ParagonTM Control Module (PCM) Slide Valve and Protection...
Transcript of ParagonTM Control Module (PCM) Slide Valve and Protection...
-
1
Application Guide 575-012ParagonTM Control Module (PCM)
Slide Valve and Protection Control 10/25/2016
Rev 1
Carlyle Controller Part No. 2BSB000928
-
2
General Description
The PCM is part of Paragon Compressor control packages 6BSB000929 and 6BSB000930.
Besides this Application Guide, the following manuals, I/O Zone Installation Guide and I/O Zone Integration Guide are necessary for proper installation and Network Protocol configuration.
PCM Configuration
-
3
Compressor Protection
See Table A & B for Tm control points.
See Table A & B for Td control points.
Run Recognition Signal
The Slide Valve and Compressor Protection functionality are not active until the PCM receives the Run Recognition signal from the System Controller.
LED Fault Indication
Fault Description LED Indication (Output #4) Output #5 CompressorManual Reset
Required
Table C
-
33
LED Indicators are provided in the PCM Controller Kit. Install labels next to each LED light identifying the indication.
Place adhesive label in a location next to the PCM Controller so it is visible for Field Service and Refrigeration Technicians.
4
Slide Valve Control:
The end user will have to configure the PCM in the following way:
Pressure TemperaturePhysical Input Network Input
See Table/Chart D & E
Logic
1.)Upper DB-1
Upper DB-2.
UpperDB-2 Lower DB-3
3.)Lower DB-4
Slide Valve Coil #1, Coil #2
Slide Valve Coil #1, Coil #2
Logic
2.)Upper DB-2 UpperDB-2 Lower DB-3
4.)
Lower DB-3
lower and upper dead-bands are adjustable inputs
Note: 1 2
3 4
-
5
32
-
31
6
PCM Module Inputs
Input #1: Slide-Valve Capacity Control
See Chart ESee Table F
Input #2: Motor Temperature Control
Note: The motor thermistor connection points are located in the compressors electrical box at terminals S1 and C. In the event of a thermistor failure, a spare thermistor is available between S2 and C terminal points.
Table D
Table A & B.
Input #3: Discharge Temperature Control
Table D
Table A & B
-
7
Input #4: Dry Contact for Compressor Oil Protection
Input #5: Compressor recognition signal (received from Master Controller)
Tells the PCM Controller that the compressor is actually on/running. Slide Valve Control and Compressor Protection are activated when the PCM receives the recognition signal that the compressor is on. PCM controller initiates a 15 second delay regarding monitoring input#1 (suction pressure or thermistor temperature). PCM controller allows for a 3 second delay prior to beginning to monitoring inputs and taking action for inputs #2, #3, and #4 (eliminate nuisance trips on startup). When the compressor is off, there will be no oil flow. Therefore the oil flow switch will be open, causing output #5 to open, therefore not allowing the compressor to start. Therefore the controller must ignore the oil flow switch until the compressor is started and actual compressor oil flow is established, resulting in a closed oil flow switch.
Input #6: Dry Contact for Manual Reset
Compressor Operational
PCM Module Outputs
30
General Installation Pictorials (for example only)
-
29
Web Control Software
8
Output #1 & #2: Slide Valve Control
Output #3: Open/Close Motor Cooling Valve
Output #4: LED Status indication for a Compressor Trip
Table C.
.
Output #5: Enables the Compressor to Run
When output is closed (energized), the compressor is enabled to run and therefore there are no fault conditions. Output must be part of Refrigeration System’s pilot duty Start/Stop Compressor circuit. An alternative to output #5 is the end user receiving this compressor start/stop signal (run enable) via the PCM’s communication port to the System Controller. Output will open (de-energize), tripping the compressor off line if the following fault conditions arise
o High Discharge Temperature o High Motor Temperature o Low oil level o Low oil flow o Faulty pressure transducer (open or short) o Faulty thermistor (open or short)
Controller Default Setting:
PCM Default SettingSlide Valve Control: Enabled Upper Deadband-B: 2 FCompressor Protection: Enabled Upper Deadband-A: 1 FUpper Deadband-B: 2 psig Lower Deadband-A: 1 FUpper Deadband-A: 1 psig Lower Deadband-B: 2 FLower Deadband-A: 1 psig Suction Pressure set-point: 30 psigLower Deadband-B: 2 psig Temperature set-point: 35F
-
9
PCM Control Points
Motor and Discharge Temperature Control Points
ALC Controller Injection On (°F ) Injection Off (°F) ShutdownCompressor (°F)
Manually ResetCompressor (°F)
Time Delay required before manual reset (sec)
Table A
Slide Valve Override Control Points
ALC Controller Restrict Further Compressor Unloading Energized SV Coil #2 continuously
(°F)
Fully Load Compressor and restrict unloading below 100%Energize SV Coil #1 and Coil #2 continuously
(°F)
Table B
28
-
27
10
Sensor Profile
Table D
Sig Gnd
0
0.2
0.4
0.6
0.8
1
1.2
50 100 150 200 250 300
VDC
Deg F
5K NTC, Part# HH79NZ065 Deg F vs VDC
VDC
-
11
Chart E
Chart F
PCM Layout and Interface:
Note:
The I/O Zone Installation Guide is for controller specifications, mounting requirements, and electrical requirements and installation.
The I/O Zone Integration guide is for instruction regarding using the PCM with Network Protocols.
-60
-40
-20
0
20
40
60
80
100
120
1.000 1.500 2.000 2.500 3.000 3.500
NTC Thermistor, Part# A1004MS24P1 VDC vs Deg F
Deg F
26
ZS PRO Display
For permanent installation with the PCM Controller. See the I/O Zone Installation Guide for specifications and installation instruction for the ZS Pro.
• Large, easy-to-read LCD on the ZS Pro can be configured to display virtually any analog or digital value in your equipment. Here are some examples: zone temperature, outside air temperature, energy-saving mode icon, heating set-point, cooling set-point, relative humidity, CO2, VOCs, override time remaining, fan status, compressor status, alarms, and much more. • Occupancy override is simple using the "Manual On" momentary push button on the ZS Pro. A single push switches the zone to an Occupied mode for a preset period of time. The user can increase or decrease the override time with the up or down arrows, and the LCD displays precisely how long the zone will stay occupied. The occupied time increment and maximum override time are fully adjustable. • Zone set-points can be changed on the ZS Pro by pressing the up or down arrow buttons. Setpoint adjust increment amount and the maximum total adjustment are fully adjustable.
-
25
BACview6 Virtual Display
BACview User Guide
12
24 VAC Supply Power Input required.
End User interface for pilot duty compressor on/off control circuit.
24VAC Supply Power Input required for BUS Outputs. 24 VAC input Supply Power required to the BUS.
-
13
How to Wire the Inputs for Pressure Transducer, Thermistor, or Dry Contact
5vdc Power Supply
White Wire
Red Wire
24
Connection port for portable or temporary installation.
Hardwire connection location for permanent installations.
-
23
PCM Controller Display Features
BACview6 HandheldBACview6 SoftwareZS PRO Web Control
BACview6 Handheld Display
BACview User Guide
14
PCM Input #1 (Process Control Set-point):
(3 WIRE)Carlyle kit 6BSB000931
BLACK
WHITE
RED
Set the configuration jumper for input #1 depending on if the control set-point will be measured via Pressure or Temperature. The jumper comes installed on the PCM and may already be in the correct position.
Place the configuration jumper to this position if the Process Control Variable is a thermistor sensor for Input #1.
OR
Place the configuration jumper to this position if the Process Control Variable is a 0-5 vdc Pressure Transducer sensor for Input #1.
-
15
PCM Input #2:
S1
C
S2
Must set the configuration jumper to this position for Input #2. This sets the type of signal the input will receive as a Thermistor. Failure to do so will result in input #2 not working correctly.
22
Slide Valve Wiring Diagram with System Controller
System Controller
Slide Valve Override
Output #1 Output #2
Supply Power 24/120/240 Vac
SV Coil #1 (Capacity Control)
SV Coil #2 (Capacity Control)
I/OZ 560 Module
-
21
PCM output #5:
mustOutput will open (de-energize), tripping the compressor off line, for the following fault
conditions:o High Discharge Temperature o High Motor Temperature o Low oil level o Low oil flow o Faulty pressure transducer (open or short) o Faulty thermistor (open or short)
Slide Valve Override
Table B. See wiring diagram below.
Slide Valve Override Control Points
ALC Controller Restrict Further Compressor Unloading Energized SV Coil #2 continuously
(°F)
Fully Load Compressor and restrict unloading below 100%Energize SV Coil #1 and Coil #2 continuously
(°F)
Table B
16
PCM Input #3:
Table A & B.
-
17
PCM Input #4:
Flow Switch RatingsVA Volts AMPS AC AMPS DC
20
PCM output #3:
PCM output #4:
Fault Description LED Indication (Output #4) Output #5 CompressorManual Reset
Required
-
19
PCM outputs #1 & #2:
Note: All PCM outputs are rated for 24vac @ 1 amp.
Loads Comp Unloads Comp Freezes Unloading
18
PCM Input #5:
PCM Input #6
User must set the configuration jumper to this position for Input #5. This configures Input #5 as a Dry Contact. Failure to do so will result in input #5 not working correctly.