Series LF007 Specification Sheet

5
 For Non-Health Hazard Applications ES-LF007 Now Available WattsBox Insulated Enclosures. For more information, send for literature ES-WB. Series LF007 Double Check Valve Assemblies Sizes: 1  ⁄ 2" – 3" (15 – 80mm) Series LF007 Double Check Valve Assemblies shall be installed at referenced cross-connections to prevent the backflow of polluted water into the potable water supply. Only those cross-connections identifie d by local inspection authorities as non-health hazard shall be allowed the use of an approved double check valve assembly.  The LF007 feat ures Lead Free* construc tion to compl y with Lead Free* installation requirements. Check with local authority having jurisdiction regarding vertical orientation, frequency of testing or other installation requirements.  The valve sha ll meet the requirements of ASSE Std. 1015 and  AWWA Std . C510. Approv ed by the Foundati on for Cross- Connection Control and Hydraulic Research at the University of Southern California. Features • Ease of maintenance — only one cover • Top entry • Replaceable seats and seat discs • Modular construction • Compact design • Lead Free* cast copper silicon alloy body construction — 1  ⁄ 2" – 2" (15 – 50mm) • Fused epoxy coated cast iron body — 2 1  ⁄ 2" – 3" (65 – 80mm) • Top mounted Lead Free* ball valve test cocks • Low pressure drop • No special tools required for servicing 1  ⁄ 2" – 1" (15 – 25mm) have tee handles Specifications  A Double Che ck Valve As sembly sh all be insta lled at each noted location. The assembly shall consist of two positive seating check modules with captured springs and rubber seat discs. The check module seats and seat discs shall be replaceable. Service of all internal components shall be through a single access cover secured with stainless steel bolts. The Double Check Valve  Assemb lies shall b e construc ted using Lea d Free* cast co pper silicon alloy. Lead Free* Double Check Valve Assemblies shall comply with state codes and standards, where applicable, requir- ing reduced lead content. The assembly shall also include two resilient seated isolation valves; four top mounted, resilient seated test cocks. The assembly shall meet the requirements of ASSE Std. 1015 and AWWA Std. C510. Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California. Assembly shall be a Watts Series LF007. Test Cocks First Check Module Assembly The LF007 Series features a modular design concept which facilitates complete maintenance and assembly by retaining the spring load. Second Check Module Assembly *The wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight. Job Name –––––––––––––––––––––––––––––––––––––––––––  Contractor –––––––––––––––––––––––––––––––––––––––––––– Job Location –––––––––––––––––––––––––––––––––––––––––  Approval ––––––––––––––––––––––––––––––––––––––––––––– Engineer –––––––––––––––––––––––––––––––––––––––––––––  Contractor’s P.O. No. ––––––––––––––––––––––––––––––––––  Approval –––––––––––––––––––––––––––––––––––––––––––––  Representative –––––––––––––––––––––––––––––––––––––––– LEAD FREE * NOTICE Inquire with governing authorities for local installation requirements Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with- out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold. 3  ⁄ 4" (20mm) LF007M3QT  The information con tained he rein is not i ntended t o replace th e full product installation and safety information available or the experience of a trained product installer. You are required to thoroughly read all installation instructions and product safety information before beginning the installation of this product. NOTICE 

Transcript of Series LF007 Specification Sheet

Page 1: Series LF007 Specification Sheet

8/8/2019 Series LF007 Specification Sheet

http://slidepdf.com/reader/full/series-lf007-specification-sheet 1/4

 For Non-Health Hazard Applications

ES-LF007

Now AvailableWattsBox Insulated Enclosures.

For more information, send for literature ES-WB.

Series LF007Double Check Valve Assemblies

Sizes: 1 ⁄ 2" – 3" (15 – 80mm)Series LF007 Double Check Valve Assemblies shall be installed atreferenced cross-connections to prevent the backflow of pollutedwater into the potable water supply. Only those cross-connectionsidentified by local inspection authorities as non-health hazard shallbe allowed the use of an approved double check valve assembly.

 The LF007 features Lead Free* construction to comply with LeadFree* installation requirements.

Check with local authority having jurisdiction regarding verticalorientation, frequency of testing or other installation requirements.

 The valve shall meet the requirements of ASSE Std. 1015 and AWWA Std. C510. Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the Universityof Southern California.

Features• Ease of maintenance — only one cover

• Top entry

• Replaceable seats and seat discs

• Modular construction

• Compact design

• Lead Free* cast copper silicon alloy body construction —1 ⁄ 2" – 2" (15 – 50mm)

• Fused epoxy coated cast iron body — 21 ⁄ 2" – 3" (65 – 80mm)

• Top mounted Lead Free* ball valve test cocks

• Low pressure drop

• No special tools required for servicing

• 1 ⁄ 2" – 1" (15 – 25mm) have tee handles

Specifications A Double Check Valve Assembly shall be installed at each notedlocation. The assembly shall consist of two positive seating checkmodules with captured springs and rubber seat discs. The checkmodule seats and seat discs shall be replaceable. Service ofall internal components shall be through a single access cover

secured with stainless steel bolts. The Double Check Valve Assemblies shall be constructed using Lead Free* cast coppersilicon alloy. Lead Free* Double Check Valve Assemblies shallcomply with state codes and standards, where applicable, requir-ing reduced lead content. The assembly shall also include tworesilient seated isolation valves; four top mounted, resilient seatedtest cocks. The assembly shall meet the requirements of ASSEStd. 1015 and AWWA Std. C510. Approved by the Foundation forCross-Connection Control and Hydraulic Research at the Universityof Southern California. Assembly shall be a Watts Series LF007.

Test Cocks

First Check

Module Assembly

The LF007 Series features a modular design concept which facilitatescomplete maintenance and assembly by retaining the spring load.

Second Check

Module Assembly

*The wetted surface of this product contacted by consumablewater contains less than 0.25% of lead by weight.

Job Name –––––––––––––––––––––––––––––––––––––––––––   Contractor ––––––––––––––––––––––––––––––––––––––––––––

Job Location –––––––––––––––––––––––––––––––––––––––––   Approval –––––––––––––––––––––––––––––––––––––––––––––

Engineer –––––––––––––––––––––––––––––––––––––––––––––   Contractor’s P.O. No. ––––––––––––––––––––––––––––––––––

 Approval –––––––––––––––––––––––––––––––––––––––––––––   Representative ––––––––––––––––––––––––––––––––––––––––

LEAD FREE*

NOTICE 

Inquire with governing authorities for local installation requirements

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,

please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-

out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.

3 ⁄ 4" (20mm) LF007M3QT

 The information contained herein is not intended to replace the fullproduct installation and safety information available or the experiencof a trained product installer. You are required to thoroughly readall installation instructions and product safety information beforebeginning the installation of this product.

NOTICE 

Page 2: Series LF007 Specification Sheet

8/8/2019 Series LF007 Specification Sheet

http://slidepdf.com/reader/full/series-lf007-specification-sheet 2/4

As

A

C

B

TRD

Bs

F

Subscript ‘S’ = strainer model

Pressure — Temperature1 ⁄ 2" – 2" (15 – 50mm)

 Temperature Range: 33°F – 180°F (0.5°C – 82°C).

Maximum Working Pressure: 175psi (12.1 bar).

21 ⁄ 2" – 3" (65 – 80mm)

 Temperature Range: 33̊F – 110°F (0.5˚C – 43°C) continuous,140°F (60°C) intermittent.

Maximum Working Pressure: 175psi (12.1 bar).

Standards ASSE Std. 1015, AWWA Std. C510

IAPMO PS31, CSA B64.5

 Approvals† ASSE, AWWA, IAPMO, CSA, UPC

s  Approved by the Foundation for Cross-Connection Control andHydraulic Research at the University of Southern California.

• Models with suffix LF and S are not listed.

u  UL Classified (without shutoff valves only) 3 ⁄ 4" – 2"(20 – 50mm) (except 007M3LF)

u  UL Classified with OSY gate valves(21 ⁄ 2" and 3" horizontal only.)

▼ 1 ⁄ 2" - 2" models Lead Free* with strainer

  Horizontal and vertical “flow up" approval on all sizes

ModelsSizes:1 ⁄ 2" – 2" (15 – 50mm)

Suffix:

S – copper silicon alloy strainerLF – without shutoff valvesW/Press** – press inlet x press outlet (1 ⁄ 2" - 2" only)

Prefix:

U – Union connections

21

 ⁄ 2" – 3" (65 – 80mm)Suffix:

NRS – non-rising stem resilient seated gate valves

OSY – UL/FM outside stem and yoke resilient seated gatevalves

LF – without shutoff valves

QT-FDA – FDA epoxy coated quarter-turn ball valves

MODEL SIZE (DN) DIMENSIONS WEIGHT

 A B C D F G R T

in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kgs.

†s▼ LF007QT 1 ⁄ 2 15 10 254 45 ⁄ 8 117 27 ⁄ 16 62 — — 5 127 33 ⁄ 8 85 25 ⁄ 16 59 21 ⁄ 16 52 4.5 2†s▼ LF007M3QT 3 ⁄ 4 20 111 ⁄ 8 282 4 102 31 ⁄ 8 79 — — 63 ⁄ 16 157 37 ⁄ 16 87 21 ⁄ 8 54 15 ⁄ 16 33 5 2.3†s▼ LF007M1QT 1 25 131 ⁄ 4 337 51 ⁄ 8 130 4 102 — — 71 ⁄ 2 191 33 ⁄ 8 85 111 ⁄ 16 43 111 ⁄ 16 43 12 5.4†s▼ LF007M2QT 11 ⁄ 4 32 163 ⁄ 8 416 5 127 35 ⁄ 16 84 — — 91 ⁄ 2 241 5 127 3 76 2 50 15 6.8†s▼ LF007M2QT 11 ⁄ 2 40 163 ⁄ 4 425 47 ⁄ 8 124 31 ⁄ 2 89 — — 93 ⁄ 4 248 513 ⁄ 16 148 31 ⁄ 8 79 211 ⁄ 16 68 15.9 7.2†s▼ LF007M1QT 2 50 191 ⁄ 2 495 61 ⁄ 4 159 4 102 — — 133 ⁄ 8 340 61 ⁄ 8 156 37 ⁄ 16 87 211 ⁄ 16 68 25.7 11.7

•▼ LF007QT-S 1 ⁄ 2 15 13 330 6 152 27 ⁄ 16 62 3 76 5 127 33 ⁄ 8 85 25 ⁄ 16 59 21 ⁄ 16 52 5.5 2.5•▼ LF007M3QT-S 3 ⁄ 4 20 141 ⁄ 2 368 61 ⁄ 8 156 31 ⁄ 8 79 3 76 63 ⁄ 16 157 37 ⁄ 16 87 21 ⁄ 8 54 15 ⁄ 16 33 6.7 3.1•▼ LF007M1QT-S 1 25 1715 ⁄ 16 157 73 ⁄ 4 197 4 102 31 ⁄ 4 83 71 ⁄ 2 191 33 ⁄ 8 85 111 ⁄ 16 43 111 ⁄ 16 43 14 6.4•▼ LF007M2QT-S 11 ⁄ 4 32 211 ⁄ 2 546 71 ⁄ 16 179 35 ⁄ 16 84 31 ⁄ 2 83 91 ⁄ 2 241 5 127 3 76 2 50 19 8.6•▼ LF007M2QT-S 11 ⁄ 2 40 251 ⁄ 16 637 71 ⁄ 16 179 31 ⁄ 2 89 33 ⁄ 4 95 93 ⁄ 4 248 513 ⁄ 16 148 31 ⁄ 8 79 211 ⁄ 16 68 19.6 8.9•▼ LF007M1QT-S 2 50 271 ⁄ 4 692 83 ⁄ 4 222 4 102 4 102 133 ⁄ 8 340 61 ⁄ 8 156 37 ⁄ 16 87 211 ⁄ 16 68 33.5 15.2

Dimensions – Weights

** Viega ProPress® connections are optional factory-installed

fitting on each end of the approved/certified assembly.

Page 3: Series LF007 Specification Sheet

8/8/2019 Series LF007 Specification Sheet

http://slidepdf.com/reader/full/series-lf007-specification-sheet 3/4

MODEL SIZE(DN) DIMENSIONS A 

in. mm in. mm  

LFU007QT 1 ⁄ 2 15 1213 ⁄ 16 326LFU007M2QT 3 ⁄ 4 20 1313 ⁄ 16 350LFU007M2QT 1 25 165 ⁄ 8 422

LFU007M2QT 11 ⁄ 4 32 203 ⁄ 4 527LFU007M2QT 11 ⁄ 2 40 211 ⁄ 2 546LFU007M1QT 2 50 241 ⁄ 2 622

Strainer Dimensions

SIZE WEIGHT

M N

in. mm in. mm in. mm lbs. kgs.

21 ⁄ 2 65 10 254 61 ⁄ 2 165 28 133 80 101 ⁄ 8 267 7 178 34 15

A

C (open)9" (229mm)

45 ⁄ 16" (109mm)

N

E1 E R

A

Union Tailpiece Union Tailpiece

Union Nut Union Nut

Dimensions – Weights Sizes: 21 ⁄ 2" – 3" (65 – 80mm)

1" LFU007M1QT

Sizes: 1 ⁄ 2" – 2" (15 – 50mm)

M

MODEL SIZE (DN) DIMENSIONS WEIGHT

 A B E, E1 R

in. mm in. mm in. mm in. mm in. mm lbs. kgs.

LF007QT-FDA 21 / 2 65 331 / 8 841 63 / 8 162 91 ⁄ 16 230 83 / 4 222 155 70s LF007-NRS 21 / 2 65 331 / 8 841 93 / 8 238 91 ⁄ 16 230 83 / 4 222 155 70su LF007-OSY 21 / 2 65 331 / 8 841 163 / 8 416 91 ⁄ 16 230 83 / 4 222 158 72

LF007-QT-FDA 3 80 341 / 4 870 63 / 8 162 91 ⁄ 16 230 83 / 4 222 155 70s LF007-NRS 3 80 341 / 4 870 101 / 4 260 91 ⁄ 16 230 83 / 4 222 185 84su LF007-OSY 3 80 341 / 4 870 187 ⁄ 8 479 91 ⁄ 16 230 83 / 4 222 185 84

Page 4: Series LF007 Specification Sheet

8/8/2019 Series LF007 Specification Sheet

http://slidepdf.com/reader/full/series-lf007-specification-sheet 4/4

CapacityAs compiled from documented Foundation for Cross-Connection Control andHydraulic Research at the University of Southern California lab tests.

†† Typical maximum system flow rate (7.5 feet/sec., 2.3 meters/sec.)** UL rated flow

bars psi

1.5 22

1.2 18

.96 14

.69 10

.41 6

.14 2

0 5 10 15 20 25 30 35 40 45 50 gpm

0 19 38 57 76 95 114 133 152 171 190 lpm

  7.5 15 lps

  2.3  4.6 mps

   P   r   e   s   s   u

   r   e

   D   r   o   p

Flow

3 ⁄ 4" (20mm)

††

ES-LF007 1720 © 2017 Watts

USA:  Tel: (978) 689-6066 • Fax: (978) 975-8350 • Watts.com

Canada:  Tel: (905) 332-4090 • Fax: (905) 332-7068 • Watts.ca

Latin America:  Tel: (52) 81-1001-8600 • Fax: (52) 81-8000-7091 • Watts.com

   P   r   e   s   s   u   r   e

   D   r   o   p

11 ⁄ 2" (40mm)

bars psi.8 12.7 10

.5 8.4 6

.3 4

.1 20 0

0 10 20 30 40 50 60 70 80 90 100 110 120 gpm

0 38 76 114 152 190 228 66 304 342 380 418 456 lpm

  5 7.5  10 15 fps

  1.5 2.5  3.0 4.5 mps

††

Flow

   P   r   e

   s   s   u   r   e

   D   r   o   p

0 25 50 75 100 125 150 175 200 gpm

0 95 190 285 380 475 570 665 760 lpm

  5 7.5  10 15 fps

  1.5 2.3  3.0 4.6 mps

2" (50mm)

bars psi

.8 12

.7 10

.5 8

.4 6

.3 4

.1 2

0 0

††

Flow

bars psi.8 12.7 10.5 8

.4 6

.3 4

.1 20 0

0 2 4 6 8 10 12 gpm

0 7.6 15.2 22.8 30.4 38 45.6 lpm

  5 7.5  10 fps

  1.5 2.5  3.0 mps

   P   r   e   s   s   u   r   e

   D   r   o   p

  1 ⁄ 2" (15mm) 

††

Flow

bars psi1.1 16.8 12.7 10.5 8.4 6

.3 4.1 2

0 5 10 15 20 25 30 35 40 45 50 55 60 gpm

0 19 38 57 76 95 114 133 152 171 190 209 228 lpm

  5 7.5  10 15 fps

  1.5 2.3  3.0 4.6 mps

1" (25mm)

††

Flow

   P   r   e   s   s   u   r   e

   D   r   o   p

0 25 50 75 100 125 150 175 200 225 250 gpm

0 95 190 285 380 475 570 665 760 855 950 lpm

  5 7.5  10 15 fps

  1.5 2.3  3.0 4.6 mps

21 ⁄ 2" (65mm)bars psi

.7 10

.5 8

.4 6

.3 4

.1 2

0 0

**††

Flow

   P   r   e   s   s   u   r   e

   D   r   o   p

bars psi

1 14

.8 12

.7 10

.5 8

.4 6

.3 4

.1 2

0 0 0 10 20 30 40 50 60 70 80 90 100 110 120 gpm

0 38 76 114 152 190 228 266 304 342 380 418 456 lpm

  5 7.5  10 15 fps

  1.5 2.3  3.0 4.6 mps

11 ⁄ 4" (32mm)††

Flow

   P   r   e   s   s   u   r   e

   D   r   o   p

0 25 50 75 100 125 150 175 200 225 250 275 300 325 gpm

0 95 190 285 380 475 570 665 760 855 950 1045 1140 1235 lpm

  5 7.5  10 fps  1.5 2.3  3.0 mps

3" (80mm)bars psi

.7 10

.5 8

.4 6

.3 4

.1 2

0 0

**††

Flow

   P   r   e   s   s   u   r   e

   D   r   o   p