R801P- Upflow/Horizontal Series 80% A.F.U.E.† Input Rates 50-150 kBTU A.F.U.E. (Annual Fuel Utilization Efficiency) calculated in accordance with Department of Energy test procedures. FORM NO. G22-543 REV. 8 Gas Furnaces R801P (UF/HZ) Series Rely on Ruud.™ Ruud Achiever ® Series Upflow/Horizontal Gas Furnace Ruud Achiever ® Series Upflow/Horizontal Gas Furnace 80% residential Gas Furnace CSA certified 3 way multi poise design UF / HZ PlusOne Diagnostics — 7 Segment LED all units PlusOne Ignition System – DSI for reliability and longevity Heat exchanger is removable for improved serviceability. Alu- minized steel construction provides maximum corrosion resis- tance and thermal fatigue reliability. Solid doors provide quiet operation Solid bottom Insulated blower compartment Low profile 34" cabinet ideal for space constrained installations Blower shelf design – serviceable in all furnace orientations Hemmed edges on cabinets and doors 1/4 turn door knobs for tool less access Integrated Control board features dip switches for easy system set up QR code for quick access to product information from your smart phone or tablet Cabinet air leakage less than 2% at 1 inch H2O when tested in accordance with ASHRAE standard 193

Transcript of Ruud Achieve r Series Upflow /Horizontal Gas Furnace › WebPartners › Product... · R8 01 P-...

Page 1: Ruud Achieve r Series Upflow /Horizontal Gas Furnace › WebPartners › Product... · R8 01 P- Upflow/Horizontal Series 80% A.F.U.E.† Input Rates 5 0-1 50 kBTU †A.F.U.E. (Annual

R801P- Upflow/Horizontal Series80% A.F.U.E.†Input Rates 50-150 kBTU

†A.F.U.E. (Annual Fuel Utilization Efficiency) calculated in accordance withDepartment of Energy test procedures.

FORM NO. G22-543 REV. 8

Gas FurnacesR801P (UF/HZ) Series

Rely on Ruud.™

Ruud Achiever® SeriesUpflow/Horizontal Gas FurnaceRuud Achiever® SeriesUpflow/Horizontal Gas Furnace

• 80% residential Gas Furnace CSA certified• 3 way multi poise design UF / HZ• PlusOne™ Diagnostics — 7 Segment LED all units• PlusOne™ Ignition System – DSI for reliability and longevity• Heat exchanger is removable for improved serviceability. Alu-minized steel construction provides maximum corrosion resis-tance and thermal fatigue reliability.

• Solid doors provide quiet operation• Solid bottom• Insulated blower compartment• Low profile 34" cabinet ideal for space constrained installations

• Blower shelf design – serviceable in all furnace orientations• Hemmed edges on cabinets and doors• 1/4 turn door knobs for tool less access• Integrated Control board features dip switches for easy systemset up

• QR code for quick access to product information from yoursmart phone or tablet

• Cabinet air leakage less than 2% at 1 inch H2O when tested inaccordance with ASHRAE standard 193

Page 2: Ruud Achieve r Series Upflow /Horizontal Gas Furnace › WebPartners › Product... · R8 01 P- Upflow/Horizontal Series 80% A.F.U.E.† Input Rates 5 0-1 50 kBTU †A.F.U.E. (Annual

Rely on Ruud.™2

Standard & Optional Equipment ......................................................................3

Model Features/Physical Data & Specifications ................................................4

Model Number Identification ............................................................................5

Dimensional Data ........................................................................................6-7

Blower Performance Data................................................................................8

Accessories....................................................................................................9

Limited Warranty ..........................................................................................10

TABLE OF CONTENTSTABLE OF CONTENTS

Table of ContentsR801P (UF/HZ) Series

Page 3: Ruud Achieve r Series Upflow /Horizontal Gas Furnace › WebPartners › Product... · R8 01 P- Upflow/Horizontal Series 80% A.F.U.E.† Input Rates 5 0-1 50 kBTU †A.F.U.E. (Annual

Standard & Optional EquipmentR801P (UF/HZ) Series

Rely on Ruud.™ 3

WARNINGTHIS FURNACE IS NOT APPROVED

OR RECOMMENDEDFOR USE IN MOBILE HOMES

DIRECT SPARK IGNITOR

IN-SHOT BURNERS

DRAFT INDUCER MOTOR

PATENTED HEAT EXCHANGER

INTEGRATEDFURNACECONTROL

STANDARD EQUIPMENTCompletely assembled and wired; induced draft; pressure switch;redundant main gas control; blower compartment door safety switch;solid state time on/time off blower control; limit control; manual shut-off valve, pressure regulator for natural and L.P. (propane) gas;transformer; direct drive multi-speed blower motor. Furnaces areequipped with cooling/heating relay and transformer (40VA) ready forair conditioning applications. (Please note: a thermostat is notincluded as standard equipment.) Flame sensor diagnostics.

OPTIONAL EQUIPMENTSide and bottom filter frame assembly. Return air cabinet for all sizes.NOTE: Furnace is not listed for use with fuels other than natural or L.P.

(propane) gas.The complete terms of limited and other warranties are available at oursales office, or through local installer.All models can be converted by a qualified Ruud distributor or localservice dealer to use L.P. (propane) gas without changing burners.Factory approved kits must be used to convert from natural to L.P.(propane) gas and may be ordered as optional accessories from aRuud parts distributor.For L.P. (propane) operation, refer to Conversion Kit Index Form.NOTE: For natural and L.P. (propane) gas models, direct spark ignitionis 100% safety lockout type.

Page 4: Ruud Achieve r Series Upflow /Horizontal Gas Furnace › WebPartners › Product... · R8 01 P- Upflow/Horizontal Series 80% A.F.U.E.† Input Rates 5 0-1 50 kBTU †A.F.U.E. (Annual

Model Features/Physical Data & SpecificationsR801P (UF/HZ) Series

Rely on Ruud.™4

MODEL NUMBERS R801P SERIES R801PA050314M*A R801PA075317M*A R801PA075417M*A R801PA100417M*A R801PA100521M*A R801PA125524M*A R801PA150524M*A

Input-BTU/Hr � 50,000 75,000 75,000 100,000 100,000 125,000 150,000

Heating Capacity BTU/Hr � 40,000 61,000 60,000 80,000 80,000 100,000 120,000

Heat Ext. Static Pressure .18 .20 .20 .28 .28 .28 .28

Blower (D x W) 11 x 6 11 x 7 11 x 7 11 x 7 11 x 10 11 x 10 11 x 10

Motor H.P.–Speed–Type 1/3-4-PSC 1/2-4-PSC 1/2-4-PSC 1/2-4-PSC 1/2-4-PSC 3/4-4-PSC 3/4-4-PSC

Min. Circuit Ampacity 9 10 11 11 11 12 13

Min. Overload Protection Device 15 15 15 15 15 15 15

Max. Overload Protection Device 15 15 15 15 15 15 20

Heating Speed Med-Low Med-High Med-High Med-High Med-Low Med-High Med-High

Cooling Speed High Low Med-Low Med-Low High High High

Cooling CFM @ 70" W.C. E.S.P. 1164 1198 1657 1582 1807 1742 1916

Max. E.S.P. (In. W.C.) 0.8 0.8 0.8 0.8 0.8 0.8 0.8

Temperature Rise Range °F 25-55 25-55 25-55 35-65 35-65 35-65 45-75

Max. Outlet Air Temp. °F 155 155 155 165 180 165 190

Approx. Shipping Weight (Lbs.) 110 110 125 110 140 150 160

AFUE � 80.0% 80.0% 80.0% 80.0% 80.0% 80.0% 80.0%

NOTES: All models are 115V, 60HZ, 1 Ph. Gas connection size for all models is 1/2" N.P.T. � In accordance with D.O.E. test procedures. � See Conversion Kit Index Form for high altitude derate. * S = Standard, X = Low Nox

This furnace does not meet air district requirements of 14 ng/J NOx emissions limit, and thus is subject to a mitigation fee of up to $450. This furnace is not eligible for the Clean Air Furnace Rebate Program: www.CleanAirFurnaceRebate.com.

This furnace is to be installed for propane firing only in air districts requiring 14 ng/J NOx emission limits. Operating in natural gas mode is in violation of these Rules.

• 80% residential Gas Furnace CSA certified• 3 way multi poise design UF / HZ• PlusOne™ Diagnostics — 7 Segment LED all units• PlusOne™ Ignition System – DSI for reliability and longevity• Heat exchanger is removable for improved serviceability.

Aluminized steel construction provides maximum corrosionresistance and thermal fatigue reliability.

• Solid doors provide quiet operation• Solid bottom• Insulated blower compartment

• Low profile 34" cabinet ideal for space constrained installations

• Blower shelf design serviceable in all furnace orientations• Hemmed edges on cabinets and doors• 1/4 turn door knobs for tool less access• Integrated Controls board features dip switches for easy

system set up• QR code for quick access to product information from your

smart phone or tablet

Model Features

Physical Data and Specifications

Page 5: Ruud Achieve r Series Upflow /Horizontal Gas Furnace › WebPartners › Product... · R8 01 P- Upflow/Horizontal Series 80% A.F.U.E.† Input Rates 5 0-1 50 kBTU †A.F.U.E. (Annual

R 80 1 P A 075 4 17 M S A

Ruud 80 =80% AFUE

1 = Single Stage P = PSC Motorw/PremiumCabinet

Design SeriesA = 1st Design

InputBTU/HR [kW]050 = 50,000075 = 75,000100 = 100,000125 = 125,000150 = 150,000

3 = Up to3 Ton

4 = 21/2 to4 Ton

5 = 31/2 to5 Ton

CabinetWidth

14 = 14".017 = 17.5"21 = 21".024 = 24.5"

M = Multi X = Low NOx

S = StandardRevision-Marketing

(A – First TimeRelease)

Model Number IdentificationR801P (UF/HZ) Series

Rely on Ruud.™ 5

Model Number Identification

Page 6: Ruud Achieve r Series Upflow /Horizontal Gas Furnace › WebPartners › Product... · R8 01 P- Upflow/Horizontal Series 80% A.F.U.E.† Input Rates 5 0-1 50 kBTU †A.F.U.E. (Annual

Dimensional DataR801P (UF/HZ) Series

Rely on Ruud.™6

Upflow Application

MODELR801P- A B C D E F

MINIMUM CLEARANCE (IN.) SHIPWGTS.(LBS.)

LEFTSIDE

RIGHTSIDE BACK TOP FRONT VENT

050 141/2 1227/32 105/8 � 111/2 17/8 0 4 � 0 1 3 6 � 85075/

100417 171/2 1611/32 123/8 � 151/2 21/2 0 3 � 0 1 3 6 � 105

100521 211/2 1927/32 141/8 � 181/2 21/2 0 0 0 1 3 6 � 120125 241/2 2311/32 157/8 � 221/2 21/2 0 0 0 1 3 6 � 140150 241/2 2311/32 157/8 � 221/2 21/2 0 0 0 1 3 6 � 150.

NOTES: � May require a 3" to 4" or 3" to 5" adapter. � May be 0" with type B vent. � May be 1" with type B vent. Furnaces must be vented in accordance with the National Fuel Gas Code, ANSI Z223.1 and/or Can/CGA-B149 Installation Codes and in accordance with

local codes.

Dimensional Data: Upflow Model

Page 7: Ruud Achieve r Series Upflow /Horizontal Gas Furnace › WebPartners › Product... · R8 01 P- Upflow/Horizontal Series 80% A.F.U.E.† Input Rates 5 0-1 50 kBTU †A.F.U.E. (Annual

Dimensional DataR801P (UF/HZ) Series

Rely on Ruud.™ 7

Horizontal Application

MODELR801P- A B C D E F

MINIMUM CLEARANCE (IN.) SHIPWGTS.(LBS.)

SUPPLYAIR SIDE

RETURNAIR SIDE BACK TOP FRONT VENT

050 141/2 1227/32 105/8 � 111/2 17/8 0 4 � 0 1 3 6 � 85075/

100417 171/2 1611/32 123/8 � 151/2 21/2 0 3 � 0 1 3 6 � 105

100521 211/2 1927/32 141/8 � 181/2 21/2 0 0 0 1 3 6 � 120125 241/2 2311/32 157/8 � 221/2 21/2 0 0 0 1 3 6 � 140150 241/2 2311/32 157/8 � 221/2 21/2 0 0 0 1 3 6 � 150.

NOTES: � May require a 3" to 4" or 3" to 5" adapter. � May be 0" with type B vent. � May be 1" with type B vent. Furnaces must be vented in accordance with the National Fuel Gas Code, ANSI Z223.1 and/or Can/CGA-B149 Installation Codes and in accordance with

local codes.

Dimensional Data: Horizontal Model

WARNINGTHIS FURNACE IS NOT APPROVED

OR RECOMMENDED FOR INSTALLATIONON ITS BACK, WITH ACCESS DOORS

FACING UPWARDS.

Page 8: Ruud Achieve r Series Upflow /Horizontal Gas Furnace › WebPartners › Product... · R8 01 P- Upflow/Horizontal Series 80% A.F.U.E.† Input Rates 5 0-1 50 kBTU †A.F.U.E. (Annual

Blower Performance DataR801P (UF/HZ) Series

Rely on Ruud.™8

MODELMOTOR H.P. [W]BLOWER SIZE

IN

SPEEDTAP

CFM AIR DELIVERYEXTERNAL STATIC PRESSURE INCHES WATER COLUMN

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8

(-)801PA050314M*A 1/311 x 6

LowMed. LoMed. Hi

High

823103011291361

803101811321353

787100611121331

73297610871297

71892910541264

69189710281232

6518509711164

5938089191117

(-)801PA075317M*A 1/211 x 7

LowMed. LoMed. Hi

High

1008121514211668

977118114081648

935113313721633

893109813261580

854106512991545

823102312471481

77797511981442

73593711521373

(-)801PA075417M*A 1/211 x 7

LowMed. LoMed. Hi

High

1229130815531969

1200126715421924

1181126615161893

1155123314911840

1120120414511803

1078117614171728

1013111313581657

970106213061570

(-)801PA100417M*A 1/211 x 7

LowMed. LoMed. Hi

High

1211130515201874

1183126114981810

1148122514641767

1116118514271686

1077115713871678

1040111313401650

984106812921582

953101212261497

(-)801PA100521M*A 1/211 x 10

LowMed. LoMed. Hi

High

1209143819022071

1182142018832037

1131138618442001

1112135018171962

1051132017531905

976129317001856

929124816361807

867118615471709

(-)801PA125524M*A 3/411 x 10

LowMed. LoMed. Hi

High

1358154117992015

1354151717741989

1331147617461929

1301145317121902

1250141616911862

1224137116291815

1154133915541742

1089127714951665

(-)801PA150524M*A 3/411 x 10

LowMed. LoMed. Hi

High

1411160618892178

1395157918912160

1370156918492105

1334153718282067

1310149917642024

1252146817171976

1220140716591916

1150134616091832

Note: Bold data is factory heating tap.Table represents blower performance data WITHOUT filters.

Blower Performance Data

Page 9: Ruud Achieve r Series Upflow /Horizontal Gas Furnace › WebPartners › Product... · R8 01 P- Upflow/Horizontal Series 80% A.F.U.E.† Input Rates 5 0-1 50 kBTU †A.F.U.E. (Annual

AccessoriesR801P (UF/HZ) Series

Rely on Ruud.™ 9

FILTER RACK FILTER SIZES* INCHES

MODELRXGF-CB(UPFLOW/

HORIZONTAL)

RXGF-CD(UPFLOW)

SIDE RETURN

R801PA050 121/4 x 25 153/4 x 25R801PA075/

R801PA100417 153/4 x 25 153/4 x 25

R801PA100521 191/4 x 25 153/4 x 25R801PA125 223/4 x 25 153/4 x 25R801PA150 223/4 x 25 153/4 x 25

WARNING: IMPORTANT NOTICE

A SOLID METAL BASE PLATE (SEE TABLE) MUST BE IN PLACE WHEN THEFURNACE IS INSTALLED WITH SIDE AIR RETURN DUCTS. FAILURE TOINSTALL A BASE PLATE COULD CAUSE PRODUCTS OF COMBUSTION TOBE CIRCULATED INTO THE LIVING SPACE AND CREATE POTENTIALLYHAZARDOUS CONDITIONS.

FURNACE SOLID BASE BASE WIDTH BOTTOM PLATE NO. PLATE SIZE IN. KIT NO. IN.141/2 RXGB-D14 AE-61874-01 115/8 x 239/16

171/2 RXGB-D17 AE-61874-02 151/8 x 239/16

211/2 RXGB-D21 AE-61874-03 185/8 x 239/16

241/2 RXGB-D24 AE-61874-04 255/8 x 239/16

FOR HIGH ALTITUDES:OPTION CODE FOR HIGH ALTITUDE: U.S. & CanadaNone required for high altitudes.

HIGH ALTITUDE CONVERSION KITS: U.S. & CanadaNone required for high altitudes.

80+ HIGH ALTITUDE INSTRUCTIONS CAUTION: Always follow National Fuel Gas Code (NFGC) guidelineswhen converting for high altitudes.

High altitude option codes are not required for these models.However, the burner orifice size needs to be recalculated and verifiedat elevations above 2000 ft. See Installation Instructions for moreinformation.

NOTE: For Canadian installations only, an optional derate (manifoldgas pressure reduction) method may be used to adjust thefurnace for altitude. See Installation Instructions for moreinformation. This optional method may NOT be used for U.S.installations.

SIDE RETURN FILTER RACK: RXGF-CDBOTTOM RETURN FILTER RACK FORUPFLOW APPLICATION: RXGF-CB

INDOOR COIL CASINGSMODEL

NUMBER

RXBC-D14AIRXBC-D17AIRXBC-D21AIRXBC-D21BIRXBC-D24AI

4" FLUE ADAPTER: RXGW-C01

Page 10: Ruud Achieve r Series Upflow /Horizontal Gas Furnace › WebPartners › Product... · R8 01 P- Upflow/Horizontal Series 80% A.F.U.E.† Input Rates 5 0-1 50 kBTU †A.F.U.E. (Annual

Limited WarrantyR801P (UF/HZ) Series

Rely on Ruud.™10

GENERAL TERMS OF LIMITED WARRANTY*Ruud will furnish a replacement for any part of this productwhich fails in normal use and service within the applicableperiod stated, in accordance with the terms of the limited warranty.*For complete details of the Limited and Conditional Warranties,including applicable terms and conditions, contact your local contractoror the Manufacturer for a copy of the product warranty certificate.

Conditional Parts* (Registration Required) ......Ten (10) YearsHeat Exchanger ......................................Twenty (20) Years

Page 11: Ruud Achieve r Series Upflow /Horizontal Gas Furnace › WebPartners › Product... · R8 01 P- Upflow/Horizontal Series 80% A.F.U.E.† Input Rates 5 0-1 50 kBTU †A.F.U.E. (Annual

NotesR801P (UF/HZ) Series

Rely on Ruud.™ 11

Page 12: Ruud Achieve r Series Upflow /Horizontal Gas Furnace › WebPartners › Product... · R8 01 P- Upflow/Horizontal Series 80% A.F.U.E.† Input Rates 5 0-1 50 kBTU †A.F.U.E. (Annual

Rely on Ruud.™PRINTED IN U.S.A. 3/19 QG FORM NO. G22-543 REV. 8

Rely on Ruud.™

In keeping with its policy of continuous progress and product improvement, Ruud reserves the right to make changes without notice.