kW) 5.23 5.67 5.92 6.11 6.36 6.80 7.12
75 0F/24ºC DB 63 0F/17ºC
Tcc(kW) 16.96 16.16 15.36 14.40 14.08 13.28 12.48 Scc(kW) 12.72 12.60 12.44 12.10 11.97 11.69 11.23
S/T 0.75 0.78 0.81 0.84 0.85 0.88 0.90 PW(kW) 5.54 5.92 6.17 6.49 6.74 7.12 7.43
80 0F/27ºC DB 66 0F/19ºC WB
Tcc(kW) 17.28 16.48 16.00 14.88 14.56 13.76 12.96 Scc(kW) 12.79 12.69 12.48 12.20 12.08 11.83 11.28
S/T 0.74 0.77 0.78 0.82 0.83 0.86 0.87 PW(kW) 5.67 5.99 6.30 6.62 6.87 7.06 7.56
84 0F/29ºC DB 66 0F/19ºC WB
Tcc(kW) 17.44 16.64 16.32 15.04 14.64 13.92 13.12 Scc(kW) 14.65 14.14 14.04 13.69 13.76 13.36 12.73
S/T 0.84 0.85 0.86 0.91 0.94 0.96 0.97 PW(kW) 5.80 6.11 6.36 6.74 7.12 7.43 7.75
90 0F/32ºC DB 73 0F/23ºC WB
Tcc(kW) 17.60 16.96 16.64 15.36 14.88 14.40 13.44 Scc(kW) 14.96 14.76 14.64 14.28 14.28 13.97 13.31
S/T 0.85 0.87 0.88 0.93 0.96 0.97 0.99 PW(kW) 5.92 6.17 16.00 6.87 7.25 7.75 7.94
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
40
Heating Outdoor DB (°C) 24 7 2 -5 -7 outdoor WB (°C) 18 6 1 -6 -8
MODEL Evap. Entering Air DB TC KW TC KW TC KW TC KW TC KW (°C) Capacity (kW)
MKH25 15 25.09 5.62 20.27 4.84 16.60 4.16 15.05 3.90 14.09 3.69 20 24.32 6.14 19.30 5.20 15.63 4.58 14.67 4.21 13.51 3.95 27 22.77 6.50 18.14 5.62 14.67 4.94 14.28 4.58 12.74 4.26
8.2.7. MRA-36CW-V (208~230V-1Ph-60Hz) Outdoor Temperature (DB)
21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Indoor Conditions
21ºC DB 15ºC WB
Total capacity[kW] 10.82 10.50 10.08 9.77 9.56 9.14 8.72 Sensitive capacity[kW] 8.00 7.98 7.86 7.81 7.84 7.67 7.58 Input[kW] 3.24 3.39 3.59 3.67 3.71 3.86 4.10
24ºC DB 17ºC WB
Total capacity[kW] 11.13 10.82 10.40 10.08 9.62 9.66 8.93 Sensitive capacity[kW] 8.35 8.33 8.21 8.16 7.98 8.21 7.76 Input[kW] 3.43 3.57 3.73 3.82 3.94 4.10 4.29
27ºC DB 19ºC WB
Total capacity[kW] 11.34 11.03 10.71 10.50 10.08 9.66 9.24 Sensitive capacity[kW] 8.39 8.38 8.25 8.19 8.06 7.92 7.85 Input[kW] 3.51 3.62 3.78 3.90 4.02 4.17 4.29
32ºC DB 23ºC WB
Total capacity[kW] 11.55 11.34 11.03 10.92 10.40 9.87 9.56 Sensitive capacity[kW] 9.82 9.75 9.59 9.61 9.46 9.38 9.17 Input[kW] 3.67 3.74 3.94 4.10 4.17 4.40 4.68
8.2.8. MRA-48CW-V (208~230V-1Ph-60Hz) Outdoor Temperature (DB)
21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Indoor Conditions
21ºC DB 15ºC WB
Total capacity[kW] 14.42 14.00 13.44 13.02 12.74 12.18 11.62 Sensitive capacity[kW] 10.67 10.64 10.48 10.42 10.45 10.23 10.11 Input[kW] 4.40 4.61 4.88 4.98 5.04 5.25 5.57
24ºC DB 17ºC WB
Total capacity[kW] 14.84 14.42 13.86 13.44 12.82 12.88 11.90 Sensitive capacity[kW] 11.13 11.10 10.95 10.89 10.64 10.95 10.35 Input[kW] 4.66 4.85 5.07 5.19 5.35 5.57 5.83
27ºC DB 19ºC WB
Total capacity[kW] 15.12 14.70 14.28 14.00 13.44 12.88 12.32 Sensitive capacity[kW] 11.19 11.17 11.00 10.92 10.75 10.56 10.47 Input[kW] 4.77 4.91 5.14 5.30 5.46 5.67 5.83
32ºC DB 23ºC WB
Total capacity[kW] 15.40 15.12 14.70 14.56 13.86 13.16 12.74 Sensitive capacity[kW] 13.09 13.00 12.79 12.81 12.61 12.50 12.23 Input[kW] 4.98 5.09 5.35 5.57 5.67 5.98 6.36
8.2.9. MRA-60CW-V (208~230V-1Ph-60Hz) Outdoor Temperature (DB)
21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Indoor Conditions
21ºC DB 15ºC WB
Total capacity[kW] 18.11 17.58 16.88 16.35 16.00 15.29 14.59 Sensitive capacity[kW] 13.40 13.36 13.16 13.08 13.12 12.85 12.69 Input[kW] 5.06 5.31 5.61 5.73 5.80 6.04 6.41
24ºC DB 17ºC WB
Total capacity[kW] 18.63 18.11 17.40 16.88 16.10 16.17 14.94 Sensitive capacity[kW] 13.98 13.94 13.75 13.67 13.37 13.75 13.00 Input[kW] 5.37 5.58 5.84 5.98 6.16 6.41 6.71
27ºC DB 19ºC WB
Total capacity[kW] 18.99 18.46 17.93 17.58 16.88 16.17 15.47 Sensitive capacity[kW] 14.05 14.03 13.81 13.71 13.50 13.26 13.15 Input[kW] 5.49 5.65 5.92 6.10 6.28 6.53 6.71
32ºC DB 23ºC WB
Total capacity[kW] 19.34 18.99 18.46 18.28 17.40 16.53 16.00 Sensitive capacity[kW] 16.44 16.33 16.06 16.09 15.84 15.70 15.36 Input[kW] 5.73 5.86 6.16 6.41 6.53 6.88 7.32
8.2.10. MRA-60CW-D (208~230V-3Ph-60Hz) Outdoor Temperature (DB)
21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Indoor Conditions
21ºC DB 15ºC WB
Total capacity[kW] 18.11 17.58 16.88 16.35 16.00 15.29 14.59 Sensitive capacity[kW] 13.40 13.36 13.16 13.08 13.12 12.85 12.69 Input[kW] 5.31 5.57 5.89 6.02 6.08 6.34 6.72
24ºC DB 17ºC WB
Total capacity[kW] 18.63 18.11 17.40 16.88 16.10 16.17 14.94 Sensitive capacity[kW] 13.98 13.94 13.75 13.67 13.37 13.75 13.00 Input[kW] 5.63 5.86 6.12 6.27 6.46 6.72 7.04
27ºC DB 19ºC WB
Total capacity[kW] 18.99 18.46 17.93 17.58 16.88 16.17 15.47 Sensitive capacity[kW] 14.05 14.03 13.81 13.71 13.50 13.26 13.15 Input[kW] 5.76 5.93 6.21 6.40 6.59 6.85 7.04
32ºC DB 23ºC WB
Total capacity[kW] 19.34 18.99 18.46 18.28 17.40 16.53 16.00 Sensitive capacity[kW] 16.44 16.33 16.06 16.09 15.84 15.70 15.36 Input[kW] 6.02 6.14 6.46 6.72 6.85 7.22 7.68
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
41
8.2.11. MRA-60HW-V (208~230V-1Ph-60Hz) Cooling
Outdoor Temperature (DB) 21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Indoor Conditions
21ºC DB 15ºC WB
Total capacity[kW] 18.11 17.58 16.88 16.35 16.00 15.29 14.59 Sensitive capacity[kW] 13.40 13.36 13.16 13.08 13.12 12.85 12.69 Input[kW] 5.23 5.48 5.80 5.92 5.99 6.24 6.62
24ºC DB 17ºC WB
Total capacity[kW] 18.63 18.11 17.40 16.88 16.10 16.17 14.94 Sensitive capacity[kW] 13.98 13.94 13.75 13.67 13.37 13.75 13.00 Input[kW] 5.54 5.76 6.03 6.17 6.36 6.62 6.93
27ºC DB 19ºC WB
Total capacity[kW] 18.99 18.46 17.93 17.58 16.88 16.17 15.47 Sensitive capacity[kW] 14.05 14.03 13.81 13.71 13.50 13.26 13.15 Input[kW] 5.67 5.84 6.11 6.30 6.49 6.74 6.93
32ºC DB 23ºC WB
Total capacity[kW] 19.34 18.99 18.46 18.28 17.40 16.53 16.00 Sensitive capacity[kW] 16.44 16.33 16.06 16.09 15.84 15.70 15.36 Input[kW] 5.92 6.05 6.36 6.62 6.74 7.11 7.56
Heating Outdoor DB (°C) 24 7 2 -5 Outdoor WB (°C) 18 6 1 -6
Evap. Entering Air DB TC KW TC KW TC KW TC KW (°C) Capacity (kW) 15 25.09 6.05 20.27 5.21 16.60 4.48 15.05 4.20 20 24.32 6.61 19.30 5.60 15.63 4.93 14.67 4.54 27 22.77 7.00 18.14 6.05 14.67 5.32 14.28 4.93
8.2.12. MRC-36CW-V (208~230V-1Ph-60Hz) Outdoor Temperature (DB)
21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Indoor Conditions
21ºC DB 15ºC WB
Total capacity[kW] 9.91 9.62 9.24 8.95 8.75 8.37 7.98 Sensitive capacity[kW] 7.33 7.31 7.20 7.16 7.18 7.03 6.95 Input[kW] 3.30 3.46 3.66 3.74 3.78 3.94 4.18
24ºC DB 17ºC WB
Total capacity[kW] 10.20 9.91 9.52 9.24 8.81 8.85 8.18 Sensitive capacity[kW] 7.65 7.63 7.52 7.48 7.31 7.52 7.11 Input[kW] 3.50 3.64 3.81 3.90 4.02 4.18 4.38
27ºC DB 19ºC WB
Total capacity[kW] 10.39 10.10 9.81 9.62 9.24 8.85 8.47 Sensitive capacity[kW] 7.69 7.68 7.56 7.50 7.39 7.26 7.20 Input[kW] 3.58 3.69 3.86 3.98 4.10 4.26 4.38
32ºC DB 23ºC WB
Total capacity[kW] 10.58 10.39 10.10 10.00 9.52 9.04 8.75 Sensitive capacity[kW] 8.99 8.94 8.79 8.80 8.67 8.59 8.40 Input[kW] 3.74 3.82 4.02 4.18 4.26 4.49 4.78
8.2.13. MRC-48CW-V (208~230V-1Ph-60Hz) Outdoor Temperature (DB)
21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Indoor Conditions
21ºC DB 15ºC WB
Total capacity[kW] 12.97 12.59 12.09 11.71 11.46 10.95 10.45 Sensitive capacity[kW] 9.60 9.57 9.43 9.37 9.39 9.20 9.09 Input[kW] 4.15 4.35 4.60 4.70 4.75 4.95 5.25
24ºC DB 17ºC WB
Total capacity[kW] 13.35 12.97 12.46 12.09 11.53 11.58 10.70 Sensitive capacity[kW] 10.01 9.99 9.85 9.79 9.57 9.85 9.31 Input[kW] 4.40 4.58 4.79 4.90 5.05 5.25 5.50
27ºC DB 19ºC WB
Total capacity[kW] 13.60 13.22 12.84 12.59 12.09 11.58 11.08 Sensitive capacity[kW] 10.06 10.05 9.89 9.82 9.67 9.50 9.42 Input[kW] 4.50 4.64 4.85 5.00 5.15 5.35 5.50
32ºC DB 23ºC WB
Total capacity[kW] 13.85 13.60 13.22 13.09 12.46 11.83 11.46 Sensitive capacity[kW] 11.77 11.69 11.50 11.52 11.34 11.24 11.00 Input[kW] 4.70 4.80 5.05 5.25 5.35 5.64 6.00
8.2.14. MRC-60CW-V (208~230V-1Ph-60Hz) Outdoor Temperature (DB)
21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Indoor Conditions
21ºC DB 15ºC WB
Total capacity[kW] 14.16 13.75 13.20 12.79 12.51 11.96 11.41 Sensitive capacity[kW] 10.48 10.45 10.30 10.23 10.26 10.05 9.93 Input[kW] 5.03 5.27 5.58 5.70 5.76 6.00 6.36
24ºC DB 17ºC WB
Total capacity[kW] 14.58 14.16 13.61 13.20 12.60 12.65 11.69 Sensitive capacity[kW] 10.93 10.91 10.75 10.69 10.45 10.75 10.17 Input[kW] 5.33 5.54 5.80 5.94 6.12 6.36 6.67
27ºC DB 19ºC WB
Total capacity[kW] 14.85 14.44 14.03 13.75 13.20 12.65 12.10 Sensitive capacity[kW] 10.99 10.97 10.80 10.73 10.56 10.37 10.29 Input[kW] 5.45 5.62 5.88 6.06 6.24 6.48 6.67
32ºC DB 23ºC WB
Total capacity[kW] 15.13 14.85 14.44 14.30 13.61 12.93 12.51 Sensitive capacity[kW] 12.86 12.77 12.56 12.58 12.39 12.28 12.01 Input[kW] 5.70 5.82 6.12 6.36 6.48 6.84 7.27
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
42
8.2.15. MRC-60CW-X (208~230V-3Ph-60Hz)
Outdoor Temperature (DB)
21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Indoor Conditions
21ºC DB 15ºC WB
Total capacity[kW] 14.81 14.38 13.80 13.37 13.09 12.51 11.94
Sensitive capacity[kW] 10.96 10.93 10.77 10.70 10.73 10.51 10.38
Input[kW] 5.06 5.31 5.61 5.73 5.80 6.04 6.41
24ºC DB 17ºC WB
Total capacity[kW] 15.24 14.81 14.24 13.80 13.17 13.23 12.22
Sensitive capacity[kW] 11.43 11.40 11.25 11.18 10.93 11.25 10.63
Input[kW] 5.37 5.58 5.84 5.98 6.16 6.41 6.71
27ºC DB 19ºC WB
Total capacity[kW] 15.53 15.10 14.67 14.38 13.80 13.23 12.65
Sensitive capacity[kW] 11.49 11.48 11.29 11.22 11.04 10.85 10.76
Input[kW] 5.49 5.65 5.92 6.10 6.28 6.53 6.71
32ºC DB 23ºC WB
Total capacity[kW] 15.82 15.53 15.10 14.96 14.24 13.52 13.09
Sensitive capacity[kW] 13.45 13.36 13.14 13.16 12.95 12.84 12.56
Input[kW] 5.73 5.86 6.16 6.41 6.53 6.88 7.32
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
43
9. Electrical Data 9.1. Evaporator part
Model Indoor Unit Power Supply IFM Hz Voltage Min. Max. MCA MFA KW FLA
MRA-24CW 50 220-240 198 242 3.5 5 0.27 2.8 MRA-36CW 50 220-240 198 242 3.5 5 0.27 2.8 MRA-36CW 50 380-415 342 418 3.5 5 0.27 2.8 MRA-48CW 50 380-415 342 418 4.8 15 0.35 3.8 MRA-60CW 50 380-415 342 418 4.8 15 0.35 3.8
MRA-24HW-Q 50 220-240 198 264 3.5 35 0.65 2.8 MRA-36HW-Q 50 220-240 198 264 3.5 45 0.65 2.8 MRA-36HW-R 50 380-415 342 456 3.5 30 0.65 2.8 MRA-48HW-R 50 380-415 342 456 4.75 30 0.86 3.8 MRA-60HW-R 50 380-415 342 456 4.75 30 0.86 3.8 MRC-36HW 50 220-240 198 242 1.88 45 0.33 1.5
MRC-36HW-R 50 380-415 342 418 1.88 30 0.33 1.5 MRC-48HW-R 50 380-415 342 418 4.5 30 0.79 3.6 MRC-60HW-R 50 380-415 342 418 4.5 30 0.79 3.6
MRA-24CW 60 208-230 198 242 2.4 5 0.17 1.63 MRA-36CW 60 208-230 198 242 2.4 5 0.17 1.63 MRA-48CW 60 208-230 198 242 3.37 5 0.17 1.63 MRA-60CW 60 208-230 198 242 3.37 5 0.17 1.63
MRA-60CW-D 60 208-230 187 253 3.37 4 0.62 2.69 MRA-60HW-V 60 208-230 188 253 3.37 54 0.62 2.69 MRA-36CW-V 60 208-230 198 242 2.79 35.7 0.27 2.23 MRA-48CW-V 60 208-230 198 242 3.37 48.9 0.35 2.69 MRA-60CW-V 60 208-230 198 242 3.37 57.6 0.35 2.69 MRA-60CW-D 60 208-230 198 242 3.37 37.7 0.35 2.69 MRA-60HW-V 60 208-230 198 242 3.37 64.4 0.35 2.69 MRC-36CW-V 60 208-230 188 253 2.63 34 0.25 2.15 MRC-48CW-V 60 208-230 188 253 3.23 42 0.3 2.85 MRC-60CW-X 60 208-230 188 253 3.5 50 0.5 2.8 MRC-60CW-V 60 208-230 188 253 3.5 30 0.5 2.8
Remark: MCA: Min. Current Amps. (A) MFA: Max. Fuse Amps. (A) KW: Fan Motor Rated Output (kW) FLA: Full Load Amps. (A) IFM: Indoor Fan Motor
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
44
9.2. Compressor & condenser part Model Outdoor Unit Power Supply Compressor OFM
Hz Voltage Min. Max MCA TOCA MFA MSC RLA kW FLA MRA-24CW 50 220-240 198 242 18 14.7 40 69 12 0.17 1.2 MRA-36CW 50 220-240 198 242 30 21.9 70 122 19.8 0.17 1.2 MRA-36CW 50 380-415 342 418 10 7.6 25 45 7.3 0.17 1.2 MRA-48CW 50 380-415 342 418 11 9.3 30 52 8.5 0.17 1.2 MRA-60CW 50 380-415 342 418 14 11.1 40 69 9.5 0.17 1.2
MRA-24HW-Q 50 220-240 198 264 18 14.7 40 55 12 0.28 1.24 MRA-36HW-Q 50 220-240 198 264 30 21.9 70 122 17.4 0.28 1.24 MRA-36HW-R 50 380-415 342 456 10 7.6 25 48 6.8 0.28 1.24 MRA-48HW-R 50 380-415 342 456 11 9.3 30 52 7.9 0.28 1.24 MRA-60HW-R 50 380-415 342 456 14 11.1 40 66 9.3 0.26 1.17 MRC-36HW 50 220-240 198 242 25 28 35 19.3 112 0.25 1.2
MRC-36HW-R 50 380-415 342 418 9 10 15 6.9 45 0.25 1.2 MRC-48HW-R 50 380-415 342 418 12 13 18 8.2 55 0.25 1.2 MRC-60HW-R 50 380-415 342 418 14 15 20 9.7 69 0.25 1.2
MRA-24CW 60 208-230 198 242 18 13.4 40 54 12.4 0.27 2.23 MRA-36CW 60 208-230 198 242 22 17.9 50 62 15.3 0.27 2.23 MRA-48CW 60 208-230 198 242 31 25.6 70 130 23 0.35 2.69 MRA-60CW 60 208-230 198 242 39 29.1 90 151 27 0.35 2.69
MRA-60CW-D 60 208-230 187 253 20.5 42.2 50 135 16.4 0.33 1.49 MRA-60HW-V 60 208-230 188 253 39 29.1 90 161 26 0.33 1.5 MRA-36CW-V 60 208-230 198 242 22 23.8 35.7 100 17.9 0.18 2.0 MRA-48CW-V 60 208-230 198 242 30 32.6 48.9 132 23.6 0.18 2.0 MRA-60CW-V 60 208-230 198 242 35 39.1 58.7 150 28.0 0.18 2.0 MRA-60CW-D 60 208-230 198 242 21.4 25.1 37.7 100 15.8 0.18 2.0 MRA-60HW-V 60 208-230 198 242 36 42.9 64.4 150 28.0 0.18 2.0 MRC-36CW-V 60 208-230 188 253 22.5 23.8 35.7 100 17.9 0.18 2.0 MRC-48CW-V 60 208-230 188 253 28.4 30.9 46.3 132 23.6 0.18 2.0 MRC-60CW-X 60 208-230 188 253 35.4 39.7 59.5 150 28.0 0.18 2.0 MRC-60CW-V 60 208-230 188 253 20.6 24.2 36.3 100 15.8 0.18 2.0
Remark: MCA: Min. Current Amps. (A) TOCA: Total Over-current Amps. (A) MFA: Max. Fuse Amps. (A) MSC: Max. Starting Amps. (A) RLA: Rated Locked Amps. (A) OFM: Outdoor Fan Motor. FLA: Full Load Amps. (A) kW: Rated Motor Output (kW)
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
45
10. Refrigerant Cycle Diagram and Sound Level 10.1. Cooling Only
Comp
High Pressure Switch
Low Pressure Switch
Condenser
Evaporator
Capillary
10.2. Heat Pump
Comp
High Pressure Switch
Condenser
Evaporator
Capillary
Low Pressure Switch
4-way Valve
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
46
11. Operation Limit 11.1. Cooling only
StandardOperation
17°C
43°C
17°C 30°C
Out
door
tem
pera
ture
(°C
DB
)
Indoor temperature(°C WB)
11.2. Heat pump
17 3
-8
24
Out
door
air
tem
pera
ture
℃
Indoor air temperature ℃
Heating
Standard operation
17 30
17
43
Out
door
air
tem
pera
ture
℃
Indoor air temperature ℃
Cooling
Standard operation
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
47
12. Installation 12.1. Accessories Standard accessories:
Name of accessories Quantity Outline
Manual 1 ――
Drain outlet 1
Snap ring 1
Drain pipe 1
12.2. General Information Important: read this entire manual before beginning installation procedures. Caution: Bodily injury can result from high voltage electrical components, fast moving fans. For protection from these inherent hazards during installation and servicing, the electrical supply must be is connected.
If operating checks must be performed with the unit operating, it is the technician’s responsibility to recognize these hazards and proceed safely.
Read this manual carefully before attempting to install, operate, or perform maintenance on this unit. Installation and maintenance should be performed by qualified service technicians only.
Inspection 1. Check for damage after the unit is unloaded. Report promptly, to the carrier, any damage found to the unit.
Do not drop the unit.
2. Check the unit's nameplate to determine if the unit is correct for the intended application. The power supply must be adequate for both the unit and all accessories.
Important: Reconnect all grounding devices. All parts of this product capable of conducting electrical current are grounded. If grounding wires, screws, straps, clips nuts or washers used to complete a path to ground are removed for service, they must be returned to their original position and properly fastened.
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
48
Notice: Warnings and cautions appear at appropriate locations throughout this manual. Read these carefully.
Warning: Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Caution: Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices and where property-damage-only accidents could occur.
12.3. Dimensional Data Capacity(Btu/h) A (Height)
24000~36000 630 mm
48000~60000 830 mm
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
49
12.4. Locations and Recommendations 12.4.1. Horizontal Airflow Application
These units are designed certified for outdoor installations. These units may be installed directly on wood flooring or on Class A, Class B, or Class C roof covering material.
Location of the unit must allow service clearance around it. Clearance of the unit must be given careful consideration.
Check the handling facilities to ensure the safety of personnel and the unit(s).
Caution must be taken at all times to avoid Personal injuries and/or damage to equipment.
The unit must be mounted level for proper drainage of water through the holes in the base pan.
The unit must not be exposed to direct roof water runoff.
Flexible duct connectors must be of a flame retardant material. All duct work outside of the structure must be insulated and weatherproofed in accordance with local codes.
Holes through exterior walls must be sealed in accordance with local codes.
All fabricated outdoor ducts should be as short as possible. 12.4.2. Downflow Application -- Curb Mounting
The Roof Mounting Curb, or a field fabricated curb must be in place before the unit is hoisted to the roof top.
The Roof Mounting Curb (frame) must be installed on a flat, level section of the roof and provide a level mounting surface for the unit. In addition, be sure to provide sufficient height above the roof to prevent water from entering the unit. Remove covers from the downflow supply and return air openings and place them over the horizontal supply return air openings and secure with sheet metal screws.
Be sure the mounting curb spans structural members (trusses) of the roof, thereby providing sufficient support for the weight of the unit, the curb, the duct(s), and any factory or field installed accessories.
Be sure the hole in the structure for the ducts is large enough to accommodate the fabricated ducts and the insulation surrounding them.
These units are designed certified for outdoor installation. These units may be installed directly on wood flooring or on Class A, Class B, or Class C roof covering material.
Location of the unit must allow for service clearance around it. Clearance of the unit must be given careful consideration.
Check the handling facilities to ensure the safety of personnel and the unit(s).
Caution must be taken at all times to avoid personal injuries and/or damage to the equipment.
The unit must be mounted level for proper drainage of water through the holes in the base pan.
The unit must not be exposed to direct roof water runoff.
Flexible duct connectors must be of a flame retardant material. All duct work outside of the structure must be insulated and weatherproofed in accordance with local codes.
Roof flashing must be installed to seal the roof curb cavity and must conform to local building codes.
All fabricated outdoor ducts should be as short as possible.
12.4.3. Clearances The recommended clearances for single-unit installations are illustrated in Figure 1. These minimum requirements are not only an important consideration when determining unit placement, but they are also essential to ensure adequate serviceability, maximum capacity, and peak operating efficiency.
Any reduction of the unit clearances indicated in these illustrations may result in condenser coil starvation or the recirculation of warm condenser air. Actual clearances which appear to be inadequate should be reviewed with a local engineer.
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
50
See the unit's nameplate for the absolute minimum clearance between the unit and any combustible surface(s).
12.5. Installation 12.5.1. Rooftop Units
For roof top applications using a field fabricated frame and ducts, use the following procedure:
The frame must be located and secured by bolting or welding to the roof. Flashing is required.
The hole in the roof must be prepared in advance of installing the unit.
Secure the ducts to the roof.
Place the unit on the frame or roof curb.
Secure the unit to the frame or roof curb.
Insulate any ductwork outside of the structure with at least two (2) inches of insulation and then weatherproof. There must be a weatherproof seal where the duct enters the structure.
Complete the installation according to the instructions in the following sections of this manual.
Figure 2 Typical rooftop application with frame
Typical rooftop application with frame:
Remove covers from the downflow supply and return air openings and place them over the horizontal supply return air openings and secure with sheet metal screws.
Figure 3 Typical rooftop application with frame
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
51
12.5.2. Ground Level -- Horizontal Units For ground level installations, the unit should be positioned on a pad the size of the unit or larger. The unit must be level on the pad. The pad must not come in contact with the structure. Be sure the outdoor portion of the supply and return air ducts are as short as possible.
Proceed with the installation as follows:
Place the unit on the pad.
Attach the supply and return air ducts to the unit.
Insulate any ductwork outside of the structure with at least 2 inches of insulation and weatherproof. There must be a weatherproof seal where the duct enters the structure.
Complete the installation according to the instructions in the following sections of this manual.
Figure 4 Typical ground level application
12.5.3. Condensate Drain Piping Twist drain outlet into drain connection hole, sheathe drain pipe, lock in the snap ring.
Figure 5 Condensate drain piping
12.5.4. Ductwork 12.5.4.1. Attaching Horizontal Ductwork to Unit
All conditioned air ductwork should be insulated to minimize heating and cooling duct losses. Use a minimum of two (2) inches of insulation with a vapor barrier. The outside ductwork must be weatherproofed between the unit and the building. When attaching ductwork to a horizontal unit, provide a flexible watertight connection to prevent noise transmission from the unit to the ducts. The flexible connection must be indoors and made out of heavy canvas. Note: Do not draw the canvas taut between the solid ducts.
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
52
12.5.4.2. Attaching Downflow Ductwork to Roof Curb
Supply and return air flanges are provided on the roof curb for easy duct installation. All ductwork must be run and attached to the curb before the unit is set into place.
Follow these guidelines for ductwork construction:
Connections to the unit should be made with three-inch canvas connectors to minimize noise and vibration transmission.
Elbows with turning vanes or splitters are recommended to minimize air noise and resistance.
The first elbow in the ductwork leaving the unit should be no closer than two feet from the unit, to minimize noise and resistance.
12.6. Electrical Wiring Electrical Power It is important that proper electrical power be available for the unit. Voltage variation should remain within the limits stamped on the unit nameplate. Disconnect Switch Provide an approved weatherproof disconnect either on the side of the unit or within close proximity and within sight of the unit. Over Current Protection The branch circuit feeding the unit must be protected as shown on the unit rating plate. Power Wiring The power supply lines must be run in weather tight conduit to the disconnect and into the bottom of the unit control box. Provide strain relief for all conduits with suitable connectors. Provide flexible conduit supports whenever vibration transmission may cause a noise problem within the building structure. Be sure all connections are made tight. Control Wiring (Class II) Low voltage control wiring should not be run in conduit with power wiring unless Class 1 wire of proper voltage rating is used. Make connections as shown on the unit wiring diagram. Do not short thermostat wires since this will damage the control transformer. Important: Upon completion of wiring check all electrical connections, including factory wiring within the unit, make sure all connections are tight. Replace and secure all electrical box covers and access doors before leaving the unit or turning on the power to the unit.
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
53
Note
Knock down the control box access panel, first twist off screws and then up it, the control box access panel is getting out.
12.7. Start–Up Packaging and Components n Is the unit properly located and level with the proper clearance?
n Is the duct work correctly sized, run, taped, insulated , and weatherproofed with proper unit arrangement? See Ductwork Installation section.
n Is the wiring properly sized and run according to the unit wiring diagram?
n Are all the wiring connections, including those in the unit, tight?
n Has the unit been properly grounded and fused with the recommended fuse size? See Wiring Data.
n Have the air conditioning systems been checked at the service ports for charge and leak tested if necessary?
n Does the condenser fan and indoor blower turn free without rubbing, and are they tight on the shafts?
n Has the indoor blower speed been determined and the proper speed been set? See the Unit Wiring Diagram.
n Are all covers and access panels in place to prevent air loss and safety hazards?
Starting the Unit in the Cooling Mode Caution:
Before starting the system on the cooling cycle, turn the thermostat switch to OFF and close the unit disconnect switch. This procedure energizes the compressor crankcase heater, vaporizing any liquid refrigerant in the crankcase. This is a precaution against foaming at startup which could damage the compressor bearings.
Allow the heater to operate a minimum of eight (8) hours.
To start the unit in the cooling mode, set the thermostat system switch to COOL and move the thermostat COOL indicator to a setting below room temperature. The condenser (outdoor) fan motor compressor and evaporator (indoor) fan motor will operate automatically.
Voltage
With the compressor operating, check the line voltage at the unit. The voltage should be within the range shown on the unit nameplate.
If low voltage is encountered, check the size and length of the supply line from the main disconnect to the unit. The line may be undersized for the length of the run.
Cooling Shut Down
Place the system selector in the OFF position or reset thermostat at a setting above room temperature.
Do not de-energize the main power disconnect except when unit is to be serviced. Power is required to keep the heat pump compressor warm and boil off refrigerant in the compressor.
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
54
12.8. Maintenance Routine Maintenance by Owner You can do some of the periodic maintenance functions for your unit yourself; this includes cleaning the permanent air filters, cleaning the unit cabinet, cleaning the condenser coil, and conducting a general unit inspection on a regular basis
Cleaning the Air Filter 1. Dismantle the air filter.
● Twist of screws and up the plate that is gets out.
● Make the Clasp of air filter from horizontal to vertical.
● The air filter turns 30 degree to out.
Figure 9
2. Clean the air filter (Vacuum cleaner or pure water may be used to clean the air filter. If the dust accumulation is too heavy, please use soft brush and mild detergent to clean it and dry out in cool place).
Figure 10
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
55
● The air-in side should face up when using vacuum cleaner.
● The air-in side should face down when using water.
Caution: Do not dry out the air filter under direct sunshine or with fire.
3. Re-install the air filter
Condenser Coil
Unfiltered air circulates through the unit's condenser coil and can cause the coil's surface to become clogged with dust, dirt, etc. To clean the coil, vertically (i.e., with the fins) stroke the coil surface with a soft-bristled brush. Be sure to keep all vegetation away from the condenser coil area.
MAINTENANCE PERFORMED BY SERVICEMAN--COOLING SEASON
To keep your unit operating safely and efficiently, the manufacturer recommends that a qualified serviceman check the entire system at least once each year and any other time that you feel one is needed. Your serviceman should examine these areas of your unit:
● filters
● motors and drive system components
● economizer gaskets (for possible replacement)
● safety controls (for mechanical cleaning)
● electrical components and wiring (for possible replacement and connection tightness)
● condensate drain (for cleaning)
● unit duct connections (to see that they are physically sound and sealed to the unit casing)
● unit mounting support (for structural integrity)
● the unit (for obvious unit deterioration)
Caution
Do not operate the unit without the evaporator fan access panel in place. Reinstall the access panel after performing any maintenance procedures on the fan. Operating the unit without the access panel properly installed may result in severe personal injury or death.
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
56
13. System Operation 13.1. LED Display The control would display any fault code that is currently active using the LED. The control will display the fault code, when the LEDS are flashing quickly; there is something wrong with the system. Refer to below table for detail fault code. Function: 1. the compressor and indoor fan will start when the system is energized, outdoor fan starts with compressor 2. When the system is de-energized, the outdoor fan and compressor would close soon, but the indoor fan
would close later. 13.2. Operational Codes:
No. Code LED1(Red) LED2(Yellow) LED3(Green) 1 Standby OFF OFF ON
2 Function ON ON ON
3 Lack of phase
Flash Flash Flash Phase-error
4
T1 sensor failure
Flash Flash Flash High pressure protection
Vent protection
5 T2 sensor failure Flash OFF Flash
6 T3 sensor failure OFF Flash Flash
7 T4 sensor failure ON Flash Flash
8 T2 Evaporator low temp, protection OFF Flash OFF
9 T2 Evaporator high temp, protection Flash ON ON
10 T3 Condenser high temp, protection Flash OFF OFF
11 Wired controller input failure Flash Flash ON
12 Compressor current protection OFF OFF Flash
13 Compressor-inhaling low pressure protection Flash ON Flash
14 Defrost ON Flash Flash
13.3. Low pressure switch The control will detect the status of low pressure switch, which is normally close. If the low pressure switch is open during the first time of power supply, the control will de-energized the compressor. If low pressure switch protection appears 3 times in 20 minutes, the control should be restored by switch off the power supply. The control will ignore the low pressure switch input during the following conditions: defrost operation, 4 minutes following the completion of a defrost cycle, first5minuteofcompressor operation during the heat mode. 13.4. High pressure switch The Unit is equipped with a high-pressure switch that is connected to the mainboard, If the high-pressure switch opens for more than 40 milliseconds, the control will de-energize the compressor and store and display the appropriate fault code. If the pressure switch closes and a thermostat call for compressor operation is present, the control will apply the three-minute anti-short cycle delay timer and start the compressor when the timer expires. 13.5. Temperature sensor The unit has two temperature sensors, which are called T3 and T4, T3 means pipe temperature sensor, T4 means outdoor unit circumstance temperature sensor. When the temperature sensor was damaged, the system would close and the LED would flash. 13.6. Indications of proper operation When the LEDS in lighting states, no matter which one, it is means the system runs properly.
MCAC-UTSM-2010-15 T1 Condition Rooftop Package
57
14. Wired Controller 14.1. Optional Midea’s wired controller: KJR-12B/DP (T)-E / KJR-25B
KJR-12B/DP (T)-E KJR-25B 14.2. Optional well-known brand thermostat controller: KJR-23B
KJR-23B