Report run on: June 7, 2006 3:47 PM
RECAPP Facility Evaluation Report
Chestermere High School
B9379AChestermere
Rocky View Sch Div #41
Report run on: June 7, 2006 3:47 PM Page 2 of 48
B9379ABuilding Id:
Chestermere High SchoolBuilding Name:
ChestermereLocation:Address:
0.00Gross Area (sq. m): $14,429,350Replacement Cost:0Construction Year:
Evaluation Date: June 2 2005
Quinn Young ARchitectsEvaluation Company:
Mr. Sheldon QuinnEvaluator Name:
The original building was built in 1961 with an addition in 1972 and includes a basement mechanical room. In 1984 a newbuilding was constructed on the north side with a link to the original building. An addition was added to the 1984 buildingin 1995. Student capacity is approximately 800 students The building is in acceptable condition.
General Summary:
Structural Summary:Both buildings have concrete foundations with slab on grade construction. Mezzanine floors in the 1984 addition aresuspended concrete slabs. The roofs are constructed of a combination of glu-laminated , wood joists and wood decking andsteel beams and steel pans. Load bearing masonry throughout with a few interior steel columns supporting the glu-laminated and steel beams. The structure of the building is in good condition.
Envelope Summary:Exterior walls are finished with painted concrete block, split faced concrete block and clab brick. Windows are aluminumwith stucco panels below and above the windows in the 1961 and 1972 building sections. Portions of the BUR roof havebeen replaced with SBS. Exterior plywood wall surfaces and painted concrete block are in need of refinishing. Overall the envelope is in marginal to acceptable condition.
Interior Summary:The majoroty of the floors throughout are vinyl composite tile with some sheet vinyl and carpet in the admistration,library, and information processing spaces. Tile floors are typical in all washrooms. Walls are mostly painted concrete block with a few painted drywall and vinyl clad wood studs assemblies. The majority of the ceilings are T-Bar with painted gypsum board in some washrooms. Interior finshes are in acceptable condition.
Mechanical Summary:North & south buildings HVAC is provided by a heat pump system with dry and wet coolers and Make up air units. Twogas fire ventilation units serve the link between the two buildings. North and south buildings have indipendant heatingsystems consisting of gas boilers feeding heat exchangers, perimeter radiation, cabinet unit heatres and unit heaters.Plumbing systems in good working condition.
Electrical Summary:1600Amp Distribution system. The florescent lighting has recently been upgraded to T-8 technology, exit lightingrequires upgrading, structured cabling is up to date. The emergency generator electrical system requires upgrades toensure proper operation. The lighting neads some attention as numerous fixtures are not working. Generally, the facilityis in acceptable condition electrically.
2.41%5 year Facility Condition Index (FCI):
Facility Details Evaluation Details
Total Maintenance Events Next 5 years: $347,322
Chestermere - Chestermere High School (B9379A)
Condition Rating Performance1 - Critical Unsafe, high risk of injury or critical system failure.2 - Poor Does not meet requirements, has significant deficiencies. May have high operating/maintenance costs.
3 - Marginal Meets minimum requirements, has significant deficiencies. May have above average operating maintenance costs.4 - Acceptable Meets present requirements, minor deficiencies. Average operating/maintenance costs.
Rating Guide
5 - Good Meets all present requirements. No deficiencies.6 - Excellent As new/state of the art, meets present and foreseeable requirements.
Report run on: June 7, 2006 3:47 PM Page 3 of 48
Chestermere - Chestermere High School (B9379A)
Report run on: June 7, 2006 3:47 PM Page 4 of 48
A1030 Slab on Grade*
A2020 Basement Walls (& Crawl Space)*
B1010.01 Floor Structural Frame*(Building Frame)
B1010.02 Structural Interior Walls Supporting Floors*
B1010.05 Mezzanine Construction*
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
0
0
0
0
0
Installed
Installed
Installed
Installed
Installed
100
100
100
100
100
Design Life
Design Life
Design Life
Design Life
Design Life
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
Updated
Updated
Updated
Updated
Updated
Concrete slab at transformer has dropped
Repair 2006 $7,490 Medium
drop in slab has caused concrete split faced block (blast wall)to seperate from building
Concern:
mudjack slab if possible and repair damaged wallRecommendation:
Chestermere - Chestermere High School (B9379A)
S1 STRUCTURAL
Event:
Type Year Cost Priority
Updated: November 16 2005
1961: 125 mm conc. slab on grade, grade beam and concrete piles to sandstone 1972: 100 mm conc. slab on grade and reinforced concrete foundation walls vary 915-2100 deep 1984: 100-150 conc. slab on grade and combination of conc foundation walls, grade beams with piles 1995: slab on grade with reinforced foundation wall and strip footings
1961: Mechanical Room - concrete foundation walls & footings to slab level. Concrete block above 1984: Dressing areas below stage - concrete foundation walls & footings to slab level. Concrete block above
1972: combination of HSS columns with glu-lam beams and concrete block walls 1995: exterior concrete block walls with HSS columns and steel beams
1961: concrete block walls 1972: combination of concrete block walls and steel columns 1984: concrete block walls
1984: Library Music, Mechanical, Exercise, Industrial Arts - 200 mm reinforced concrete slab
Report run on: June 7, 2006 3:47 PM Page 5 of 48
B1010.09 Floor Construction Fireproofing*
B1010.10 Floor Construction Firestopping*
B1020.01 Roof Structural Frame*
B1020.04 Canopies*
B1020.06 Roof Construction Fireproofing*
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
0
0
0
0
0
Installed
Installed
Installed
Installed
Installed
100
100
100
100
100
Design Life
Design Life
Design Life
Design Life
Design Life
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
Updated
Updated
Updated
Updated
Updated
Chestermere - Chestermere High School (B9379A)
concrete floors throughout
1961: 19mm shiplap sheathing on 38x337 wood joists 1972: 38 steel deck on glulam beams 1984: metal deck on a combination of O.W.S.J. and steel channels in corridor 1995: metal deck on a combination of O.W.S.J. and steel beams
1984: recess entry at main entrance with linear soffit and recessed lights 1992: metal canopy and metal soffit with recessed lights at upgraded entrance
1961 and 1972: a mixture of combustible and non-combustible construction (sprinklered)
Report run on: June 7, 2006 3:47 PM Page 6 of 48
B2010.01.02.01 Brick Masonry: Ext. Wall Skin*
B2010.01.06.03 Metal Siding**
3 - Marginal
3 - Marginal
Rating
Rating
0
0
Installed
Installed
75
40
Design Life
Design Life
JUN-05
JUN-05
Updated
Updated
damaged bricks on 1992 wall upgrade
damaged upper brickwork on east wall of 1984building
cap flashing on metal cladding requires repair
Repair
Repair
Repair
2007
2007
2006
$1,070
$2,140
$535
Medium
Low
Low
damaged bricks 1992 wall upgrade
damaged bricks
bent cap flashing on east wall metal cladding near corridor link
Concern:
Concern:
Concern:
remove damage bricks and replace with new
replace brickwork
repair bent and twisted cap flashing
Recommendation:
Recommendation:
Recommendation:
Chestermere - Chestermere High School (B9379A)
S2 ENVELOPE
Event:
Event:
Event:
Type
Type
Type
Year
Year
Year
Cost
Cost
Cost
Priority
Priority
Priority
Updated:
Updated:
Updated:
November 16 2005
November 16 2005
November 16 2005
1992: brick exterior upgrade to existing 1961 and 1972 street elevation
1984: metal cladding on 1972 east wall face 1992: metal cladding of the upper wall upgrade to 1961& 1972 addition
Report run on: June 7, 2006 3:47 PM Page 7 of 48
B2010.01.06.04 Wood Siding**
B2010.01.08 Cement Plaster (Stucco): Ext. Wall*
B2010.01.09 Expansion Control: Exterior Wall Skin*
B2010.01.11 Joint Sealers (caulking): Ext. Wall**
3 - Marginal
4 - Acceptable
4 - Acceptable
2 - Poor
Rating
Rating
Rating
Rating
0
0
0
0
Installed
Installed
Installed
Installed
40
75
75
15
Design Life
Design Life
Design Life
Design Life
JUN-05
JUN-05
JUN-05
JUN-05
Updated
Updated
Updated
Updated
Expansion joint missing
Missing and damaged caulking
Repair
Repair
2006
2006
$535
$8,560
Low
Medium
expansion joint missing
Caulking around windows of 1992: upgrade has failed
Concern:
Concern:
fill opening with approved caulking
Replace caulking with new
Recommendation:
Recommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
November 16 2005
November 16 2005
1972: painted plywood panels and soffit. Refer to B2010.09
1971: stucco fascia
expansion joints generally acceptable
Generally caulking is acceptable however 1992: caulking at windows cracked and missing
Report run on: June 7, 2006 3:47 PM Page 8 of 48
B2010.01.13 Paints (& Stains): Exterior Wall**
B2010.02.03.02 Concrete Masonry: Ext. Wall Const.
2 - Poor
3 - Marginal
Rating
Rating
0
0
Installed
Installed
15
0
Design Life
Design Life
JUN-05
JUN-05
Updated
Updated
paint finish over stucco is wearing and uneven
paint is peeling an blistering
mortar in block work missing in a few locations
Lifecycle Replacement
Repair
Repair
2007
2007
2007
$5,350
$8,560
$1,070
Low
Medium
Medium
stucco finish is wearing and uneven. It has been painted brownon one side and grey in other areas
peeling and blistering paint on walls
Mortar in block work missing in a few locations
Concern:
Concern:
Concern:
refinish stucco with new acrylic finish
repaint block walls and replace plywood panel with metalcladding
Repoint mortor joints
Recommendation:
Recommendation:
Recommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Event:
Event:
Type
Type
Type
Year
Year
Year
Cost
Cost
Cost
Priority
Priority
Priority
Updated:
Updated:
Updated:
November 16 2005
November 16 2005
November 16 2005
1961 and 1972: paint finish is peeling and blistering on plwood and concrete block walls 1961 and 1972: painted stucco panels
1961: Concrete block 1972: Concrete block 1984: Split faced concrete block walls 1995: Split faced concrete block
Report run on: June 7, 2006 3:47 PM Page 9 of 48
B2010.06 Exterior Louvers, Grilles, and Screens*
B2010.09 Exterior Soffits*
B2020.01.01.02 Aluminum Windows (Glass & Frame)**
4 - Acceptable
3 - Marginal
3 - Marginal
Rating
Rating
Rating
0
0
0
Installed
Installed
Installed
20
20
35
Design Life
Design Life
Design Life
JUN-05
JUN-05
JUN-05
Updated
Updated
Updated
plywood soffits require frequent painting andmaintenance
insects between panes of 1984 windows (28 units)clerstory windows not checked (49 units) may havethe same problem
Preventative Maintenance
Repair
2009
2006
$5,350
$69,550
Medium
Medium
Plywood soffits on east face require repair and painting
Insects are between window panes of 1984 windows indicatingseals have failed
Concern:
Concern:
Strip patch and repair. Refer also to fascia (replacement)
Replace with sealed units and new glazing stops (or) replace aluminum winodows with new units c/w sealedglazing
Recommendation:
Recommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
November 16 2005
November 16 2005
painted louvers throughout
1984: linear metal soffit @ entrance 1995: vented metal soffits @ upgraded 1961original building and 1972 addition 1972: plywood and wood slats field doors (marginal) 1961: plywood soffits in courtyard
1984: on-site sealed units (seals have failed) 1992: window upgrades on west elevation of 1961 and 1972 additions (acceptable)
Report run on: June 7, 2006 3:47 PM Page 10 of 48
B2020.01.01.05 Wood Windows (Glass & Frame)**
B2030.01.01 Aluminum-Framed Storefronts**
B2030.01.02 Steel-Framed Storefronts**
B2030.01.06 Automatic Entrance Doors**
B2030.03 Large Exterior Special Doors*
B3010.04.01 Built-up Bituminous Roofing (Asphalt & Gravel)**
3 - Marginal
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
Rating
0
0
0
0
0
0
Installed
Installed
Installed
Installed
Installed
Installed
35
30
15
30
30
25
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
Updated
Updated
Updated
Updated
Updated
Updated
Existing wood framed windows. paint is peeling
Lifecycle Replacement 2008 $3,210 Low
wood framed windows lower portions have been replaced withvented units. Paint is peeling
Concern:
replace windows with vented metal unitsRecommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Type Year Cost Priority
Updated: November 16 2005
1961: wood windows at washrooms 1094 & 1095
1995: upgraded entrance to 1961 and 1972 addition
1984: main entrance
1995: Barrier Free access auto-operators installed at 1961 main entrance
CTS workshop overhead door
1972: Tar & Gravel built-up roof
Report run on: June 7, 2006 3:47 PM Page 11 of 48
B3010.04.04 Modified Bituminous Membrane Roofing (SBS)**
B3010.07 Sheet Metal Roofing**
3 - Marginal
3 - Marginal
Rating
Rating
0
0
Installed
Installed
25
40
Design Life
Design Life
JUN-05
JUN-05
Updated
Updated
low points in roof provide areas for water ponding
Preventative Maintenance 2007 $5,350 Low
Water ponding due to poor roof sloopesConcern:
Reslope roof at low points to provide proper drainageRecommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Type Year Cost Priority
Updated: November 16 2005
1961 & 1972: portions of original roof have been replaced with SBS membrane
refer to connecting link under temporary/portable structures
Report run on: June 7, 2006 3:47 PM Page 12 of 48
B3010.08 Flashing and Sheet Metal
4 - AcceptableRating
0Installed
30Design Life
JUN-05Updated
Clad wood fascia and plywood soffits
Metal flashing on roof twisted at gym wall
Preventative Maintenance
Failure Replacement
2008
2006
$21,400
$535
Low
Low
Wood fascia and plywood soffits require ongoing maintenance
Flashings are bent and twisted at gym roof
Concern:
Concern:
Clad with metal siding and sheet metal
Replace twisted flashings
Recommendation:
Recommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
November 16 2005
November 16 2005
1961: wood facsia in courtyard (marginal) 1972: metal cap flashings 1984: metal cap flashings 1995: metal cap flashings
Report run on: June 7, 2006 3:47 PM Page 13 of 48
B3010.08.02 Metal Gutters and Downspouts**
3 - MarginalRating
0Installed
25Design Life
JUN-05Updated
Rainwater leaders have been upgraded but do notdrain directly to splashpads
Study 2007 $2,140 Low
potential water damage at wall in heavy rains there is apotential for ice to build-up at wall locations during freeze/thawcycles
Concern:
review maintenance records for frequency of damage orproblems with drainage
Recommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Type Year Cost Priority
Updated: November 16 2005
1961 & 1972: courtyard roof drains lead to exposed rainwater leaderswhich drain to courtyard
Report run on: June 7, 2006 3:47 PM Page 14 of 48
B3020.02 Other Roofing Openings (Hatch,Vent, etc)*
2 - PoorRating
0Installed
0Design Life
JUN-05Updated
Roof hatch opens on opposite side of ladderr
damaged flashing at vents drain guards damagedor missing
Repair
Repair
2006
2006
$3,210
$1,070
High
Low
ladder access to roof is on hinge side of roof hatch making roofaccess dangerous
Roof drain guards are damaged and missing and flashings aredamaged around vent stacks in more than one location
Concern:
Concern:
remove existing hatch and replace (or if in good condition rotate180 degrees), install new flashings
Replace draing guards repair or replace damaged vent flashings
Recommendation:
Recommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
November 16 2005
November 16 2005
1972: Metal roof Hatch 1961 and 1972: roof drain guards
Report run on: June 7, 2006 3:47 PM Page 15 of 48
C1010.01 Interior Fixed Partitions*
C1010.02 Interior Demountable Partitions*
C1010.03 Interior Operable Folding Panel Partitions**
C1010.04 Interior Balustrades and Screens, Interior Railings*
3 - Marginal
4 - Acceptable
3 - Marginal
4 - Acceptable
Rating
Rating
Rating
Rating
0
0
0
0
Installed
Installed
Installed
Installed
50
30
30
40
Design Life
Design Life
Design Life
Design Life
JUN-05
JUN-05
JUN-05
JUN-05
Updated
Updated
Updated
Updated
Damaged drywall in rooms 1076, 1069, 1074
Damaged vinyl on one panel in 1019
Repair
Repair
2006
2007
$1,070
$1,070
Low
Low
Damaged drywall in upgraded walls in 3 locations
Damaged vinyl covering on panel in 1019
Concern:
Concern:
Patch & repair damaged drywall , repaint entire wall to naturalbreak
Replace vinyl on one panel section
Recommendation:
Recommendation:
Chestermere - Chestermere High School (B9379A)
S3 INTERIOR
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
November 16 2005
November 16 2005
1961: concrete block & wood/gypsum board 1972: concrete block & wood/gypsum board
post 1972 vinyl clad wall board and trim has been used on some infill walls
2000 upgrade: drama room stage 1984: folding partition 1019 1995: between 1022 and 1023
1984: bleacher railing - metal & glass (acceptable) 1984: handrails at ramps to gym (acceptable)
Report run on: June 7, 2006 3:47 PM Page 16 of 48
C1010.05 Interior Windows*
C1010.07 Interior Partition Firestopping*
C1020.01 Interior Swinging Doors**
4 - Acceptable
3 - Marginal
4 - Acceptable
Rating
Rating
Rating
0
0
0
Installed
Installed
Installed
40
50
50
Design Life
Design Life
Design Life
JUN-05
JUN-05
JUN-05
Updated
Updated
Updated
potential window failure
Incomplete drywall around beam at stage area
Preventative Maintenance
Repair
2006
2007
$5,350
$2,140
Low
Low
if glass is not tempered it may shatter and cause injury
Drywall has been attached to exposed existing beam at stagearea but is not taped or complete
Concern:
Concern:
investigate and replace with laminated or wired glass ifnecessary
Review for other exposed conditions and determine whethermechanical or architectural fire separation is required. Finishincomplete work.
Recommendation:
Recommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
November 16 2005
November 16 2005
1972: glass in pressed steel frames between 1053 and 1053D (acceptable) 1972: glass in metal frames between 1072 and 1070A / 1070 and 1070A (acceptable) upgrade: glass sidelites install with doors in 1961 portion date unknown (acceptable): 1984: wired glass in metal frame at adminstration office (acceptable) 1984: glass in metal frame between councelling and ante room (acceptable) 1984: glass windows in library office (acceptable) 1984: glass windows between CTS workshop and classroom (marginal)
1961 & 1972: Building has been upgraded to sprinklers system Fire rating of fire separations only required at storage rooms(refer to doors for events) 1984: building is compartmentalized with 2 hr masonry fire walls
solid core birch doors to classrooms through-out
Report run on: June 7, 2006 3:47 PM Page 17 of 48
C1020.03 Interior Fire Doors*
3 - MarginalRating
0Installed
50Design Life
JUN-05Updated
Wood door frame does not provide the ratingrequired 1068A Storage room
Wood door to 1076A not rated
wood door in metal frame should be 90 min.
Code Repair
Code Repair
Code Repair
2006
2006
2006
$1,070
$535
$1,070
Unassigned
Medium
Unassigned
unrated door frame
Unrated wood door to storage room
2 hr firewall between 1984 building and 1995 addition requires a90 min rated door assembly. the Janitors room opens into themechanical space and has a wood door
Concern:
Concern:
Concern:
Replace frame and dorr with rated frame and door
Confirm rating and install rated door in metal frame if required
replace wood door with rated metal door to janitors room andmusic room
Recommendation:
Recommendation:
Recommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Event:
Event:
Type
Type
Type
Year
Year
Year
Cost
Cost
Cost
Priority
Priority
Priority
Updated:
Updated:
Updated:
November 16 2005
November 16 2005
November 16 2005
1961 & 1972: building sprinklered in 2000 (service rooms do not require a rating. storage rooms require a min. 45 minute rating) 1984: building is separated into fire compartments corridor doors are rated (acceptable) 1995: 20 minute doors between classrooms and corridor (acceptable) 1995: door to 1984 Janitor room wood (poor)
Report run on: June 7, 2006 3:47 PM Page 18 of 48
C1030.01 Visual Display Boards**
C1030.02 Fabricated Compartments(Toilets/Showers)**
4 - Acceptable
3 - Marginal
Rating
Rating
0
0
Installed
Installed
10
20
Design Life
Design Life
JUN-05
JUN-05
Updated
Updated
Damaged vinyl tackborads in 4 locations
Toilet compartment cubicles and doors have beenvandalized in a few locations
Failure Replacement
Preventative Maintenance
2007
2007
$1,177
$10,700
Low
Low
Damaged Tack boards in 4 locations
Some doors and cubicles have been vandalized.
Concern:
Concern:
Replace 4 tackboards
Refinish or replace
Recommendation:
Recommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
November 16 2005
November 16 2005
a combination of white boards and chalkboards through-out Tack boards in all classrooms and in corridors (4 damaged)
Painted metal toilet compartments (throughout)
Report run on: June 7, 2006 3:47 PM Page 19 of 48
C1030.08 Interior Identifying Devices*
C1030.10 Lockers**
C1030.12 Storage Shelving*
3 - Marginal
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
0
0
0
Installed
Installed
Installed
10
30
20
Design Life
Design Life
Design Life
JUN-05
JUN-05
JUN-05
Updated
Updated
Updated
Interior directional signage is limited.
1984: lockers have some damage
Operating Efficiency Upgrade
Lifecycle Replacement
2008
2009
$8,560
$5,350
Low
Low
Interior directional signage is limited. New visitors to the schooldo not have any clues as to the location of the main office,gymnasiums and washrooms. Exterior vestibule doors to thewashrooms have been removed. Improved signage is required inthe main hallway to identify male vs. female toilets.
Damaged doors on a number of lockers
Concern:
Concern:
Updated directional and washrooms signage signage
replace 50 damaged doors (allowance)
Recommendation:
Recommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
November 16 2005
November 16 2005
The buildings have 4 street side entrances with parking at each end and limited parking in the centre. Once inside the main door directional signage is very limited.
lockers throughout
freestanding wood shelving throughout
Report run on: June 7, 2006 3:47 PM Page 20 of 48
C1030.14 Toilet, Bath, and Laundry Accessories*
C1030.17 Other Fittings*
C2010 Stair Construction*
4 - Acceptable
3 - Marginal
4 - Acceptable
Rating
Rating
Rating
0
0
0
Installed
Installed
Installed
20
0
100
Design Life
Design Life
Design Life
JUN-05
JUN-05
JUN-05
Updated
Updated
Updated
Damaged mirror in staff washroom
Towel hook are missing and broken
Lifecycle Replacement
Failure Replacement
2008
2006
$1,605
$2,140
Low
Low
Mirror shows signs of desilvering and dmage below soapdispenser
Towel hookas area missing and broken
Concern:
Concern:
Mirror is strill useable but should be replaced in near future
Replace towel hooks throughout locker rooms
Recommendation:
Recommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
November 16 2005
November 16 2005
toilet paper, soap dispensors, mirrors throughout
1984: towel hooks in locker rooms
1961: concrete stair to basement mechanical 1984: concrete stairs to mezzanines and basement shower rooms 1984: metal ship ladder to mechanical mezzanine 2000: metal ladder to upper mechanical above stage
Report run on: June 7, 2006 3:47 PM Page 21 of 48
C2020.05 Resilient Stair Finishes**
C2020.06 Carpet Stair Finishes**
C2020.08 Stair Railings and Balustrades*
C2020.11 Other Stair Finishes*
C3010.02 Wall Paneling**
C3010.04 Gypsum Board Wall Finishes*
3 - Marginal
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
Rating
0
0
0
0
0
0
Installed
Installed
Installed
Installed
Installed
Installed
20
10
50
0
30
40
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
Updated
Updated
Updated
Updated
Updated
Updated
Stair treads and nosing starting to crack/wear.Nosing damaged in one location
Lifecycle Replacement 2010 $2,140 Low
Stair nosing damaged treads are starting to show wearConcern:
Replace in near futureRecommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Type Year Cost Priority
Updated: November 16 2005
1984: resilient tile nosing and treads to workshop mezzanine
1984: Library
1984: library metal railing on stairs metal & glass @ mezzanine (acceptable) 1984: CTS space metal railing on concrete curb (acceptable) 1984: music room metal railing @ mezzanine (acceptable)
1984: metal channel mechanical room staircase
2000: MDF wall panels either side of display case
painted drywall throughout
Report run on: June 7, 2006 3:47 PM Page 22 of 48
C3010.06 Tile Wall Finishes**
C3010.11 Interior Wall Painting**
C3010.12 Wall Coverings**
C3020.01 Concrete Floor Finishes (Paint)*
4 - Acceptable
4 - Acceptable
4 - Acceptable
3 - Marginal
Rating
Rating
Rating
Rating
0
0
0
0
Installed
Installed
Installed
Installed
50
5
10
75
Design Life
Design Life
Design Life
Design Life
JUN-05
JUN-05
JUN-05
JUN-05
Updated
Updated
Updated
Updated
painted and unpainted floor in 1984 mechanicalroom in poor condition numerous mechanical leaks
Repair 2007 $10,700 Medium
painted and unpainted floor in 1984 mechanical room in poorcondition due to maitenance operations and requirements,leaking
Concern:
Strip & clean floor and repaint entire mechanical room floors toseal
Recommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Type Year Cost Priority
Updated: November 16 2005
1984: 100X100 ceramic tiles in washrooms 1032, 1033,1041, 1042 1972: showers in 1090, 1091 1972: washrooms 1094, 1095 1961: behind urinals in 1067
Painted concrete block and drywall throughout
Some vinyl finshes on demountable partitions
1961: mechanical room (acceptable) 1984: mechanical room (poor)
Report run on: June 7, 2006 3:47 PM Page 23 of 48
C3020.02 Tile Floor Finishes**
C3020.04 Wood Flooring**
3 - Marginal
3 - Marginal
Rating
Rating
0
0
Installed
Installed
30
25
Design Life
Design Life
JUN-05
JUN-05
Updated
Updated
Floor mounted urinals are on a raised platformabout 125 above the finished floor
Flooring was to be replasced with a pulasticsystem in 2000
Barrier Free Access Upgrade
Program Functional Upgrade
2010
2010
$16,050
$53,500
Low
Low
Raised platform at urinals creates a tripping hazard and limitsaccessibility for use of walkers, canes
Wood flooring was to be replaced with a pulastic floor systemto make the gym multi-functional
Concern:
Concern:
Replace floor mounted urinals (near the end of their life-cycle)with updated wall hung remove platform and retile
Replace with pulastic floor as previously proposed.
Recommendation:
Recommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
November 16 2005
November 16 2005
1961, 1972, 1984: quarry tile vestibule entrances All washrooms and shower areas have a variation of 25x25, 50x50 and 100x100 non slip ceramic tiles 1972 washroom floors have quarry tile finish in rooms 1094 and 1095
1984: gymnsaium (acceptable) 1961: gymnasium floor (marginal)
Report run on: June 7, 2006 3:47 PM Page 24 of 48
C3020.07 Resilient Flooring**
3 - MarginalRating
0Installed
20Design Life
JUN-05Updated
Uneven transition between additions
sheet vinyl flooring in corridor
Preventative Maintenance
Lifecycle Replacement
2008
2010
$4,280
$16,050
Low
Low
Corridor transition between floor slabs has created an unevenarea. Sheet vinyl has been repaired. Sheet Vinyl is also nearinglife cycle replacement
Sheet vinyl is starting to show wear
Concern:
Concern:
Sheet vinyl appears to have been patched at transition, removeflooring repair damaged slab (smooth) replace sheet vinyl toturn in corridor
replace as soon as funding is available
Recommendation:
Recommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
November 16 2005
November 16 2005
VCT tile throughout 1961 & 1972: sheet vinyl upgraded in portion of corridor 1984: sheet vinyl on ramp to main gymnasium 2000: sheet vinyl in upgraded corridor/student gathering space
Report run on: June 7, 2006 3:47 PM Page 25 of 48
C3020.08 Carpet Flooring**
C3020.11 Floor Painting
3 - Marginal
5 - Good
Rating
Rating
0
0
Installed
Installed
10
5
Design Life
Design Life
JUN-05
JUN-05
Updated
Updated
Carpet in staff admin offices is worn
carpet stained Room 1005
patch in carpet
Failure Replacement
Repair
Preventative Maintenance
2009
2006
2010
$32,100
$1,070
$1,070
Low
Low
Low
Older worn carpet is near end of life-cycle
Carpet stained Room 1005
patch in carpet
Concern:
Concern:
Concern:
Replace with new
Thorough cleaning of computer room if stain won't releasepatch & repair carpet
repair carpet or install proper access panel and clean wholecarpet
Recommendation:
Recommendation:
Recommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Event:
Event:
Type
Type
Type
Year
Year
Year
Cost
Cost
Cost
Priority
Priority
Priority
Updated:
Updated:
Updated:
November 16 2005
November 16 2005
November 16 2005
1984: admin offices, Computer rooms, library 1984: Room 1003 updated carpet in staff room (marginal)
1984: gymnasium floor 2000: upgrade to 1961 gym floor
Report run on: June 7, 2006 3:47 PM Page 26 of 48
C3020.14 Other Floor Finishes**
C3030.02 Ceiling Paneling (Wood)*
C3030.04 Gypsum Board Ceiling Finishes*
4 - Acceptable
3 - Marginal
3 - Marginal
Rating
Rating
Rating
0
0
0
Installed
Installed
Installed
0
25
50
Design Life
Design Life
Design Life
JUN-05
JUN-05
JUN-05
Updated
Updated
Updated
old exposed soffit, wood slats and stucco @ link
Missing access panel in room 1016
Lifecycle Replacement
Repair
2010
2006
$1,605
$1,070
Low
Low
older finishes require more frequent maintenance
Missing access panel at storage room ceiling.
Concern:
Concern:
upgrade soffit and remove wood slats to reduce on-goingmaintenance costs
Confirm that ceiling does not require a rating (due to storageuse do wall extend up to u/s of deck?), replace missing accesspanel
Recommendation:
Recommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
November 16 2005
November 16 2005
1972: upgraded sports flooring in weight training rooms #1096 & 1097
1984: corridor/link Room 1996 old plaster soffit and wood slats original 1972 addition
painted gypsum board ceilings in some washrooms, shower areas and storage rooms
Report run on: June 7, 2006 3:47 PM Page 27 of 48
C3030.06 Acoustic Ceiling Treatment (Susp.T-Bar)**
C3030.07 Interior Ceiling Painting**
C3030.09 Other Ceiling Finishes*
3 - Marginal
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
0
0
0
Installed
Installed
Installed
25
10
10
Design Life
Design Life
Design Life
JUN-05
JUN-05
JUN-05
Updated
Updated
Updated
stained tiles 3 locations in corridor 1992 stained tiles 2 locations in 1052 Stained tiles 2 locations in 1093 Stained tile 1 location in 1029 Stained tile 1 location in 1024 Stained tile in corrdior adjacent to 1018A
Repair 2006 $5,350 Medium
Stained ceiling tiles in various rooms indicating service pipingleak or roof leaks
Concern:
Investigate each location repair leak condition and replacedamaged ceiling tile
Recommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Type Year Cost Priority
Updated: November 16 2005
Acoustic Tiles throughout classrooms and corridors in classrooms and corridors 2000: upgraded corridor 1961 & 1972 addition
Painted gyspum board
1984: stipple ceiling on concrete roof in locker areas below bleachers
Report run on: June 7, 2006 3:47 PM Page 28 of 48
D2010.01 Water Closets**
D2010.02 Urinals**
D2010.03 Lavatories**
D2010.04 Sinks**
D2010.05 Showers**
D2010.08 Drinking Fountains / Coolers**
D2010.09 Other Plumbing Fixtures**
4 - Acceptable
4 - Acceptable
4 - Acceptable
5 - Good
4 - Acceptable
4 - Acceptable
5 - Good
Rating
Rating
Rating
Rating
Rating
Rating
Rating
0
0
0
0
0
0
0
Installed
Installed
Installed
Installed
Installed
Installed
Installed
30
30
30
30
30
30
0
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
Updated
Updated
Updated
Updated
Updated
Updated
Updated
Chestermere - Chestermere High School (B9379A)
S4 MECHANICAL
Floor mounted WC with flush tanks.
South side, Wall hung china with flush valve Stall urinals with flush valve. North side, Crane stall urinals with auto flush valves.
south side , Chins vanity basins. North side, Stel enamel vanity with two handle taps.
south side, single ss sinks with two handle taps in science rooms, 1014, 1031, Staff & Laundry. Double ss sinks with two handle taps in food labs, 1030, 1025, 1024 Triple ss sink with gooseneck tap in room 1029.
South side, Individual shower cubicles for female and gang shower for boys. Push button control. Office has single lever shower.
China drinking fountains.
Wasing machine in food lab, Cast iron sink in room 1009, Janitors mop siks with vacuum breaker faucets. Food lab with grilles over cookers to exhaust fan
Report run on: June 7, 2006 3:47 PM Page 29 of 48
D2020.01.01 Pipes and Tubes: Domestic Water*
D2020.01.03 Piping Specialties (Backflow Preventors)**
D2020.01.08 Hose Bibbs
D2020.02.02 Plumbing Pumps: Domestic Water**
D2020.02.04 Domestic Water Conditioning Equipment**
D2020.02.06 Domestic Water Heaters**
D2020.03 Water Supply Insulation*: Domestic
D2030.01 Waste and Vent Piping*
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
Rating
Rating
Rating
0
0
0
0
0
0
0
0
Installed
Installed
Installed
Installed
Installed
Installed
Installed
Installed
40
30
0
20
10
20
30
50
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
Updated
Updated
Updated
Updated
Updated
Updated
Updated
Updated
Chestermere - Chestermere High School (B9379A)
150 incoming water. 150 branch to fire pump and 100mm copper pipe to school. Copper pipe and fittings
check valve and meter on the domestic supply. Two pressure tanks. Backflow on boiler feeds.
Exterior lawn services
Booster pump on the incoming water supply from outside. Domestic Hot water recirc pump Astro 30B.
Domestic water recirculation system to holding tanks with clorine chemical injection.
North side has a State SRX-75, Gas fired 67600 btu North side, Three Rheem GL85-250A gas fired tanks
25mm fibreglass
Sanitary to Sewage to lagoon at the north end of the property.
Report run on: June 7, 2006 3:47 PM Page 30 of 48
D2030.03 Waste Piping Equipment*
D2040.01 Rain Water Drainage Piping Systems*
D2040.02.04 Roof Drains**
D3010.02 Gas Supply Systems*
D3010.06 Other Energy Supply Systems*
D3020.02.01 Heating Boilers and Accessories: H.W.**
D3020.02.02 Chimneys (&Comb. Air): H.W. Boiler**
4 - Acceptable
5 - Good
5 - Good
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
Rating
Rating
0
0
0
0
0
0
0
Installed
Installed
Installed
Installed
Installed
Installed
Installed
30
50
40
50
50
30
30
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
Updated
Updated
Updated
Updated
Updated
Updated
Updated
Chestermere - Chestermere High School (B9379A)
South side. Duplex sump pump for mechanical room drains North side duplex pump and sump for groundwater with level controls. Industrial Arts area sump.
Cast iron Internal rainwaters to outside splash pads
cast iron roof drains with domes
North end gas meter room, 50mm gas line to equipment. room is heated and ventilated South side, Gas enters below siamese connection, 75mm gas line to distribution. Gas turrets in science rooms withemergency shut offs.
Waterous emegency diesel generator with diesel storage. 150mm welded exhaust. electric motorised dampers for air cooling
North side. Three Hydrotherm Multi temp gas boilers, Each with 3 gas burners and controls. Low water cut off, boiler feed,Safty valves, Expansion tanks, Two boiler pumps. South side, Two Weil McLain A310827p8286, 2 stage gas fired boilers. 780,000 btu with low water cut offs, safety valves,Expantion tanks, Air eliminator, Boiler feed, Armstong Pumps P1 & 2, Armstrong pumps P3 & 4 with suction guides,Flexible connections,
North and south side.Venting and insulation, Combustion air
Report run on: June 7, 2006 3:47 PM Page 31 of 48
D3020.02.03 Water Treatment: H. W. Boiler*
D3030.05.02 Mechanical-Draft Cooling Towers
D3030.05.02 Mechanical-Draft Cooling Towers
D3030.07.03 Water Source Heat Pumps
D3040.01.01 Air Handling Units: Air Distribution**
D3040.01.01 Air Handling Units: Air Distribution**
D3040.01.02 Fans: Air Distribution*
D3040.01.03 Air Cleaning Devices:Air Distribution*
5 - Good
4 - Acceptable
5 - Good
5 - Good
4 - Acceptable
5 - Good
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
Rating
Rating
Rating
0
0
0
0
0
0
0
0
Installed
Installed
Installed
Installed
Installed
Installed
Installed
Installed
30
0
0
0
30
30
30
30
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
Updated
Updated
Updated
Updated
Updated
Updated
Updated
Updated
Chestermere - Chestermere High School (B9379A)
North side, Water treatment plan in place, Chemical Pot feed, By-pass filter. South side, boiler system with pot feeder and by-pass. Glycol side with pot feeder and by-pass.and glycol fill tank.
North side, Baltimore water cooled unit VX136-3 for heat pump system.
South side, Roof top dry cooler with fans, for south heat pump system
Most areas served by local heat pumps (Climate Masters)
North side , Unit F5, Engineered Air B69-N-03 gas fired inshot power burner. Industial arts area have two roof top units.
Roof top Make up air units, Engineered air DG series, gas fired. ICE unit (no model) gas fired.
Air distribution with heat pump fans.
Filters in Make up air units, Heat pumps
Report run on: June 7, 2006 3:47 PM Page 32 of 48
D3040.01.04 Ducts: Air Distribution*
D3040.01.07 Air Outlets & Inlets:Air Distribution*
D3040.03.01 Hot Water Distribution Systems**
D3040.04 Special Exhaust Systems
D3040.04.01 Fans: Exhaust**
D3040.04.03 Ducts: Exhaust*
D3040.04.05 Air Outlets and Inlets: Exhaust*
D3040.05 Heat Exchangers**
5 - Good
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
5 - Good
Rating
Rating
Rating
Rating
Rating
Rating
Rating
Rating
0
0
0
0
0
0
0
0
Installed
Installed
Installed
Installed
Installed
Installed
Installed
Installed
50
30
40
30
30
0
0
30
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
Updated
Updated
Updated
Updated
Updated
Updated
Updated
Updated
Chestermere - Chestermere High School (B9379A)
Suply, return and make up air Galvanised ducting
Grilles and diffusers, Louvers and Penthouse
North and South sides have steel pipe distribution with copper connections to the heat pumps three way valves and bypass. Flexible connections at the heating pumps.
Industrial Arts Dust collection system, Outside Camco Redboine Shaker unit with recirculated air back to space
Industrial arts, four exhaust fans for booths, Darkroom ex fan, Ex fan hood and fan for parts cleaning. Copier room localexhaust. Washroom roof top fans. Laundry room exhaust.
Galvanized rectangular and round duxts
Grilles
Glycol heat exchanger for heat pump system. South side, Armstrong glycol exchanger with 3 way elec valve
Report run on: June 7, 2006 3:47 PM Page 33 of 48
D3040.06 Other HVAC Distribution Systems*
D3050.03 Humidifiers**
D3050.05.02 Fan Coil Units**
D3050.05.03 Finned Tube Radiation**
D3050.05.06 Unit Heaters**
D3050.06 Energy Recovery Units*
D3060.02.01 Electric and Electronic Controls**
D3060.02.02 Pneumatic Controls**
4 - Acceptable
4 - Acceptable
5 - Good
5 - Good
5 - Good
4 - Acceptable
5 - Good
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
Rating
Rating
Rating
0
0
0
0
0
0
0
0
Installed
Installed
Installed
Installed
Installed
Installed
Installed
Installed
0
25
30
40
30
0
30
40
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
Updated
Updated
Updated
Updated
Updated
Updated
Updated
Updated
Chestermere - Chestermere High School (B9379A)
Two gas fired roof top unis above the link between the north and south buildings serve te corridor areas. (No name)
North mechanical unit has humidifier
South side, Horizontal cabinet unit heaters at entrance ways North side, Cabinet unit heaters.
Perimeter radiation and High level radiation to upper widows.
Unit heaters in mechanical areas, Round style heaters in the industrial arts areas. South side hot water Sigma unit.
North side, 3 large insulated storage tanks for heat pump system
Heat pump control valves. Boiler controls and safetys, Heat pump coolers, Ex fans
Curtis Wright compressor, Thompson Gordon Drye. Pneumatic control dampers
Report run on: June 7, 2006 3:47 PM Page 34 of 48
D3060.02.05 Building Systems Controls(BMCS, EMCS)**
D4010 Sprinklers: Fire Protection*
D4030.01 Fire Extinguisher, Cabinets and Accessories**
D4090 Other Fire Protection Systems*
D4090.06 Smoke Protection & Exhaust Fans**
D4090.07 Fire Pumps & Water Storage Tanks**
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
Rating
0
0
0
0
0
0
Installed
Installed
Installed
Installed
Installed
Installed
30
50
30
0
0
0
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
Updated
Updated
Updated
Updated
Updated
Updated
Chestermere - Chestermere High School (B9379A)
BMS Excell controls both north and south sides
South side is sprinklered. Siameze connection at the west entrance.
Fire extinguishers throughout
Outside Fire Hydrant on school property.
Smoke detection in ducting.
Fire pump, outside domestic storage tank (Water delivered by tanker)
Report run on: June 7, 2006 3:47 PM Page 35 of 48
D5010.03 Main Electrical Switchboards (Main Distribution)**
D5010.05 Electrical Branch Circuit Panelboards (Secondary Distribution)**
D5010.07 Motor Control Centers (Motor Control)**
D5010.07.02 Motor Starters and Accessories**
D5020.01 Electrical Branch Wiring*
D5020.02.02.02 Interior Florescent Fixtures**
5 - Good
5 - Good
5 - Good
4 - Acceptable
4 - Acceptable
3 - Marginal
Rating
Rating
Rating
Rating
Rating
Rating
0
0
0
0
0
0
Installed
Installed
Installed
Installed
Installed
Installed
40
25
30
0
50
30
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
Updated
Updated
Updated
Updated
Updated
Updated
Provide proper maintenance of lamps and ballasts
Preventative Maintenance 2006 $8,025 Low
Numerous fixtures have burn't out lamps and or ballasts.Various pot lights are missing finishing trims and lamps.
Concern:
Repair and replace as required lamps and ballasts.Recommendation:
Chestermere - Chestermere High School (B9379A)
S5 ELECTRICAL
Event:
Type Year Cost Priority
Updated: November 16 2005
(1985+) FPE 1600A service entrance board with 1200A trip, Power logic digital meter
(1985+) CDP's and panelboards, most with spare capacity. (1972) School has FPE 400A CDP
(1984) Klockner Moller MCC in the main electrical room. Some spare capacity. The 1984 shop area has emergency should down switch to all electrical equipment in the shop.
(1984) Has a small number of loose motor starters (1972) Has loose motor starters.
Generally the switches and receptacles are in good condition. Some outlets in the 1972 area are starting to show signs ofwarring.
All florescent fixtures within the school have been retrofitted with T-8 lamps with electronic ballasts. Numerous fixtures arenot working and in a general state of disrepair.
Report run on: June 7, 2006 3:47 PM Page 36 of 48
D5020.02.02.03 Interior Metal Halide Fixture*
D5020.02.03 Emergency Lighting*
D5020.03.01.03 Exterior Metal Halide Fixtures*
D5030.01 Detection and Fire Alarm**
D5030.02.01 Door Answering*
4 - Acceptable
3 - Marginal
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
0
0
0
0
0
Installed
Installed
Installed
Installed
Installed
30
0
0
25
25
Design Life
Design Life
Design Life
Design Life
Design Life
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
Updated
Updated
Updated
Updated
Updated
Replace exit lights
Lifecycle Replacement 2010 $21,400 Low
Exit lights are near the end of their life cycle.Concern:
Replace the exit lights with LED style fixtureRecommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Type Year Cost Priority
Updated: November 16 2005
(1984) Gym has HID high bay light fixtures. (1995) Centre core has HID indirect uplighting.
(1980+) exit lighting is connected to the emergency distribution. Exit lights are incandescent lamp type fixtures.
(1985+) HID exterior pole lighting in the parking lot (1985+) HID wall pack at various locations around the school (1972+) HID under eave pot lights at entrances to the 1972 building All controlled by photocell and timer in the main electrical room.
(1990+) SImplex 4020 fire alarm panel located in the 1984 building operator office, LCD annunciator located at the mainentrance. Bell/strobe devices in all areas except the 1984 addition.
Push button at the main entrance operates a buzzer in the school.
Report run on: June 7, 2006 3:47 PM Page 37 of 48
D5030.02.03 Security Access**
D5030.02.04 Video Surveillance**
D5030.03 Clock and Program Systems**
D5030.04.01 Telephone Systems**
D5030.04.02 Paging Systems*
D5030.04.04 Data Systems**
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
Rating
0
0
0
0
0
0
Installed
Installed
Installed
Installed
Installed
Installed
25
25
25
25
25
25
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
Updated
Updated
Updated
Updated
Updated
Updated
Add door security contacts
Operating Efficiency Upgrade 2007 $5,350 Low
Not all exterior doors have magnetic door contacts. Somedoors show signs that at one time there were door contactsinstalled, but are now missing.
Concern:
Install door security contacts at all exterior doors that requirethem.
Recommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Type Year Cost Priority
Updated: November 16 2005
Magnum Alert security system, key pad at the main entrance, ceiling and wall mounted motion detectors in corridors andall exrerior classrooms. Door contacts at most, but not all exterior doors.
There are 2 pole mounted secuity cameras and few interior ceiling mounted cameras. They are wired to a monitor located inthe main office.
Rauland master clock system and digital clock through out the school and in each classroom.
(1990+) Rauland hand sets in the office areas and in each classroom. There are various Bix blocks in all parts of the school.
Paging is done through the phone system.
Cisco hubs and Cat 5 cabling throughout. Each classroom has at least one data outlet.
Report run on: June 7, 2006 3:47 PM Page 38 of 48
D5030.04.05 Local Area Network Systems*
D5030.06 Television Systems*
D5090.02 Packaged Engine Generator Systems (Emergency Power System)**
4 - Acceptable
4 - Acceptable
3 - Marginal
Rating
Rating
Rating
0
0
0
Installed
Installed
Installed
25
20
35
Design Life
Design Life
Design Life
JUN-05
JUN-05
JUN-05
Updated
Updated
Updated
Up date emergency generator battery system andblock heater. Review transfer switch operation
Repair 2007 $10,700 Low
With the broken test switch on the transfer switch in themechanical room, regular testing of the generator isquestionable. No battery charging system and no block heaterincrease the risk the generator will not start when required.
Concern:
The entire emergency generator system should be upgraded toensure proper operation.
Recommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Type Year Cost Priority
Updated: November 16 2005
Cisco hubs and Cat 5 cabling in each computer labs in the 1961, 1972 and 1984 additions. All cabling and power is runthrough wiremold to each work station.
Cable TV enters the 1984 building, each classroom in the 1995 addition has a cable TV outlet
(1984) 125KW generator is located in a shed behind the 1984 addition. Schmidtec transfer switch in the 1985 mechanicalroom (has a broken test switch). It appears there is no battery charger for the generator battery and no block heater on theengine.
Report run on: June 7, 2006 3:47 PM Page 39 of 48
E1020.02 Library Equipment*
E1020.03 Theater and Stage Equipment*
4 - Acceptable
3 - Marginal
Rating
Rating
0
0
Installed
Installed
25
25
Design Life
Design Life
JUN-05
JUN-05
Updated
Updated
no proper access panel/door is provided to motorcontrol of operable partition at stage
Repair 2007 $1,070 Low
no proper access panel/door is provided to motor control ofoperable partition at stage
Concern:
install premanufacturered metal access panel to finish openingRecommendation:
Chestermere - Chestermere High School (B9379A)
S6 EQUIPMENT, FURNISHINGS AND SPECIAL CONSTRUCTION
Event:
Type Year Cost Priority
Updated: November 16 2005
Book security system in library
2000: Drama Stage upgrade
Report run on: June 7, 2006 3:47 PM Page 40 of 48
E1020.07 Laboratory Equipment*
E1090.02 Solid Waste Handling Equipment*
5 - Good
4 - Acceptable
Rating
Rating
0
0
Installed
Installed
25
0
Design Life
Design Life
JUN-05
JUN-05
Updated
Updated
Safety cabinets are not vented properly
Safety cabinets in prep room do not appear to beconnected to a ventilation system
Existing wood cladding has missing boards andrequires painting
Code Repair
Code Repair
Repair
2006
2006
2008
$1,070
$2,140
$2,140
High
Medium
Unassigned
Safety cabinet below fumehood does not vent without furmhoodactivated
Storage of chemicals in unvented cabinets
garbage enclosure has missing boards and requires painting
Concern:
Concern:
Concern:
Exhaust fan should be on at all times even when hood is notused.
Confirm whether safety cabinets are being used. If chemicalsrequiring venting are being stored cabinets shold be ventedaccordingly
replace missing boards and repaint or install new prefinshedclad metal similar to south enclosure
Recommendation:
Recommendation:
Recommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Event:
Event:
Type
Type
Type
Year
Year
Year
Cost
Cost
Cost
Priority
Priority
Priority
Updated:
Updated:
Updated:
November 16 2005
November 16 2005
November 16 2005
1995: new laboratories 1972: science labs have been upgraded
Garbage Bin Enclosure on east side (marginal) GArbage Enclosure on South side (acceptable)
Report run on: June 7, 2006 3:47 PM Page 41 of 48
E1090.03 Food Service Equipment*
E1090.07 Athletic, Recreational, and Therapeutic Equipment*
E2010.02.05 Educational Facility Casework*
E2010.02.07 Kitchen Casework*
E2010.02.08 Laboratory Casework*
E2010.02.09 Library Casework*
4 - Acceptable
4 - Acceptable
3 - Marginal
4 - Acceptable
5 - Good
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
Rating
0
0
0
0
0
0
Installed
Installed
Installed
Installed
Installed
Installed
25
15
35
35
35
35
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
Updated
Updated
Updated
Updated
Updated
Updated
Home Economics lab casework is original
Lifecycle Replacement 2010 $21,400 Low
Older casework has been refinished and is tsill useable butrequires upgrading
Concern:
replace within 5 yearsRecommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Type Year Cost Priority
Updated: November 16 2005
1995: Food Services Kiosk in Hallway 2001: Food Services Kiosk upgrade to 1961 kitchen Vending machines in hallways
weight training equipment
1972: Home-Economics casework (marginal) 1984: Home-Economics casework (acceptable)
1995: Food services Kiosk 2001: Food services kiosk upgrade to 1961 Kitchen
1995: new laboratories 1972: science labs have been upgraded
metal library shelving throughout
Report run on: June 7, 2006 3:47 PM Page 42 of 48
E2010.03.01 Blinds**
E2010.03.06 Curtains and Drapes**
E2010.05 Fixed Multiple Seating**
E2020 Moveable Furnishings*
F1010.02.04 Portable and Mobile Building P189
4 - Acceptable
4 - Acceptable
5 - Good
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
0
0
0
0
0
Installed
Installed
Installed
Installed
Installed
35
35
25
0
0
Design Life
Design Life
Design Life
Design Life
Design Life
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
Updated
Updated
Updated
Updated
Updated
minor water damage on ceiling tile
Repair 2007 $1,070 Low
water damage starting to be seen on ceiling tilesConcern:
patch & repair gum-boxes, check flashings or leaks and rectify,replace ceiling tiles
Recommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Type Year Cost Priority
Updated: November 16 2005
vertical louver blinds throughout
vertical blinds throughout
2001: prefinished metal seating in upgraded student gathering space
chairs and tables throughout
Sheet vinyl flooring, painted drywall walls, T-bar ceiling, vertical blinds on windows. Roof Top AC unit 90,000 BTU Air #PAC-V90N (Amani refrigeration Co PGA36B0903A) - Good condition
Report run on: June 7, 2006 3:47 PM Page 43 of 48
F1010.02.04 Portable and Mobile Buildings P186
4 - AcceptableRating
0Installed
0Design Life
JUN-05Updated
damaged plywood skitring
minor water damage on ceiling tile
Preventative Maintenance
Repair
2007
2006
$1,070
$1,070
Low
Low
portables are built very close to grade; plywood skirting isdamaged and deteriorating, snow and water could penetrateand get under crawl space
minor water damage on ceiling tile
Concern:
Concern:
replace damaged skirting
patch & repair gumboxes, check flashings to rectify leaking
Recommendation:
Recommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
November 16 2005
November 16 2005
Sheet vinyl flooring, painted drywall walls, T-bar ceiling, vertical blinds on windows. Roof Top AC unit 90,000 BTU Air #PAC-V90N (Amani refrigeration Co PGA36B0903A) - Good condition
Report run on: June 7, 2006 3:47 PM Page 44 of 48
F1010.02.04 Portable and Mobile Buildings P187
4 - AcceptableRating
0Installed
0Design Life
JUN-05Updated
minor water damage on ceiling tile
rainwater leader drains within incghes of plywoodskirting
Repair
Preventative Maintenance
2007
2008
$1,070
$1,070
Low
Low
minor water damage on ceiling tile
water may collect in crawl space
Concern:
Concern:
patch & reapir gum boxes, check flashings to rectify leaking
replace skirting and caulk joint at sidewalk to prevent watercollecting in crawl space
Recommendation:
Recommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
November 16 2005
November 16 2005
Sheet vinyl flooring, painted drywall walls, T-bar ceiling, vertical blinds on windows Roof Top AC unit 90,000 BTU Air #PAC-V90N (Amani refrigeration Co PGA36B0903A) - Good condition
Report run on: June 7, 2006 3:47 PM Page 45 of 48
F1010.02.04 Portable and Mobile Buildings P188
F1010.02.05 Grandstands and Bleachers**
4 - Acceptable
4 - Acceptable
Rating
Rating
0
0
Installed
Installed
0
50
Design Life
Design Life
JUN-05
JUN-05
Updated
Updated
minor water damage on ceiling tile
wood framed structure very close to grade
Repair
Preventative Maintenance
2007
2008
$1,070
$2,140
Low
Low
minor water damage on ceiling tile
rain water is being deirected away from building but grade hasbeen built-up at edge of skirting and water may not be able todrain form under portables
Concern:
Concern:
patch & repair gum-boxes on roof, check flashings to rectifyleaks, replace damqaged tiles
regrade to improve drainage or provide culvert to drain to fields
Recommendation:
Recommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
November 16 2005
November 16 2005
Sheet vinyl flooring, painted drywall walls, T-bar ceiling, vertical blinds on windows Roof Top AC unit 90,000 BTU Air #PAC-V90N (Amani refrigeration Co PGA36B0903A) - Good condition
1984: retractable bleachers in main gymnasium 1984: retractable stage
Report run on: June 7, 2006 3:47 PM Page 46 of 48
F1010.03 Connecting Link
F1030.05 Other Special Construction Systems*
2 - Poor
4 - Acceptable
Rating
Rating
0
0
Installed
Installed
0
50
Design Life
Design Life
JUN-05
JUN-05
Updated
Updated
SIding damaged and dented
caulking around exiting windows cracked andmissing
Repair
Repair
2006
2006
$16,050
$1,070
Low
Unassigned
exterior metal panels are damaged
caulking at jambs and sills cracked and missing
Concern:
Concern:
replace metal cladding with more durable cladding pattern
recaulk to seal
Recommendation:
Recommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
November 16 2005
November 16 2005
1984: Concrete slab on grade, 75 mm metal stud framing batt insulation, metal cladiing on walls and roof, mechanical rooftop units
1984: welding cutains and benches in CTS workshop
Report run on: June 7, 2006 3:47 PM Page 47 of 48
F2020.04 Mould*
1 - CriticalRating
0Installed
0Design Life
JUN-05Updated
Window seal has failed. Mould is growing betweenwindow panes
Hazardous MaterialManagement Upgrade
2006 $1,070 High
window seal in window has failedConcern:
replace sealed glazed unit, caulk exterior frameRecommendation:
Chestermere - Chestermere High School (B9379A)
Event:
Type Year Cost Priority
Updated: November 16 2005
1972: window in room 1092
Report run on: June 7, 2006 3:47 PM Page 48 of 48
K3010 Building Services
K3020 Indoor Environment
K40 Current Code Issues
K4010.01 Barrier Free Route: Parking to Entrance
K4010.02 Barrier Free Entrances
K4010.03 Barrier Free Interior Circulation
K4010.04 Barrier Free Washrooms
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
Rating
Rating
0
0
0
0
0
0
0
Installed
Installed
Installed
Installed
Installed
Installed
Installed
0
0
0
0
0
0
0
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
JUN-05
Updated
Updated
Updated
Updated
Updated
Updated
Updated
Chestermere - Chestermere High School (B9379A)
S8 FUNCTIONAL ASSESSMENT
Generally in acceptable condition. Refer to Mechanical and Electrical
generally acceptable
2000 Upgrade has addressed code issues in the 1961 and 1972 portions of the building. 1984 and 1995 additions appear to meet current code requirements
Barrier Free stall is located in North and South lot
Barrier Free auto-operator is installed at south building entrance
One floor with ramps to gym
No handicapped accessible shower (curbs at shower stalls) 1984: washrooms have been upgraded 1961: washrooms have been upgraded
Report run on: June 7, 2006 4:18 PM
RECAPP Facility Evaluation Report
Chestermere High School
S9379Chestermere
Report run on: June 7, 2006 4:18 PM Page 2 of 8
S9379Building Id:
Chestermere High SchoolBuilding Name:
ChestermereLocation:Address:
0.00Gross Area (sq. m): $0Replacement Cost:0Construction Year:
Evaluation Date:
Evaluation Company:
Evaluator Name:
The site is generally flat with gravel access roads to three parking areas. The site drains to a drainage swale adjacent tothe highway on the west side and rainwater from the building is drained to a drainage pond on the north side of thebuilding. Playing fields are located on the northeast and southeast sides of the school. The school uses water which is trucked to the site and stored in holding tanks The site is in acceptable condition.
General Summary:
Structural Summary:
Envelope Summary:
Interior Summary:
Mechanical Summary:
Electrical Summary:
0%5 year Facility Condition Index (FCI):
Facility Details Evaluation Details
Total Maintenance Events Next 5 years: $25,680
Chestermere - Chestermere High School (S9379)
Condition Rating Performance1 - Critical Unsafe, high risk of injury or critical system failure.2 - Poor Does not meet requirements, has significant deficiencies. May have high operating/maintenance costs.
3 - Marginal Meets minimum requirements, has significant deficiencies. May have above average operating maintenance costs.4 - Acceptable Meets present requirements, minor deficiencies. Average operating/maintenance costs.
Rating Guide
5 - Good Meets all present requirements. No deficiencies.6 - Excellent As new/state of the art, meets present and foreseeable requirements.
Report run on: June 7, 2006 4:18 PM Page 3 of 8
G2010.02.01 Aggregate Roadway (Gravel)**
G2010.05 Roadway Curbs and Gutters*
G2020.02.01 Aggregate Parking Lots (Gravel)**
G2020.02.02 Flexible Paving Parking Lots(Asphalt)**
G2020.05 Parking Lot Curbs and Gutters*
G2020.06.01 Traffic Barriers*
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
Rating
0
0
0
0
0
0
Installed
Installed
Installed
Installed
Installed
Installed
0
0
0
0
0
0
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
Updated
Updated
Updated
Updated
Updated
Updated
Chestermere - Chestermere High School (S9379)
S7 SITE
5 gravel access roads to the site, Gravel fire lane on the north and east sides of the 1984 and 1995 buildings
concrete curbs throughout
gravel parking throughout
Asphalt paving between 1984 and 1972 buildings
Concrete curbs around perimeter of parking lot
Metal posts (bollards) installed on south side by garbage enclosure to limit vehicle access to rear of school
Report run on: June 7, 2006 4:18 PM Page 4 of 8
G2020.06.02 Parking Bumpers*
G2020.06.03 Parking Lot Signs*
G2020.06.04 Pavement Markings*
G2030.02.02 Asphalt Pedestrain Pavement**
3 - Marginal
3 - Marginal
3 - Marginal
4 - Acceptable
Rating
Rating
Rating
Rating
0
0
0
0
Installed
Installed
Installed
Installed
0
0
0
0
Design Life
Design Life
Design Life
Design Life
Updated
Updated
Updated
Updated
install preacast curbs to prvenet cars for parking toclose to pedestrina link
Limited directional signage
Preventative Maintenance
Repair
2006
2007
$3,210
$1,070
Medium
Low
metal cladding at link damaged due to cars backing into wall
Limited directional signage
Concern:
Concern:
install precast curbs
add more signs at parking lot entrances and bus zonelocations
Recommendation:
Recommendation:
Chestermere - Chestermere High School (S9379)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
November 16 2005
November 16 2005
precast concrete curbs have been used at entrances and where cars could damage mechanical piping.
limited exterior parking signs
Paint markings only at concrete islands and along face of concrete curbs. GRavel lots only allow for marks on bumbers andisland curbs. Repainting is requrired (under $1000)
concrete and asphalt pavement at both doors leading form pedestrianl link to playing fields
Report run on: June 7, 2006 4:18 PM Page 5 of 8
G2030.04 Rigid Pedestrian Pavement (Concrete)**
G2040.02 Fences and Gates**
G2040.03 Athletic and Recreational Surfaces**
G2040.05 Site and Street Furnishings*
4 - Acceptable
4 - Acceptable
4 - Acceptable
3 - Marginal
Rating
Rating
Rating
Rating
0
0
0
0
Installed
Installed
Installed
Installed
0
0
0
0
Design Life
Design Life
Design Life
Design Life
Updated
Updated
Updated
Updated
wood benches at pedestrian link are in variousconditions
Repair 2007 $10,700 Unassigned
minimal exterior benches for seatingConcern:
replace existing and add newRecommendation:
Chestermere - Chestermere High School (S9379)
Event:
Type Year Cost Priority
Updated: November 16 2005
concrete sidewalks throughout
Frost fence between parking lot and playing fields
grassed, red shale and asphalt play areas
steel exterior garbage enclosure, smoking recpetacles, wood benches, precast bench, Boot scrapers at entrances, bikeracks
Report run on: June 7, 2006 4:18 PM Page 6 of 8
G2040.06 Exterior Signs*
G2040.08 Flagpoles*
G2050.04 Lawns and Grasses*
G2050.05 Trees, Plants and Ground Covers*
3 - Marginal
4 - Acceptable
3 - Marginal
4 - Acceptable
Rating
Rating
Rating
Rating
0
0
0
0
Installed
Installed
Installed
Installed
0
0
0
0
Design Life
Design Life
Design Life
Design Life
Updated
Updated
Updated
Updated
Visitors cannot tell which is the main entranceonce they access the site.
Grass area at north area isn't growing
Program Functional Upgrade
Preventative Maintenance
2010
2010
$21,400
$10,700
Low
Low
The main entrance is difficult to find since the roadway runsparallel to the entrance and you cannot see the signage on thebuilding
Grass won't grow as this appears to be a student congregationarea on the north side
Concern:
Concern:
Create a Landscape or Architectural feature to highlighth theentrance
install pavers and a seating area for student gathering
Recommendation:
Recommendation:
Chestermere - Chestermere High School (S9379)
Event:
Event:
Type
Type
Year
Year
Cost
Cost
Priority
Priority
Updated:
Updated:
November 16 2005
November 16 2005
One exterior lit sign, wall mounted sign over main entrance
Aluminum flagpole
Grass fields, Grass drainage swale at highway
coniferous and deciduos trees on highway side, small conifers between playing fields, one large decisuous and conifer incourtyard
Report run on: June 7, 2006 4:18 PM Page 7 of 8
G3010.02 Site Domestic Water Distribution*
G3010.03 Site Fire Protection Water Distribution*
G3020.01 Sanitary Sewage Collection*
G3020.03 Sanitary Sewage Equipment*
G3030.01 Storm Water Collection*
G3030.02 Storm Water Equipment*
G3030.03 Storm Water Ponds and Reservoirs*
G3060.01 Gas Distribution*
G4010.02 Electrical Power Distribution Lines*
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
Rating
Rating
Rating
Rating
Rating
Rating
0
0
0
0
0
0
0
0
0
Installed
Installed
Installed
Installed
Installed
Installed
Installed
Installed
Installed
0
0
0
0
0
0
0
0
0
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
Design Life
Updated
Updated
Updated
Updated
Updated
Updated
Updated
Updated
Updated
Chestermere - Chestermere High School (S9379)
water is trucked to the site and stored in underground tanks
Fire Hydrant on school property
Sanitary is pumped toa sewage lagoon on the north side.
sewage lagoon
storm catch basins, centre courtyard and weeping tile are piped to an underground holding tank and pumped to the lagoon
Storm water holding tank
Drainage swale at highway to drain front of school. excess water is piped to holding tank and pumped to the lagoon
Two underground gas supplies one at the north end one at the west entrance
Overhead power on south side into parking lot Underground service on north end to transformer pad on east side
Report run on: June 7, 2006 4:18 PM Page 8 of 8
G4010.03 Electrical Power Distribution Equipment*
G4010.04 Car Plugs-ins*
G4020.01 Area Lighting*
4 - Acceptable
4 - Acceptable
4 - Acceptable
Rating
Rating
Rating
0
0
0
Installed
Installed
Installed
0
0
0
Design Life
Design Life
Design Life
Updated
Updated
Updated
Chestermere - Chestermere High School (S9379)
Transalta Transformer on north side of building Stand by generator building
7 Plug-ins at north lot 17 plug-ins bewteen buildings 27 plug-ins in south lot
Parking lot light standards, wall and soffit mounted lighting throughout