Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario....
-
Upload
trinhtuyen -
Category
Documents
-
view
217 -
download
0
Transcript of Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario....
![Page 1: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/1.jpg)
© 2016 Pinchin Ltd.
Revised FINAL Baseline Property Condition Assessment Camp Orenda 44579 Truman Line Rd., Belmont, Ontario
Prepared for:
Girl Guides of Canada, Ontario Council Girl Guides of Canada, Ontario Council 180 Duncan Mill Rd., Suite 100 Toronto, ON M3B 1Z6
Attention: Ms. Jillian Dundas, Executive Director Executive Director
December 8, 2016
Pinchin File: 108378
![Page 2: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/2.jpg)
Baseline Property Condition Assessment December 8, 2016
44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378
Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page ii
Issued to: Contact: Issued on: Pinchin file: Issuing Office: Primary Contact:
Girl Guides of Canada, Ontario Council Ms. Jillian Dundas, Executive Director December 8, 2016 108378 2470 Milltower Court, Mississauga, ON L5N 7W5 Casey Norouzian, M.Sc. Senior Project Manager 905.363.1366 [email protected]
Author: Marko Balen, B.A., C.E.T. Building Scientist 905.363.1428 [email protected]
Reviewer: Majid Milani-Nia, P.Eng. Senior Project Engineer 613.851.3771 [email protected]
![Page 3: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/3.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page iii
EXECUTIVE SUMMARY
Pinchin Ltd. (Pinchin) was retained by Ms. Jillian Dundas, Executive Director of Girl Guides of Canada,
Ontario Council (Client) to conduct a Baseline Property Condition Assessment (BPCA), subject to the
limitations outlined in Section 6.0 of this report. Based on Pinchin’s scope of work this service did not
include any specialist reviews of items such as fire protection and life safety systems,
mechanical/electrical systems, structural components, etc. The municipal address for the property is
44579 Truman Line Rd., Belmont, Ontario (Site) referred to as Camp Orenda. Mr. Marko Balen of
Pinchin, a member of the Pinchin Group of Companies, conducted a visual assessment of the Site on
November 26, 2015 at which time Pinchin interviewed and was accompanied by Ms. Barb Robinson, Site
Chair, hereafter collectively referred to as the Site Representative.
Pinchin was advised by the Client that the purpose of the BPCA was to assess visible deficiencies in
relation to the internal due diligence requirements of the Site.
The Site is located within a wooded area and approximately 15km south of London. The Site is a near
rectangular-shaped property approximately 99 acres in area consisting of wooded areas and trails as well
as a multi-building camp site consisting of eleven Site buildings (excluding the Pavilions and Latrines).
The following is a general description of the Site Buildings:
Site Building Description
Toadstool
• A two-storey building complete with a basement which was reportedly constructed in the 1960’s with a subsequent addition to the south portion of the building in the mid-1990’s.
• The Site Building possesses a footprint area of approximately 2,000 Square Feet (ft2) and total building area of approximately 3,000 ft2.
• The Site Building reportedly sleeps 18 persons.
Workshop
• A single-storey building used as a workshop. • The Site Building is estimated to be constructed in the early-1980’s. • Possesses a footprint and total building area of approximately 1,150 ft2.
Clubhouse/Barn
• A single-storey building reportedly constructed in the mid-1980’s and is used as a playhouse and storage building.
• The Site Building possesses a footprint and total building area of approximately 1,750 ft2.
Chapandale
• A two-storey building complete with a basement which was reportedly constructed in the 1986.
• The Site Building possesses a footprint area of approximately 3,000 ft2 and total building area of approximately 5,500 ft2.
• The Site Building reportedly sleeps 30 persons.
![Page 4: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/4.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page iv
Site Building Description
Kesoki
• A single-storey Site Building which was reportedly constructed in approximately 1985.
• The Site Building possesses a footprint and a total building area of approximately 900 ft2.
• The campsite is equipped with seasonal wood-framed tent platforms.
Norloki
• A single-storey Site Building which was reportedly constructed in approximately 1985.
• The Site Building possesses a footprint and a total building area of approximately 1,300 ft2.
• The Site Building reportedly sleeps 19 persons. • The campsite is equipped with seasonal wood-framed tent platforms.
Norloki Storage Shed
• A single-storey Site Building used a storage building which is estimated to be constructed in approximately 1985.
• The Site Building possesses a footprint and a total building area of approximately 120 ft2.
Program House
• A single-storey Site Building used a storage building which is estimated to be constructed in approximately 1985.
• The Site Building possesses a footprint and a total building area of approximately 120 ft2.
Soames Building
• A single-storey Site Building which is estimated to be constructed in approximately 1985.
• The Site Building possesses a footprint and a total building area of approximately 400 ft2.
Soames Storage Shed
• A single-storey Site Building used a storage building which is estimated to be constructed in approximately 1985.
• The Site Building possesses a footprint and a total building area of approximately 64 ft2.
Pax Hollow Storage Shed
• A single-storey Site Building used a storage building which is estimated to be constructed in approximately 1985.
• The Site Building possesses a footprint and a total building area of approximately 64 ft2.
Pavilions • Five open-air structures located on various campgrounds with a combined
approximate footprint and total building area of 1,500 ft2.
Latrines • Three single-storey latrines located on various campgrounds with a
combined approximately footprint and total building area of 150 ft2.
![Page 5: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/5.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page v
The Site Buildings appear to be in satisfactory condition and in comparable standing with typical camp
sites within the area. Based on our visual assessment, the Site Buildings appears to have been
constructed in general accordance with standard building practices in place at the times of
construction.The assessment did not reveal any visual evidence of major structural failures, soil erosion
or differential settlement. However, cracked and bowed foundation walls were noted at the Barn,
Workshop and Toadstool buildings. Additionally, deteriorated wood framing members and previous
foundation repairs were observed and reported by the Site Representative.
No immediate repair requirements have been identified. Repair and replacement requirements (under
replacement reserves) over the term of the analysis (i.e., 15 years) of $422,000.00 have been identified.
As noted during the Site visit, deficiencies relating to the roof systems, wall systems, balcony systems,
structural systems, interior finishes, Site features, mechanical and life safety systems were noted. Of
particular note, recommendations, repairs and replacements for the following items are included
throughout the term of the analysis:
• Replacement of the sloped asphalt shingled roof systems located atop selective Site
Buildings (i.e., Toadstool, Barn, Chapandale, Norloki Storage Shed, Program House,
selective Pavilions and the Latrines);
• General repairs to the exterior walls systems (i.e., wood/vinyl wood siding, metal
cladding, etc.) of the Site Buildings;
• Replacement and removal of the asbestos siding (Type 1 abatement) on Toadstool and
re-cladding the exterior with vinyl siding;
• Repairs to the deteriorated framing members within Toadstool and the cracked and
displaced concrete foundation walls at the Workshop and Barn under the supervision of a
Structural Engineer;
• Repairs to the cracked concrete floor slabs within the Workshop and Clubhouse/Barn;
• On-going repairs and replacement of the interior finishes;
• Allowances for re-grading the gravel driveways;
• Allowances for replacement of selective electrical panels;
• Replacement of two forced-air furnaces;
• Replacement of two Domestic Hot Water (DHW) heaters; and
• Rehabilitating the on-Site accessibility features to a satisfactory level based on a non-
specialist review.
![Page 6: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/6.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page vi
Consideration has been given regarding required ongoing maintenance and repairs of the major elements
and at the direction of the Client, Pinchin has utilized a threshold of $1,000.00 per system, per year as a
limit in determining and carrying anticipated expenditures. Anticipated expenditures associated with
maintenance and reparation of the major components below the threshold are carried within the annual
operating budget and excluded from the Summary of Anticipated Expenditures.
Regular maintenance should be conducted on the roof systems, wall systems, interior finishes,
mechanical systems, electrical and life safety systems to ensure that the Projected Useful Life (PUL) of
the major components is realized. Repair costs for the aforementioned items have been included over the
term of the analysis (i.e., 15 years) included within Appendix I. The specific deficiencies identified during
the BPCA and their associated recommendations for repair are described in the main body of the report.
These deficiencies should be corrected as part of routine maintenance unless otherwise stated within the
report. Costs associated with desired upgrades have not been carried.
The detailed breakdown of all costs for the Site can be found in Appendix I.
This Executive Summary is subject to the same standard limitations as contained in the report and must
be read in conjunction with the entire report.
![Page 7: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/7.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 1 of 64
TABLE OF CONTENTS
EXECUTIVE SUMMARY ............................................................................................................................. III
1.0 INTRODUCTION .............................................................................................................................. 3
2.0 SCOPE AND METHODOLOGY ...................................................................................................... 3
3.0 OBSERVATIONS AND COMMENTS .............................................................................................. 5 3.1 Site Information..................................................................................................................... 5 3.2 Roof Systems ..................................................................................................................... 10 3.3 Wall Systems ...................................................................................................................... 16 3.4 Balcony Systems ................................................................................................................ 26 3.5 Structural Elements ............................................................................................................ 29 3.6 Underground Parking Garage ............................................................................................ 35 3.7 Vertical Transportation Systems ......................................................................................... 36 3.8 Interior Finishes .................................................................................................................. 36 3.9 Site Features ...................................................................................................................... 41 3.10 Mechanical Systems ........................................................................................................... 45
3.10.1 Heating, Ventilation and Air Conditioning (HVAC) ..................................................... 46 3.10.2 Plumbing ..................................................................................................................... 46 3.10.3 Fire Protection ............................................................................................................ 47
3.11 Electrical Systems .............................................................................................................. 52 3.11.1 Electrical Power .......................................................................................................... 52 3.11.2 Emergency Electrical Power....................................................................................... 54 3.11.3 Fire Alarm System and Life Safety ............................................................................. 54
4.0 NON-SPECIALIST BARRIER FREE ACCESSIBILITY REVIEW .................................................. 60
5.0 KNOWN VIOLATIONS TO CODE ................................................................................................. 61
6.0 CONCLUSIONS AND RECOMMENDATIONS.............................................................................. 61
7.0 LIMITATIONS ................................................................................................................................. 62
APPENDICES APPENDIX I Table 1 – Summary of Anticipated Expenditures ................................................... 1 APPENDIX II Table 2 – Non-Specialist Review of AODA Compliance........................................ 2
APPENDIX III Avison Young Commercial Real Estate – Viability Study ...................................... 3
![Page 8: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/8.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 2 of 64
LIST OF TABLES
Table 3.1 - Site Information ........................................................................................................................... 9
Table 3.2 – Roof Systems ........................................................................................................................... 11
Table 3.3 – Wall Systems ........................................................................................................................... 18
Table 3.4 – Balcony Systems...................................................................................................................... 26
Table 3.5 – Structural Elements .................................................................................................................. 31
Table 3.6 – Underground Parking Garage .................................................................................................. 35 Table 3.7 – Vertical Transportation Systems .............................................................................................. 36
Table 3.8 – Interior Finishes........................................................................................................................ 36
Table 3.9 – Site Features ............................................................................................................................ 41
Table 3.9 – Mechanical Systems (including HVAC, Plumbing, and Fire Protection) .................................. 48
Table 3.10 – Electrical Systems (including Electrical Power and Fire Alarm and Life Safety) ................... 54
![Page 9: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/9.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 3 of 64
1.0 INTRODUCTION
Pinchin Ltd. (Pinchin) was retained by Ms. Jillian Dundas, Executive Director of Girl Guides of Canada,
Ontario Council (Client) to conduct a Baseline Property Condition Assessment (BPCA), subject to the
limitations outlined in Section 6.0 of this report. Based on Pinchin’s scope of work this service did not
include any specialist reviews of items such as fire protection and life safety systems,
mechanical/electrical systems, structural components, etc. The municipal address for the property is
44579 Truman Line Rd., Belmont, Ontario (Site) referred to as Camp Orenda. Mr. Marko Balen of
Pinchin, a member of the Pinchin Group of Companies, conducted a visual assessment of the Site on
November 26, 2015 at which time Pinchin interviewed and was accompanied by Ms. Barb Robinson, Site
Chair, hereafter collectively referred to as the Site Representative.
Pinchin was advised by the Client that the purpose of the BPCA was to assess visible deficiencies in
relation to the internal due diligence requirements of the Site.
The Client has advised Pinchin that no previous Baseline Property Condition Assessments or other
building reports have been prepared for the Site.
It was reported to Pinchin that the costs associated with ongoing general maintenance of the major
components of the Site Buildings are carried as part of the annual operating budget for the Site.
Consideration has been given regarding required ongoing maintenance and repairs of the major elements
and at the direction of the Client, Pinchin has utilized a threshold of $1,000.00 per system, per year as a
limit in determining and carrying anticipated expenditures. Anticipated expenditures associated with
maintenance and reparation of the major components below the threshold are carried within the annual
operating budget and excluded from the Summary of Anticipated Expenditures.
The results of the BPCA are presented in the following report. This report is subject to the Limitations
discussed in Section 6.0. The term of the analysis requested by the Client is 15 years.
2.0 SCOPE AND METHODOLOGY
The scope of the BPCA included a visual examination (without any intrusive testing or demolition of
finishes to observe hidden areas) of the following:
• The building envelope, comprised of the exterior walls, windows, exterior doors and roof
systems;
• The structural elements (i.e., walls, floors, beams, columns);
• The interior finishes of the common areas and individual units;
• The Site features;
• The mechanical systems (i.e., furnaces, domestic hot water, plumbing, etc.); and
• The electrical and life safety systems.
![Page 10: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/10.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 4 of 64
The object of the BPCA included the following:
• A visual examination of the property in order to assess the condition of the major
elements;
• Review of general documentation on the repair/maintenance history of the elements, if
available;
• Cursory review of previous reports pertaining to the Site Buildings, if made available by
the Site Representative;
• Interviews and discussions with on-Site personnel regarding the repair/maintenance
conducted on the Site Buildings;
• Documentation of observed existing deficiencies observed within the various elements;
• Photographic documentation of various components and observed deficiencies; and
• Compilation of Pinchin’s findings in a formal written report including observed
deficiencies, together with a list of recommendations for repair/replacement with
associated estimated costs for both short and long term.
The report provides:
• A basic description of each of the various major components of the Site Buildings;
• A list of deficiencies noted with respect to the components examined; and
• Recommendations and cost estimates for the corrections recommended.
Cost estimates provided in this report are preliminary Class “D” and provided only as an indication of the
order of magnitude of the remedial work. These values have been arrived at by determining a
representative quantity from the visual observations made at the time of our Site visit and by applying
current market value unit costs to such quantities and or a reasonable lump sum allowance for the work.
More precise cost estimates would require more detailed investigation to define the scope of work. They
are not intended to warrant that the final costs will not exceed these amounts or that all costs are
covered. The estimates assume the work is performed at one time and do not include costs for potential
de-mobilization and re-mobilization if repairs/replacement are spread out over the term of analysis.
All costs are identified in 2016 Canadian Dollars, and do not include consulting fees or applicable taxes.
(For consulting fees, Pinchin typically recommends a budget allowance of 10% to 15% of the costs
identified).
All cost estimates assume that regular annual maintenance and repairs will be performed to all building
elements at the facility. No cost allowance is carried for this regular maintenance.
![Page 11: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/11.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 5 of 64
The cost estimates provided in this report are based on costs of past repairs at similar buildings, recent
costing data such as “RS Means Repair and Remodelling Cost Data – Commercial/Residential” and
“Hanscomb’s Yardsticks for Costing”, or Pinchin’s professional judgment.
Unless otherwise stated, the replacement costs identified for an element reflects the cost to remove and
replace the existing element with the same type of element.
3.0 OBSERVATIONS AND COMMENTS
3.1 Site Information
General view of the Site (Google Maps 2016).
General view of Toadstool located at the north portion of the Site.
![Page 12: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/12.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 6 of 64
General view of the Workshop located at the north portion of the Site.
General view of the Clubhouse/Barn located at the north portion of the Site.
General view of Chapandale located at the central portion of the Site.
![Page 13: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/13.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 7 of 64
General view of the Kesoki building located at the west portion of the Site.
General view of Norloki located at the west portion of the Site.
View of the Norloki Shed (right) and a typical Latrine (left).
![Page 14: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/14.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 8 of 64
View of Program Shed located at the west portion of the Site.
View of Soames and a typical Pavilion located at the west portion of the Site.
View of the latrine located at the west portion of the Site.
![Page 15: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/15.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 9 of 64
Table 3.1 - Site Information Site Occupant/Name Camp Orenda
Site Address 44579 Truman Line Rd., Belmont, Ontario
Existing Land Use Type Commercial Primary On-Site Activity
Recreational Camp Site
Multi-Tenant/Single Occupant
Single-Occupant Number of Units Varies
Date First Developed Unknown Site Area ~ 99 acres
Number of Buildings Eleven (not including Pavilions and Latrines)
Building Footprint Area(s)
Refer to Executive Summary
Number of Storeys (Excluding Basement)
Toadstool and Chapandale: 2 Remaining Site Buildings: 1
Total Building Area(s)
Refer to Executive Summary
Date Building(s) Constructed
From ~ 1960’s to early 1990’s
Area of Tenant Spaces
Varies
Date Building(s) Renovated
Early 1990’s – foundation repairs at Toadstool ~ 1995: Addition to the south portion of Toadstool On-going minor repairs
Basement and/or U/G Parking
Basement in Toadstool and Chapandale buildings
Type of Roof System(s) Sloped asphalt shingled roof system Sloped metal roof system
Number of Levels U/G
One
Type of Wall Cladding Fibre cement (asbestos) transite siding Horizontal vinyl/metal siding Preformed metal cladding Painted wood cladding Painted wood sheathing
Area of Roof System(s)
Refer to Section 3.2 – Roof Systems
Type of Doors Hollow-core wood and metal doors Solid wood doors Hollow core wood doors Overhead sectional metal doors
Types of Windows Operable Insulated Glass (IG) units within vinyl frames Single Glazed (SG) units within metal, wood and vinyl frames
Number of Above Grade Parking Spaces
No designated parking spaces on-Site
Electrical Source Erie Thames Power Corporation
![Page 16: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/16.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 10 of 64
Table 3.1 - Site Information Site Occupant/Name Camp Orenda
Site Address 44579 Truman Line Rd., Belmont, Ontario
Surface Type Gravel stone and dirt driveways Soft landscaping (i.e., grass, shrubs, trees, etc.) Undeveloped woodlands and fields
Type of Heating/Cooling
Forced-air furnaces Wood burning fireplace
3.2 Roof Systems
The roof systems atop the Site Buildings consist of a combination of sloped asphalt shingled roof systems
and sloped metal roof systems. The roof systems of the Site Buildings are installed atop wood roof
decking supported by wood roof trusses or wood rafters. Neither the presence of a vapour barrier, nor the
type, or the thickness of the insulation could be verified during the inspection of the roof systems in the
Site Buildings as the scope of the work did not include destructive testing.
Drainage of the roof systems is achieved by a combination of surface deflection and eavestroughs
complete with downspouts where rainwater is discharged at grade.
Penetrations through selective roof systems consist of plumbing stacks and chimneys.
The type, reported approximate age and approximate area of the roof systems atop the Site Buildings are
tabulated in the following table:
Site Building Roof System(s) Approximate Age Approximate Roof Area
Toadstool Sloped asphalt shingled roof 2010 (~ 6 years old) ~ 2,050 ft2
Workshop Sloped metal roof system 1980 (~ 36 years old) ~ 1,265 ft2
Clubhouse/Barn Sloped asphalt shingled roof 2012 (~ 4 years old) ~ 1,100 ft2
Sloped metal roof system 1980 (~ 36 years old) ~ 800 ft2
Chapandale Sloped asphalt shingled roof 2006 (~ 10 years old) ~ 3,300 ft2
Kesoki Sloped asphalt shingled roof 2001 (~ 5 years old) ~ 990 ft2
Norloki Sloped asphalt shingled roof 2001 (~ 5 years old) ~ 1,450 ft2
Norloki Storage Shed Sloped asphalt shingled roof 2000 (~16 years old) ~ 140 ft2
Program House Sloped asphalt shingled roof 2000 (~16 years old) ~ 140 ft2
Soames Building Sloped asphalt shingled roof 2011 (~ 5 years old) ~ 450 ft2
![Page 17: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/17.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 11 of 64
Site Building Roof System(s) Approximate Age Approximate Roof Area
Soames Storage Shed Sloped asphalt shingled roof 2011 (~ 5 years old) ~ 70 ft2
Pax Hollow Storage Shed Sloped asphalt shingled roof 2011 (~ 5 years old) ~ 70 ft2
Pavilions
Sloped asphalt shingled roof 2011 (~ 5 years old) ~ 350 ft2
Sloped asphalt shingled roof 1995 (~ 21 years old) ~ 250 ft2
Sloped metal roof system 1985-1990 (~ 26-31 years old) ~ 1,050 ft2
Latrines Sloped asphalt roof system 1985-1995 (~ 21-31) ~ 165 ft2
Total Roof Area ~ 13,640 ft2
It is noted that overall the total area of the roof systems is larger than the total footprint area of the Site
Buildings due to sloped areas, soffit overhangs and covered balcony systems (noted at Chapandale).
It is noted that the sloped roofs of the Site Buildings were not accessed at the time of the Site visit and the
visual assessment of the roof systems was completed from the ground level.
No active roof leaks were reported or noted during the time of the Site visit.
Table 3.2 outlines the findings of the inspection of the roof systems:
Table 3.2 – Roof Systems Findings Remarks/Recommendations
Major Deficiencies/Findings
• The sloped asphalt shingled roof systems atop selective Site Buildings are anticipated to reach or have exceeded their PUL within the term of analysis.
• Allowances for replacement of the aged and older sloped asphalt shingled roof systems atop the Site Buildings.
• The metal roof systems atop the Workshop, Clubhouse and selective Pavilions are anticipated to reach their PUL within the term of analysis.
• Allowances for replacement of the aged and older metal roof systems atop the Site Buildings.
Minor Deficiencies/Findings
• Deteriorated (i.e., cracked, curled and lifted) asphalt shingles were noted atop various Site Buildings.
• The deteriorated asphalt shingled roof systems will be addressed during the recommended roof replacements. Monitor and repair if required until the recommended roof replacements are completed.
• Localized areas of damaged eavestroughs and downspouts were noted atop the Clubhouse and Workshop.
• Repair the damaged eavestroughs and downpipes to ensure adequate drainage.
![Page 18: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/18.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 12 of 64
Table 3.2 – Roof Systems Findings Remarks/Recommendations
• A sagging roof was noted atop the north portion of Toadstool.
• Monitor the sagging roof until the recommended roof replacement. Repair if necessary.
• Corroded metal fasteners on the metal roof system were noted atop the Clubhouse.
• The corroded metal fasteners will be addressed during the recommended roof replacement.
• Areas of debris (i.e., twigs, leaves, pine cones/needles) were noted atop the roofs and within the eavestroughs of various Site Buildings.
• Remove the debris (i.e., twigs, leaves, pine cones/needles) regularly to avoid potential obstruction of the drains.
• A localized area of missing shingles along the roof ridge was noted atop the Norloki Storage Shed.
• Install the missing asphalt shingles atop Norloki Storage Shed.
General view of the sloped asphalt shingled roof system noted atop Toadstool.
View of the sloped metal roof system noted atop the Clubhouse.
![Page 19: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/19.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 13 of 64
General view of the sloped asphalt roof system noted atop Chapandale.
View of the sagging roof noted atop the north portion of Toadstool.
View of deteriorated (i.e., cracked) fascia board noted on the “Winter Sports Centre”.
![Page 20: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/20.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 14 of 64
View of typical corroded metal roof fasteners noted atop the Clubhouse.
View of deteriorated and cracked asphalt shingles noted atop a latrine.
View of missing asphalt shingles along the roofline of the Norloki Storage Shed.
![Page 21: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/21.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 15 of 64
View of debris (i.e., twigs, leaves, pine cones/needles) within the eavestrough of the Clubhouse.
View of a disconnected downspout noted on the Clubhouse.
It has been Pinchin’s experience that the PUL of a typical sloped asphalt shingled roof ranges between
15-25 years while the PUL of a typical sloped metal roof system ranges between 30-40 years depending
on the quality of workmanship during installation and the level to which the roof system has been
maintained.
Based on the reported ages of the sloped asphalt shingled roof systems as well as their visual condition
observed at the time of the Site visit, replacement of the roof systems atop the following Site Buildings is
anticipated:
• Toadstool • Norloki Storage Shed
• Workshop • Program House
• Clubhouse/Barn • Selective Pavilions
• Chapandale • Latrines
Assuming that the above-mentioned roof systems are replaced, the aforementioned deficiencies are
addressed and regular maintenance is performed, the roof systems of the Site Buildings should perform
![Page 22: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/22.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 16 of 64
in a satisfactory manner throughout the term of the analysis. Annual walk-on inspections are
recommended to ensure the integrity of the roof systems and to extend the service life.
3.3 Wall Systems
The exterior wall systems of each Site Building are tabulated in the following table:
Site Building Wall System(s)
Toadstool • Horizontal fibre cement cladding • Horizontal vinyl siding • Horizontal metal siding
Workshop • Preformed metal cladding
Clubhouse/Barn • Metal cladding
Chapandale • Prefinished metal cladding
Kesoki • Preformed metal cladding
Norloki • Preformed metal cladding
Norloki Storage Shed • Painted wood cladding
Program House • Painted wood sheathing
Soames Building • Preformed metal cladding
Soames Storage Shed • Painted wood cladding
Pax Hollow Storage Shed • Painted wood sheathing
Pavilions • N/A
Latrines • Painted wood sheathing
![Page 23: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/23.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 17 of 64
The window and door systems of each Site Building are tabulated in the following table:
Site Building Window and Door Systems
Toadstool
• Window systems: Double hung and fixed windows within wood frames set into punched openings complete with Single Glazed (SG) and Insulated Glass (IG) units
• Door systems: Hollow core metal doors within wood frames and selective doors complete with a storm door
Workshop
• Window systems: None • Door systems: A combination of hollow core metal and solid
wood doors within metal frames (selective doors complete with a storm door) and sectional metal overhead doors within wood frames
Club House/Barn • Window systems: Fixed windows within wood frames set into
punched openings complete with SG units • Door systems: Hollow core metal doors within wood frames
Chapandale
• Window systems: Double hung and fixed windows within wood frames set into punched openings complete with IG units
• Door systems: Hollow core metal doors within wood frames
Kesoki
• Window systems: Hopper and fixed windows within metal frames set into punched openings complete with SG units
• Door systems: Sectional metal overhead doors within wood frames
Norloki • Window systems: Horizontally-sliding windows within vinyl
frames set into punched openings complete with IG units • Door systems: Hollow core metal doors within wood frames
Norloki Storage Shed • Window systems: None • Door systems: A wood door within a wooden frame
Program House • Window systems: None • Door systems: A solid wood door within a wood frame
Soames Building
• Window systems: Horizontally-sliding windows within vinyl frames set into punched openings complete with IG units
• Door systems: A hollow core wood door within a wood frame and a hollow core metal door within a metal frame
Soames Storage Shed
• Window systems: None • Door systems: A wood door within a wooden frame
Pax Hollow Storage Shed
• Window systems: None • Door systems: A wood door within a wooden frame
Pavilions • Window systems: N/A • Door systems: N/A
Latrines • Window systems: None • Door systems: A wood door within a wooden frame
![Page 24: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/24.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 18 of 64
It should be noted that due to the fact that the scope of work did not include any intrusive/destructive
testing the presence or condition of concrete block masonry ties behind the masonry walls could not be
visually inspected.
Table 3.3 outlines the findings of the inspection of the wall systems:
Table 3.3 – Wall Systems Findings Remarks/Recommendations
Major Deficiencies/Findings
• Areas of cracked and damaged asbestos transite cladding was noted on all elevations of Toadstool.
• Pinchin recommends the exterior cladding be replaced with vinyl siding. Additionally, an allowance has been carried for a Type 1 asbestos abatement which includes disposal of the asbestos siding.
• Localized areas of cracked and displaced concrete foundation walls were noted at the Workshop and Barn.
• Repair the areas of cracking and monitor for further deterioration (Refer to Section 3.5 – Structural Elements).
Minor Deficiencies/Findings
• Selective windows and doors serving the Site Buildings appear to be original and are anticipated to require replacement within the term of analysis.
• Allowances have been carried within the term of analysis for the on-going replacement of the aged window and door systems of the Site Buildings.
• Isolated areas of deterioration (i.e., impact damaged metal cladding and peeled paint finishes) were noted on selective Site Buildings.
• Perform wall repairs which includes painting the deteriorated finishes.
• Areas of spalled brick masonry along the window sills were noted on Chapandale.
• Replace the spalled brick masonry and install new window sills at the affected locations.
• Corroded metal cladding was noted on the north elevation of the Barn.
• Replace the corroded metal cladding on the north elevation of the Barn.
• Localized areas of deteriorated (i.e., stained, cracked) wood cladding were noted at selective Site Buildings.
• Allowances have been carried for on-going repairs to the wood cladding throughout the term of analysis.
• A failed IG unit was noted at Chapandale. • Replace the failed IG unit.
• Deteriorated paint finishes on the overhead metal doors were noted at Kesoki.
• Refinish the paint finishes on the overhead metal doors.
• An unsealed opening surrounding the electrical conduit was noted on Chapandale.
• Seal the thru-wall opening and ensure the wall is water tight.
![Page 25: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/25.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 19 of 64
General view of the wall systems (i.e., fibre cement cladding) noted on Toadstool.
General view of the wall systems (i.e., prefinished metal cladding) noted on Chapandale.
View of damaged (i.e., cracked) transite siding noted on Toadstool.
![Page 26: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/26.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 20 of 64
View of spalled brick masonry along the window sill noted on Chapandale.
View of cracked transite cladding noted on Chapandale.
View of corroded metal cladding noted on the north elevation of the Barn.
![Page 27: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/27.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 21 of 64
View of peeled paint on the metal cladding noted on the north elevation of the Clubhouse.
View of impact damage on the preformed metal cladding noted on the Workshop.
View of the cracked and bowed concrete foundation wall note at the northeast corner of the Barn.
![Page 28: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/28.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 22 of 64
View of the deteriorated (i.e., cracked and stained) wooden window frame noted at the Clubhouse.
View of scraped paint finishes on the prefinished metal cladding of Chapandale.
View of a failed IG unit noted at Chapandale.
![Page 29: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/29.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 23 of 64
View of typical deteriorated wood frames (i.e., cracked) and peeled paint finishes noted on Chapandale.
View of the unsealed pipe opening through the exterior wall noted on Chapandale.
View of deteriorated (i.e., cracked) perimeter door sealants noted on Chapandale.
![Page 30: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/30.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 24 of 64
View of typical deteriorated (i.e., peeled) paint finishes on the Latrines.
View of deteriorated paint finishes on the overhead metal doors noted on the Kesoki building.
View of deteriorated (i.e., peeled) paint finishes on the metal door noted on the Norloki building.
![Page 31: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/31.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 25 of 64
View of impact damage on the prefinished metal cladding noted on the Norloki building.
View of deteriorated (i.e., cracked, aged) wood cladding noted on a Pavilion.
In general, the wall, window and door systems of the Site Buildings were noted to be in fair condition, with
the exception of the deteriorated wood and metal cladding noted at selective Site Buildings which were
noted to be in poor condition. As such, allowances have been carried for repairs of the wall systems to
address the above-noted deficiencies within the term of analysis.
Of particular note, cracked and damaged asbestos transite cladding was noted on all elevations of
Toadstool. As such, allowances have been carried to re-clad the exterior with vinyl siding cladding and to
conduct a Type 1 asbestos abatement which includes disposal of the asbestos siding.
As mentioned previously, selective windows and doors appear to be original/aged and are nearing the
end of their PUL with evidence of deteriorated and cracked frames. Pinchin has carried allowances for
on-going selective replacement of the aging and deteriorated window and door systems serving the Site
Buildings within the term of analysis.
![Page 32: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/32.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 26 of 64
Assuming that Toadstool is re-clad, general wall repairs are conducted, the aged window and door
systems are replaced, the above-referenced deficiencies are addressed and regular annual maintenance
is performed, the wall, window and door systems of the Site Building should perform in a satisfactory
manner throughout the term of the analysis.
Typical buildings constructed prior to 1978 may contain polychlorinated biphenyls (PCBs) in mastics,
caulking and window putties. Testing for the presence of PCBs in these materials is beyond the scope of
this BPCA report. The potential presence of PCBs in these materials could give rise to additional costs in
future if extensive renovation requiring removal of these materials or demolition activities are undertaken
at the Site. The extent of such potential issues could not be assessed as part of this Baseline PCA
report.
3.4 Balcony Systems
A walk-out balcony system was noted on the west elevation of Chapandale. Access to the balcony from
the 2nd-floor level of the building is provided by a hollow core metal door within a wood frame, complete
with an aluminum and glazed storm door. The balcony is a wood framed structure consisting of wood
decking atop 8-inch wood joists which are attached to the Site Building via joist hangers and supported by
4”x4” pressure-treated wood posts sitting atop concrete piers. Overhead protection is present in the form
of the roof overhang. Water accumulated on the balcony system is drained via surface drainage.
Fall protection for the balcony systems is provided by a wood framed guardrail (i.e., posts, pickets) which
is mechanically fastened to the balcony floor deck.
The balcony systems were generally noted to be in serviceable condition at the time of the Site visit and
no major deficiencies were reported to Pinchin at the time of the Site visit.
Table 3.4 outlines the findings of the balcony systems.
Table 3.4 – Balcony Systems Findings Remarks/Recommendations
Major Deficiencies/Findings
• None observed/reported. • None required.
Minor Deficiencies/Findings
• Localized areas of checking in the wood posts were noted on the balcony system.
• Repair the areas of wood checking and monitor for further deterioration. Pinchin recommends regular repairs be conducted on the balcony systems which can be managed as part of the capital threshold.
• An offset wood column atop a concrete pier was noted at the balcony system.
• Monitor the column/pier for movement which may potentially compromise the integrity of the balcony system and repair if required.
![Page 33: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/33.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 27 of 64
General view of the balcony system noted adjacent to the west elevation of Chapandale.
View of an offset wood column atop the concrete pier noted on the balcony system (below).
Note: Checking was noted in the wood posts supporting the balcony system (above).
View of stained wood finishes on the balcony system.
![Page 34: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/34.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 28 of 64
View of floor joist framing noted on the balcony system.
View of checking in the wood post noted on the balcony system.
The balcony system of Chapandale was noted to be in satisfactory condition with the above referenced
deficiencies. Pinchin recommends on-going repairs to the balcony system throughout the term of the
analysis which can be managed below the capital threshold.
Assuming that the above-referenced deficiencies are addressed and regular annual maintenance is
performed, the balcony system of Chapandale should continue to perform in a satisfactory manner
throughout the term of the analysis.
![Page 35: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/35.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 29 of 64
3.5 Structural Elements
As outlined in the scope of work, a visual assessment of the condition of the structural elements was
carried out on the elements which were visible at the time of the inspection. The structural systems of the
Site Buildings are tabulated in the following table:
Site Building Structural Systems
Toadstool
Substructure: • A cast-in-place concrete substructure (i.e., basement level slab-on-
grade) and stone and cement foundation walls (at the original portion) and concrete block masonry foundation walls (at the addition)
Superstructure: • Wood frame support structure (i.e., columns, beams and stud walls)
supporting wood roof trusses and a wood roof deck
Workshop
Substructure: • A cast-in-place concrete slab-on-grade (i.e., no basement-level)
Superstructure: • Wood frame support structure (i.e., columns, beams and stud walls)
supporting wood roof trusses and a wood roof deck
Club House/Barn
Substructure: • A cast-in-place concrete slab-on-grade (i.e., no basement-level) and
poured concrete foundation walls Superstructure: • Wood frame support structure (i.e., columns, beams and stud walls)
supporting wood roof trusses and a wood roof deck
Chapandale
Substructure: • A cast-in-place concrete substructure (i.e., basement-level slab-on-
grade) and poured concrete foundation walls Superstructure: • Wood frame support structure (i.e., columns, beams and stud walls)
supporting wood roof trusses and a wood roof deck
Kesoki
Substructure: • A cast-in-place concrete slab-on-grade (i.e., no basement-level)
Superstructure: • Wood frame support structure (i.e., columns, beams and stud walls)
supporting wood roof trusses and a wood roof deck
Norloki
Substructure: • A cast-in-place concrete slab-on-grade (i.e., no basement-level)
Superstructure: • Wood frame support structure (i.e., columns, beams and stud walls)
supporting wood roof trusses and a wood roof deck
Norloki Storage Shed
Substructure: • A cast-in-place concrete slab-on-grade (i.e., no basement-level)
Superstructure: • Wood frame support structure (i.e., columns, beams and stud walls)
supporting wood roof trusses and a wood roof deck
![Page 36: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/36.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 30 of 64
Site Building Structural Systems
Program House
Substructure: • A cast-in-place concrete slab-on-grade (i.e., no basement-level)
Superstructure: • Wood frame support structure (i.e., columns, beams and stud walls)
supporting wood roof trusses and a wood roof deck
Soames Building
Substructure: • A cast-in-place concrete slab-on-grade (i.e., no basement-level)
Superstructure: • Wood frame support structure (i.e., columns, beams and stud walls)
supporting wood roof trusses and a wood roof deck
Soames Storage Shed
Substructure: • A wood framed floor system (i.e., plywood sheathing atop wood
floor joists) bearing directly atop grade Superstructure: • Wood frame support structure (i.e., columns, beams and stud walls)
supporting wood roof trusses and a wood roof deck
Pax Hollow Storage Shed
Substructure: • A wood framed floor system (i.e., plywood sheathing atop wood
floor joists) bearing directly atop grade Superstructure: • Wood frame support structure (i.e., columns, beams and stud walls)
supporting wood roof trusses and a wood roof deck
Pavilions
Substructure: • Wood posts set within cast-in-place concrete piers
Superstructure: • Wood frame support structure (i.e., posts, beams) supporting a
wood roof deck
Latrines
Substructure: • A cast-in-place concrete slab-on-grade (i.e., no basement-level)
Superstructure: • Wood frame support structure (i.e., columns, beams and stud walls)
supporting wood roof trusses and a wood roof deck
No structural drawings were provided to Pinchin for review. Based on discusisons with the Site
Representative, foundation wall repairs within Toadstool were conducted in the early 1990’s.
![Page 37: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/37.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 31 of 64
Table 3.5 outlines the findings of the inspection of the structural elements:
Table 3.5 – Structural Elements Findings Remarks/Recommendations
Major Deficiencies/Findings
• Localized areas of cracked and displaced concrete foundation walls were noted at the Workshop, Barn and Toadstool buildings.
• Pinchin recommends a structural review on cracked and displaced concrete foundation walls under the supervision of a Structural Engineer. Allowances have been carried for a structural review under the supervision of a Structural Engineer and repairs to the affected areas of cracked foundation within the early portion of the term of analysis.
• Deteriorated (i.e., cracked) wood framing was noted in the basement-level of Toadstool.
• Allowances have been carried for repairs/replacement of the deteriorated framing members. Additionally, Pinchin recommends the condition/adequacy of the framing members be verified by a Structural Engineer.
• Localized areas of repairs to the stone and cement foundation walls were observed in the basement of Toadstool.
• Pinchin recommends the condition/adequacy of the repairs be verified by a Structural Engineer.
Minor Deficiencies/Findings
• Unsecured (i.e., non-fastened) adjustable supporting steel posts were noted within the basement-level of Toadstool.
• Securely fasten the adjustable steel posts.
• A localized area of step cracking in the brick masonry foundation wall was noted within Toadstool.
• Repoint the brick masonry foundation wall and monitor for further deterioration.
General view of the wood framed structure (i.e., wood floor joists) noted within the basement of Toadstool.
![Page 38: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/38.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 32 of 64
General view of the wood framed structure (i.e., wood trusses and roof decking) noted within Barn.
View of typical deteriorated (i.e., cracked) floor joists noted within the basement of Toadstool.
View of the unsecured (i.e., non-fastened) adjustable supporting steel post noted within the basement-level of Toadstool.
![Page 39: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/39.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 33 of 64
View of foundation wall repairs and poor workmanship (i.e., excess mortar, loose brick masonry) noted within Toadstool.
View of step cracking in the brick masonry foundation wall noted within Toadstool.
View of cracking in the concrete foundation wall noted at Barn.
![Page 40: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/40.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 34 of 64
View of cracking in the concrete foundation wall noted at the Barn.
View of cracking in the concrete foundation wall noted at the Workshop.
View of cracking in the concrete foundation wall noted at the Workshop.
As mentioned previously, localized areas of cracking in the loadbearing concrete foundation walls were
noted in the Barn, Workshop and Toadstool. As such, Pinchin recommends performing a structural
investigation to verify the cause of the displacement and cracking, construction/capacity of the affected
foundation walls and condition/adequacy of their reinforcements.
![Page 41: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/41.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 35 of 64
Assessment of the original or existing building design, compliance with prior or current Building Code or
detection or comment upon concealed structural deficiencies are outside the scope of work. Accordingly,
the findings are limited to the extent that the assessment has been made based on a walk-through visual
inspection of accessible areas of the structure.
Pinchin’s visual review of the structural elements including localized areas of displaced and cracked
loadbearing concrete foundation walls existed within the visibly accessible components of the Site
Buildings. Pinchin has attempted to identify and quantify the deficiencies associated with the structural
elements, however Pinchin recommends that a Structural Engineer be retained to assess affected areas
prior to the repair work and to ensure the extent of damage is fully understood. Until such time that the
exterior wall systems are investigated, costs associated with the remedial work necessary cannot be
determined and have the potential for significant costs based on results of the survey.
Due to the fact that the scope of work was based on a visual inspection, Pinchin has attempted to identify
and quantify the deficiencies associated with the structural systems. It is noted that the cost estimates
provided in this report are preliminary and provided only as an indication of the order of magnitude of the
remedial work. Without a defined scope of work (i.e., tender documents) estimated costs could be
potentially higher than provided. More precise cost estimates would be determined following the
recommended detailed investigation under the supervision of a structural Engineer to define the scope of
work.
3.6 Underground Parking Garage
The Site is not equipped with an underground parking garage.
Table 3.6 – Underground Parking Garage Findings Remarks/Recommendations
Major Deficiencies/Findings
• N/A • N/A
Minor Deficiencies/Findings
• N/A • N/A
![Page 42: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/42.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 36 of 64
3.7 Vertical Transportation Systems
The Site Buildings are not equipped with vertical transportation systems:
Table 3.7 – Vertical Transportation Systems
Findings Remarks/Recommendations
Major Deficiencies/Findings
• N/A • N/A
Minor Deficiencies/Findings
• N/A • N/A
3.8 Interior Finishes
As outlined in the scope of work, the interior finishes of the Site Buildings were reviewed during the Site
assessment.
The floor finishes within the Site Buildings consist of a combination of unfinished concrete floor slabs,
membranes installed atop concrete floor slabs, linoleum, vinyl floor tiles and plywood sheathing (within
the latrines).
The wall finishes within the Site Buildings consist of painted gypsum wall board, stone/brick masonry,
wood siding and concrete block masonry, plywood sheathing and the backside of metal cladding.
The ceiling finishes within the Site Buildings consist primarily of exposed wood roof decks and exposed
wood roof decking, exposed floor joists and decking (in the basement of Toadstool), gypsum board and
metal sheathing.
Table 3.8 outlines the findings of the inspection of the interior finishes:
Table 3.8 – Interior Finishes Findings Remarks/Recommendations
Major Deficiencies/Findings
• None noted/reported. • None required.
Minor Deficiencies/Findings
• Stained, worn and cracked floor finishes (i.e., vinyl floor tiles) were noted within Toadstool and Chapandale.
• Repair/replace the stained, cracked and worn floor finishes.
• Areas of cracked concrete floor slab were noted within the Workshop and Clubhouse/Barn.
• An allowance has been carried to repair the areas of cracked concrete floor slab. Pinchin recommends monitoring the floor slab for further cracking.
![Page 43: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/43.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 37 of 64
Table 3.8 – Interior Finishes Findings Remarks/Recommendations
• Localized areas of stained gypsum board and peeled paint finishes were noted within Toadstool and Chapandale.
• Determine/repair the cause of moisture/water staining and repair/refinish the moisture stained gypsum board and peeled paint finishes.
• Localized areas of delaminated flooring membrane were noted within Chapandale.
• Repair/replace the delaminated floor membrane.
• A damaged door closure was noted within the Norloki building.
• Replace the damaged door closure.
General view of the interior finishes within Toadstool.
General view of the interior finishes within Chapandale.
![Page 44: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/44.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 38 of 64
View of cracked vinyl tiles noted within Toadstool.
View of water-stained ceiling finishes noted within Toadstool.
View of cracked concrete floor slab noted within the Workshop.
![Page 45: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/45.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 39 of 64
View of cracked concrete floor slab noted within the Clubhouse.
View of peeled paint finishes noted within the Clubhouse.
View of missing and cracked vinyl tiles noted on the stairwell steps within Chapandale.
![Page 46: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/46.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 40 of 64
The interior finishes within the Site Buildings were noted to be in satisfactory condition commensurate
with their usage, with the exception of the above-referenced deficiencies. It has been Pinchin’s
experience that the PUL of hard furnishings for camp operations, including furniture, refrigerators,
carpeting and wall coverings typically ranges between 15-20 years.
View of delaminated flooring membrane noted within Chapandale.
View of lifted vinyl floor tiles noted within the Norloki building.
View of damaged closure hardware noted within the Norloki building.
![Page 47: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/47.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 41 of 64
Allowances have been carried for localized repairs and replacements of the interior finishes throughout
the term of the analysis. Assuming that the above-referenced deficiencies are addressed and regular
maintenance is performed, the interior finishes of the Site Buildings should perform in a satisfactory
manner throughout the term of the analysis.
3.9 Site Features
The Site is located within a wooded area and approximately 15 km south of London. The Site is a near
rectangular-shaped property approximately 99 acres in area consisting of wooded areas and trails as well
as a multi-building camp site consisting of eleven Site buildings (excluding the Pavilions and Latrines).
The Site Buildings occupy approximately less than 0.5% of the Site.
Gravel surfaced driveways are located at the north portion of the Site which provides access to the west,
central and east portions of the Site. Vehicular access to the Site is provided by three gravel driveways
located on the south side of Truman Line.
It should be noted, there is no drainage system on-Site.
Table 3.9 outlines the findings of the inspection of the Site features:
Table 3.9 – Site Features Findings Remarks/Recommendations
Major Deficiencies/Findings
• None observed/reported. • None required.
Minor Deficiencies/Findings
• Uneven gravel surfaced and driveways were noted at various locations of the Site.
• Allowances have been carried for on-going repairs to the gravel surfaced driveways throughout the term of analysis.
• A deteriorated and leaning wooden planter box was noted adjacent to Toadstool.
• Repair/replace the deteriorated and leaning planter box adjacent to Toadstool.
• Displaced interlocking pavers were noted adjacent to the Program House.
• Re-level the base and re-install the interlocking pavers.
• A concrete block masonry platform/step was noted adjacent to a Latrine.
• Pinchin recommends removing the concrete block masonry platform/step and installing a sturdier alternative (i.e., wood-framed stairs).
• Areas of corrosion on the exterior metal stairs were noted adjacent to Toadstool.
• Repair/repaint the corroded exterior metal stairs with corrosion resistant paint.
![Page 48: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/48.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 42 of 64
General view of the gravel surfaced access driveway from Truman Line Road.
View of the gravel surfaced driveway serving the west portion of the Site.
Note: Uneven areas and pot holes were noted at various locations of the Site.
View of the wooded area located between the central and west campsites.
![Page 49: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/49.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 43 of 64
View of the steel stairs which provide access from the central to the west portion of the Site.
View of the season tent platforms noted on the Norloki Site.
View of the leaning wooden planter box noted adjacent to Toadstool.
![Page 50: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/50.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 44 of 64
View of deteriorated (i.e., aged, cracked) stairs noted adjacent to a Latrine.
View of displaced interlocking pavers noted adjacent to Program House.
View of a concrete block masonry platform/step noted adjacent to a Latrine.
![Page 51: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/51.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 45 of 64
View of corrosion on the exterior metal stairs noted adjacent to Toadstool.
The Site features were noted to be in satisfactory condition with the exception of the above-referenced
deficiencies. As mentioned previously, deteriorated and corroded steps and stairs were noted at adjacent
to various Site Buildings. Pinchin has carried allowances for repairs to the stairs within the term of
analysis. Additionally, allowances have been carried for on-going repairs and regarding to the gravel
surfaced driveways located throughout the Site.
Assuming that the aforementioned deficiencies are addressed and regular maintenance is performed, the
Site features should perform in a satisfactory manner throughout the term of the analysis.
Assessment of or comment upon concealed deficiencies and any buried/concealed utilities or
components are outside the scope of work.
3.10 Mechanical Systems
Major Service Providers
The following providers serve the subject property:
Water On-Site Wells
Electric Erie Thames Power Corporation
Sewer On-Site Septic Systems
Propane Superior Propane
Police Elgin County Ontario Provincial Police
Fire Central Elgin Fire Department
![Page 52: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/52.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 46 of 64
3.10.1 Heating, Ventilation and Air Conditioning (HVAC)
Heating, ventilation and cooling within the Site Buildings is summarized in the table below:
Site Building Mechanical Systems
Toadstool
• Heating is provided by one “Carrier” propane-fired forced air furnace located in the basement level of Toadstool. Based on the manufacturer’s data plate, the forced air furnace possesses a maximum input heating capacity of 100,000 British Thermal Units per Hour (BTUH), and was manufactured in 2006 (i.e., approximately 10 years old).
Workshop • Heating within the building is provided by a wood burning stove.
Clubhouse/Barn • Heating within the Clubhouse portion of the building is provided by a wood burning stove.
Hilltop Building • No heating, ventilation and cooling provided within the Site Building.
Chapandale • Heating within the Site Building is provided by a propane-fired forced-
air furnace manufactured by “Keeprite”. Based on review of the manufacturer’s data plate, the forced-air furnace possesses an input heating capacity of 80,000 BTUH and was manufactured in 2013 (i.e.,
Kesoki • Heating within the building is provided by a wood burning stove.
Norloki • Heating within the building is provided by a wood burning stove.
Norloki Storage Shed • No heating, ventilation and cooling provided within the Site Building.
Program House • No heating, ventilation and cooling provided within the Site Building.
Soames Building • Heating within the building is provided by a wood burning stove.
Soames Storage Shed • No heating, ventilation and cooling provided within the Site Building.
Pax Hollow Storage Shed • No heating, ventilation and cooling provided within the Site Building.
Pavilions • N/A (Open-air structure)
Latrines • No heating, ventilation and cooling provided within the Site Building.
3.10.2 Plumbing
The plumbing systems in the Site Buildings include the incoming water services, cold and hot water
piping as well as the sanitary lines. Drainage piping within the Site Buildings consists of ABS piping where
visible, while plumbing for the domestic cold and hot water consist of copper piping. Due to the concealed
nature of the plumbing systems, the condition of the equipment could not be verified. Local repairs to the
piping can be managed as part of on-going maintenance.
![Page 53: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/53.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 47 of 64
The domestic water for the Site is reportedly provided by two on-Site wells. The incoming domestic water
service is available annually at Toadstool and Chapandale while water is available seasonally at the
Kesoki, Norloki, and Soames Sites via outdoor taps. The incoming domestic water service is driven by
electric motor-driven water pumps and are equipped with pre-charged pressure tanks manufactured by
“A.O. Smith”. The incoming water is purified by ultraviolet water filtration systems noted within the
Toadstool and Chapandale. Based on discussions with the Site Representative, the water filtration
systems were installed in 2004 (i.e., ~ 10 years ago) and are serviced annually by “Elgin Contractors”, an
independent contractor.
Domestic Hot Water (DHW) at the Site is provided within Toadstool and Chapandale domestic hot water
tanks. DHW within Toadstool is provided by an electric hot water heater manufactured by “Hotpoint” in
2006 (i.e., ~ 10 years old) and possesses a DHW storage capacity of 270 Litres. DHW within Chapandale
is provided by a propane-fired DHW heater manufactured by “A.O. Smith” in 1984 (i.e., ~ 31 years old)
and possesses a storage capacity of 378 Litres. It should be noted, DHW is unavailable at the remaining
Site Buildings. There was no shortage of hot water reported to Pinchin at the time of the Site visit.
Washroom facilities are provided within Toadstool and Chapandale are connected to on-Site septic
systems. It should be noted, the Latrines are not connected to the septic system. Based on discussions
with the Site Representative, the septic system is equipped with two septic fields while the holding tanks
are cleaned every three years.
Additionally, it should be noted plastic sump pits embedded within the concrete slab-on-grade were noted
within the basement of Toadstool and Chapandale. The sump pumps are driven by 120V electric motors
and are reportedly 3 and 6 years old each.
The inspection of the interior of boilers, pressure vessels, equipment, fan coils, ductwork or associated
components was beyond the scope of work. It should be noted that the heating and cooling duct work
within the Site Buildings may contain interior insulation. The Site Representative did not possess
knowledge of the presence of insulation within the duct work within the Site Buildings. It is Pinchin’s
experience that interior insulation within duct work is prone to deterioration or development of mould
which may require removal of the insulation. In the case where interior insulation is present within the
duct work, Pinchin recommends that the duct work insulation be inspected for the presence of mould.
3.10.3 Fire Protection
Fire protection within Toadstool, Chapandale, Soames, Keoski and Norloki buildings is provided by wall
mounted chemically-charged ABC-class fire extinguishers located throughout. The remaining Site
Buildings are not equipped with fire protection systems. The fire extinguishers were noted to possess up-
to-date inspection tags last dated in November 2015 by “Chubb Edwards”.
![Page 54: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/54.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 48 of 64
Table 3.9 outlines the findings of the inspection of the mechanical systems:
Table 3.9 – Mechanical Systems (including HVAC, Plumbing, and Fire Protection) Findings Remarks/Recommendations
Major Deficiencies/Findings
• The forced-air furnaces noted within Toadstool and Chapandale are approximately 3 and 10 years old and are anticipated to reach their PUL within the term of analysis.
• Pinchin has carried an allowances for replacement of the forced-air furnaces within the term of analysis.
Minor Deficiencies/Findings
• Two DHW heaters noted within Toadstool and Chapandale are 12 and 31 years old have exceeded or are anticipated to reach their PUL within the term of analysis.
• Allowance have been carried for replacement of two DHW heaters within the term of analysis.
• A wood-burning fireplaces were noted within various Site Buildings.
• Pinchin recommends the fireplaces be inspected by a Wood Energy Technical Training (WETT) certified contractor to ensure the condition of the wood-burning fireplaces.
• A pre-charged well pressure tanks were noted within Toadstool and Longhouse and are anticipated to require replacement within the term of analysis.
• A contingency allowance has been carried for replacement of a portion of the pre-charged well pressure tanks within the latter portion of the term of analysis.
• Water filtration systems within Toadstool and Chapandale were reportedly installed in 2004 (i.e., ~ 10 years old) and are anticipated to reach their PUL within the term of analysis.
• An allowance has been carried for replacement of the water filtration systems within Toadstool and Chapandale.
• Equipment and flammable materials (i.e., gasoline) stored adjacent to the fireplace was noted within Workshop.
• Ensure equipment and materials are stored within safe distance from the fireplace.
View of the propane tank noted at north portion of the Site.
![Page 55: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/55.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 49 of 64
View of the propane-fired furnace noted within Chapandale.
View of a wood burning fireplace noted within the Clubhouse.
View of the wood burning fireplace noted within the Norloki building.
![Page 56: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/56.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 50 of 64
View of the wood burning fireplace noted within the Keoski building.
View of the well pipe noted at the north portion of the Site.
View of the pre-charged pressure tanks (right) and water filtration system (left) noted within the basement of Chapandale.
![Page 57: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/57.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 51 of 64
View of the DHW heater noted within Chapandale.
View of the sump pit complete with sump pump noted within Toadstool.
View of equipment and flammable materials (i.e., gasoline) noted adjacent to the fireplace within the Workshop.
![Page 58: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/58.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 52 of 64
View of a typical wall-mounted fire extinguisher noted within Chapandale.
It has been Pinchin’s experience that the PUL of a forced-air furnace typically ranges between 15-20
years, while the PUL of a DHW heater typically ranges between 10-15 years depending on the quality of
the unit and the level to which the unit has been maintained.
The mechanical systems of the Site Buildings were generally noted to be in serviceable condition with the
exception of the above-referenced deficiencies. As previously mentioned, the forced-air furnaces and
DHW heaters have either exceeded or are anticipated to reach their PUL within the term of the analysis.
As mentioned previously, wood-burning fireplaces were noted within several Site Buildings. As such,
Pinchin recommends the fireplaces be inspected by a Wood Energy Technical Training (WETT) certified
contractor to verify the condition of the wood-burning fireplaces.
Assuming that the aforementioned deficiencies are addressed and regular maintenance is performed, the
mechanical systems of the Site Buildings should perform in a satisfactory manner throughout the term of
the analysis.
In accordance with the proposed scope of work, no physical or destructive testing or design calculations
will be conducted on any of the major components of the building. Similarly the inspection of the interior of
ductwork or associated mechanical components is not included in the scope of work. Accordingly, the
findings are limited to the extent that the assessment will be made visually from the exterior of the
systems.
3.11 Electrical Systems
3.11.1 Electrical Power
Electrical power at the Site is provided by pole-mounted transformers located throughout the Site which
feed electrical panels located within the Site Buildings.
![Page 59: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/59.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 53 of 64
The electrical power systems for the Site Buildings are summarized in the following table:
Site Building Electrical Systems
Toadstool
• Electrical power is supplied to a Single Phase, 3 Wire “CNB” main disconnect panel rated at 150 Amperes and 120/240 Volts main bus capacity and voltage tension.
• An additional electrical disconnect switch manufactured by “Crouse-Hinds” was noted within the east portion of the building which is rated at 100 Ampere 120/240 Volts main bus capacity and voltage tension.
Workshop • Electrical power is supplied to a Single Phase, 3 Wire “Federal
Pioneer” main disconnect panel rated at 70 Amperes and 120/240 Volts main bus capacity and voltage tension.
Club House/Barn • Electrical power is supplied to a Single Phase, 3 Wire “Square D” main
disconnect panel rated at 30 Amperes and 120/240 Volts main bus capacity and voltage tension.
Chapandale • Electrical power is supplied to a “Commander” main disconnect switch
rated at 200 Amperes and 120/240 Volts main bus capacity and voltage tension.
Kesoki • Electrical power is fed to a glass fuse box panel manufactured by
“Amalgamated Electric” and rated at 60 Ampere and 230 Volts main bus capacity and voltage tension
Norloki • Electrical power is supplied to a Single Phase, 3 Wire “ITE” electrical
panel rated at 100 Amperes and 120/240 Volts main bus capacity and voltage tension.
Norloki Storage Shed • Electrical power is not supplied to the Site Building.
Program House • Electrical power is not supplied to the Site Building.
Soames Building • Electrical power is fed to a glass fuse box panel manufactured by
“Amalgamated Electric” and rated at 60 Ampere and 230 Volts main bus capacity and voltage tension
Soames Storage Shed • Electrical power is not supplied to the Site Building.
Pax Hollow Storage Shed • Electrical power is not supplied to the Site Building.
Pavilions • Electrical power is not supplied to the Pavilions.
Latrines • Electrical power is not supplied to the Site Buildings.
No problems with power sufficiency were noted or reported to Pinchin at the time of the Site visit. The
visible sections of the electrical services appear to be in satisfactory condition with no major deficiencies
noted.
![Page 60: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/60.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 54 of 64
The Site Representatives were not aware if aluminum wiring is present in the electrical systems of the
Site Buildings. Aluminum wiring was not observed at the time of the Site visit, however, based on the age
of the Site Buildings, selective Site Buildings may contain aluminum wiring. If aluminum wiring is present,
regular inspection of the electrical systems by a licensed electrician and an electrical evaluation is
recommended.
3.11.2 Emergency Electrical Power
There is reportedly no emergency backup power provided for the Site Buildings.
3.11.3 Fire Alarm System and Life Safety
Chapandale is equipped with a multi-zoned, single-stage “Edwards” fire alarm panel located within the
basement. The fire alarm panel is estimated to be approximately 5 years old and was noted to possess
an up-to-date inspection tag (i.e., July 3, 2015 by Chubb Edwards). The remaining Site Buildings and
structures do not possess fire alarm panels. The fire alarm system is activated by smoke and heat
detectors which are located throughout Chapandale and manual pull stations which were noted at the
vicinity of the entrances/exits. The fire alarm systems reportedly do not possess 24/7 monitoring by a
monitoring company.
The fire alarm systems within Toadstool and Chapandale consist of ceiling mounted battery powered and
interconnected smoke detectors located throughout. It should be noted, fire alarm systems were not
observed within the remaining Site Buildings.
Illuminated exit signage and emergency lighting within Toadstool and Chapandale is provided by ceiling
mounted battery powered units which are located within the vicinity of the exits. The remaining Site
Buildings do not possess emergency lighting.
Table 3.10 outlines the findings of the inspection of the electrical systems:
Table 3.10 – Electrical Systems (including Electrical Power and Fire Alarm and Life Safety) Findings Remarks/Recommendations
Major Deficiencies/Deterioration
• None noted/reported. • None required.
Minor Deficiencies/Deterioration
• Smoke/heat detectors and carbon monoxide detectors were not observed in various Site Buildings during the time of the Site visit.
• An allowance has been carried for installation of fire alarm systems within various Site Buildings.
• The electrical panels within selective Site Buildings are aged and will be approaching the end of their PUL within the term of the
• Allowances for replacement of the aged electrical panels have been carried within the term of analysis.
![Page 61: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/61.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 55 of 64
Table 3.10 – Electrical Systems (including Electrical Power and Fire Alarm and Life Safety) Findings Remarks/Recommendations
analysis.
• Aged and discoloured wiring insulation jackets were noted in Toadstool.
• Consideration should be given to conduct an electrical survey by a qualified electrical contractor prior to replacement of the aged distribution systems to better identify the need for replacement.
• Aged and dirty ceiling-mounted smoke and heat detectors were noted within Toadstool and Chapandale.
• Ensure the smoke and heat detectors are operational and replace if required.
• An exterior non-GFI receptacle was noted on the Soames building.
• Replace the receptacle with a GFI receptacle.
• A localized area of exposed wiring (i.e., missing protective conduit) was noted at the Barn.
• Ensure the exterior wiring is protected by a conduit to prevent accidental damage to the wire.
• Deadbolt locks were noted on the emergency exit doors within Chapandale.
• Remove the locks from the emergency exit doors while the building is in operation.
• Contact a qualified electrician to install outdoor rated wiring or an electrical conduit at the Site Building.
• Contact a qualified electrician to install outdoor rated wiring or an electrical conduit at the Site Building.
• Deteriorated and leaning hydro poles were noted at various locations of the Site.
• Pinchin has carried a contingency allowance for replacement of the deteriorated/leaning hydro poles within the term of analysis.
View of the main disconnect panel noted within Toadstool.
![Page 62: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/62.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 56 of 64
View of the electrical panel noted within Chapandale.
View of the “Edwards” fire alarm panel noted within Chapandale.
View of typical emergency lighting noted within Toadstool.
![Page 63: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/63.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 57 of 64
View of a typical smoke detector noted within Toadstool.
View of an aged and stained heat detector noted within Chapandale.
View of a plug-in carbon monoxide detector noted within Chapandale.
![Page 64: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/64.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 58 of 64
View of a wall-mounted emergency lighting battery pack noted within Chapandale.
View of exposed electrical wiring was noted at the Barn.
View of a deadbolt lock on the emergency exit door noted at Chapandale.
![Page 65: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/65.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 59 of 64
View of aged and deteriorated electrical wiring insulation jackets noted within Toadstool.
View of a glass bulb electrical panel noted within the Keseoki building.
View of an exterior non-GFI receptacle noted on the Soames building.
![Page 66: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/66.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 60 of 64
Upon visual inspection, the electrical and life safety systems were noted to be in satisfactory condition
with the exception of the above-referenced deficiencies. As previously mentioned, based on the ages of
selective electrical panels and distribution systems, allowances have been carried for repairs/replacement
of selective electrical panels and their distribution systems within the term of analysis.
Assuming that the aged electrical panels and wiring are replaced, the aforementioned deficiencies are
addressed and regular maintenance is performed, the electrical and life safety systems of the Site
Building should perform in a satisfactory manner throughout the term of the analysis. Completing a
regular infrared scan of the electrical systems is recommended as part of the regular maintenance of the
electrical system.
4.0 NON-SPECIALIST BARRIER FREE ACCESSIBILITY REVIEW
As part of the survey, a cursory review of the barrier free requirements pertaining to site and building
access was completed. As part of the report, a questionnaire, which was completed during the survey,
has been included in Appendix II. Generally, the Site Buildings do not meet the requirements for barrier
free design as it pertains to building access, corridors and washrooms. Allowances have been
View of a leaning electrical/light pole noted adjacent to Chapandale.
View of a deteriorated (i.e., cracked, rotted) wooden hydro pole noted adjacent to the Workshop.
![Page 67: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/67.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 61 of 64
carried for the installation of a barrier free access at Toadstool and Chapandale as well as the
construction/renovations of barrier free accessible washrooms within Toadstool and Chapandale. Please
refer to Appendix II for information regarding the elements which do not meet requirements.
5.0 KNOWN VIOLATIONS TO CODE
It was reported to Pinchin by the Site Representative that no outstanding violations from the Building
Department existed pertaining to the property. Compliance with the National Building Code (NBC) and
National Fire Code (NFC) was not reviewed as it was beyond the scope of this survey.
6.0 CONCLUSIONS AND RECOMMENDATIONS
Based on Pinchin’s review of the property, conducted on November 26, 2015, the Site Buildings appear
to be in satisfactory condition and in comparable standing to other similar Camp properties in the area.
Based on our visual assessment, the Site Buildings appear to have been constructed in general
accordance with standard building practices in place at the time of construction. The assessment did not
reveal any visual evidence of major structural failures, soil erosion or differential settlement. However,
cracked and bowed foundation walls were noted at the Barn, Workshop and Toadstool buildings.
Additionally, deteriorated wood framing members and previous foundation repairs were observed and
reported by the Site Representative.
No immediate repair requirements have been identified. As noted during the Site visit, deficiencies
relating to the roof systems, wall systems, balcony systems, structural systems, interior finishes, Site
features and mechanical/life safety systems were noted. Of particular note, recommendations, repairs
and replacements for the following items are included throughout the term of the analysis:
• Replacement of the sloped asphalt shingled roof systems located atop selective Site
Buildings (i.e., Toadstool, Barn, Chapandale, Norloki Storage Shed, Program House,
selective Pavilions and the Latrines);
• General repairs to the exterior walls systems (i.e., wood/vinyl wood siding, metal
cladding, etc.) of the Site Buildings;
• Replacement and removal of the asbestos siding (Type 1 abatement) on Toadstool and
re-cladding the exterior with vinyl siding;
• Repairs to the deteriorated framing members within Toadstool and the cracked and
displaced concrete foundation walls at the Workshop and Barn under the supervision of a
Structural Engineer;
• Repairs to the cracked concrete floor slabs within the Workshop and Clubhouse/Barn;
• On-going repairs and replacement of the interior finishes;
• Allowances for re-grading the gravel driveways;
![Page 68: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/68.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 62 of 64
• Allowances for replacement of selective electrical panels;
• Replacement of two forced-air furnaces;
• Replacement of two DHW heaters; and
• Rehabilitating the on-Site accessibility features to a satisfactory level based on a non-
specialist review.
It was reported to Pinchin that the costs associated with ongoing general maintenance of the major
components of the Site Buildings are carried as part of the annual operating budget for the Site.
Consideration has been given regarding required ongoing maintenance and repairs of the major elements
and at the direction of the Client, Pinchin has utilized a threshold of $1,000.00 per system, per year as a
limit in determining and carrying anticipated expenditures. Anticipated expenditures associated with
maintenance and reparation of the major components below the threshold are carried within the annual
operating budget and excluded from the Summary of Anticipated Expenditures.
Regular maintenance should be conducted on the roof systems, wall systems, interior finishes, Site
features, mechanical systems, electrical and life safety systems to ensure that the PUL of the major
components is realized. Repair costs for the aforementioned items have been included over the term of
the analysis (i.e., 15 years) included within Appendix I. The specific deficiencies identified during the
BPCA and their associated recommendations for repair are described in the main body of the report.
These deficiencies should be corrected as part of routine maintenance unless otherwise stated within the
report. Costs associated with desired upgrades have not been carried.
7.0 LIMITATIONS
In accordance with the proposed scope of work, no physical or destructive testing or design calculations
were conducted on any of the components of the building. Assessment of the original or existing building
design, or detection or comment upon concealed structural deficiencies and any buried/concealed utilities
or components are outside the scope of work. Similarly the assessment of any Post Tension reinforcing is
not included in the scope of work. Determination of compliance with any Codes is beyond the scope of
this Work. The Report has been completed in general conformance with the ASTM Designation: E 2018 –
08 Standard Guide for Property Condition Assessments: Baseline Property Condition Assessment
Process.
It should be noted that Pinchin has attempted to identify all the deficiencies required by this Standard
associated with this project. Pinchin does not accept any liability for deficiencies that were not within the
scope of the investigation.
![Page 69: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/69.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 63 of 64
As indicated above the personnel conducting the building assessment, where applicable, have performed
a non-specialist review of the building and all associated finishes and related systems including the,
mechanical and electrical systems, fire and life safety systems, site features, etc. The personnel
conducting the assessment are knowledgeable of building systems and construction, but not technical
specialists in each of these fields. The intent of Pinchin’s comments on these systems are for the sole
purpose of identifying areas where Pinchin has observed a noteworthy condition which will lead to a likely
significant expenditure during the term of the assignment and/or where Pinchin would recommend that
the client consider a further, more detailed investigation. The budget costs for remedial work for each
specific item has been provided to the best of our ability and will provide an order of magnitude cost for
the individual item and the overall possible remedial work. Our experience has shown that the costs that
Pinchin have provided are appropriate and of reasonable accuracy for the purpose intended. It should be
noted that the budget cost or reserve costs for any specific item may vary significantly based on the fact
that the schedule or phasing of the future remedial work is unknown at this time, the impact on building
operations of this remedial work is unknown at this time and that no intrusive inspection or detailed design
work is included in the BPCA. If a more accurate, detailed or documented reserve cost is required at this
time the client should request Pinchin to provide the additional proposal to provide a more accurate cost
estimate.
The assessment is based, in part, on information provided by others. Unless specifically noted, Pinchin
has assumed that this information was correct and has relied on it in developing the conclusions.
It is possible that unexpected conditions may be encountered at the Site that have not been explored
within the scope of this report. Should such an event occur, Pinchin should be notified in order to
determine if we would recommend that modifications to the conclusions are necessary and to provide a
cost estimate to update the report.
The inspection of the interior of boilers, pressure vessels, equipment, fan coils, ductwork or associated
components was beyond the scope of work. It should be noted that the heating and cooling duct work
within the Site Buildings may contain interior insulation. The Site Representative did not possess
knowledge of the presence of insulation within the duct work within the Site Buildings. It is Pinchin’s
experience that interior insulation within duct work is prone to deterioration or development of mould
which may require removal of the insulation. In the case where interior insulation is present within the
duct work, Pinchin recommends that the duct work insulation be inspected for the presence of mould.
Due to the concealed nature of the plumbing system the condition of the risers could not be verified.
Environmental Audits or the identification of designated substances, hazardous materials, PCBs,
insect/rodent infestation, concealed mould and indoor air quality are excluded from this BPCA report.
![Page 70: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/70.jpg)
Baseline Property Condition Assessment December 8, 2016 44579 Truman Line Rd., Belmont, Ontario Pinchin File: 108378 Girl Guides of Canada, Ontario Council FINAL
© 2016 Pinchin Ltd. Page 64 of 64
Further to the aforementioned, determination of the presence of asbestos containing material within the
building such as drywall joint compound or the lead content within the older paint finishes was beyond the
scope of work.
This report was prepared for the exclusive use of Girl Guides of Canada, Ontario Council subject to the
conditions and limitations contained within the duly authorized workplan. Pinchin will not be responsible
for the use of this report by any third party, or reliance on of any decision to be made based on it without
the prior written consent of Pinchin. Pinchin accepts no responsibility for damages, if any, by any third
party as a result of decisions or actions based on this report.
Pinchin will not be responsible for any consequential or indirect damages. Pinchin will only be liable for
damages resulting from the negligence of Pinchin. Pinchin will not be liable for any losses or damage if
the Client has failed, within a period of two years following the date upon which the claim is discovered
(Claim Period), to commence legal proceedings against Pinchin to recover such losses or damage unless
the laws of the jurisdiction which governs the Claim Period which is applicable to such claim provides that
the applicable Claim Period is greater than two years and cannot be abridged by the contract between the
Client and Pinchin, in which case the Claim Period shall be deemed to be extended by the shortest
additional period which results in this provision being legally enforceable.
This report presents an overview on issues of the building condition, reflecting Pinchin’s best judgment
using information reasonably available at the time of Pinchin’s review and Site assessment. Pinchin has
prepared this report using information understood to be factual and correct and Pinchin is not be
responsible for conditions arising from information or facts that were concealed or not fully disclosed to
Pinchin at the time of the Site assessment.
J:\108000s\108378 GIRLGUIDESOFC,multilocation,DDIL,BCA\BPCA Reports\Camp Orenda\Old\108378_FINAL_BPCA_Report, 44579 Truman Line Road, Belmont, ON, April
4 2016.docx
Template: Master Report for Office Building Baseline Condition Assessment, PCA, July 27, 2015
![Page 71: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/71.jpg)
APPENDIX I Table 1 – Summary of Anticipated Expenditures
![Page 72: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/72.jpg)
Baseline Property Condition AssessmentCamp OrendaBelmont, ON
Table 1: Summary of Anticipated ExpendituresReplacement Reserve Costs
CONFIDENTIAL
LS - Lump SumSF - Square FootEA - Each (per unit component)LF - Lineal Foot Pinchin Job 108378
RemainingITEM Projected
Useful Life (yrs)
Effective Age (yrs)
Projected Useful Life
(yrs)
Quantity Unit Unit Cost Total Cost2016
1 yr Cost2017
2 yr Cost2018
3 yr Cost2019
4 yr Cost2020
5 yr Cost2021
6 yr Cost2022
7 yr Cost2023
8 yr Cost2024
9 yr Cost2025
10 yr Cost2026
11 yr Cost2027
12 yr Cost2028
13 yr Cost2029
14 yr Cost2030
15 yr Cost1 - 15 Year
Total
Life Safety, Consulting and ADALife Safety & Code ComplianceFollow-up RecommendationsGeneral ADA Accessibility (Refer to Appendix II) Varies Varies Varies 1 LS $43,000 $43,000 $43,000 $43,000
Table 3.2 - Roof SystemsRoof Structures and Roofing (Repairs - Below Threshold)Roof Structures and Roofing (Replacement of the Sloped Asphalt Roof Systems atop Toadstool, Barn, Chapandale, Norloki Storage Shed, Program House, selective Pavilions and the Latrines)
Varies Varies Varies 6,045 SF $6.00 $36,500 $4,000 $20,000 $12,500 $36,500
Roof Structures and Roofing (Replacement of the Sloped Metal Roof Systems atop Workshop, Club House and selective Pavilions) Varies Varies Varies 3,115 SF $12.00 $37,500 $25,000 $12,500 $37,500
.Table 3.3 - Wall Systems
Exterior Walls (Repairs) Varies Varies Varies 1 LS $40,000 $40,000 $10,000 $10,000 $10,000 $10,000 $40,000Exterior Windows and Doors (Repairs/Replacement) Varies Varies Varies 1 LS $25,000 $25,000 $10,000 $5,000 $5,000 $5,000 $25,000Asbestos abatement at Toadstool as part of re-cladding the exterior wall systems Varies Varies Varies 1 LS $60,000 $60,000 $60,000 $60,000
Re-cladding the exterior of Toadstool with vinyl siding Varies Varies Varies 1 LS $15,000 $15,000 $15,000 $15,000Exterior Walls (Phased-in replacement of the exterior sealants) Varies Varies Varies 1 LS $15,000 $15,000 $5,000 $5,000 $5,000 $15,000
Table 3.4 - Balcony SystemsBalcony Systems (On-going repairs - Below Threshold)
Table 3.5 - Structural ElementsStructural Elements (Structural review by a Structural Engineer to verify the condition of the structural elements at the affected areas) Varies Varies Varies 1 LS $5,000 $5,000 $5,000 $5,000
Foundations (Repairs to the deteriorated floor joists and cracked foundation walls within Toadstool) Varies Varies Varies 1 LS $15,000 $15,000 $15,000 $15,000
Superstructure (Repairs to the cracked and displaced concrete foundation at Barn and Workshop) Varies Varies Varies 1 LS $7,500 $7,500 $7,500 $7,500
Table 3.6 - Underground Parking GarageParking Garage N/A N/A N/A
Table 3.7 - Vertical TransportationElevator Systems N/A N/A N/A
Table 3.8 - Interior FinishesInterior Finishes (Repairs/Replacement) Varies Varies Varies 1 LS $32,500 $32,500 $5,000 $5,000 $7,500 $7,500 $7,500 $32,500Interior Finishes (Repairs to the cracked concrete slabs within Workshop and Barn) Varies Varies Varies 1 LS $15,000 $15,000 $15,000 $15,000
Furniture (Below Threshold)Appliances (Below Threshold)
Table 3.9 - Site FeaturesUtilities N/A N/A N/AParking and Paving N/A N/A N/ADriveways (Allowances for on-going repairs and re-grading of the gravel surfaced driveways) Varies Varies Varies 1 LS $25,000 $25,000 $5,000 $5,000 $5,000 $5,000 $5,000 $25,000
Exterior Stairs (Repairs and Replacement) Varies Varies Varies 1 LS $11,000 $11,000 $2,000 $2,000 $2,000 $5,000 $11,000
Table 3.10 - Mechanical SystemsBuilding HVAC (HVAC Repairs - Below Threshold)Building HVAC (Replacement of two forced-air Furnaces) 15-20 15 0-5 2 EA $5,000 $10,000 $5,000 $5,000 $10,000Building HVAC (Inspection of a the fireplaces by a certified WETT contractor) Varies Varies Varies 1 LS $7,500 $7,500 $2,500 $2,500 $2,500 $7,500
Building Plumbing (Annual Inspection of the Wells by a Licenced Well Contractor - Below Threshold) Varies Varies Varies 1 LS
Building Plumbing (Replacement of the Water Filtration Systems) Varies Varies Varies 1 LS $1,500 $1,500 $1,500 $1,500Building Plumbing (Replacement of two DHW heaters) 10-15 Varies Varies 1 EA $1,500 $3,000 $3,000 $3,000Building Plumbing (Contingency allowance for replacement of the Precharged Pressure Tanks) Varies Varies Varies 1 LS $1,500 $1,500 $1,500 $1,500
Fire Protection & Security
Table 3.11 - Electrical SystemsElectrical Systems (Replacement of the aged electrical panels and distribution systems) Varies Varies Varies 1 LS $7,500 $7,500 $2,500 $2,500 $2,500 $7,500
Electrical Systems (Contingency allowance for replacement of two deteriorated hydro/light poles) Varies Varies Varies 2 EA $3,000 $6,000 $3,000 $3,000 $6,000
Electrical Systems (Installation of fire alarms, smoke alarms and carbon monoxide detectors within various Site Buildings) Varies Varies Varies 1 LS $3,000 $2,000 $2,000 $2,000
TOTALS (Uninflated) $422,000 $124,500 $109,000 $12,500 $13,000 $22,000 $20,000 $17,500 $8,000 $17,000 $7,500 $9,500 $7,500 $35,000 $17,500 $1,500 $422,000Inflation
Inflation Factor Rate 1.00 1.025 1.050 1.075 1.100 1.125 1.150 1.175 1.200 1.225 1.250 1.275 1.300 1.325 1.350TOTALS (Inflated) $124,500 $111,725 $13,125 $13,975 $24,200 $22,500 $20,125 $9,400 $20,400 $9,187 $11,875 $9,562 $45,500 $23,188 $2,025 $461,288
Term of Analysis 15Total square footage of the Site Buildings 16,018
$1.76$1.92
2.5%
Average Cost per Square Foot per Year (Uninflated)Average Cost per Square Foot per Year (Inflated)
Immediate Costs
Replacement Reserve Costs
![Page 73: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/73.jpg)
APPENDIX II Table 2 – Non-Specialist Review of AODA Compliance
![Page 74: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/74.jpg)
APPENDIX II
NON-SPECIALIST REVIEW OF AODA COMPLIANCE
108378 – Girl Guides of Canada – Camp Orenda Page 1 of 5
Building History
Yes
No
N/A
Remedial Action/Comments
Cost
1. Has the Borrower previously completed an AODA review? 2. Does an AODA compliance plan exist for the property? 3. Has the plan been reviewed/approved by outside Agencies (engineering
firms, building department, other agencies)?
4. Have any AODA related complaints been received in the past? Building Access
Yes
No
N/A
Remedial Action/Comments
Cost
1. Are there an adequate number (per regulation) of wheelchair-accessible parking spaces available?
2. Is there at least one wheelchair-accessible vehicle parking space (2440 wide and 7400mm long) for every 8 standard accessible spaces?
3. Are accessible parking spaces located on the shortest accessible route of travel from an accessible building entrance?
4. Does signage exist directing you to wheelchair-accessible parking and an accessible building entrance?
Installation of wheel-chair accessible signage is recommend at Toadstool and Chapandale.
5. Is there a ramp from parking to an accessible building entrance (1:12 slope or less)?
Ramp not required.
6. Does the ramp meet design requirements (minimum 900m wide, have a level area 1670mm at the top and bottom of the ramp, have a level area at intervals of 9m and is equipped with handrails on both sides)?
7. If the main entrance is inaccessible, are there alternate accessible entrances?
Construction of accessible alternative entrances is recommended at Toadstool and Chapandale.
$10,000
8. Is the accessible entrance doorway at least 860mm when the door is in the open position?
9. Are doors in the barrier free path of travel equipped with door opening devices and power door operators?
Toadstool and Chapandale do not possess power door operators. Installing a power door operator on the accessible entrances of Toadstool and Chapandale is recommended.
$8,000
![Page 75: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/75.jpg)
108378 – Girl Guides of Canada – Camp Orenda Page 2 of 5
Building Corridors
Yes
No
N/A
Remedial Action/Comments
Cost
1. Is the barrier free path of travel at least 1100mm wide and free of obstructions?
The barrier free path of travel within Toadstool does not meet current requirements.
$2,000
2. Are floor surfaces firm, stable and slip resistant (carpets “wheelchair friendly”)?
Installation of slip resistant floor surfaces are recommended within Toadstool/Chapandale.
$2,300
3. Are changes in level bevelled (1:2 bevel) and not more than 13mm? 4. Are elevator controls low enough to be reached from a wheelchair
(between 900 and 1100mm from the finished floor)?
5. Are there raised elevator markings in Braille and Standard Alphabet for the blind?
6. Are there audible signals inside cars indicating floor change? 7. Do elevator lobbies have visual and audible indicators of car arrival? 8. Does elevator interior provide sufficient wheelchair turning area (1500mm
radius minimum)?
9. Is at least one wheelchair-accessible telephone available? Pinchin recommends installing a wheel-chair accessible telephone within House.
$500
10. Are wheelchair-accessible facilities (restrooms, exits, etc.) identified with signage?
Install signage at the wheel-chair accessible washroom within Chapandale.
$200
11. Are there adequate (and AODA approved) FA visual and audible alarms located throughout the facility?
Not required for this type of occupancy.
Washrooms
Yes
No
N/A
Remedial Action/Comments
Cost
1. Are common area public restrooms located on an accessible path of travel and possess signage?
Install signage at the wheel-chair accessible facilities of Toadstool/Chapandale.
$20,000 2. Are door handles push/pull or lever type and mounted between 900 to
1100mm above the finished floor level? Install a lever-type door handles on
the accessible washrooms within Toadstool and Chapandale.
3. Are access doors wheelchair-accessible (at least 860mm wide when in the open position)?
4. Are accessible stalls at least 1500mm wide and 1500mm deep?
![Page 76: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/76.jpg)
108378 – Girl Guides of Canada – Camp Orenda Page 3 of 5
5. Are public restrooms large enough for wheelchair turnaround (1500mm turning diameter for stalls and 1700mm for universal washrooms)?
A wheelchair accessible washroom is not provided within Toadstool.
6. Are universal washrooms equipped with an emergency call system with audible and visual signal devices and activated by a control device inside the washroom?
Installing an emergency call system within the wheelchair accessible washrooms within Toadstool/Chapandale is recommended.
7. Are stall doors wheelchair-accessible (at least 860mm wide when in the open position)?
Provided in Chapandale building.
8. Are grab bars provided in washroom stalls (L-shaped or diagonal with a horizontal bar 150mm above the toilet tank)?
Horizontal grab bars were noted within the washroom in Chapandale. L-Shaped grab bars are required as a result of the accessibility requirement amendment.
9. Are lavatories mounted not more than 840mm with at least 735mm clearance?
10. Are faucets equipped with lever type handles or handsfree actuators and not more 485mm from the front edge of the vanity?
* *An accessible faucet was noted within Chapandale however, accessible washrooms were not observed within Toadstool.
11. Are exposed pipes under sinks sufficiently insulated against contact? Uninsulated pipes were noted within the accessible washroom in Chapandale. Pinchin recommends insulating the hot water pipes beneath the wheelchair accessible sinks.
12. Are soap dispensers, towels, etc. reachable (mounted between 900 and 1200mm above the finished floor and not more than 610mm from the edge of the lavatory) and operable with one hand?
To be addressed during the recommended washroom renovations.
13. Is the base of mirror no more than 1000mm off finished floor? 14. Are accessible showers provided with a slip resistant floor surface and not
less than 1500mm wide and 900mm deep?
![Page 77: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/77.jpg)
108378 – Girl Guides of Canada – Camp Orenda Page 4 of 5
View of an inaccessible entrance noted adjacent to the west elevation of Toadstool.
Note: A step was noted in the path of travel.
View of typical non-compliant thresholds and door openings noted within Toadstool.
![Page 78: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/78.jpg)
108378 – Girl Guides of Canada – Camp Orenda Page 5 of 5
View of a non-compliant door handle noted on the west elevation of Chapandale.
View of the grab bars within the accessible washroom noted within Chapandale.
Note: L-Shaped grab bars are required as a result of the accessibility requirement amendment.
![Page 79: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/79.jpg)
APPENDIX III Avison Young Commercial Real Estate – Viability Study
![Page 80: Revised FINAL Baseline Property Condition · PDF file44579 Truman Line Rd., Belmont, Ontario. Prepared for: Girl Guides of Canada, Ontario ... • The Site Building reportedly sleeps](https://reader031.fdocuments.in/reader031/viewer/2022012919/5a78cd437f8b9a83238ca6db/html5/thumbnails/80.jpg)
Population Characteristics
Population: Populaiton by Marital Status:2011 466,009 Single 28%2014 481,847 Married 48%2017 500,124 Common-Law 9%2019 512,271 Widowed 6%2024 539,755 Divorced or Separated 6%Population Change % (2014-2024) 12% Separated (legally married) 3%Total Households (2014) 201,422Persons per Household 2.36
Population Mobility Status 5+ Years Ago:Movers 42%Non-movers 58%
Dwelling Types
Occupied Dwellings by Tenure: 2014 Occupied Private Dwellings by Structure Type:Total Occupied Dwellings 201,422 Single-detached House 55%Owner 66% Apartment; building that has fewer than 5 storeys 10%Rented 34% Apartment; building that has 5+ storeys 17%
Labour Force & Income
2014 Population 15 Years & Over by Labour Force Activity:
Educational Attainment:
In the Labour Force 66% No certificate, diploma or degree 10%Not in the Labour Force 34% Bachelor's degree 16%
University certificate, diploma or degree above Bachelor 11%
2014 Labour Force by Occupation:Management 8%Business, Finance & Administrative 16% 2014 Household Income:Natural & Applied Sciences 4% Average Household Income $79,025Health 6% Median Household Income $58,503Social science, education, government & religion 13%Art, culture, recreation and sport 0% 2014 Estimated Households by Income:Sales and service 32% Under $5,000 2%Trades, Transport & equiptment operators & related 16% $5,000 to $49,999 42%Primary industry-specific 0% $50,000 to $99,999 34%Processing, manufacturing and utilities 4% $100,000 to 199,999 18%Occupation - Not applicable 1% $200,000+ 5%
The redevelopment potential of Camp 6 in the near future is Low.Redevelopment Potential
Camp Orenda (44579 Truman Line Road, Belmont - Central Elgin)Camp Orenda is located in Belmont within the regional municipality of Central Elgin. A 25 km radius search indicated that the population was 466,009 people in 2014 and is projected to increase by only 12% by 2024. Majority of the population (55%) have resided in the area for 5+ years.
There are 201,422 occupied dwellings, of which 66% are owned. A high percentage of the dwellings (55%) consist of single-detached homes.
Approximately 27% of the population has a bachelor's degree or higher level education. The average household income is $79,025. Approximatley 44% of the population earn below $50,000 and 18% of the populaiton earn between $100,000 to $199,999. The top three occupations in the area are: (Sales and Service), (Trades & Transport), and (Business, Finance & Administrative).