ROAD LIGHTING PELINDO III (GRESIK) SECTION TYPICAL ROW 22 TYPE A Date: 05-02-2012 Designer: Syaiful Fikri CalcuLuX Road 7.6.1.0 The nominal values shown in this report are the result of precision calculations, based upon precisely positioned luminaires in a fixed relationship to each other and to the area under examination. In practice the values may vary due to tolerances on luminaires, luminaire positioning, reflection properties and electrical supply.

description

L

Transcript of Road Lighting Pelindo III Gresik Section Row 22 Type A

Page 1: Road Lighting Pelindo III Gresik Section Row 22 Type A

ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE ADate: 05-02-2012

Designer: Syaiful Fikri

CalcuLuX Road 7.6.1.0

The nominal values shown in this report are the result of precision calculations, based upon precisely positioned luminaires in a fixedrelationship to each other and to the area under examination. In practice the values may vary due to tolerances on luminaires, luminairepositioning, reflection properties and electrical supply.

Page 2: Road Lighting Pelindo III Gresik Section Row 22 Type A

ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE A Date: 05-02-2012

1. Project Description

1.1 3-D Project Overview

C BRP372 LED141NW 150W 22

C

C

X

YZ

Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 2/17

Page 3: Road Lighting Pelindo III Gresik Section Row 22 Type A

ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE A Date: 05-02-2012

1.2 Top Project Overview

C BRP372 LED141NW 150W 22

-16 -11 -6 -1 4 9 14 19 24

X(m)

-6-1

49

1419

2429

3439

44Y

(m)

C

C

Scale1:250

Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 3/17

Page 4: Road Lighting Pelindo III Gresik Section Row 22 Type A

ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE A Date: 05-02-2012

2. Summary

2.1 Main Road

Luminaire Type : BRP372 LED141NW 150W 220-240V DM2ELamp Type : 1 * Luxeon R x72LEDs Ra75.1Lamp Flux : 15163 lumenTilt90 (T) : 5.0 degGrid Method : CEN LuminanceProject Maintenance Factor : 0.90

T

O

H

W

S

Carriageway : Single CarriagewayRoad Width (W) : 10.00 mNumber of Lanes : 3Reflection Table : CIE C1Q0 of Table : 0.100Maintenance Factor : 0.90Installation : Single Sided LeftHeight (H) : 13.00 mSpacing (S) : 40.00 mOverhang (O) : 2.00 m

Overall quality figures for the above road scheme.

LuminanceAverage = 1.71 cd/m2Minimum = 1.22 cd/m2Maximum = 2.43 cd/m2Minimum/Maximum = 0.50Minimum/Average = 0.69Ul = 0.60

GlareTI = 5.9 %

Horizontal IlluminanceAverage = 17.1 luxMinimum = 9.9 luxMaximum = 26.3 luxMinimum/Maximum = 0.37

Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 4/17

Page 5: Road Lighting Pelindo III Gresik Section Row 22 Type A

ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE A Date: 05-02-2012

3. Calculation Results

3.1 Main L (O1): Graphical Table

TI ( 1.67,-31.63, 1.50) = 5.4%Grid : Main at Z = -0.00 mCalculation : Luminance towards CEN Observer (O1) (1.67,

-60.00, 1.50) (cd/m2)Road Surface : CIE C1 with Q0 = 0.100

Average Min/Ave Min/Max Project maintenance factor 1.71 0.75 0.53 0.90

C BRP372 LED141NW 150W 22

-16 -11 -6 -1 4 9 14 19 24

X(m)

-41

611

1621

2631

3641

Y(m

)

C

C

1.7

1.6

1.5

1.4

1.4

1.3

1.3

1.3

1.4

1.5

1.5

1.6

1.7

1.7

1.8

1.7

1.6

1.5

1.4

1.3

1.3

1.3

1.4

1.5

1.6

1.7

1.8

1.8

2.0

1.8

1.7

1.6

1.5

1.4

1.3

1.4

1.4

1.6

1.6

1.8

1.9

2.0

2.1

2.0

1.8

1.6

1.6

1.4

1.4

1.4

1.4

1.6

1.7

1.9

2.0

2.1

2.3

2.1

1.8

1.7

1.6

1.5

1.4

1.5

1.5

1.7

1.7

1.9

2.1

2.3

2.3

2.1

1.9

1.7

1.6

1.5

1.5

1.5

1.6

1.7

1.8

2.0

2.2

2.3

2.4

2.2

1.9

1.7

1.6

1.5

1.5

1.5

1.6

1.7

1.9

2.1

2.3

2.4

2.3

2.1

1.9

1.7

1.6

1.5

1.4

1.5

1.5

1.7

1.8

2.0

2.3

2.4

2.1

2.0

1.7

1.5

1.4

1.3

1.3

1.3

1.4

1.5

1.7

1.9

2.1

2.2

Scale1:250

Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 5/17

Page 6: Road Lighting Pelindo III Gresik Section Row 22 Type A

ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE A Date: 05-02-2012

3.2 Main L (O1): Iso Contour

TI ( 1.67,-31.63, 1.50) = 5.4%Grid : Main at Z = -0.00 mCalculation : Luminance towards CEN Observer (O1) (1.67,

-60.00, 1.50) (cd/m2)Road Surface : CIE C1 with Q0 = 0.100

Average Min/Ave Min/Max Project maintenance factor 1.71 0.75 0.53 0.90

C BRP372 LED141NW 150W 22

-16 -11 -6 -1 4 9 14 19 24

X(m)

-41

611

1621

2631

3641

Y(m

)

1.5

1.5

1.75

1.75

2

2

2

2.25

2.25

C

C

Scale1:250

Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 6/17

Page 7: Road Lighting Pelindo III Gresik Section Row 22 Type A

ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE A Date: 05-02-2012

3.3 Main L (O1): Filled Iso Contour

TI ( 1.67,-31.63, 1.50) = 5.4%Grid : Main at Z = -0.00 mCalculation : Luminance towards CEN Observer (O1) (1.67,

-60.00, 1.50) (cd/m2)Road Surface : CIE C1 with Q0 = 0.100

Average Min/Ave Min/Max Project maintenance factor 1.71 0.75 0.53 0.90

C BRP372 LED141NW 150W 22

2.25

2

1.75

1.5

-10 -5 0 5 10 15 20

X(m)

-41

611

1621

2631

3641

Y(m

)

C

C

Scale1:250

Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 7/17

Page 8: Road Lighting Pelindo III Gresik Section Row 22 Type A

ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE A Date: 05-02-2012

3.4 Main L (O2): Graphical Table

TI ( 5.00,-31.63, 1.50) = 5.9%Grid : Main at Z = -0.00 mCalculation : Luminance towards CEN Observer (O2) (5.00,

-60.00, 1.50) (cd/m2)Road Surface : CIE C1 with Q0 = 0.100

Average Min/Ave Min/Max Project maintenance factor 1.74 0.72 0.51 0.90

C BRP372 LED141NW 150W 22

-16 -11 -6 -1 4 9 14 19 24

X(m)

-41

611

1621

2631

3641

Y(m

)

C

C

1.7

1.7

1.5

1.4

1.4

1.3

1.3

1.3

1.4

1.5

1.5

1.6

1.7

1.7

1.9

1.8

1.6

1.5

1.5

1.4

1.4

1.4

1.4

1.6

1.6

1.7

1.8

1.9

2.0

1.9

1.7

1.6

1.6

1.4

1.4

1.4

1.5

1.6

1.7

1.8

1.9

2.0

2.2

2.0

1.8

1.7

1.6

1.5

1.4

1.5

1.5

1.7

1.8

1.9

2.1

2.2

2.3

2.1

1.9

1.7

1.6

1.5

1.5

1.5

1.6

1.7

1.8

2.0

2.2

2.4

2.4

2.2

1.9

1.7

1.7

1.5

1.5

1.5

1.6

1.8

1.9

2.1

2.3

2.4

2.4

2.2

1.9

1.7

1.6

1.5

1.5

1.5

1.6

1.8

1.9

2.1

2.3

2.5

2.3

2.1

1.8

1.7

1.5

1.4

1.4

1.4

1.5

1.6

1.8

2.0

2.2

2.3

2.1

1.9

1.7

1.5

1.4

1.3

1.3

1.3

1.3

1.5

1.6

1.8

2.0

2.1

Scale1:250

Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 8/17

Page 9: Road Lighting Pelindo III Gresik Section Row 22 Type A

ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE A Date: 05-02-2012

3.5 Main L (O2): Iso Contour

TI ( 5.00,-31.63, 1.50) = 5.9%Grid : Main at Z = -0.00 mCalculation : Luminance towards CEN Observer (O2) (5.00,

-60.00, 1.50) (cd/m2)Road Surface : CIE C1 with Q0 = 0.100

Average Min/Ave Min/Max Project maintenance factor 1.74 0.72 0.51 0.90

C BRP372 LED141NW 150W 22

-16 -11 -6 -1 4 9 14 19 24

X(m)

-41

611

1621

2631

3641

Y(m

)

1.5

1.51.

75

1.75

2

2

2

2.25

2.25

C

C

Scale1:250

Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 9/17

Page 10: Road Lighting Pelindo III Gresik Section Row 22 Type A

ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE A Date: 05-02-2012

3.6 Main L (O2): Filled Iso Contour

TI ( 5.00,-31.63, 1.50) = 5.9%Grid : Main at Z = -0.00 mCalculation : Luminance towards CEN Observer (O2) (5.00,

-60.00, 1.50) (cd/m2)Road Surface : CIE C1 with Q0 = 0.100

Average Min/Ave Min/Max Project maintenance factor 1.74 0.72 0.51 0.90

C BRP372 LED141NW 150W 22

2.25

2

1.75

1.5

-10 -5 0 5 10 15 20

X(m)

-41

611

1621

2631

3641

Y(m

)

C

C

Scale1:250

Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 10/17

Page 11: Road Lighting Pelindo III Gresik Section Row 22 Type A

ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE A Date: 05-02-2012

3.7 Main L (O3): Graphical Table

TI ( 8.33,-31.63, 1.50) = 5.2%Grid : Main at Z = -0.00 mCalculation : Luminance towards CEN Observer (O3) (8.33,

-60.00, 1.50) (cd/m2)Road Surface : CIE C1 with Q0 = 0.100

Average Min/Ave Min/Max Project maintenance factor 1.75 0.69 0.50 0.90

C BRP372 LED141NW 150W 22

-16 -11 -6 -1 4 9 14 19 24

X(m)

-41

611

1621

2631

3641

Y(m

)

C

C

1.7

1.7

1.5

1.5

1.4

1.4

1.4

1.4

1.5

1.5

1.6

1.6

1.8

1.8

1.9

1.8

1.6

1.6

1.5

1.4

1.4

1.4

1.5

1.6

1.7

1.8

1.9

1.9

2.0

1.9

1.8

1.6

1.6

1.5

1.4

1.5

1.5

1.7

1.8

1.9

2.0

2.1

2.2

2.0

1.8

1.7

1.7

1.5

1.5

1.5

1.6

1.8

1.8

2.0

2.2

2.3

2.4

2.2

1.9

1.7

1.7

1.5

1.5

1.5

1.6

1.8

1.9

2.1

2.3

2.4

2.4

2.2

1.9

1.7

1.7

1.6

1.5

1.6

1.6

1.8

1.9

2.1

2.3

2.4

2.4

2.2

1.9

1.7

1.6

1.5

1.5

1.5

1.6

1.7

1.8

2.0

2.2

2.4

2.3

2.1

1.8

1.6

1.5

1.4

1.4

1.4

1.5

1.6

1.7

1.9

2.1

2.2

2.1

1.9

1.7

1.5

1.4

1.3

1.2

1.2

1.3

1.4

1.6

1.7

1.9

2.1

Scale1:250

Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 11/17

Page 12: Road Lighting Pelindo III Gresik Section Row 22 Type A

ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE A Date: 05-02-2012

3.8 Main L (O3): Iso Contour

TI ( 8.33,-31.63, 1.50) = 5.2%Grid : Main at Z = -0.00 mCalculation : Luminance towards CEN Observer (O3) (8.33,

-60.00, 1.50) (cd/m2)Road Surface : CIE C1 with Q0 = 0.100

Average Min/Ave Min/Max Project maintenance factor 1.75 0.69 0.50 0.90

C BRP372 LED141NW 150W 22

-16 -11 -6 -1 4 9 14 19 24

X(m)

-41

611

1621

2631

3641

Y(m

) 1.25

1.5

1.51.

75

1.75

2

2

2

2

2.25

2.25

C

C

Scale1:250

Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 12/17

Page 13: Road Lighting Pelindo III Gresik Section Row 22 Type A

ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE A Date: 05-02-2012

3.9 Main L (O3): Filled Iso Contour

TI ( 8.33,-31.63, 1.50) = 5.2%Grid : Main at Z = -0.00 mCalculation : Luminance towards CEN Observer (O3) (8.33,

-60.00, 1.50) (cd/m2)Road Surface : CIE C1 with Q0 = 0.100

Average Min/Ave Min/Max Project maintenance factor 1.75 0.69 0.50 0.90

C BRP372 LED141NW 150W 22

2.25

2

1.75

1.5

1.25

-10 -5 0 5 10 15 20

X(m)

-41

611

1621

2631

3641

Y(m

)

C

C

Scale1:250

Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 13/17

Page 14: Road Lighting Pelindo III Gresik Section Row 22 Type A

ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE A Date: 05-02-2012

3.10 Main Eh: Graphical Table

Grid : Main at Z = -0.00 mCalculation : Horizontal Illuminance (lux)

Average Min/Ave Min/Max Project maintenance factor 17.1 0.58 0.37 0.90

C BRP372 LED141NW 150W 22

-16 -11 -6 -1 4 9 14 19 24

X(m)

-6-1

49

1419

2429

3439

44Y

(m)

C

C

20

19

17

16

15

13

13

13

13

15

16

17

19

20

22

20

18

16

15

13

13

13

13

15

16

18

20

22

23

21

19

16

15

13

12

12

13

15

16

19

21

23

24

22

19

16

15

13

12

12

13

15

16

19

22

24

25

23

19

16

15

13

12

12

13

15

16

19

23

25

26

23

20

16

15

12

12

12

12

15

16

20

23

26

26

23

20

16

14

12

11

11

12

14

16

20

23

26

26

23

19

16

14

12

11

11

12

14

16

19

23

26

24

22

18

15

13

11

10

10

11

13

15

18

22

24

Scale1:250

Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 14/17

Page 15: Road Lighting Pelindo III Gresik Section Row 22 Type A

ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE A Date: 05-02-2012

3.11 Main Eh: Iso Contour

Grid : Main at Z = -0.00 mCalculation : Horizontal Illuminance (lux)

Average Min/Ave Min/Max Project maintenance factor 17.1 0.58 0.37 0.90

C BRP372 LED141NW 150W 22

-16 -11 -6 -1 4 9 14 19 24

X(m)

-6-1

49

1419

2429

3439

44Y

(m) 10

12.5

15

15

17.5

17.5

20

2022.5

22.5

25

25

C

C

Scale1:250

Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 15/17

Page 16: Road Lighting Pelindo III Gresik Section Row 22 Type A

ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE A Date: 05-02-2012

3.12 Main Eh: Filled Iso Contour

Grid : Main at Z = -0.00 mCalculation : Horizontal Illuminance (lux)

Average Min/Ave Min/Max Project maintenance factor 17.1 0.58 0.37 0.90

C BRP372 LED141NW 150W 22

25

22.5

20

17.5

15

12.5

10

-10 -5 0 5 10 15 20

X(m)

-6-1

49

1419

2429

3439

44Y

(m)

C

C

Scale1:250

Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 16/17

Page 17: Road Lighting Pelindo III Gresik Section Row 22 Type A

ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE A Date: 05-02-2012

4. Luminaire Details

4.1 Project Luminaires

Xceed Medium FOT Sample(72LED700)BRP372 LED141NW 150W 220-240V 1xLuxeon R x72LEDs Ra75.1/3934

Light output ratios DLOR : 1.00 ULOR : 0.00 TLOR : 1.00Ballast : 700mA Global DriverLamp flux : 15163 lmLuminaire wattage : 154.0 WMeasurement code : LVC1121498

Note: Luminaire data not from database.

750

750

0o 30o30o

60o 60o

90o 90o

120o 120o150o 150o180o

C = 180o C = 0o C = 270o C = 90o C = 195o Imax C = 15o

Luminous Intensity Diagram (candela/1000 lumen)

Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 17/17