Page 1: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

1Rittal Cooling Solutions – A. Tropp

Page 2: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

2Rittal Cooling Solutions – A. Tropp

Rittal Cooling Solutions Presented by Adam Tropp

Page 3: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

3Rittal Cooling Solutions – A. Tropp

Agenda

Cooling StrategiesAisle ContainmentChimney SolutionAirstream Management

Rittal Liquid Cooling PackagesData Monitoring

Page 4: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

4Rittal Cooling Solutions – A. Tropp

Cooling strategies. Aisle containment.

An economical solution to improve the performance of any cooling system.

Benefits• Increased airstream management• Supply air and return air do not mix• Uniform distribution of cold air• Higher delta T for increased efficiency• Modular, scalable, and retrofittable• Can be used with perimeter-based cooling• Can be used with row-based cooling

Page 5: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

5Rittal Cooling Solutions – A. Tropp

Cooling strategies. Aisle containment.

An economical solution to improve the performance of any cooling system.

When to use aisle containment• Issues with bypass air• Issues with hot air recirculation• Issues with hot spots• Issues with uneven cold air distribution• Issues with maximum cooling capacity

* Image from 42U.com

Page 6: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

6Rittal Cooling Solutions – A. Tropp

Cooling strategies. Aisle containment.

Hot and cold air distribution with and without containment.

Page 7: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

7Rittal Cooling Solutions – A. Tropp

Cooling strategies. Aisle containment.

An economical solution to improve the performance of any cooling system.

Why aisle containment works• Prevents hot and cold air from mixing• Higher supply air temperatures

• Increased energy savings!• Increased economizer hours

• Increased energy savings!• Increased cooling efficiency

• Increased energy savings!

Page 8: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

8Rittal Cooling Solutions – A. Tropp

Cooling strategies. Aisle containment.

An economical solution to improve the performance of any cooling system.

Cold aisle containment benefits• Precise, targeted cooling• Consistent air temperature

• Eliminates hot spots• No raised floor required• Minimal infrastructure requirements

• Creates easy retrofit installations• Using only doors shows increased efficiency

• Prevents end of row recirculation

Page 9: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

9Rittal Cooling Solutions – A. Tropp

Cooling strategies. Aisle containment.

An economical solution to improve the performance of any cooling system.

Hot aisle containment benefits• Work environment is flooded with cold air• Hot air can be ducted back to CRAC

• Increased efficiency• Consistent air temperature

• Eliminates hot spots

* Image from 42U.com

Page 10: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

10Rittal Cooling Solutions – A. Tropp

Cooling strategies. Aisle containment.

* Image from EDS – Plano TX

* Image from CoreSite – Los Angeles CA

Page 11: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

11Rittal Cooling Solutions – A. Tropp

Cooling strategies. Aisle containment.

* Images from State Department – Richmond VA

Page 12: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

12Rittal Cooling Solutions – A. Tropp

Agenda

Cooling StrategiesAisle ContainmentChimney SolutionAirstream Management

Rittal Liquid Cooling PackagesData Monitoring

Page 13: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

13Rittal Cooling Solutions – A. Tropp

Cooling strategies. Chimney solution.

Deployment Requirements• Return vents for equipment not equipped with chimneys• Return extensions for CRAC units • Chimney installed on rack• Drop ceiling installed in data center

Benefits• Increased airflow efficiency• Minimal hot/cold air intermixing• Increased cooling capacity• Hot aisle containment

Page 14: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

14Rittal Cooling Solutions – A. Tropp

Cooling strategies. Chimney solution.

Page 15: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

15Rittal Cooling Solutions – A. Tropp

Cooling strategies. Chimney solution.

Page 16: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

16Rittal Cooling Solutions – A. Tropp

Agenda

Cooling StrategiesAisle ContainmentChimney SolutionAirstream Management

Rittal Liquid Cooling PackagesData Monitoring

Page 17: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

17Rittal Cooling Solutions – A. Tropp

Cooling strategies. Airstream management.

Rack-Level Air Containment

Benefits• Increased airflow efficiency• Minimal hot/cold air intermixing• Can be set into traditional raised floor• Passive components• No energy consumption• Reduce point of failure• Can accommodate blade chassis• Cold aisle containment

Page 18: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

18Rittal Cooling Solutions – A. Tropp

Cooling strategies. Airstream management.

Page 19: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

19Rittal Cooling Solutions – A. Tropp

Cooling strategies. Airstream management.

Page 20: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

20Rittal Cooling Solutions – A. Tropp

Agenda

Cooling StrategiesRittal Liquid Cooling Packages

LCP Extend & LCP Passive CWLCP+ General FeaturesLCP+ CoolingApplications

Data Monitoring

Page 21: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

21Rittal Cooling Solutions – A. Tropp

Rittal Liquid Cooling Packages.

HybridLCP Hybrid EC

Open Loop LCP Inline EC

Closed LoopLCP+ EC

0 kW 10 15 20 25 30 35 kW

0 Tons 2.8 4.3 5.7 10.0 Tons8.57.1

Rear DoorLCP Passive CW

Page 22: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

22Rittal Cooling Solutions – A. Tropp

Rittal Liquid Cooling Packages. LCP Passive CW.

Features• Passive rear doors are designed to be

installed as a replacement rear door for the racks on which they are installed

• A passive rear door simply has the fan system removed from the equation, allowing the server fans to do the necessary work of moving the air through the heat exchanger

• Maximum energy efficiency as there is no electrical power consumption

• Uses chilled water as the rejection medium

• HxWxD: 80x24x6 in. (2000x600x170 mm)• 20 kW cooling capacity

* Image from Sun Microsystems

Page 23: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

23Rittal Cooling Solutions – A. Tropp

Agenda

Cooling StrategiesRittal Liquid Cooling Packages

LCP Extend & LCP Passive CWLCP+ CoolingLCP+ General FeaturesApplications

Data Monitoring

Page 24: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

24Rittal Cooling Solutions – A. Tropp

Rittal Liquid Cooling Packages. LCP+ Cooling.

Open Loop (Inline)• Open front• Open return• More units are required

to achieve N+1

Hybrid System• Open front• Closed return• Better redundancy can

be accomplished at row and room level

Closed Loop• Closed front• Closed return• Ultra high density• Door release option

must be used

Page 25: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

25Rittal Cooling Solutions – A. Tropp

Rittal Liquid Cooling Packages. LCP+ General Features.

Features• System Capacity: 30 kW Typical• High efficiency heat exchanger developed to

operate with 59°F chilled water• Microprocessor controller• LCD touch screen• 2-way modulating valve• 6 EC fans, N+1 design, hot-swappable• Can be monitored remotely via web browser

or SNMP via TCP/IP• HxWxD: 80x12x48 in. (2000x300x1200 mm)

• 42 in. (1050 mm) depth also available• Available in sand texture black or IBM white

Page 26: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

26Rittal Cooling Solutions – A. Tropp

Rittal Liquid Cooling Packages.

Page 27: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

27Rittal Cooling Solutions – A. Tropp

Rittal Liquid Cooling Packages. LCP+ General Features.

Heat Exchanger• 9.5” deep x 12.5” wide x 70” tall

Page 28: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

28Rittal Cooling Solutions – A. Tropp

Rittal Liquid Cooling Packages. LCP+ General Features.

Electrical Design• Wide input voltage range

• 208V, 230V, 400V• EC fan technology

• 1 year ago: step motor technology• Rated current: 6.5A

• 1 year ago: 11.5A• Power rating: 1050W

• 1 year ago: 2650W• 5 pole terminal block• Fuses are easy accessible by

opening the rear door• Every unit comes high voltage tested• EMC tested configuration

Page 29: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

29Rittal Cooling Solutions – A. Tropp

Rittal Liquid Cooling Packages. LCP+ General Features.

Page 30: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

30Rittal Cooling Solutions – A. Tropp

Rittal Liquid Cooling Packages. LCP+ General Features.

Features Summary• Auto-Temperature-Control:

Cold air inlet temperature automatically controlled via integrated controller board

• Monitoring: Integrated controller with Rittal Basic CMC

• Intelligent sensor network: Fault tolerant sensors for water inlet/outlet temperatures, air inlet/outlet temperatures, water flow rates, leakage, etc.

• Fault tolerant controller boards and systems: In the case of electronic failures the valves will open and the fans will provide maximum airflow

• Alarm / events / sensor logging

• Three fan controller boards + one water controller board (individually fused)

Page 31: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

31Rittal Cooling Solutions – A. Tropp

Agenda

Cooling StrategiesRittal Liquid Cooling Packages and their Energy Efficiency

LCP Extend & LCP Passive CWLCP+ CoolingLCP+ General FeaturesApplications

Data Monitoring

Page 32: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

32Rittal Cooling Solutions – A. Tropp

Rittal Liquid Cooling Packages. Applications.

Low Density (<5 kW)• Application

• Networking switches, half-equipped server racks

• Products• Fans• Baffles• Aisle Containment

Mid Density (5-10 kW)• Application

• Server and small blade servers

• Products• LCP Inline• LCP Hybrid• Aisle Containment• Chimney

High Density (10+ kW)• Application

• Blade servers and fully equipped server racks

• Products• LCP Inline• LCP Hybrid• LCP+ Closed Loop• Aisle Containment

Page 33: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

33Rittal Cooling Solutions – A. Tropp

Customers Using the LCP Family.

Page 34: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

34Rittal Cooling Solutions – A. Tropp

Agenda

Cooling StrategiesRittal Liquid Cooling PackagesData Monitoring

CMC IIIRiZone

Page 35: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

35Rittal Cooling Solutions – A. Tropp

Data monitoring. CMC III.

CMC 3rd generation, the monitoring system for IT, building services, and industry.

Monitors and measures up to 32 sensors.• Enclosure and room temperature• Humidity• Vandalism• Air flow• Differential pressure• Current, voltage, frequency, and energy• Cooling units

Page 36: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

36Rittal Cooling Solutions – A. Tropp

Data monitoring. CMC III.

CMC 3rd generation, the monitoring system for IT, building services, and industry.

Control system for:• Handles / Doors• Fans• Sockets

Control system with:• 8 digital inputs• 4 relay outputs• 2 energy outputs

Page 37: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

37Rittal Cooling Solutions – A. Tropp

Data monitoring. RiZone.

RiZone is Rittal software for the monitoring and management of the IT infrastructure in data centers

• Power supply and reliability• Cooling output and distribution• Rack status• Data center security (access,

temperature, etc.)• Efficiency and energy

consumption

OptimizationEfficiency

Page 38: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

38Rittal Cooling Solutions – A. Tropp

Data monitoring. RiZone.

RiZone Functions• How efficient is the data center?• How efficient is the UPS?• How efficient is the chiller?• How efficient is the cooling chain?• How efficient is the power chain?• What is the actual monthly / yearly power consumption?

RiZone Benefits• Higher visibility of systems inside the data center• Historical data trending• Making the data center more reliable and efficient

Page 39: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

39Rittal Cooling Solutions – A. Tropp

Data monitoring. RiZone.

Definition of PUE/DCiE

DCiE = Data Center Infrastructure Efficiency

IT Load (Server-Load)

Entire Electrical Load of Data Center

PUE = Power Utilization Effectiveness

Entire Electrical Load of Data Center

IT Load (Server-Load)

DCiE =

PUE =

PUE and Total Power Consumption are the basis for Data Center optimization.

Page 40: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

40Rittal Cooling Solutions – A. Tropp

Data monitoring. RiZone.

• Server,• Infrastructure,• And Total Power Consumption

• PUE• CO2 -Emission• Power Costs

Page 41: Rittal Cooling Solutions – A. Tropp - E Technologies Cooling Solutions – A. Tropp 2 Rittal Cooling Solutions Presented by Adam Tropp. ... • LCP Hybrid • Aisle Containment •

41Rittal Cooling Solutions – A. Tropp

Any Questions?

Thank you for attending and listening.