DOC273.53.90701 SC1500, SC4200—Profinet Gateway for Siemens PLC Overview This document shows the integration of Kunbus Profinet Gateway into Siemens Profinet PLC for SC1500 and SC4200 controllers. For other PLC systems, contact technical support. Network connection 1. Complete the Ethernet network connections. Refer to Figure 1 for a connection example. Figure 1 Network connection 1 DIAG LED: flashes red 4 ERROR LED: flashes red 2 LAN connection to PLC 5 LAN connection to Profinet Gateway 3 LAN connection to SC1500 or SC4200 6 LAN connection to PC PLC-Program Install the GSDML file Install the GSDML file from the Kunbus Profinet GW in the PLC as follows: 1. Download the GSDML file. Go to www.kunbus.de and look for "Gateway Modul Profinet IRT" and select "KUNBUS-GW PROFINET XML file". 2. Save and unzip the file in a local folder. 1

Transcript of SC1500, SC4200—Profinet Gateway for Siemens PLC

Page 1: SC1500, SC4200—Profinet Gateway for Siemens PLC

DOC273.53.90701

SC1500, SC4200—Profinet Gateway for Siemens PLC

OverviewThis document shows the integration of Kunbus Profinet Gateway into Siemens Profinet PLC for SC1500 andSC4200 controllers. For other PLC systems, contact technical support.

Network connection

1. Complete the Ethernet network connections. Refer to Figure 1 for a connection example.

Figure 1 Network connection

1 DIAG LED: flashes red 4 ERROR LED: flashes red

2 LAN connection to PLC 5 LAN connection to Profinet Gateway

3 LAN connection to SC1500 or SC4200 6 LAN connection to PC PLC-Program

Install the GSDML fileInstall the GSDML file from the Kunbus Profinet GW in the PLC as follows:

1. Download the GSDML file. Go to www.kunbus.de and look for "Gateway Modul Profinet IRT" and select"KUNBUS-GW PROFINET XML file".

2. Save and unzip the file in a local folder.

1

Page 2: SC1500, SC4200—Profinet Gateway for Siemens PLC

3. Start the PLC Program (e.g., Siemens TIA Portal). Select OPTIONS > MANAGE GENERAL STATIONDESCRIPTION FILES (GSD).

4. Enter the location of the GSDML file on the SOURCE PATH field. Select the file, then click INSTALL.

2

Page 3: SC1500, SC4200—Profinet Gateway for Siemens PLC

5. If the installation is correct, "INSTALLATION WAS COMPLETED SUCCESSFULLY" will show. Click CLOSE.

Put the Profinet GW in the PLC projectPut the Kunbus Profinet Gateway in the PLC project as follows:

1. On the project tree panel, select DEVICES AND NETWORKS (1). On the hardware catalog panel, look forKUNBUS GW-PROFINET element. Use the mouse to drag and drop the element to the main NETWORKOVERVIEW window (2). The preview shows in the overview window.

3

Page 4: SC1500, SC4200—Profinet Gateway for Siemens PLC

2. Make sure that DEVICES AND NETWORKS stays selected on the project tree panel (1). In the NETWORKOVERVIEW window, click PLC1, then KUNBUS GW (2).

3. On the project tree panel, look for DEVICE CONFIGURATION and double-click the element.

4

Page 5: SC1500, SC4200—Profinet Gateway for Siemens PLC

4. On the OPTIONS panel, double-click the elements INPUT XX BYTE to make the list of input bytes on theDEVICE OVERVIEW window.

5. Save the changes on the PLC as follows:

a. On the project tree panel, look for PLC_1.b. Right-click the element and select COMPILE > HARDWARE AND SOFTWARE (ONLY CHANGES).

5

Page 6: SC1500, SC4200—Profinet Gateway for Siemens PLC

6. Load the file on the PLC as follows:

a. On the project tree panel, look for PLC_1.b. Right-click the element and select DOWNLOAD TO DEVICE > HARDWARE AND SOFTWARE (ONLY

CHANGES).

7. The EXTENDED DOWNLOAD TO DEVICE window shows. Click START SEARCH.

6

Page 7: SC1500, SC4200—Profinet Gateway for Siemens PLC

8. Select the PLC device (1), then click LOAD (2).

9. Click LOAD again.

7

Page 8: SC1500, SC4200—Profinet Gateway for Siemens PLC

10. Click FINISH to complete the load on the PLC.

Give a name to the Kunbus Profinet GWGive a name to the Kunbus Profinet GW as follows:

1. On the project tree panel, look for PLC > DISTRIBUTED I/O > PROFINET IO-SYSTEM > KUNBUS-GW-PROFINET. Double-click the ONLINE AND DIAGNOSTICS element (1). On the main window, select ASSIGNIP ADDRESS (2). Then, click ACCESSIBLE DEVICES (3).

8

Page 9: SC1500, SC4200—Profinet Gateway for Siemens PLC

2. The SELECT DEVICE window shows. Click START SEARCH.

3. Select the KUNBUS-GW-PROFINET on the list (1), then click APPLY (2).

9

Page 10: SC1500, SC4200—Profinet Gateway for Siemens PLC

Change the Profinet GW IP-AddressChange the Profinet Gateway IP-Address as follows:

1. Double-click the project tree panel on the ONLINE AND DIAGNOSTICS element (1). On the main window,select ASSIGN NAME (2). Then, select the KUNBUS IP from the accesible devices in the network list (3) andclick ASSIGN NAME (4).

10

Page 11: SC1500, SC4200—Profinet Gateway for Siemens PLC

2. Double-click the project tree panel on the DEVICE CONFIGURATION element (1). On the main windowpreview, double-clik the KUNBUS-GW icon (2). The KUNBUS-GW PROFINET MODULE panel shows on thebottom window. Enter the correct IP-Address for the Kunbus GW (3).

3. Do steps 5 to 10 again from Put the Profinet GW in the PLC project on page 3 to save and load the changesin the PLC.

11

Page 12: SC1500, SC4200—Profinet Gateway for Siemens PLC

HACH COMPANY World HeadquartersP.O. Box 389, Loveland, CO 80539-0389 U.S.A.Tel. (970) 669-3050(800) 227-4224 (U.S.A. only)Fax (970) [email protected]

HACH LANGE GMBHWillstätterstraße 11D-40549 Düsseldorf, GermanyTel. +49 (0) 2 11 52 88-320Fax +49 (0) 2 11 52 [email protected]

HACH LANGE Sàrl6, route de Compois1222 VésenazSWITZERLANDTel. +41 22 594 6400Fax +41 22 594 6499

© Hach Company/Hach Lange GmbH, 2020. All rights reserved. Printed in Germany. 01/2020, Edition 1*DOC273.53.90701*