Quick Reference Guide - V1.1
Click here to load reader
-
Upload
manoj-kage -
Category
Documents
-
view
19 -
download
3
description
Transcript of Quick Reference Guide - V1.1
1
SICAM FRTU 6MD25
Quick Reference Guide
1. Power Supply Card...................................... 2
2. Analog Input Card........................................ 4
3. Digital Input Card ......................................... 5
4. Digital Output Card..................................... 7
5. Mechanical Dimensions.............................. 8
6. Terminal / Connector Details ..................... 8
2
1. Power Supply Card 1.1 Switching ON the FRTU Module To switch ON the device, proceed as follows:
1. Initially, the switch is in OFF state, i.e. at Position 1 as shown in Figure 1.1.
2. Pull this switch Outward as indicated by an arrow.
3. Then move the switch downward, i.e. at Position 2 as shown in Figure 1.1.
4. Push this switch Inward as indicated by an arrow and release the switch.
5. Now the power to the device is switched ON.
Figure 1.1 Positions of the ON/OFF Switch to power ON the unit 1.2 Switching OFF the FRTU Module To switch OFF the device, proceed as follows:
1. Initially, the switch is in ON state, i.e. at Position 1 as shown in Figure 1.2.
2. Pull this switch Outward as indicated by an arrow.
3. Then move the switch upward, i.e. at Position 2 as shown in Figure 1.2.
4. Push this switch Inward as indicated by an arrow and release the switch.
5. Now the power to the device is switched OFF.
Figure 1.2 Positions of the ON/OFF Switch to power OFF the unit
Position 1
Position 2
Outward
Inward
Position 2
Position 1
Outward
Inward
3
1.3 Connections for Power Supply Card Make the connections as shown in Figure 1.3.
6MD2520-0XA00-0AA0
Figure 1.3 Connections for power supply connector of Power Supply Card
Note: The 2.5 sq.mm cable recommended for power supply wiring connections is with pin type lugs of 2.5 sq.mm.
Voltage levels MLFB 20 - 60 V DC 6MD2520-0AA00-0AA0
85 - 265 V AC / 110 - 300 V DC 6MD2520-0BA00-0AA0
Terminals on Card DC Source AC Source + + L - - N E Not connected E
4
2. Analog Input Card Each Analog Input Card has 8 analog inputs (2 groups of 4 each, i.e. AI1 to AI4 and AI5 to AI8). Make the wiring
connections as shown in Figure 2.1.
2.1 Jumper settings on the card 2.2 DIP switch selection on the card Figure 4.1 Figure 2.1 Wiring of analog inputs
Table 2.1 Measuring Ranges for AI Card
Note:
For further details of the Analog Input Card further details refer to the Technical Manual of SICAM FRTU 6MD25.
Unipolar voltage
0 - 500 mV, 0 - 1 V, 0 - 5 V, 0 - 10 V
Bipolar voltage
-500 mV to +500mV, -2.5 V to +2.5 V, -5 V to +5 V
Unipolar current
0 - 1 mA, 0 - 10 mA, 0 - 20 mA, 4 - 20 mA
Bipolar current
-20 mA to +20 mA
Figure 2.1 Hardware Settings for Analog Input Card Current and Voltage Settings
Slide out the Analog Card from the rack through guides.
Identify the jumpers on the card as shown in the Figure 2.2.
To select current input or voltage input for Channels in Card, the
jumper settings need to be done. For Channels 1 to 8, jumpers J14
to J21 must be set respectively.
For current input on Channel 01: short 1st and 2nd terminal of J14.
For voltage input on Channel 01: short 2nd and 3rd terminal of J14.
Figure 2.3 DIP Switch on AI Card
Identify the DIP switch on the AI card as shown in the Figure 2.3.
Set the DIP switch address in the binary form.
Ex: Address 8 to be set.
This address is represented in binary form as 1000. Set the DIP
switches as shown in Figure 2.3.
Range of addressing for AI card: 1, 2
+
-
Transducer
NC*
* NC - No Connection
5
3. Digital Input Card Each Digital Input Card accepts 16 digital inputs (2 groups of 8 each, i.e. DI1 to DI8 and DI9 to DI16) from the field. These
are classified as Single Point Information and Double Point Information.
Note: Each group of digital inputs has an individual negative terminal.
Note: The wiring connections to terminals AUX V1+, AUX V1-, AUX V2+ and AUX V2- are optional and can be used for
per-channel diagnostics and monitoring purposes only.
3.1 Jumper settings on the card
3.2 DIP switch selection on the card
Figure 3.1b Hardware Settings for Digital Input Card
Voltage 220 V DC / 110 V DC
MLFB 6MD2523-0BA00-0AA0
Note: Ensure proper voltage is applied as per the
MLFB of the DI card.
Figure 3.2 DIP Switch on DI Card
Identify the DIP switch on the DI card as shown in the Figure 3.3.
Set the DIP switch address in the binary form.
Ex: Address 8 to be set.
This address is represented in binary form as 1000. Set the DIP
switches as shown in Figure 3.3.
Range of addressing for DI card: 3 - 6
Figure 3.1a Hardware Settings for Digital Input Card
Voltage 24 V DC / 48 V DC
MLFB 6MD2523-0AA00-0AA0
Note: Ensure proper voltage is applied as per the
MLFB of the DI card.
6
3.3 Wiring of Single Point Information The Single Point Information receives single information from the field data. Make the wiring connections as shown in
Figure 3.4.
Figure 3.2 Wiring of Single Point Information 3.4 Pairing of digital inputs for Double Point Information The Double Point Information receives pair information
from the field data (like breaker ON/OFF status). To wire
a pair of digital input, two consecutive channels are
wired (Refer to the Table 3.1 below). Hence 8 double
point status are obtained per card.
Note: For double point information, always wire the
digital inputs as shown in Table 3.1. Failures to
wire them in this manner will give irrelevant
information on the status of field.
Table 3.1 Pairing of digital inputs for Double
Point Information
Digital Input Pair No. DI11, DI12 1
DI13, DI14 2
DI15, DI16 3
DI17, DI18 4
DI21, DI22 5
DI23, DI24 6
DI25, DI26 7
DI27, DI28 8
For diagnostics (Optional)
V
Note:
V source in Figure 3.4 indicates field voltage,
whichever applicable as per MLFB of the card, for
digital inputs.
Note: For further details of the Digital Input Card refer to
the Technical Manual of SICAM FRTU 6MD25.
7
4. Digital Output Card No. of digital outputs per card - 8
No. of terminals for each output - 3 terminals
(C, NO and NC) Terminals Description
C Common
NO Normally Open
NC Normally Closed
Table 4.1 DO terminal description 4.1 DIP switch selection on the card
Figure 4.1 Wiring of digital outputs for the Digital Output Card
Table 4.1 Pairing of digital outputs for Double commands
For Single Command, any one channel from DO1 to
DO8 can be used.
For Double Command (e.g. Circuit Breaker’s), two
consecutive Digital Output channels must be wired. The
Table 4.1 shows the two consecutive Digital Outputs that
should be wired for double command.
Note: For double command, always wire the digital outputs as shown in Table 4.1. Failures to wire them in this manner
will irrelevant information on the status of outputs.
Digital Output Pair No.
DO1, DO2 1
DO3, DO4 2
DO5, DO6 3
DO7, DO8 4
Technical Specifications DO Contact Ratings:
48 V DC @ 0.6 A
110 V DC @ 1 A
230 V AC @ 3.5 A
C
Coil
V
NC
NO
DO1
Coil
Figure 4.2 DIP Switch on DO Card
Identify the DIP switch on the DI card as shown in the Figure 4.2.
Set the DIP switch address in the binary form.
Ex: Address 8 to be set.
This address is represented in binary form as 1000. Set the DIP
switches as shown in Figure 4.2.
Range of addressing for DI card: 7 - 10
8
5. Mechanical Dimensions
Figure 5.1 Mounting Dimension for Half 19-inch rack
Figure 5.2 Mounting Dimension for Full 19-inch rack
6. Terminal / Connector Details
Figure 6.1 Power Supply terminals Figure 6.2 AI, DI and DO terminals
Pitch 5 mm
No. of terminals 3
Tightening torque, max 0.6 Nm
Conductor cross section solid min. 0.2 mm2
Conductor cross section solid max. 2.5 mm2
Conductor cross section stranded min. 0.2 mm2
Conductor cross section stranded max. 2.5 mm2
Table 6. 1 Power Supply Connector details
Pitch 3.5 mm
No. of terminals 12
Hole diameter 1.2 mm
Table 6.2 AI, DI and DO Connector details