Series 007 Specification Sheet

5
 For Non-Health Hazard Applications ES-007 Job Name ––––––––––––––––––––––––––––––––––––––––––– Contractor –––––––––––––––––––––––––––––––––––––––––––– Job Location –––––––––––––––––––––––––––––––––––––––––  Approval ––––––––––––––––––––––––––––––––––––––––––––– Engineer ––––––––––––––––––––––––––––––––––––––––––––– Contractor’s P.O. No. –––––––––––––––––––––––––––––––––––  Approval ––––––––––––––––––––––––––––––––––––––––––––– Representative –––––––––––––––––––––––––––––––––––––––– IMPORTANT: INQUIRE WITH GOVERNING AUTHORITIES FOR LOCAL INSTALLATION REQUIREMENTS Now Available WattsBox Insulated Enclosures. For more information, send for literature ES-WB. Series 007 Double Check Valve Assemblies Sizes: 1  ⁄ 2" – 3" (15 – 80mm) Series 007 Double Check Valve Assemblies shall be installed at referenced cross-connections to prevent the backflow of pollut- ed water into the potable water supply. Only those cross-con- nections identified by local inspection authorities as non-health hazard shall be allowed the use of an approved double check valve assembly. Check with local authority having jurisdiction regarding vertical orientation, frequency of testing or other installation requirement s.  The valve shall meet the requirements of ASSE Std. 1015 and  AWWA Std. C510. Approved by the Foundation for Cross- Connection Control and Hydraulic Research at the University of Southern California. Features Ease of maintena nce — only one cover T op entry Replaceable sea ts and sea t discs • Modular construction • Compact design • Cast bronze body construct ion — 1  ⁄ 2" – 2" (15 – 50mm) Fused epoxy coated cast iron body — 2 1  ⁄ 2" – 3" (65 – 80mm) T op mounted ball valve test cocks Low pre ssure drop No special tools r equired for servicing 1  ⁄ 2" – 1" (15 – 25mm) have tee handles Specifications  A Double Check Valve Assembly shall be i nstalled at each noted location. The assembly shall consist of two positive seat- ing check modules with captured springs and rubber seat discs. The check module seats and seat discs shall be replaceable. Service of all internal components shall be through a single bronze or stainless steel access cover secured with stainless steel bolts. The assembly shall also include two resilient seated isolation valves; four top mounted, resilient seated test cocks. The assembly shall meet the requirements of ASSE Std. 1015 and AWWA Std. C510. Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California. Assembly shall be a Watts Series 007. 3  ⁄ 4" (20mm) 007M3QT 2" (50mm) 007M1QT HC Test Cocks First Check Module Assembly The 007 Series features a modular design concept which facilitates complete maintenance and assembly by retaining the spring load. Second Check Module Assembly Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts T echnical Servic e. Watts reserves the right to change or modify product design, construction, specifications, or materials with- out prior notice and without incurring any obligation to make such changes and modificati ons on Watts products previously or subsequently sold.

Transcript of Series 007 Specification Sheet

Page 1: Series 007 Specification Sheet

8/8/2019 Series 007 Specification Sheet

http://slidepdf.com/reader/full/series-007-specification-sheet 1/4

 For Non-Health Hazard Applications

ES-007

Job Name ––––––––––––––––––––––––––––––––––––––––––– Contractor ––––––––––––––––––––––––––––––––––––––––––––

Job Location –––––––––––––––––––––––––––––––––––––––––  Approval –––––––––––––––––––––––––––––––––––––––––––––

Engineer ––––––––––––––––––––––––––––––––––––––––––––– Contractor’s P.O. No. –––––––––––––––––––––––––––––––––––

 Approval ––––––––––––––––––––––––––––––––––––––––––––– Representative ––––––––––––––––––––––––––––––––––––––––

IMPORTANT: INQUIRE WITH GOVERNING AUTHORITIES 

FOR LOCAL INSTALLATION REQUIREMENTS 

Now AvailableWattsBox Insulated Enclosures.

For more information, send for literature ES-WB.

Series 007Double Check Valve Assemblies

Sizes: 1 ⁄ 2" – 3" (15 – 80mm)

Series 007 Double Check Valve Assemblies shall be installed atreferenced cross-connections to prevent the backflow of pollut-ed water into the potable water supply. Only those cross-con-nections identified by local inspection authorities as non-healthhazard shall be allowed the use of an approved double check valve assembly.

Check with local authority having jurisdiction regarding verticalorientation, frequency of testing or other installation requirements.

 The valve shall meet the requirements of ASSE Std. 1015 and AWWA Std. C510. Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California.

Features

• Ease of maintenance — only one cover

• Top entry

• Replaceable seats and seat discs

• Modular construction

• Compact design

• Cast bronze body construction — 1 ⁄ 2" – 2" (15 – 50mm)

• Fused epoxy coated cast iron body — 21 ⁄ 2" – 3" (65 – 80mm)

• Top mounted ball valve test cocks

• Low pressure drop

• No special tools required for servicing

• 1 ⁄ 2" – 1" (15 – 25mm) have tee handles

Specifications

 A Double Check Valve Assembly shall be installed at eachnoted location. The assembly shall consist of two positive seat-ing check modules with captured springs and rubber seatdiscs. The check module seats and seat discs shall be

replaceable. Service of all internal components shall be througha single bronze or stainless steel access cover secured withstainless steel bolts. The assembly shall also include tworesilient seated isolation valves; four top mounted, resilientseated test cocks. The assembly shall meet the requirementsof ASSE Std. 1015 and AWWA Std. C510. Approved by theFoundation for Cross-Connection Control and HydraulicResearch at the University of Southern California. Assemblyshall be a Watts Series 007.

3 ⁄ 4" (20mm) 007M3QT

2" (50mm) 007M1QT HC

Test Cocks

First CheckModule Assembly

The 007 Series features a modular design concept which facilitatescomplete maintenance and assembly by retaining the spring load.

Second CheckModule Assembly

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,

please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-

out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.

Page 2: Series 007 Specification Sheet

8/8/2019 Series 007 Specification Sheet

http://slidepdf.com/reader/full/series-007-specification-sheet 2/4

Pressure — Temperature1 ⁄ 2" – 2" (15 – 50mm)

 Temperature Range: 33°F – 180°F (0.5°C – 82°C).

Maximum Working Pressure: 175psi (12.1 bar).

21 ⁄ 2" – 3" (65 – 80mm)

 Temperature Range: 33˚F – 110°F (0.5˚C – 43°C) continuous,140°F (60°C) intermittent.

Maximum Working Pressure: 175psi (12.1 bar).

Standards

 ASSE Std. 1015, AWWA Std. C510

IAPMO PS31, CSA B64.5

 Approvals

† ASSE, AWWA, IAPMO, CSA, UPC

▲  Approved by the Foundation for Cross-Connection Controland Hydraulic Research at the University of SouthernCalifornia.

• Models LF and S are not listed.

◆ UL Classified (LF models only) 3 ⁄ 4" – 2" (20 – 50mm)

(except 007M3LF)◆ UL Classified with OSY gate valves

(21 ⁄ 2" and 3" horizontal only.)

* Horizontal and vertical “flow up” approval on all sizes

Dimensions – Weights

As

A

C

B

TRD

*Bs

MODEL SIZE (DN) DIMENSIONS WEIGHT

 A B C D F G R T

in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kgs.

†▲007QT 1 ⁄ 2 15 10 254 45 ⁄ 8 117 27 ⁄ 16 62 — — 5 127 33 ⁄ 8 85 25 ⁄ 16 59 21 ⁄ 16 52 4.5 2

†▲007M3QT 3 ⁄ 4 20 111 ⁄ 8 282 4 102 31 ⁄ 8 79 — — 63 ⁄ 16 157 37 ⁄ 16 87 21 ⁄ 8 54 15 ⁄ 16 33 5 2.3

†▲007M1QT 1 25 131 ⁄ 4 337 51 ⁄ 8 130 4 102 — — 71 ⁄ 2 191 33 ⁄ 8 85 111 ⁄ 16 43 111 ⁄ 16 43 12 5.4

†▲007M2QT 11 ⁄ 4 32 163 ⁄ 8 416 5 127 35 ⁄ 16 84 — — 91 ⁄ 2 241 5 127 3 76 2 50 15 6.8

†▲007M2QT 11 ⁄ 2 40 163 ⁄ 4 425 47 ⁄ 8 124 31 ⁄ 2 89 — — 93 ⁄ 4 248 513 ⁄ 16 148 31 ⁄ 8 79 211 ⁄ 16 68 15.9 7.2

†▲007M1QT 2 50 191 ⁄ 2 495 61 ⁄ 4 159 4 102 — — 133 ⁄ 8 340 61 ⁄ 8 156 37 ⁄ 16 87 211 ⁄ 16 68 25.7 11.7

• 007QT-S 1 ⁄ 2 15 13 330 6 152 27 ⁄ 16 62 3 76 5 127 33 ⁄ 8 85 25 ⁄ 16 59 21 ⁄ 16 52 5.5 2.5

• 007M3QT-S 3 ⁄ 4 20 141 ⁄ 2 368 61 ⁄ 8 156 31 ⁄ 8 79 3 76 63 ⁄ 16 157 37 ⁄ 16 87 21 ⁄ 8 54 15 ⁄ 16 33 6.7 3.1

• 007M1QT-S 1 25 1715 ⁄ 16 157 73 ⁄ 4 197 4 102 31 ⁄ 4 83 71 ⁄ 2 191 33 ⁄ 8 85 111 ⁄ 16 43 111 ⁄ 16 43 14 6.4

• 007M2QT-S 11 ⁄ 4 32 211 ⁄ 2 546 71 ⁄ 16 179 35 ⁄ 16 84 31 ⁄ 2 83 91 ⁄ 2 241 5 127 3 76 2 50 19 8.6

• 007M2QT-S 11 ⁄ 2 40 251 ⁄ 16 637 71 ⁄ 16 179 31 ⁄ 2 89 33 ⁄ 4 95 93 ⁄ 4 248 513 ⁄ 16 148 31 ⁄ 8 79 211 ⁄ 16 68 19.6 8.9

• 007M1QT-S 2 50 271 ⁄ 4 692 83 ⁄ 4 222 4 102 4 102 133 ⁄ 8 340 61 ⁄ 8 156 37 ⁄ 16 87 211 ⁄ 16 68 33.5 15.2

F

*Subscript ‘S’ = strainer model

Suffix HC — Fire Hydrant Fittings dimension “A” = 231 ⁄ 2" (594mm)

Models

Sizes: 1 ⁄ 2" – 2" (15 – 50mm)

Suffix:

S - bronze strainer

LF - without shutoff valves

LH - locking handle ball valves (open position)

SH - stainless steel ball valve handles

HC - 21 ⁄ 2" inlet/outlet fire hydrant fittings (2" valve)

Prefix:

U - Union connections

21

 ⁄ 2" – 3" (65 – 80mm)Suffix:

NRS - non-rising stem resilient seated gate valves

OSY - UL/FM outside stem and yoke resilient seated gatevalves

LF - without shutoff valves

QT-FDA - FDA epoxy coated quarter-turn ball valves

Page 3: Series 007 Specification Sheet

8/8/2019 Series 007 Specification Sheet

http://slidepdf.com/reader/full/series-007-specification-sheet 3/4

MODEL SIZE (DN) DIMENSIONS WEIGHT

 A C E, E1 R

in. mm in. mm in. mm in. mm in. mm lbs. kgs.

007QT-FDA 21 ⁄ 2 65 331 ⁄ 8 841 63 ⁄ 8 162 91 ⁄ 16 230 83 ⁄ 4 222 155 70

▲ 007-NRS 21

 ⁄ 2 65 331

 ⁄ 8 841 93

 ⁄ 8 238 91

 ⁄ 16 230 83

 ⁄ 4 222 155 70▲◆ 007-OSY 21 ⁄ 2 65 331 ⁄ 8 841 163 ⁄ 8 416 91 ⁄ 16 230 83 ⁄ 4 222 158 72

007-QT-FDA 3 80 341 ⁄ 8 867 63 ⁄ 8 162 91 ⁄ 16 230 83 ⁄ 4 222 155 70▲◆ 007-NRS 3 80 341 ⁄ 8 867 101 ⁄ 4 260 91 ⁄ 16 230 83 ⁄ 4 222 185 84

▲ 007-OSY 3 80 341 ⁄ 8 867 187 ⁄ 8 479 91 ⁄ 16 230 83 ⁄ 4 222 185 84

MODEL SIZE (DN) DIMENSIONS

 A 

in. mm in. mm  

U007QT 1 ⁄ 2 15 1213 ⁄ 16 326

U007M2QT 3 ⁄ 4 20 1313 ⁄ 16 350

U007M2QT 1 25 165 ⁄ 8 422

U007M2QT 11 ⁄ 4 32 203 ⁄ 4 527

U007M2QT 11 ⁄ 2 40 211 ⁄ 2 546

U007M1QT 2 50 241 ⁄ 2 622

Strainer Dimensions

SIZE WEIGHT

M N

in. mm in. mm in. mm lbs. kgs.

21 ⁄ 2 65 10 254 61 ⁄ 2 165 28 133* 80 101 ⁄ 8 267 7 178 34 15

*S Models only

A

A

C (open)9" (229mm)

45 ⁄ 16" (109mm)

N

E1 E R

Union Tailpiece Union Tailpiece

Union Nut Union Nut

Dimensions – Weights

Sizes: 2 1 ⁄  2 " – 3" (65 – 80mm) 

1" U007M1QT 

Sizes: 1 ⁄ 2" – 2" (15 – 50mm)

M

Page 4: Series 007 Specification Sheet

8/8/2019 Series 007 Specification Sheet

http://slidepdf.com/reader/full/series-007-specification-sheet 4/4

bars psi

.8 12

.7 10

.5 8

.4 6

.3 4

.1 2

0 0

0 2 4 6 8 10 12 gpm

0 7.6 15.2 22.8 30.4 38 45.6 lpm

5 7.5 10 fps

1.5 2.5 3.0 mps

   P   r   e   s   s   u   r   e

   D   r   o   p

Flow Flow

1 ⁄ 2" (15mm) 11 ⁄ 2" (40mm)

CapacityAs complied from documented Foundation for Cross-Connection Control andHydraulic Research at the University of Southern California lab tests.

* Typical maximum system flow rate (7.5 feet/sec., 2.3 meters/sec.)** UL rated flow

bars psi

1.5 22

1.2 18

.96 14

.69 10

.41 6

.14 2

0 5 10 15 20 25 30 35 40 45 50 gpm

0 19 38 57 76 95 114 133 152 171 190 lpm

7.5 15 lps

2.3 4.6 mps

   P   r   e   s   s   u   r   e

   D   r   o   p

Flow

   P   r   e   s   s   u   r   e

   D   r   o   p

Flow

0 25 50 75 100 125 150 175 200 gpm

0 95 190 285 380 475 570 665 760 lpm

5 7.5 10 15 fps

1.5 2.3 3.0 4.6 mps

3 ⁄ 4" (20mm) 2" (50mm)

bars psi

1.1 16

.8 12

.7 10

.5 8

.4 6

.3 4

.1 2

0 5 10 15 20 25 30 35 40 45 50 55 60 gpm

0 19 38 57 76 95 114 133 152 171 190 209 228 lpm

5 7.5 10 15 fps

1.5 2.3 3.0 4.6 mps

   P   r   e   s   s   u   r   e

   D   r   o   p

Flow

   P   r   e   s   s   u   r   e

   D   r   o   p

Flow

0 25 50 75 100 125 150 175 200 225 250 gpm

0 95 190 285 380 475 570 665 760 855 950 lpm

5 7.5 10 15 fps

1.5 2.3 3.0 4.6 mps

1" (25mm) 21 ⁄ 2" (65mm)

bars psi

1 14

.8 12

.7 10

.5 8

.4 6

.3 4

.1 2

0 0

0 10 20 30 40 50 60 70 80 90 100 110 120 gpm

0 38 76 114 152 190 228 266 304 342 380 418 456 lpm

5 7.5 10 15 fps

1.5 2.3 3.0 4.6 mps

   P   r   e   s   s   u   r   e

   D   r   o   p

Flow

   P   r   e   s   s   u   r   e

   D   r   o   p

Flow

0 25 50 75 100 125 150 175 200 225 250 275 300 325 gpm

0 95 190 285 380 475 570 665 760 855 950 1045 1140 1235 lpm

5 7.5 10 fps1.5 2.3 3.0 mps

11 ⁄ 4" (32mm) 3" (80mm)

bars psi

.8 12

.7 10

.5 8

.4 6

.3 4

.1 2

0 0

bars psi

.8 12

.7 10

.5 8

.4 6

.3 4

.1 2

0 0

bars psi

.7 10

.5 8

.4 6

.3 4

.1 2

0 0

bars psi

.7 10

.5 8

.4 6

.3 4

.1 2

0 0

0 10 20 30 40 50 60 70 80 90 100 110 120 gpm

0 38 76 114 152 190 228 66 304 342 380 418 456 lpm

5 7.5 10 15 fps

1.5 2.5 3.0 4.5 mps

   P   r   e   s   s   u   r   e

   D   r   o   p* *

*

* **

***

*

*

*

ES-007 1103 © 2011 Watts

USA: No. Andover, MA • Tel. (978) 688-1811 • Fax: (978) 794-1848 • www.watts.com

Canada: Burlington, ONT. • (905) 332-4090 • Fax: (905) 332-7068 • www.wattscanada.ca

 A Watt s Water Technolog ies Company