1Rittal Cooling Solutions – A. Tropp
2Rittal Cooling Solutions – A. Tropp
Rittal Cooling Solutions Presented by Adam Tropp
3Rittal Cooling Solutions – A. Tropp
Agenda
Cooling StrategiesAisle ContainmentChimney SolutionAirstream Management
Rittal Liquid Cooling PackagesData Monitoring
4Rittal Cooling Solutions – A. Tropp
Cooling strategies. Aisle containment.
An economical solution to improve the performance of any cooling system.
Benefits• Increased airstream management• Supply air and return air do not mix• Uniform distribution of cold air• Higher delta T for increased efficiency• Modular, scalable, and retrofittable• Can be used with perimeter-based cooling• Can be used with row-based cooling
5Rittal Cooling Solutions – A. Tropp
Cooling strategies. Aisle containment.
An economical solution to improve the performance of any cooling system.
When to use aisle containment• Issues with bypass air• Issues with hot air recirculation• Issues with hot spots• Issues with uneven cold air distribution• Issues with maximum cooling capacity
* Image from 42U.com
6Rittal Cooling Solutions – A. Tropp
Cooling strategies. Aisle containment.
Hot and cold air distribution with and without containment.
7Rittal Cooling Solutions – A. Tropp
Cooling strategies. Aisle containment.
An economical solution to improve the performance of any cooling system.
Why aisle containment works• Prevents hot and cold air from mixing• Higher supply air temperatures
• Increased energy savings!• Increased economizer hours
• Increased energy savings!• Increased cooling efficiency
• Increased energy savings!
8Rittal Cooling Solutions – A. Tropp
Cooling strategies. Aisle containment.
An economical solution to improve the performance of any cooling system.
Cold aisle containment benefits• Precise, targeted cooling• Consistent air temperature
• Eliminates hot spots• No raised floor required• Minimal infrastructure requirements
• Creates easy retrofit installations• Using only doors shows increased efficiency
• Prevents end of row recirculation
9Rittal Cooling Solutions – A. Tropp
Cooling strategies. Aisle containment.
An economical solution to improve the performance of any cooling system.
Hot aisle containment benefits• Work environment is flooded with cold air• Hot air can be ducted back to CRAC
• Increased efficiency• Consistent air temperature
• Eliminates hot spots
* Image from 42U.com
10Rittal Cooling Solutions – A. Tropp
Cooling strategies. Aisle containment.
* Image from EDS – Plano TX
* Image from CoreSite – Los Angeles CA
11Rittal Cooling Solutions – A. Tropp
Cooling strategies. Aisle containment.
* Images from State Department – Richmond VA
12Rittal Cooling Solutions – A. Tropp
Agenda
Cooling StrategiesAisle ContainmentChimney SolutionAirstream Management
Rittal Liquid Cooling PackagesData Monitoring
13Rittal Cooling Solutions – A. Tropp
Cooling strategies. Chimney solution.
Deployment Requirements• Return vents for equipment not equipped with chimneys• Return extensions for CRAC units • Chimney installed on rack• Drop ceiling installed in data center
Benefits• Increased airflow efficiency• Minimal hot/cold air intermixing• Increased cooling capacity• Hot aisle containment
14Rittal Cooling Solutions – A. Tropp
Cooling strategies. Chimney solution.
15Rittal Cooling Solutions – A. Tropp
Cooling strategies. Chimney solution.
16Rittal Cooling Solutions – A. Tropp
Agenda
Cooling StrategiesAisle ContainmentChimney SolutionAirstream Management
Rittal Liquid Cooling PackagesData Monitoring
17Rittal Cooling Solutions – A. Tropp
Cooling strategies. Airstream management.
Rack-Level Air Containment
Benefits• Increased airflow efficiency• Minimal hot/cold air intermixing• Can be set into traditional raised floor• Passive components• No energy consumption• Reduce point of failure• Can accommodate blade chassis• Cold aisle containment
18Rittal Cooling Solutions – A. Tropp
Cooling strategies. Airstream management.
19Rittal Cooling Solutions – A. Tropp
Cooling strategies. Airstream management.
20Rittal Cooling Solutions – A. Tropp
Agenda
Cooling StrategiesRittal Liquid Cooling Packages
LCP Extend & LCP Passive CWLCP+ General FeaturesLCP+ CoolingApplications
Data Monitoring
21Rittal Cooling Solutions – A. Tropp
Rittal Liquid Cooling Packages.
HybridLCP Hybrid EC
Open Loop LCP Inline EC
Closed LoopLCP+ EC
0 kW 10 15 20 25 30 35 kW
0 Tons 2.8 4.3 5.7 10.0 Tons8.57.1
Rear DoorLCP Passive CW
22Rittal Cooling Solutions – A. Tropp
Rittal Liquid Cooling Packages. LCP Passive CW.
Features• Passive rear doors are designed to be
installed as a replacement rear door for the racks on which they are installed
• A passive rear door simply has the fan system removed from the equation, allowing the server fans to do the necessary work of moving the air through the heat exchanger
• Maximum energy efficiency as there is no electrical power consumption
• Uses chilled water as the rejection medium
• HxWxD: 80x24x6 in. (2000x600x170 mm)• 20 kW cooling capacity
* Image from Sun Microsystems
23Rittal Cooling Solutions – A. Tropp
Agenda
Cooling StrategiesRittal Liquid Cooling Packages
LCP Extend & LCP Passive CWLCP+ CoolingLCP+ General FeaturesApplications
Data Monitoring
24Rittal Cooling Solutions – A. Tropp
Rittal Liquid Cooling Packages. LCP+ Cooling.
Open Loop (Inline)• Open front• Open return• More units are required
to achieve N+1
Hybrid System• Open front• Closed return• Better redundancy can
be accomplished at row and room level
Closed Loop• Closed front• Closed return• Ultra high density• Door release option
must be used
25Rittal Cooling Solutions – A. Tropp
Rittal Liquid Cooling Packages. LCP+ General Features.
Features• System Capacity: 30 kW Typical• High efficiency heat exchanger developed to
operate with 59°F chilled water• Microprocessor controller• LCD touch screen• 2-way modulating valve• 6 EC fans, N+1 design, hot-swappable• Can be monitored remotely via web browser
or SNMP via TCP/IP• HxWxD: 80x12x48 in. (2000x300x1200 mm)
• 42 in. (1050 mm) depth also available• Available in sand texture black or IBM white
26Rittal Cooling Solutions – A. Tropp
Rittal Liquid Cooling Packages.
27Rittal Cooling Solutions – A. Tropp
Rittal Liquid Cooling Packages. LCP+ General Features.
Heat Exchanger• 9.5” deep x 12.5” wide x 70” tall
28Rittal Cooling Solutions – A. Tropp
Rittal Liquid Cooling Packages. LCP+ General Features.
Electrical Design• Wide input voltage range
• 208V, 230V, 400V• EC fan technology
• 1 year ago: step motor technology• Rated current: 6.5A
• 1 year ago: 11.5A• Power rating: 1050W
• 1 year ago: 2650W• 5 pole terminal block• Fuses are easy accessible by
opening the rear door• Every unit comes high voltage tested• EMC tested configuration
29Rittal Cooling Solutions – A. Tropp
Rittal Liquid Cooling Packages. LCP+ General Features.
30Rittal Cooling Solutions – A. Tropp
Rittal Liquid Cooling Packages. LCP+ General Features.
Features Summary• Auto-Temperature-Control:
Cold air inlet temperature automatically controlled via integrated controller board
• Monitoring: Integrated controller with Rittal Basic CMC
• Intelligent sensor network: Fault tolerant sensors for water inlet/outlet temperatures, air inlet/outlet temperatures, water flow rates, leakage, etc.
• Fault tolerant controller boards and systems: In the case of electronic failures the valves will open and the fans will provide maximum airflow
• Alarm / events / sensor logging
• Three fan controller boards + one water controller board (individually fused)
31Rittal Cooling Solutions – A. Tropp
Agenda
Cooling StrategiesRittal Liquid Cooling Packages and their Energy Efficiency
LCP Extend & LCP Passive CWLCP+ CoolingLCP+ General FeaturesApplications
Data Monitoring
32Rittal Cooling Solutions – A. Tropp
Rittal Liquid Cooling Packages. Applications.
Low Density (<5 kW)• Application
• Networking switches, half-equipped server racks
• Products• Fans• Baffles• Aisle Containment
Mid Density (5-10 kW)• Application
• Server and small blade servers
• Products• LCP Inline• LCP Hybrid• Aisle Containment• Chimney
High Density (10+ kW)• Application
• Blade servers and fully equipped server racks
• Products• LCP Inline• LCP Hybrid• LCP+ Closed Loop• Aisle Containment
33Rittal Cooling Solutions – A. Tropp
Customers Using the LCP Family.
34Rittal Cooling Solutions – A. Tropp
Agenda
Cooling StrategiesRittal Liquid Cooling PackagesData Monitoring
CMC IIIRiZone
35Rittal Cooling Solutions – A. Tropp
Data monitoring. CMC III.
CMC 3rd generation, the monitoring system for IT, building services, and industry.
Monitors and measures up to 32 sensors.• Enclosure and room temperature• Humidity• Vandalism• Air flow• Differential pressure• Current, voltage, frequency, and energy• Cooling units
36Rittal Cooling Solutions – A. Tropp
Data monitoring. CMC III.
CMC 3rd generation, the monitoring system for IT, building services, and industry.
Control system for:• Handles / Doors• Fans• Sockets
Control system with:• 8 digital inputs• 4 relay outputs• 2 energy outputs
37Rittal Cooling Solutions – A. Tropp
Data monitoring. RiZone.
RiZone is Rittal software for the monitoring and management of the IT infrastructure in data centers
• Power supply and reliability• Cooling output and distribution• Rack status• Data center security (access,
temperature, etc.)• Efficiency and energy
consumption
OptimizationEfficiency
38Rittal Cooling Solutions – A. Tropp
Data monitoring. RiZone.
RiZone Functions• How efficient is the data center?• How efficient is the UPS?• How efficient is the chiller?• How efficient is the cooling chain?• How efficient is the power chain?• What is the actual monthly / yearly power consumption?
RiZone Benefits• Higher visibility of systems inside the data center• Historical data trending• Making the data center more reliable and efficient
39Rittal Cooling Solutions – A. Tropp
Data monitoring. RiZone.
Definition of PUE/DCiE
DCiE = Data Center Infrastructure Efficiency
IT Load (Server-Load)
Entire Electrical Load of Data Center
PUE = Power Utilization Effectiveness
Entire Electrical Load of Data Center
IT Load (Server-Load)
DCiE =
PUE =
PUE and Total Power Consumption are the basis for Data Center optimization.
40Rittal Cooling Solutions – A. Tropp
Data monitoring. RiZone.
• Server,• Infrastructure,• And Total Power Consumption
• PUE• CO2 -Emission• Power Costs
41Rittal Cooling Solutions – A. Tropp
Any Questions?
Thank you for attending and listening.