Operationalizing Phasor Technology ... - Electric Power Group

25
©Electric Power Group. 2014. All rights reserved. Operationalizing Phasor Technology Model Validation Webinar March 4, 2014 Presented by Ken Martin Page 0

Transcript of Operationalizing Phasor Technology ... - Electric Power Group

Page 1: Operationalizing Phasor Technology ... - Electric Power Group

©Electric Power Group. 2014. All rights reserved.

Operationalizing Phasor Technology

Model Validation

Webinar March 4, 2014

Presented by

Ken Martin

Page 0

Page 2: Operationalizing Phasor Technology ... - Electric Power Group

©Electric Power Group. 2014. All rights reserved.

SYNCHROPHASOR DATA

Compare System Performance with Model Prediction

Identify Root Cause for Differences

e.g., Generator parameters

Tune Model to Match System

Response

Model Use and Validation for Operations and Planning

Page 1

Page 3: Operationalizing Phasor Technology ... - Electric Power Group

©Electric Power Group. 2014. All rights reserved.

SYNCHROPHASOR

DATA

Presentation Outline

Frequently asked questions

What is a model?

Types of power system models

Why model validation is important

How to validate models

Model validation examples

Summary

Q & A

Page 2

Page 4: Operationalizing Phasor Technology ... - Electric Power Group

©Electric Power Group. 2014. All rights reserved.

Frequently Asked Questions

Why are models important?

What models are used in operations and planning?

Why do I need to validate a model?

How do I validate the model?

How do I prove that the model is accurate?

Is phasor data sufficient to validate a model?

Page 3

Page 5: Operationalizing Phasor Technology ... - Electric Power Group

©Electric Power Group. 2014. All rights reserved.

What is a Model?

Page 4

Transmission & Distribution

Load Generation

~

𝑌𝑏𝑢𝑠𝑉 = 𝐼 𝑌𝑏𝑢𝑠 =

𝑌11 𝑌12 … 𝑌1𝑛𝑌21 𝑌22 … 𝑌2𝑛… … … …𝑌𝑛1 𝑌𝑛2 … 𝑌𝑛𝑛

𝑆 = 𝑉𝐼∗

A modern Power System

Model is a set of equations

representing a real power

system

All components including

generators, transformers,

transmission lines, reactive

devices, and loads are

represented as model

elements

The system model includes

all elements connected as

they are in the real system

For any given condition, it

should produce the same

response as the real power

system

Real-time operation

depends on an accurate

system model

Page 6: Operationalizing Phasor Technology ... - Electric Power Group

©Electric Power Group. 2014. All rights reserved.

Types of Power System Models

Page 5

Model Time Use Tools

Steady State sec Power Flows; Operating

Conditions

PSLF; PSS\E; Power

World; Eurostag

Dynamic ms System response to

disturbances

e.g. oscillations, phase angle

change

PSLF; PSS\E; Power

World; RSCAD-RTDS;

ePHASORSim

Transient µs Faults, Transients EMTP;RTDS; PSCAD;

Aspen

Page 7: Operationalizing Phasor Technology ... - Electric Power Group

©Electric Power Group. 2014. All rights reserved.

Why Do We Use Models?

Power Systems Are Complex Networks

– Thousands of components

– Loads are not clearly defined

– Exact state unknown

– Require models to understand system behavior

Correct Models are Used for Simulating Power System to:

– Establish safe operation limits

– Develop operating guidelines

– Study system contingencies

– Analyze system events

– Plan system expansion and resource integration

Page 6

Page 8: Operationalizing Phasor Technology ... - Electric Power Group

©Electric Power Group. 2014. All rights reserved.

What Happens When Models Fail?

WECC 1996 blackout

– Model did not predict system oscillation

EI 2003 blackout

– Model did not predict power swing

Pacific SW 2011 blackout

– Model did not predict transmission overload

Similar blackouts:

– Italy 2003 – Europe 2006 – India 2012

Page 7

Page 9: Operationalizing Phasor Technology ... - Electric Power Group

©Electric Power Group. 2014. All rights reserved.

How Do We Validate Models?

Validate Models Using Events

– Significant operation (large generation loss, etc.)

– Unexpected behavior

Calibrate Models Through Staged Tests

– Generator testing

– System testing

Tune Models By Comparing Events and Simulations

– Run model with same conditions as recorded data

– Compare measured performance with model results

– Tune Model to match recording

Page 8

Page 10: Operationalizing Phasor Technology ... - Electric Power Group

©Electric Power Group. 2014. All rights reserved.

Validation Using a Significant Event

Page 9

Transmission & Distribution

Load Generation

~

Model was NOT Accurate !

Measured System

Performance

Model Simulation

Results

Page 11: Operationalizing Phasor Technology ... - Electric Power Group

©Electric Power Group. 2014. All rights reserved.

Model Tuning

Page 10

Model After

Tuning –

Matches

System

Performance

Models Tuned − Load

− Governor

− HVDC

Page 12: Operationalizing Phasor Technology ... - Electric Power Group

©Electric Power Group. 2014. All rights reserved.

Model Validation Example – Frequency Response

Page 11

Measured Frequency Response (per NERC methods) ΔP / (10 * ΔF)

Generation loss: ΔP = 655 MW

ΔF = 0.089 Hz

Frequency Response =

736 MW/0.1Hz

Area Frequency Bias = 672 MW/0.1Hz

% difference = (736-672)/736 = 8.7%

Pre-event: F=59.975 Hz

Post-event: F=59.886 Hz

ΔF=0.089 Hz

Frequency response is expected to match area bias within 10%. Model valid!

Generation Trip Event

Page 13: Operationalizing Phasor Technology ... - Electric Power Group

©Electric Power Group. 2014. All rights reserved.

Voltage Oscillations Before and After Controller Adjustment

Page 12

Screenshot of RTDMS – Real Time Dynamics Monitoring System

Monitor Diagnosis Act

Noise on signal – 2

Hz oscillation

Signal originating at wind farm – likely

controller setting problem

Contact generator & advise that

observing oscillations

352.10

354.50

Result

Observe that oscillation has ceased, system back to normal operating voltage

Page 14: Operationalizing Phasor Technology ... - Electric Power Group

©Electric Power Group. 2014. All rights reserved.

Generator Model Validation Process

Monitor voltage, current, and frequency

Compare MW & MVAR of measurement & model

Tune the model, adjust

– Generator

– Governor

– Exciter

– Stabilizer

– Etc.

Page 13

MW & MVAR responses very different

MW & MVAR responses very close

Bad Model

Good Model

Page 15: Operationalizing Phasor Technology ... - Electric Power Group

©Electric Power Group. 2014. All rights reserved.

On-line Generator Model Validation with PMUs

Page 14

PMU Measurement

– At point of interconnection

– Records V, I, & F

– Equivalence system

Simulate model response using the equivalence

– Compare with measurement

– Tune the model

Generator validation on-line

– Can validate frequently

Source: Dmitry Kosterev, “Hydro-Turbine Model Validation in Pacific northwest”, IEEE Transactions on Power Systems, vol. 19, no.2, pp.1144-1149, May 2004.

Page 16: Operationalizing Phasor Technology ... - Electric Power Group

©Electric Power Group. 2014. All rights reserved.

Generator Model Validation Example – with Tuning

Source: Dmitry Kosterev, “Hydro-Turbine Model Validation in Pacific northwest”, IEEE Transactions on Power Systems, vol. 19, no.2, pp.1144-1149, May 2004.

Page 15

Page 17: Operationalizing Phasor Technology ... - Electric Power Group

©Electric Power Group. 2014. All rights reserved.

Generator Model Parameter Tuning Tool Measurements – Equivalence – Tuning

Page 16

Source: Chin-Chu Tsai, Wei-Jen Lee, Nashawati, E., Chin-Chung Wu, Hong-Wei Lan, "PMU based generator parameter identification to improve the system planning and operation," 2012 IEEE Power and Energy Society General Meeting, vol., no., pp.1,8, 22-26 July 2012

Page 18: Operationalizing Phasor Technology ... - Electric Power Group

©Electric Power Group. 2014. All rights reserved.

Generator Model Parameter Tuning Tool Automated Tuning

Simulation Results (50 Iteration)

Page 17

50

70

90

110

130

150

170

190

210

230

0 500 1000 1500

Act

ive

Pow

er (M

W)

Samples

Best Fitness

Fitting Target

First Iteration

-100

-50

0

50

100

150

0 500 1000 1500

Rea

ctiv

e P

ow

er (

M V

ar)

Samples

Best Fitness

Fitting Target

First Iteration

Page 19: Operationalizing Phasor Technology ... - Electric Power Group

©Electric Power Group. 2014. All rights reserved.

NERC Requirements Standards on Model Validation

MOD-012 requires power plant owners to provide power plant data for dynamic simulations

MOD-026 requires power plant owners to verify that the provided dynamic models of excitation controls are accurate and up to date

MOD-027 requires power plant owners to verify that the provided dynamic models of governors and turbine controls are accurate and up to date

MOD-032-1 exists in conjunction with MOD-033-1, both of which are related to system-level modelling and validation

Page 18

Page 20: Operationalizing Phasor Technology ... - Electric Power Group

©Electric Power Group. 2014. All rights reserved.

What Can YOU Do?

Page 19

Analyze System Events – Validate model prediction with actual system performance – Check response as indicated by key measurements using tools such

as RTDMS and PGDA • Frequency response • Voltage response • Oscillations • P&Q power flow

Periodically validate generator and load models – Tune models when event and model data do not match

Encourage PMU deployment at key locations (such as POI)

Frequency

Oscillation

Page 21: Operationalizing Phasor Technology ... - Electric Power Group

©Electric Power Group. 2014. All rights reserved.

Key Model Validation Facts

Page 20

Power system operation and planning are based on models

The model must be accurate for reliable operation and efficient planning

Models need to be validated against actual operations

Synchrophasor measurement provides the data needed for dynamic model validation

Models have been improved using phasor data!

Page 22: Operationalizing Phasor Technology ... - Electric Power Group

©Electric Power Group. 2014. All rights reserved.

SYNCHROPHASOR

DATA

Compare System Performance with Model Prediction

Identify Root Cause For Differences

e.g., Generator parameters

Tune Model to Match System

Response

Model Use and Validation for Operations and Planning

Page 21

Page 23: Operationalizing Phasor Technology ... - Electric Power Group

©Electric Power Group. 2014. All rights reserved.

EPG Webinar Series URL: http://www.electricpowergroup.com/solutions/index.html

Page 22

Webinars are planned monthly, on a Tuesday from 11 a.m. to 12 Noon Pacific. The webinar topic list includes:

• System Events - Deciphering the Heartbeat of the Power Grid (Jul 16, 2013)

• Using Synchrophasor Technology For Real-Time Operation and Reliability Management (Aug

20, 2013)

• Phase Angle Differences – What They Mean and How to Use Them For Operations (Sep 17,

2013)

• Establishing Alarm Limits For Use in Operations (Oct 8, 2013)

• Phasor Simulations – How Can They Be Used in Operations? (Nov 19, 2013)

• Synchrophasor Data Diagnostics: Detection & Resolution of Data Problems for Operations and

Analysis (Jan 28, 2014)

• Model Validation (Mar 4, 2014)

• Voltage and Angle Sensitivities – What Do They Mean and How Can They Be Used

(April, 2014)

Page 24: Operationalizing Phasor Technology ... - Electric Power Group

©Electric Power Group. 2014. All rights reserved.

Your feedback and suggestions are important! PLEASE do let us know…

Page 23

Feedback

Page 25: Operationalizing Phasor Technology ... - Electric Power Group

©Electric Power Group. 2014. All rights reserved.

201 S. Lake Ave., Suite 400

Pasadena, CA 91101

(626)685-2015

www.ElectricPowerGroup.com

Thank You!

Page 24

For questions, please contact Frank Carrera: [email protected]

Or if you prefer, call and tell us directly:

(626) 685-2015

Q&A