MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light...

160
Description Pneumatic MPA−L Valve terminal Type: MPA−L−MPM−VI MPA−L−FB−VI Description 556 354 en 1008NH [722 279] MPA−L valve terminal

Transcript of MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light...

Page 1: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

DescriptionPneumatic MPA−L

Valve terminal

Type:MPA−L−MPM−VIMPA−L−FB−VI

Description556 354en 1008NH [722 279]

MPA−L valve terminal

Page 2: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical
Page 3: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

Contents and general safety instructions

IFesto P.BE−MPAL−EN en 1008NH

Original de. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Edition en 1008NH. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Designation P.BE−MPAL−EN. . . . . . . . . . . . . . . . . . . . . . . . . .

Order�No. 556 354. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E (Festo AG�&�Co. KG, D�73726 Esslingen, Federal Republic of Germany, 2010)Internet: �http://www.festo.comE−Mail: �[email protected]

The copying, distribution and utilization of this document aswell as the communication of its contents to others withoutexpress authorization is prohibited. Offenders will be heldliable for the payment of damages. All rights are reserved,in particular the right to carry out patent, registered designor ornamental design registration.

Page 4: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

Contents and general safety instructions

II Festo P.BE−MPAL−EN en 1008NH

TÜV® is a registered trade mark of the respective trademark owner. . . . . . . . . . . . . . . . . in certain countries.

VDE® is a registered trade mark of the respective trademark owner. . . . . . . . . . . . . . . . . in certain countries.

Torx® is a registered trade mark of the respective manufacturer in. . . . . . . . . . . . . . . . . certain countries.

Page 5: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

Contents and general safety instructions

IIIFesto P.BE−MPAL−EN en 1008NH

Contents

Intended use VII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Areas of application and approval by authorities VII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Target group VIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Service VIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Structure of this manual VIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Important user instructions IX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Terms and abbreviations XI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1. Overview of components 1−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.1 The valve terminal MPA−L 1−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.2 Valve terminal design 1−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.3 Electrical multi−pin connection 1−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.3.1 Versions of the connector 1−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.3.2 Versions of the IP protection class 1−7 . . . . . . . . . . . . . . . . . . . . . . . . . .

1.4 Electrical connection via CPX terminal 1−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5 Description of components 1−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5.1 Valves 1−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5.2 Main and additional power supply 1−10 . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5.3 Pilot air supply 1−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5.4 Exhaust air 1−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5.5 Sub−bases and pressure zone separation 1−13 . . . . . . . . . . . . . . . . . . . .

1.5.6 Vertical stacking 1−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5.7 Pressure regulating plates 1−16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.6 Connecting elements 1−20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.7 Display and control elements 1−22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.7.1 �Identification system" (as per catalogue) 1−23 . . . . . . . . . . . . . . . . . . .

1.7.2 Manual override (MO) 1−23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.7.3 Pressure regulator 1−24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.7.4 Switching status displays for valves 1−25 . . . . . . . . . . . . . . . . . . . . . . . . .

2. Mounting 2−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.1 General instructions on mounting/dismantling 2−3 . . . . . . . . . . . . . . . . . . . . . . .

Page 6: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

Contents and general safety instructions

IV Festo P.BE−MPAL−EN en 1008NH

2.2 Installation/removal on an H−rails 2−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3 Wall installation/removal 2−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3.1 Standard mounting points of the valve terminal 2−9 . . . . . . . . . . . . . . .

2.3.2 Additional mountings of the valve terminal 2−11 . . . . . . . . . . . . . . . . . . .

2.4 Fitting/removing optional inscription label holders 2−13 . . . . . . . . . . . . . . . . . . . .

3. Installation 3−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.1 Compressed air preparation 3−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.1.1 Operation with unlubricated compressed air 3−3 . . . . . . . . . . . . . . . . .

3.1.2 Operation with lubricated compressed air 3−3 . . . . . . . . . . . . . . . . . . . .

3.2 General instructions on installation 3−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3 Connecting the valve terminal MPA−L 3−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3.1 Pilot control of the solenoid coils (pilot air supply) 3−7 . . . . . . . . . . . . .

3.3.2 Valve terminal MPA−L with pressure zone separation 3−8 . . . . . . . . . . .

3.3.3 Setting the pressure regulating valve 3−10 . . . . . . . . . . . . . . . . . . . . . . .

3.3.4 Vacuum/low pressure operation 3−11 . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4 Connecting the pneumatic lines 3−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4.1 Installation/replacement of the threadless cartridges 3−15 . . . . . . . . . .

3.4.2 Laying the tubing 3−18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4.3 Common pneumatic lines 3−20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.5 Connecting the electric cables 3−21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.6 Address assignment of the valves 3−24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.6.1 Valve terminal MPA−L with multi−pin plug connection 3−28 . . . . . . . . . . .

3.6.2 Valve terminal MPA−L with CPX terminal 3−28 . . . . . . . . . . . . . . . . . . . . .

4. Commissioning 4−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.1 General Information 4−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.1.1 Prior to commissioning 4−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.1.2 Pressure build−up in the overall supply 4−3 . . . . . . . . . . . . . . . . . . . . . .

4.2 Checking the valves and the valve/actuator combination 4−6 . . . . . . . . . . . . . . .

4.3 Mounting/removing the optional manual override cover cap 4−11 . . . . . . . . . . . .

Page 7: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

Contents and general safety instructions

VFesto P.BE−MPAL−EN en 1008NH

4.4 Troubleshooting 4−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.4.1 Switching status indicator of the solenoid coils 4−13 . . . . . . . . . . . . . . .

4.4.2 Impairment of functions 4−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.4.3 Operating states of the pneumatic system 4−15 . . . . . . . . . . . . . . . . . . .

5. Conversion and maintenance 5−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.1 General preventive action 5−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.2 Maintaining the valve terminal MPA−L 5−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.2.1 Clean or replace flat plate silencer 5−4 . . . . . . . . . . . . . . . . . . . . . . . . . .

5.2.2 Replacing valves or cover plates 5−5 . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.3 Conversion of the MPA−L valve terminal 5−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.3.1 Tie rod system 5−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.3.2 Exchange sub−base, supply plate or extend or exchange right−hand end plate 5−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.3.3 Replace the electronic module 5−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.3.4 Conversion between ducted and unducted exhaust air 5−15 . . . . . . . . .

5.3.5 Conversion between internal and external pilot air supply 5−16 . . . . . . .

5.3.6 Converting the valve terminal MPA−L to different pressure zones 5−18 .

5.3.7 Conversion of the left−hand end plate of IP40 on IP65 cover 5−19 . . . . .

5.3.8 Conversion of the outlet direction of the multi−pin cable 5−19 . . . . . . . .

5.3.9 Conversion of the end plate between multi−pin and CPX connection 5−22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.4 Replace the pneumatic interface 5−24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A. Technical appendix A−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.1 Technical data A−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.2 Festo accessories A−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B. Supplementary overview of components B−1 . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.1 Overview of valve position components B−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

C. Index C−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 8: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

Contents and general safety instructions

VI Festo P.BE−MPAL−EN en 1008NH

Page 9: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

Contents and general safety instructions

VIIFesto P.BE−MPAL−EN en 1008NH

Intended use

The MPA valve terminals are intended for fitting into a machine or automated system and must be used exclusivelyas follows:

� In industrial applications

� In original status without unauthorised modifications.Only the conversions or modifications described in thedocumentation supplied with the product are permitted.

� In perfect technical condition

If used together with additional commercially available com�ponents, such as actuators, the specified limits for pressures,temperatures, electrical data, torques etc. must be observed.

In addition to the safety instructions in this manual alwaysobserve the regulations of the trade associations and theGerman Technical Control Board (TÜV) and the VDE condi�tions or corresponding national conditions on−site.

Areas of application and approval by authorities

The product fulfils the requirements of the EU directives andis marked with the CE marking symbol.

Standards and test values, which the product must complywith and fulfil, can be found in the section� A.1 �Technicaldata". The product−relevant EC directive can be found in thedeclaration of conformity.

Page 10: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

Contents and general safety instructions

VIII Festo P.BE−MPAL−EN en 1008NH

Target group

This manual is intended exclusively for technicians trained incontrol and automation technology.

Service

Please consult your local Festo repair service if you have anytechnical problems.

Structure of this manual

This manual contains general basic information on fitting,installing and commissioning the valve terminal MPA−L, aswell as on its mode of operation.

Page 11: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

Contents and general safety instructions

IXFesto P.BE−MPAL−EN en 1008NH

Important user instructions

Danger categories

This description contains instructions on the possible dangerswhich can arise if the product is not used correctly. Theseinstructions are marked (Warning, Caution, etc.), printed on a shaded background and marked additionally with a picto�gram. A distinction is made between the following dangerwarnings:

Warning... means that failure to observe this instruction may resultin serious personal injury or material damage.

Caution... means that failure to observe this instruction may resultin personal injury or material damage.

Note... means that failure to observe this instruction may resultin material damage.

Additionally, the following pictogram designates text passages,which describe activities with electrostatically sensitive devices:

Electrostatically sensitive devices: inappropriate handling canresult in damage to components.

Page 12: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

Contents and general safety instructions

X Festo P.BE−MPAL−EN en 1008NH

Identification of special information

The following pictograms designate text passages that contain special information.

Pictograms

Information:Recommendations, tips and references to other sources ofinformation.

Accessories:Information on necessary or useful accessories for the Festo product.

Environment:Information on environmentally friendly use of Festo products.

Text designations

· Bullet points indicate activities that may be carried outin any sequence.

1. Numerals indicate activities that must be carried out inthe sequence specified.

� Arrowheads indicate general listings.

Page 13: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

Contents and general safety instructions

XIFesto P.BE−MPAL−EN en 1008NH

Terms and abbreviations

The following product−specific terms and abbreviations areused in this manual:

Term/abbreviation Meaning

Blanking plate Plate without valve function for sealing vacant valve positions on sub−bases (vacant position).

Cartridge fitting Plug connector for connection of the power supply cables to the valveterminal

Components Common term for pneumatic interface, multipin sub−base, exhaustplate, silencer, pneumatic sub−base or pneumatic supply plate, endplate, pressure regulator plate, solenoid valve and cover plate

Electronics module Module in the sub−base with an LED and solenoid coil management

End plate Extreme right−hand plate with/without connections for power andpilot pressure and exhaust air, and extreme left−hand plate with multi−pin plug connection and CPX terminal as well as holes for H−rail andwall mountings.

Exhaust plate Plate for ducted exhaust with connection 3/5

MO Manual override

MPA1 Sizes of the solenoid valves: MPA1 = 10 mm wide

Multi−pin plug connection Electrical connection for controlling the valve terminal MPA−L

Pneumatic interface The pneumatic interface is the interface between the modular electrical peripherals of the CPX terminal and the MPA−L pneumatics

Pneumatic module Module consisting of pneumatic Sub−base, electronics module, solenoid valves or cover plates

Solenoid valves Monostable solenoid valve with a solenoid coil, double−solenoid ormid−position valves with two solenoid coils and additional variants

Sub−base Plate with working lines 2 and 4 for the mounting of valves and verti�cal stackings

Supply plate Plate for (additional) supply of compressed air to the solenoid valves,e.�g. with several pressure zones.

Page 14: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

Contents and general safety instructions

XII Festo P.BE−MPAL−EN en 1008NH

Term/abbreviation Meaning

Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34)multi−pin plug connection or for CPX−Terminal

Vertical stacking Pneumatic components that are installed between the sub−base andthe solenoid valve

Tab.�0/1: Product−specific terms and abbreviations

Page 15: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

Overview of components

1−1Festo P.BE−MPAL−EN en 1008NH

Chapter 1

Page 16: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

1. Overview of components

1−2 Festo P.BE−MPAL−EN en 1008NH

Contents

1. Overview of components 1−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.1 The valve terminal MPA−L 1−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.2 Valve terminal design 1−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.3 Electrical multi−pin connection 1−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.3.1 Versions of the connector 1−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.3.2 Versions of the IP protection class 1−7 . . . . . . . . . . . . . . . . . . . . . . . . . .

1.4 Electrical connection via CPX terminal 1−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5 Description of components 1−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5.1 Valves 1−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5.2 Main and additional power supply 1−10 . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5.3 Pilot air supply 1−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5.4 Exhaust air 1−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5.5 Sub−bases and pressure zone separation 1−13 . . . . . . . . . . . . . . . . . . . .

1.5.6 Vertical stacking 1−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5.7 Pressure regulating plates 1−16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.6 Connecting elements 1−20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.7 Display and control elements 1−22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.7.1 �Identification system" (as per catalogue) 1−23 . . . . . . . . . . . . . . . . . . .

1.7.2 Manual override (MO) 1−23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.7.3 Pressure regulator 1−24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.7.4 Switching status displays for valves 1−25 . . . . . . . . . . . . . . . . . . . . . . . . .

Page 17: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

1. Overview of components

1−3Festo P.BE−MPAL−EN en 1008NH

1.1 The valve terminal MPA−L

Festo supports your automation tasks at machine level withthe valve terminal MPA−L. The modular structure of the valveterminal MPA−L enables you to match this valve terminal opti�mally to your machine or system.

The valve terminal MPA−L provides the following connections:

� Common ducts for supply and exhaust air

� Electric signals from all solenoid coils

Working lines (2) and (4) are provided for each valve positionon the individual pneumatic sub−bases. The valves are sup�plied with compressed air (operating pressure and pilot pres�sure) via the common channels and connections in the basiccomponents. The exhaust air (from the valves and the pilotexhaust air) is also exhausted via these common channels.Further components for compressed air supply are also avail�able, e.�g. in order to supply pressure zones.

The valve terminal MPA−L is equipped with current reduction.The nominal current of the solenoid coils is then reducedafter the high−current phase (switching procedure). The cur�rent reduction offers the following advantages:

� The valve terminal MPA−L has a lower power consumption

� The power unit for the voltage supply to the valve ter�minal MPA−L can be designed more economically depend�ing on the individual case

� The solenoid coils have less leakage power and produceless waste heat

Page 18: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

1. Overview of components

1−4 Festo P.BE−MPAL−EN en 1008NH

1.2 Valve terminal design

The valve terminal MPA−L consists of the following pneumaticand electric components: The most important componentsare shown in Fig.�1/1.

1 2 3

4 5 6

1 Multipin sub−base with cover (here:IP40 cover)

2 Pneumatic supply plate with exhaustplate for ducted exhaust air (3/5)

3 Sub−base with electronic module andvalve or blanking plate

4 Sub−bases, 4 off set, with commonelectronic module and valves orblanking plates

5 Vertical stacking (here: Pressureregulator plate with installed valve andoptional pressure gauge)

6 Right−hand end plate

Fig.�1/1: Main components of the valve terminal MPA−L

Page 19: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

1. Overview of components

1−5Festo P.BE−MPAL−EN en 1008NH

The following operating modes can be used � independentlyof valve type:

� Standard operation with one or more pressure zones

� Reversible operation with compressed air supply via connections (3), (5) and exhaust via port (1)

� Low−pressure operation at 0 ... 3� bar

� Vacuum operation at −0.9 ... 0� bar

1.3 Electrical multi−pin connection

The electrical connection of the solenoid coils is made cen�trally via a multi−pin plug in the left−hand end plate, which is available in various variants for the he valve terminal MPA−L(see Tab.�1/1). One or two solenoid coils per v alve positioncan be controlled. Each solenoid coil occupies one pin of themulti−pin plug.

Page 20: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

1. Overview of components

1−6 Festo P.BE−MPAL−EN en 1008NH

1.3.1 Versions of the connector

Multi−pin connection,Type of left−hand end plate

Plug type Number of controllablesolenoid coils

Sub−D with 9�pins 1, 2, 3, ... 8

Sub−D with 25�pins 1, 2, 3, ... 24

Sub−D with 44�pins 1, 2, 3, ... 32

Terminal strip 1) 1, 2, 3, ... 32

Ribbon cable 2) 1, 2, 3, ... 32

1) Note that all cables to a cable harness must be grouped to ensure EMC conformity.2) Note that all 0� V−/24�V supply cables must be used and grouped to a cable harness.

Tab.�1/1: Multi−pin plug types of the left−hand end plates

Page 21: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

1. Overview of components

1−7Festo P.BE−MPAL−EN en 1008NH

1.3.2 Versions of the IP protection class

For variants with sub−D plugs the multipin connection can be implemented with various cover types (see Tab.�1/2).

Multipin sub−base Cover types for sub−D plug

IP65 cover:closed cover, Protection class IP65, with pre−prepared cableExclusively for the sub−D plug with 25−/44 pins.

IP40 cover:open cover, protection class IP40(In this case: Sub−D with 25� pins .

Tab.�1/2: Multipin sub−base and cover types

Page 22: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

1. Overview of components

1−8 Festo P.BE−MPAL−EN en 1008NH

1.4 Electrical connection via CPX terminal

The electrical interface of the solenoid coils on the CPX ter�minal is made centrally via the pneumatic interface (seeFig.�1/2). Per valve position one or two solenoid coils andwithin the valve terminal MPA−L maximum 32�solenoid coilscan be controlled via the CPX terminal.

1 CPX bus node

2 Pneumatic inter�face

3 Optional: addi�tional CPX module

4 Multipin sub−base of the CPX terminal

1

2

3

4

Fig.�1/2: Electric components of the valve terminal MPA−L with CPX terminal

Page 23: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

1. Overview of components

1−9Festo P.BE−MPAL−EN en 1008NH

1.5 Description of components

1.5.1 Valves

The valve terminal MPA−L can be fitted with 2x�2/2−, 2x�3/2−wayvalves, 5/2−way valves and 5/3−way valves and further valvetypes (see Tab.�1/3).

Valve labelling The valves on the MPA−S valve terminal are marked byidentification codes (see Tab.�1/3). By means of this identifi �cation on the top of the valve, you can ascertain the equip�ment fitted on your valve terminal MPA−L.

ID code Valve

B 5/3−way valve, mid−position open

D Two monostable 2/2−way valves, normally closed, pneumatic spring return

DS Two monostable 2/2−way valves, normally closed, pneumatic spring return

I 5/3−way valve, mid−position exhausted

R 5/3−way valve, mid−position closed

H Two monostable 3/2−way valves, control side 12 normally open, control side 14normally closed, pneumatic spring return

HS Two monostable 3/2−way valves, control side 12 normally open, control side 14normally closed, pneumatic spring return

I Two 2/2−way valves, normally closed, pneumatic spring returnWith dual−pressure operation:Operating pressure via connection (1) or connection (5)With vacuum operation:Operating pressure at connection (1), Vacuum at connection (5) (e.g. for vacuum switching with ejector pulse)

J 5/2−way double pilot valve

K Two monostable 3/2−way valves, normally closed, pneumatic spring return

KS Two monostable 3/2−way valves, normally closed, pneumatic spring return

Page 24: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

1. Overview of components

1−10 Festo P.BE−MPAL−EN en 1008NH

ID code Valve

M Monostable 5/2−way valve

N Two monostable 3/2−way valves, normally closed, pneumatic spring return

NS Two monostable 3/2−way valves, normally open, pneumatic spring return

W Monostable 3/2−way valve, open in basic position, external compressed airsupply via connection 2

X Monostable 3/2−way valve, closed in basic position, external compressed airsupply via connection (4)

L Blanking plate for sealing an vacant valve position

Tab.�1/3: Identification codes of the valves

Further information on the valves can be found in Appendix�B.

1.5.2 Main and additional power supply

The main supply of the valve terminal with operating pressurecan be made via a pneumatic supply plate (see Fig.�1/3) orvia the right−hand end plate with lateral ports (Tab.�1/4below).

Page 25: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

1. Overview of components

1−11Festo P.BE−MPAL−EN en 1008NH

1 Supply plate

2 Exhaust plate forducted exhaustair

1

2

Fig.�1/3: Pneumatic supply plate

The pneumatic supply plate can also be used for additionalpower supplies. These are, for�example, necessary in the caseof valve terminals operated with several pressure zones orwhen a large number of valves on the valve terminal areswitched simultaneously to flow.

1.5.3 Pilot air supply

The pilot control of the solenoid coils is supplied with internalor external pilot air. This pilot air is made available for thecomplete valve terminal (also via the pressure zones) via theright−hand end plate (see Tab.�1/4).

A selector plate on the right−hand end plate makes it possibleto branch the pilot air internally from the supply port (1) or totake it from the separate supply via the port (12/14).

NoteInternal pilot air supply is only permitted if the operatingpressure of the last pressure zone (at the right−hand endplate) is between 3 and 8� bar .

Page 26: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

1. Overview of components

1−12 Festo P.BE−MPAL−EN en 1008NH

End plate type Properties

End plate without connections at side

� space−saving, low end plate with front, round selectorplate

� separate pneumatic supply plate required for the valveterminal

End plate with exhaust ports at side

� high end plate with upper, square selector plate� supply connections (1), (3) and (5) are integrated at theside

Tab.�1/4: Right−hand end plate versions

The way in which the pilot control of your valve terminal is set can be determined from Tab.�1/5. The conversion between the internal and external pilot air supply is describedin Chapter� 5.3.5.

Page 27: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

1. Overview of components

1−13Festo P.BE−MPAL−EN en 1008NH

Pilot control variant

Properties Internal pilot air supply External pilot air supply

Identification on the endplate/ Setting of the selector plate

�Int" �Ext"

Type of pilot air supply Internally from the supplyport�(1) distributed operatingpressure

Externally via the pilot connection(12/14) supplied, separately controllable pressure (3�...�8�bar)

Requirement The operating pressure must bein the range 3�...�8�bar and befree of pressure fluctuations.

The operating pressure can bebelow 3�bar and above 8�bar, so long as separately controlledpilot pressure (3�...�8�bar) is available.

Tab.�1/5: Features of the pilot control variants

1.5.4 Exhaust air

The exhaust (3) and (5) of the air is exhausted together viathe flat plate silencer and the exhaust plate or separately viathe right−hand end plate with ports at the side.

The pilot exhaust air (82/84) is led to a connection on theright−hand end plate and can either be ducted there or ex�hausted via a silencer.

1.5.5 Sub−bases and pressure zone separation

The valves of valve terminal MPA−L are supplied pneumati�cally via the sub−bases and via the electronic module that isinstalled in the sub−base (see Fig.�1/4).

In addition to the individual sub−bases there are also the 4 offsub−bases with common 4 off electronic module.

Page 28: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

1. Overview of components

1−14 Festo P.BE−MPAL−EN en 1008NH

1 Sub−base

2 Electronicsmodule

1

2

Fig.�1/4: Sub−base with electronic module

In addition valves within a valve terminal MPA−L can be sup�plied with different pressures by creating different pressurezones. The separation of the pressure zones is achieved byspecial sub−bases. In each case the valve mounted to theright of the special sub−base belongs to the next (following onto the right) pressure zone, which is the valve mounted on thespecial sub−base in the current pressure zone.

The sub−bases with integrated pressure zone separation are in various versions with corresponding identification (see Tab.�1/6):

Page 29: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

1. Overview of components

1−15Festo P.BE−MPAL−EN en 1008NH

Sub−base design MPA1

Supply duct (1) separated Type: VMPAL−AP−...−T1

Exhaust ducts (3) and (5) separated Type: VMPAL−AP−...−T135

Supply channel (1) and exhaustducts (3) and (5) separate

Type: VMPAL−AP−...−T135

Tab.�1/6: Variants of the sub−bases with integrated pressure zone separation

Pressure zone separation of the pilot channels (12) and (14)is not provided, as on the valve terminal MPA−L the air supplyfor the pilot control of the valves is supplied centrally via theright−hand end plate.

1.5.6 Vertical stacking

You can fit further pneumatic components to each valve position between the sub−base and the valve. These verticalstackings enable you to implement certain additional func�tions as desired.

Page 30: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

1. Overview of components

1−16 Festo P.BE−MPAL−EN en 1008NH

Tab.�1/7 shows the main structure and possible componentsof the vertical stacking.

Components

Directional controlvalves

See chapter � 1.5.1.

Vertical stacking,optional

� Pressure regulator plate Type VMPA...B8−R... C2−C−... (Pressuregauge optional), see Chapter� 1.5.7

� Pressure shut−off plate, Type VMPA1−HS

Sub−base Type VMPAL−AP−... with electronics module

Tab.�1/7: Components of the vertical stacking

1.5.7 Pressure regulating plates

Mode of operation A pressure regulator plate with adjustable pressure regulatorcan be installed between the sub−base and the valve in orderto control the force of the connected actuators. This pressureregulator maintains an essentially constant output pressure(secondary side) independent of supply pressure (primaryside) and air consumption.

Identification The pressure regulator plates of the vertical stacking aremarked on the valve terminal MPA−L with the Ident. code. This is marked on the side of the pressure regulator plate.Using Tab.�1/8 you can identify the pressure regulator plates.

Page 31: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

1. Overview of components

1−17Festo P.BE−MPAL−EN en 1008NH

IDcode

Vertical stacking component

PF Pressure regulator plate for connection (1), supply pressure 6 bar

PH Operating pressure regulator plate for connection (2), supply pressure 6 bar

PG Work pressure regulator plate for connection (4), supply pressure 6 bar

PA Pressure regulator plate for connection (1), supply pressure 10 bar

PC Operating pressure regulator plate for connection (2), supply pressure 10 bar

PB Work pressure regulator plate for connection (4), supply pressure 10 bar

T Pressure gauge for pressure regulator plate

Tab.�1/8: Identification of the regulator plates in the type code

The circuit symbol of the pressure regulating valve is provided in appendix B, Tab.�B/5.

P pressure regulating valve(identification PF, PA)

Supply process The P pressure regulating valve regulates the pressure infront of the valve in duct (1)/(P). This provides the same regulated air pressure in channels (2) and (4).

Exhaust procedure The exhaust flow is from channel (2) to channel (3) and fromchannel (4) to channel (5) through the pressure regulatorplate to the valve terminal.

The advantages of this pressure regulating valve are:

� The pressure regulating valve is not affected by exhausting,since the pressure is regulated upstream of the valve.

� The pressure regulating valve can always be adjusted because the pressure from the valve terminal is always present.

Page 32: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

1. Overview of components

1−18 Festo P.BE−MPAL−EN en 1008NH

Application examples:

� An equal air pressure is required at working lines (2) and (4).

� A lower air pressure (e.g.�3�bar) than the operating pres �sure present on the valve terminal (e.g.�8�bar) is required.

A or B pressure regulator (identifier PH, PG, PC, PB)

Supply process The work or operating pressure regulator regulates the relevant pressure of the air (see 1 in Tab.�1/9) when thepressure medium has flowed through the valve. The exhaustair is passed through the pressure regulator plate and isswitched to the relevant exhaust duct in the valve (see 2in Tab.�1/9).

Exhaust procedure During exhausting the air is passed unregulated through thevalve and the pressure regulator plate to the valve terminal(see 3 in Tab.�1/9).

Pressureregulator

Pressurizing Exhaust process:regulator

regulatedpressure of the workair 1

exhaust vented via thepressure regulator plate 2

unregulated exhaustvented via the regulator 3

A pressureregulatingvalve

in channel (4) from channel (2) to channel (3) from channel (4) to channel (5)

B pressureregulatingvalve

in channel (2) from channel (4) to channel (5) from channel (2) to channel (3)

Tab.�1/9: Mode of operation of the A and B pressure regulator

Restrictions:

� The exhaust flow in the regulating direction is limited bythe pressure regulating valve.

Page 33: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

1. Overview of components

1−19Festo P.BE−MPAL−EN en 1008NH

� The pressure of the air in channel (2) can only be set andread on the pressure gauge when the valve is in theswitch position: Flow from (1) to (2).

Application examples:

� If different air pressures are required at ports (2) and (4)instead of the operating pressure of the valve terminal.

Fig.�1/5 shows the following switching position of the operat �ing pressure regulator:The air is passed from channel (1) through the pressure regu�lator plate and the valve to the operating pressure regulator,where it is regulated and then passed to connection (2) of the sub−base. The unregulated exhaust air is then fed viachannel (4) through the pressure regulator plate and then tochannel (5) and vented.

1

2

3

4

1 Control regulator within the pressureregulator plate

2 Valve

3 Pressure regulator plate

4 Sub−base

Fig.�1/5: B pressure regulating valve

Page 34: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

1. Overview of components

1−20 Festo P.BE−MPAL−EN en 1008NH

1.6 Connecting elements

Pneumatic elements The following pneumatic connecting elements can be foundon the valve terminal MPA−L:

2

3

4

1

3

1 Common exhaust port (3/5) �Valve"

2 Pilot air connections (12/14) and(82/84) dependent on the design of the right−hand end plate (seeChapter�1.5.3)

3 Supply connections �Operating pressure" (1)

4 Working lines (2) and (4), per valve

Fig.�1/6: Pneumatic connecting elements

Page 35: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

1. Overview of components

1−21Festo P.BE−MPAL−EN en 1008NH

Electrical elements The following electrical connecting elements can be foundon the pneumatic components of the valve terminal MPA−L:

1 Sub−D multipinplug with cable

2 Connection forfunctional earth

3 Sub−D connection(here: 25−Pinversions)

1

2

3

Fig.�1/7: Electric connecting elements of valve terminal MPA−L with multipin connection

Page 36: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

1. Overview of components

1−22 Festo P.BE−MPAL−EN en 1008NH

1.7 Display and control elements

The following connecting and control elements can be foundon the valve terminal MPA−L:

2

3

1

4

5

1 switching status indicator (yellow LEDs)of the valves

2 Manual override (per pilot solenoidcoil, non−detenting or detenting)

3 Inscription panel

4 Slot for inscription label holder (see Chapter� 2.4)

5 Pneumatic interface fault LED (see Chapter� 3.6.2)

Fig.�1/8: Display and control elements on the example of the valve terminal with CPXterminal

Information on the electrical connection and display compo�nents of the CPX bus node is provided in the corresponding�Electronics description" (see the system description for yourCPX terminal, table �Descriptions of the CPX terminal").

Page 37: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

1. Overview of components

1−23Festo P.BE−MPAL−EN en 1008NH

1.7.1 �Identification system" (as per catalogue)

Alternatively or supplementary to the inscription labels attached to sub−bases, inscription labels with large surfaceareas can be attached to the pneumatic interface.

Information about corresponding accessories can be found in the Festo Catalogue (see www.festo.com\catalogue).

1.7.2 Manual override (MO)

The manual override (MO) enables the valve to be actuatedwhen not electrically activated or energised. You only need to switch on the compressed air supply. You should use themanual override especially when commissioning the pneu�matic system, in order to check the function and operation of the valve or the valve−actuator combination.

Non−detenting actuation The valve is activated by pushing the manual override. On release of the manual override the spring−loaded valve switches automatically from the switch position to the normally open position.

Detenting actuation By turning the manual override clockwise the switch positioncan be detented. It remains actuated until it is reset by hand.

These basic functions of the manual override can be changedby installing a corresponding manual override cover cap:With a cover for manual override, code: N, locking is pre�vented. The manual override can then only be operated bynon−detenting.With a cover for manual override, code: V, the manual over�ride can be safeguarded against undesired operation

The operation of the manual override is described inChapter�4.2.

Page 38: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

1. Overview of components

1−24 Festo P.BE−MPAL−EN en 1008NH

NoteA manually actuated valve (by manual override) cannot beactuated electrically. Conversely, an electrically actuatedvalve cannot be activated using the mechanical manualoverride. The valve only returns to the rest position whenboth actuations are reset.

1.7.3 Pressure regulator

On the pressure regulator plate you will find the followingdisplay and control elements:

1 Adjusting screwfor pressureregulator plate MPA1

2 Pressure gauge(optional)

3 Connection forpressure gauge(can be tilted 90)

1

3

2

Fig.�1/9: Display and control element of the pressure regulator plates

Page 39: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

1. Overview of components

1−25Festo P.BE−MPAL−EN en 1008NH

1.7.4 Switching status displays for valves

There is an LED and a manual override for each solenoid coil.The position of the LED and MO for the relevant solenoid coilis as follows:

1

2

1

2

12 12 12 12

14 14 14 14 14 14 14 14

1 LED and manual override for valvesolenoid coil 14

2 LED and manual override for valvesolenoid coil 12

Fig.�1/10: The assignment of LEDs and manual overrides to the solenoid coils

The switching states of the solenoid coils and their signifi�cance can be found in Chapter� 4.4.1.

Page 40: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

1. Overview of components

1−26 Festo P.BE−MPAL−EN en 1008NH

Page 41: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

Mounting

2−1Festo P.BE−MPAL−EN en 1008NH

Chapter 2

Page 42: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

2. Mounting

2−2 Festo P.BE−MPAL−EN en 1008NH

Contents

2. Mounting 2−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.1 General instructions on mounting/dismantling 2−3 . . . . . . . . . . . . . . . . . . . . . . .

2.2 Installation/removal on an H−rails 2−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3 Wall installation/removal 2−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3.1 Standard mounting points of the valve terminal 2−9 . . . . . . . . . . . . . . .

2.3.2 Additional mountings of the valve terminal 2−11 . . . . . . . . . . . . . . . . . . .

2.4 Fitting/removing optional inscription label holders 2−13 . . . . . . . . . . . . . . . . . . . .

Page 43: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

2. Mounting

2−3Festo P.BE−MPAL−EN en 1008NH

2.1 General instructions on mounting/dismantling

WarningUncontrolled movements of the connected actuators andloose tubing can cause injury to persons and/or damage toproperty.

Before carrying out mounting, installation and maintenancework, switch off the following:

� Compressed air supply

� The operating and load voltage supplies.

NoteHandle all modules and components of the valve terminalMPA−L with great care. Note especially the following:

� The specified torques must be complied with.

� Electrostatically sensitive devices.Therefore, do not touch any contact surfaces.

NoteMount the valve terminal MPA−L so that there is sufficientspace for heat dissipation and ensure that the maximumlimits for temperatures are observed (see �Technical specifications").

Page 44: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

2. Mounting

2−4 Festo P.BE−MPAL−EN en 1008NH

2.2 Installation/removal on an H−rails

The valve terminal MPA−L is suitable for fitting onto an H−rail(support rail as per EN 60715). There is a guide groove on theback for hanging the valve terminal onto the H−rail.

CautionH−rails with mounted valve terminals can break if they aresubjected to vibration exceeding severity level� 1:

� 0.15�mm Amplitude at 15 ... 58� Hz

� 2� g acceleration at 58 ... 150� Hz

This can damage the valve terminal, your machine or yoursystem.

· In this case use wall mounting.

· Note the permitted values for vibration and shock (see Tab.�A/2 in Appendix�A).

CautionH−rail mounting without an H−rail clamping unit is not per�mitted.

· Secure the valve terminal MPA−L using the H−rail clamping:against sliding down with the retaining screw intended forthis purpose (see Tab.�2/1 and Fig.�2/1)� against unintentional loosening/opening.

In order to mount the valve terminal onto an H−rail you willrequire the following mounting kits:

� for valve terminal MPA−Ls with multi−pin plug connection:Mounting, type CPA−BG−NRH. This kit contains 2 M4x10screws and 2 clamping elements.

� for valve terminal MPA−Ls with CPX terminal: Mounting,type VMPAF−FB−BG−NRH. This set consists of 3 clampingcomponents, two M4x12 screws and one M4x10 screw.

Page 45: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

2. Mounting

2−5Festo P.BE−MPAL−EN en 1008NH

Valve terminal variant Mounting points

1

MPA−L with multi−pin plug connection

1

Required mounting of the H−railclamping units:� In the right−hand end plate

and the multipin sub−base:each with one M4 screw 1and each with a clampingcomponent

1 1

MPA−L with CPX terminal

2

Required mounting of the H−railclamping units:� In the end plates:

each with one M4 screw 1and each with a clampingcomponent

� In the pneumatic interface:one M6 screw 2 and aclamping component

Tab.�2/1: Mounting points for H−rail mounting

Mounting Proceed as follows:

1. Make sure that the mounting surface can support the weight of the valve terminal MPA−L (weights see appendix A, Tab.�A/1).

2. Mount the H−rail (DIN mounting rail EN�60715 − 35x7.5;width 35�mm, height 7.5�mm). Make sure there is suffi �cient space for connecting the power supply cables andtubing. Fasten the H−rail(see Fig.�2/1) to the mountingsurface approximately every 100� mm.

3. Mount the H−rail clamping units at all required mountingpoints (see Tab.�2/1). Make sure that the clamping ele �ment (see Fig.�2/1, 3) lies horizontally to the H−rail.

Page 46: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

2. Mounting

2−6 Festo P.BE−MPAL−EN en 1008NH

4. Hang the valve terminal MPA−L onto the H−rail (see Fig.�2/1, arrow A).

5. Swing the valve terminal MPA−L onto the H−rail (see Fig.�2/1, arrow B).

1 H−rail

2 Retaining screwof the H−railclamping unit

3 Clampingcomponent of theH−rail clampingunit

4 Mounting surface

(A)

(B)

1

2

3

4

Fig.�2/1: Fitting the valve terminal MPA−L onto a H−rail

6. Turn the clamping components to the mechanical lockvertically behind the H−rail (see Fig.�2/2, Arrow A) andtighten the locking screws of the H−rail clamping compo�nent with1.3�Nm ±10%, to protect the v alve terminalMPA−L against slipping or sliding down.

Page 47: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

2. Mounting

2−7Festo P.BE−MPAL−EN en 1008NH

1 H−rail

2 MPA−L�Connectionblocks

3 Vertically rotatedclamping compo−nent of the H−railsclamping units 1

2

3

(A)

Fig.�2/2: Rear view: Fitting the valve terminal MPA−L onto a H−rail

Additional information on H−rail mounting of the valve terminal MPA−L with CPX terminal can be found in the CPX system description.

Dismantling Proceed as follows:

1. Loosen the retaining screw of the H−rail clamping unit �(for position of the screws, see Tab.�2/1). Make sure thatthe clamping components are horizontal to the H−rail.

2. Swing the valve terminal MPA−L forwards from the H−rail(see Fig.�2/3, arrow A).

3. Lift the valve terminal MPA−L off the H−rail (see Fig.�2/3,arrow B).

Page 48: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

2. Mounting

2−8 Festo P.BE−MPAL−EN en 1008NH

1 H−rail

2 Retaining screwof the H−railclamping unit

3 Clampingcomponent of theH−rail clampingunit

4 Mounting surface

(A)

(B)

1

2

3

4

Fig.�2/3: Dismantling the valve terminal MPA−L

Page 49: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

2. Mounting

2−9Festo P.BE−MPAL−EN en 1008NH

2.3 Wall installation/removal

NoteInstallation on uneven, flexible surfaces can damage thevalve terminal MPA−L.

· Mount the valve terminal MPA−L only on flat, torsionallyrigid surfaces.

NoteThe overloading of mounting holes or natural resonancewhen vibrating can cause damage.

· In addition to the information about standard mountingpoints in Chapter� 2.3.1 also observe the informationabout additional mounting points in Chapter� 2.3.2.

2.3.1 Standard mounting points of the valve terminal

The end plates, the multipin sub−base and pneumatic interface contain holes for fitting the terminal onto a wall (see Tab.�2/2).

Page 50: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

2. Mounting

2−10 Festo P.BE−MPAL−EN en 1008NH

Variant Mounting points

1

1

1

1

2

2 2

2

Valve terminal MPA−L with multi−pin plug connection � Multipin sub−base: two M4 1 or M6 screws 2each

� Right end plate:two M4 1 or M6 screws 2each

1 1

22

1

2

Valve terminal MPA−L with CPX terminal

1

2

3

� End plates:two M4 1 or M6 screws 2each

� Pneumatic interface:two M6 screws 3

Tab.�2/2: Standard mounting points for wall mounting

Mounting Proceed as follows:

1. Make sure that the mounting surface is flat and that it can support the valve terminal MPA−L (weights see appendix A, Tab.�A/1).

2. Make sure there is sufficient space for connecting thepower supply cables and tubing.

3. Drill mounting holes in the mounting surface.

4. Fasten the valve terminal MPA−L with M4 or M6 screws ofsufficient length to the mounting surface (see Tab.�2/2).

Page 51: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

2. Mounting

2−11Festo P.BE−MPAL−EN en 1008NH

Dismantling Proceed as follows:

1. Prevent a hanging−mounted valve terminal MPA−L fromfalling down before you loosen it from the mounting surface.

2. Loosen the mounting screws (see Tab.�2/2).

3. Remove the valve terminal MPA−L from the mounting surface.

2.3.2 Additional mountings of the valve terminal

Valve terminal MPA−L The valve terminal MPA−L has standard mounting points forwall mounting.

The use of additional mountings, type VMPAL−BD, is necessaryunder the following conditions (Tab.�2/3):

� For increased vibration/shock loads (limits for vibrationsand shock see Appendix A, Tab. A/2and:

� For valve terminal MPA−Ls that are longer than 200� mm,additional mountings must be used every 130� mm.

CPX terminal A CPX terminal on the valve terminal MPA−L with four or moreinterlinking blocks must be fitted with additional mountingclips, type CPXBG−RW−..., (see CPX system description).

Page 52: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

2. Mounting

2−12 Festo P.BE−MPAL−EN en 1008NH

Variant Mounting points

1

Valve terminal MPA−L with multi−pin plug connection � For each mounting, type VMPAL−BD, half of whichis clipped into two neighbour�ing sub−bases (see also

Information in Appendix A,Tab.�A/2): one M6 screw 1

Valve terminal MPA−L with CPX terminal

1

Tab.�2/3: Additional mounting for wall mounting

Mounting Proceed as follows:

1. Attach the mounting to the rear lower surface in such away that each half of it lies on two adjacent connection/supply plates.

2. Rotate (1.) the mounting in the direction of the slots of theconnection/supply plates (see Fig.�2/4).

3. Press up (2.) the mounting on the connection/supplyplates until the hooks snap into the slots.

Page 53: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

2. Mounting

2−13Festo P.BE−MPAL−EN en 1008NH

1 Mounting, Type VMPAL−BD

2 Slots inconnection andsupply plates

1

2

1.

2.

Fig.�2/4: Assembly of an additional mounting

2.4 Fitting/removing optional inscription label holders

For identification of the valves or the working ports labels can be attached to the sub−bases, if corresponding Inscrip�tion label holders type VMPAL−ST−AP−10, are fitted.

Information about accessories can be found in the Festo Catalogue (see www.festo.com\catalogue).

Mounting Proceed as follows:

Page 54: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

2. Mounting

2−14 Festo P.BE−MPAL−EN en 1008NH

1. Press the label holder in the recess of the sub−base (see Fig.�2/5), until it engages.

2. Press the label from above into the label holder.

1 Support for labelholder on thesub−base

2 Label holder, typeVMPAL−ST−AP−10

3 Label, Type IBS 6x10

1

2

3

Fig.�2/5: Fitting the identification plate

Dismantling Proceed as follows:

· Remove the label holder from the sub−base, using a crossslot screwdriver if necessary, (see Fig.�2/6) by suppor tingon the valve located above.

1 Label holder withlabel

1

Fig.�2/6: Dismantling the label holder

Page 55: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

Installation

3−1Festo P.BE−MPAL−EN en 1008NH

Chapter 3

Page 56: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−2 Festo P.BE−MPAL−EN en 1008NH

Contents

3. Installation 3−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.1 Compressed air preparation 3−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.1.1 Operation with unlubricated compressed air 3−3 . . . . . . . . . . . . . . . . .

3.1.2 Operation with lubricated compressed air 3−3 . . . . . . . . . . . . . . . . . . . .

3.2 General instructions on installation 3−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3 Connecting the valve terminal MPA−L 3−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3.1 Pilot control of the solenoid coils (pilot air supply) 3−7 . . . . . . . . . . . . .

3.3.2 Valve terminal MPA−L with pressure zone separation 3−8 . . . . . . . . . . .

3.3.3 Setting the pressure regulating valve 3−10 . . . . . . . . . . . . . . . . . . . . . . .

3.3.4 Vacuum/low pressure operation 3−11 . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4 Connecting the pneumatic lines 3−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4.1 Installation/replacement of the threadless cartridges 3−15 . . . . . . . . . .

3.4.2 Laying the tubing 3−18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4.3 Common pneumatic lines 3−20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.5 Connecting the electric cables 3−21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.6 Address assignment of the valves 3−24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.6.1 Valve terminal MPA−L with multi−pin plug connection 3−28 . . . . . . . . . . .

3.6.2 Valve terminal MPA−L with CPX terminal 3−28 . . . . . . . . . . . . . . . . . . . . .

Page 57: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−3Festo P.BE−MPAL−EN en 1008NH

3.1 Compressed air preparation

CautionUnfiltered or incorrectly lubricated compressed air willreduce the service life of the valve terminal.

3.1.1 Operation with unlubricated compressed air

CautionToo much residual oil content in the compressed air will reduce the service life of the valve terminal.

� If bio−oils are used (oils with synthetic ester or true esterbasis, e.g. rape or methylester), the residual oil contentmust not exceed 0.1�mg/m3 (see ISO�8573−1 class�2).

� When using mineral oils (e.g. HLP oils to DIN� 51524,parts�1 to 3) or similar oils based on poly−alpha−olefins (PAO), the maximum residual oil content of5�mg/m3 must not be exceeded (see ISO�8573−1 Class�4).

This avoids operative malfunction of the valves.

Excessive residual oil is not permissible irrespective of thecompressor oil, as otherwise the basic lubrication will bewashed out with time.

3.1.2 Operation with lubricated compressed air

Operate system equipment with unlubricated compressed air,if possible. This is better for the environment. Festo pneu�matic valves and actuators have been designed so that, ifused as intended, they will not require additional lubricationand will still achieve a long service life.

Page 58: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−4 Festo P.BE−MPAL−EN en 1008NH

CautionOperation with lubricated compressed air will cause thelife−time lubrication, which is necessary for unlubricatedoperation, to be �washed out".

Note the following instructions if lubricated compressed airmust be used:The compressed air prepared with the compressor mustcorrespond in quality to unlubricated compressed air. If possible, do not operate all of your equipment with lubricatedcompressed air. If possible, always install the lubricators directly upstream of the consuming actuators.

CautionUnsuitable additional oil and an excessive oil content inthe compressed air reduce the service life of the valve ter�minal.

� Use Festo special oil OFSW−32 or the alternatives listedin the Festo catalogue (as specified in DIN�51524−HLP32;basic oil viscosity 32�CST at�40 °C).

� The additional lubrication must not exceed 25� mg/m 3

(ISO�8573−1 class 5).

� Make sure that the lubricator setting is correct (see following section)

This avoids operative malfunction of the valves.

Setting the lubricator: With the machine running (typical operating status) 0.2 tomax. 1 drops/min. or 0.5 to 5 drops/1000�l of air .

Checking the setting: The procedure described below can be used for checking thesetting of the lubricator.

Proceed as follows, in order to check the service units withrespect to condensate and lubricator settings two times perweek.

Page 59: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−5Festo P.BE−MPAL−EN en 1008NH

1. Ascertain the actuator which is furthest from the lubricator.

2. Ascertain the valve terminal which controls this cylinder.

3. Remove the silencer, if fitted, from port (3/5).

4. Hold a piece of white cardboard 10�cm in front of the exhaust port.

5. Let the system run for a short period.There must be only a slight yellow colouring on the card�board.

If oil droplets appear, this is an indication that too much oilhas been used. Another indicator is the coloration or thecondition of the exhaust air silencer. Distinctly yellow colour�ing of the filter element or drops of oil on the silencer indicatethat the lubricator setting is too high.

Page 60: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−6 Festo P.BE−MPAL−EN en 1008NH

3.2 General instructions on installation

WarningUncontrolled movements of the connected actuators andloose tubing can cause injury to persons and/or damageto property.

Before carrying out mounting, installation and mainten�ance work, switch off the following:

� Compressed air supply

� The operating and load voltage supplies.

Pay attention to the following:The components of the valve terminal contain electrostaticallysensitive components. The components will be damaged if you touch the contact surfaces of the plug connectors or if you do not observe the handling specifications for electro−statically sensitive devices.

NoteHandle all modules and components of the valve terminalMPA−L with great care.

Note especially the following:

� Screws must be fitted accurately (in particular to avoiddamage to threads on plastic housing parts) andscrewed in by hand

� The specified torques must be observed

� Clean connecting services (avoidance of leaking andcontact faults) and intact seals and sealing surfaces

� Close unused connections with blanking plugs to avoidcontamination and maintain reliability.

back pressure When exhausting large volume actuators or if the exhaustperformance is too small, back pressures can build up in thevalve terminal exhaust ducts. The back pressures can lead topneumatic actuation of other valves, especially with un�switched 3/2−way valves that are normally closed.

Page 61: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−7Festo P.BE−MPAL−EN en 1008NH

To avoid back pressures:

· Optimise the ventilation and exhaust performance of the valve terminal e.�g. by using lar ger pipe diameters oradditional compressed air supply via pneumatic supplyplates with exhaust via silencers and exhaust plate.

· Separate exhaust ducts by using pressure zones ifnecessary (see Chapter� 1.5.3).

3.3 Connecting the valve terminal MPA−L

Connections on the following components are available forsupplying the valve terminal:

� To the pneumatic supply plate, type VMPAL−SP

� To the right−hand end plate, type VMPAL−EPR−SP

3.3.1 Pilot control of the solenoid coils (pilot air supply)

Internal pilot air supply If the operating pressure lies between 3 ... 8� bar , you canoperate the pilot control of the solenoid coils with an inter�nally branched pilot air supply.

Note· Internal pilot air supply is branched centrally from sup�ply connection�(1) for all solenoid coils. When operatingthe valve terminal with several pressure zones the inter�nal pilot air supply is taken from the pressure zone,which is directly adjacent to the right−hand end plate(see Fig.�3/1 and Fig.�3/2).

Page 62: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−8 Festo P.BE−MPAL−EN en 1008NH

External pilot air supply If the operating pressure lies below 3�bar or abo ve 8�bar,pilot control of the solenoid coils must be operated with an external pilot air supply.

Note· Use preferably closed−loop regulated external pilot air.Reliable faultless operation of the valve terminal is thenpossible, e.�g. even with fluctuating operating pressure.

· The external pilot air supply is supplied centrally for allsolenoid coils via pilot connections�(12/14) on the right−hand end plate. This also applies when the valve ter�minal is operated with two pressure zones.

· For external pilot air supply the pilot air pressure mustbe adapted to the operating pressure, but only withinthe values of 3� ...�8�bar .

The conversion between the internal and external pilot airsupply is described in Chapter� 5.3.6.

3.3.2 Valve terminal MPA−L with pressure zone separation

The pressure zones are separated from each other by specialsub−bases (see Chapter� 1.5.5). Each pressure zone must besupplied by pneumatic supply plate and via a right−hand endplate with side connections with compressed air. The positionof the supply plate within the pressure zone (left, centre orright) is arbitrary.

By fitting a second supply plate within a pressure zone youcan provide additional supply air and exhaust air to optimisethe ventilation and exhaust performance of the valve ter�minal.For each additional pressure zone a special sub−base is re�quired for separation and a special pneumatic supply plate isrequired for supply (see Fig.�3/1 and Fig.�3/2).

Page 63: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−9Festo P.BE−MPAL−EN en 1008NH

The following diagrams show as an example the assignmentof the supply and exhaust ports to the valves on a valve ter�minal with three and four pressure zones and blocked chan�nels (1), (3) and (5) and with blocked channel (1).

1 2 3

4

5

6

Zone 1 Zone 2 Zone 3

1 Pressure zone�1

2 Pressure zone�2

3 Pressure zone�3

4 Right−hand end plate (here: Versionwithout side connections)

5 Supply plate (here: for pressurezone�1)

6 Identification of the special sub−basewith integrated pressure zoneseparation (here: for the separation ofchannels (1) and (3/5) betweenpressure zone� 1 and pressure zone� 2)

Fig.�3/1: Example: Valve terminal MPA−L with three pressure zones

Page 64: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−10 Festo P.BE−MPAL−EN en 1008NH

1 2 3 4

5

6

7

Zone 1 Zone 2 Zone 3 Zone 4

1 Pressure zone�1

2 Pressure zone�2

3 Pressure zone�3

4 Pressure zone�4

5 Right−hand end plate with supplyconnection (1) and exhaust ports (3)and (5) for pressure zone� 4

6 Supply plate (here: for pressurezone�1)

7 Identification of the special sub−basewith integrated pressure zoneseparation (here: for the separation ofchannel (1) between pressure zone� 1and pressure zone� 2)

Fig.�3/2: Example: Valve terminal MPA−L with four possible pressure zones

3.3.3 Setting the pressure regulating valve

Using the adjusting screw on the pressure regulator plate (seeFig.�3/3) you can change the flow (see also �Flow diagrams ofthe pressure regulator valve plates" in Appendix A).

Page 65: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−11Festo P.BE−MPAL−EN en 1008NH

Proceed as follows:

· Turn the adjusting screw clockwise to increase the flow.

· Turn the adjusting screw anti−clockwise to decrease theflow.

1 Adjusting screw

2 Pressure gaugeconnection

1

2

Fig.�3/3: Setting the pressure regulator plate

3.3.4 Vacuum/low pressure operation

NoteThe 2x2/2−way valves with Ident. code D, I and the 2x3/2−wayvalves with Ident. code N, K, H are not suitable for vacuum orlow pressure operation.

· For the above�mentioned valves use a separate pressurezone for mixed operation with other valves in vacuum oper�ation on the same valve terminal.

· The operating pressure for this pressure zone must beset in accordance with the diagram in Fig.�A/1.

If valves are used for switching a vacuum, then filters mustbe used in the suction line to avoid operative malfunctionscaused by foreign matter sucked into the line.

Page 66: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−12 Festo P.BE−MPAL−EN en 1008NH

The following conditions must be fulfilled in order that youcan operate the valve terminal at supply connection (1) withvacuum or low pressure between −0.9 ... 3� bar:

� The pilot control of the solenoid coils is operated with aregulated external pilot air supply.

� The valve terminal is fitted with the following valve sub−bases (see Tab.�3/1) and sometimes has additional pres �sure zones.

Valve sub−bases

Pressure zone with vacuum orlow pressure supply via supplyconnection (1) 1)

The pressure zone must be fitted only with the following valvesub−bases:� 5/2−way valve, monostable (Ident. code M)� 5/2−way double pilot valve (Ident. code J)� 5/3−way valves (Ident. codes B, E and G)� 3/2−way valve (Ident. code W and X) see 2) and the following

note.� 2 x 3/2−way valves (Ident. code HS, KS and NS)� 2x 2/2−way valve (Ident. code DS)

Pressure zone with excess pressure supply 3) via supplyport (1)

The pressure zone can be fitted additionally with the followingvalve sub−bases:� 2x3/2−way valves (ident. code H, K and N)� 2 x 2/2−way valves (Ident. code D, I), see also following instruc�

tions

1) The valve plates with Ident. code D, H, K, N and I are not vacuum or low−pressure operation!2) In accordance with diagrams in Appendix A, Fig.�A/33) In accordance with diagrams in Appendix A, Fig.�A/1

Tab.�3/1: Valve sub−bases, suitable for vacuum and low pressure

The pressure ranges of individual valve types can be foundTab.�A/4 in the Technical Specification..

Page 67: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−13Festo P.BE−MPAL−EN en 1008NH

NoteValves with Ident. code I, 2 x 2/2−way valves:

� With these valves, vacuum is supplied at connection (5).Solenoid coil 14 switches the vacuum to connection� (4)

� The operating pressure at supply connection (1) can beused as an ejector pulse at connection�(2). The operatingpressure is switched to connection�2 with solenoid coil 12. If the valve terminal is also equipped with other valves,then operate these vacuum and low pressure valves in aseparate pressure zone with a separate exhaust duct (5).

Valves with Ident. codes W and X, 3/2−way valves:

� These valves can be supplied individually and thereforeoperated in the pressure range of −0.9 ... 10�bar. They areindependent of supply connection (1) of the valve terminal.The connections via which these valves are supplied withcompressed air or vacuum and via which exhaust air isremoved are shown in Tab.�3/2.

The pilot air is supplied via the valve terminal.

3/2−way valve Compressed airor vacuum viaconnection

Exhaust via port

Ident. code X (4) (3)

Ident. code W (2) (5)

Tab.�3/2: Connections to the valves with Ident. code X and W

3.4 Connecting the pneumatic lines

As pneumatic connection elements, terminal screws andthreadless cartridges with safety slot and and clamp strap are used in the MPA−L valve (seeFig.�3/4 and Tab.�3/3).

Page 68: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−14 Festo P.BE−MPAL−EN en 1008NH

Clamps straps are used for the positive−locking connection ofcartridges and can be mounted both form above and frombelow on sub−bases (seeFig.�3/5). For pneumatic supplyplates a clamp strap is fitted from above and for the exhaustplate from below.

If elbow connectors or multiple distributors are used, the airflow will be reduced slightly.

(1)

(1)(3) (5)

(3/5)

(12/14)

(82/84)

(2)

(4)

Fig.�3/4: Pneumatic connections of the valve terminal MPA−L (here: End plate for fittingin exhaust ports)

Page 69: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−15Festo P.BE−MPAL−EN en 1008NH

Line Connection code(ISO 5599)

Port size (ISO 228)

Port 1)

Compressed air orvacuum,Exhaust air

(1)

(3) (5)

QSPKG20 Cartridge in the pneumatic supplyplate and in the exhaust plate

Exhaust air (3), (5)G¼" Fitting in the right−hand end plate

External pilot airsupplyducted pilot exhaust air

(12/14)

(82/84)

M7 Fitting in the right−hand end plate

Air or vacuum (2) or (4) QSPKG10 Cartridge in the sub−base

1) Depending on what you have ordered, the valve terminal may already be fitted with cartridges/screw connectors.

Tab.�3/3: Assignment of the connections

3.4.1 Installation/replacement of the threadless cartridges

Installation Proceed as follows:

1. For selecting the correct cartridge use: Tab.�3/3

2. Press in and turn the cartridge to the stop in the port.

3. Keep the cartridges in the pressed in state and insert asuitable clamp strap in the slot (see Fig.�3/5). Obser ve theguide steps on both sides.The clamp strap must slot into the end position.

Page 70: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−16 Festo P.BE−MPAL−EN en 1008NH

CautionDanger of injury by automatic loosening of parts underpressure.

On pneumatic actuation cartridges can loosen and beejected at high speed, if the clamp strap is not insertedsecurely in the safety slot.

After installation check each cartridge for secure seating.

Page 71: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−17Festo P.BE−MPAL−EN en 1008NH

Fig.�3/5: Assembly of clamp straps for positive locking of the cartridges

Page 72: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−18 Festo P.BE−MPAL−EN en 1008NH

Replacement Proceed as follows:

1. Check that the installed clamp straps can be seen fromthe underside of the valve terminal.If not: First loosen the screws of the valve that is mountedover the sub−base concerned and remove the valve sothat the clamp strap can be removed from above.

2. For pneumatic supply plates:Loosen the screws on the upper part (exhaust plate andcover plate of the silencer) and remove it.

3. Using a narrow slotted screwdriver lever the clamp strapover the lugs and remove it.

4. Pull the cartridge out and replace it with a suitable type(see Tab.�3/3).

3.4.2 Laying the tubing

Note· Seal unused connections with a blanking plugs to ensure the reliability of the valve terminal.

Mounting Proceed as follows:

1. Press the hose into the hose connector as far as the stop(see Fig.�3/6).

2. Check the secure attachment of the hose to the cartridge.

3. For reasons of clarity, bundle the tubing together with:� Tube straps or � Multiple tubing holders

1 Cartridge fitting

2 Locking ring

12

Fig.�3/6: Fitting the tubing

Page 73: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−19Festo P.BE−MPAL−EN en 1008NH

Dismantling Proceed as follows:

WarningIf the pneumatic tubing is under pressure when dismantled, it may move suddenly and unexpectedly, causing injury to persons. Carry out the following stepsbefore disconnecting the pneumatic tubing on the valveterminal MPA−L:

· Switch off the compressed air supply.

· Make sure that all pneumatic tubing is unpressurized.

· Exhaust all actuators controlled by valves which areclosed in normal or mid−positions.

NoteTo disconnect the hoses from the cartridges, use releasingtool type QSO from Festo, or a screwdriver.When using a screwdriver:

· Press down the locking ring only with the broad side ofthe blade.

1. Identify all pneumatic hoses to avoid confusion when reconnecting.

2. Press down the locking ring of the cartridge e.�g. with ascrewdriver or Festo QSO releasing tool (see Fig.�3/7).

3. Remove the tubing from the cartridge.

1 Cartridge fitting

2 Locking ring

1

2

Fig.�3/7: Disconnecting the tubing

Page 74: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−20 Festo P.BE−MPAL−EN en 1008NH

3.4.3 Common pneumatic lines

NoteIn the case of several systems with centrally ducted ex�haust:

· Use non−return valves in the common exhaust lines (3/5)or (82/84) in order to prevent functional impairment dueto back pressures.

1 First valveterminal MPA−L

2 Common exhaustlines (3/5)

3 Central pilot airexhausttubing(82/84)

4 Central exhaustline (3/5)

5 Second valveterminal MPA−L

6 Common exhaustlines (82/84)

1

2

3 4 5

6

6

2

2

Fig.�3/8: Common lines with non−return valves

Page 75: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−21Festo P.BE−MPAL−EN en 1008NH

3.5 Connecting the electric cables

Warning· Use only PELV circuits as per IEC/EN 60204−1 for theelectric power supply (protective extra−low voltage,PELV).Also observe the general requirements for PELV circuitsin accordance with IEC/EN 60204−1.

· Use only power sources that guarantee reliable electrical isolation of the operating voltage as per IEC/EN 60204−1.

Protection against electric shock (protection against directand indirect contact) is guaranteed in accordance with IEC/EN 60204−1 by using PELV circuits (electrical equipmentof machines, general requirements).

NoteAscertain which measures, in line with your EMERGENCYSTOP procedures, are necessary for putting your machine/system into a safe state in the event of an EMERGENCYSTOP�(e.g. switching off the operating voltage for thevalves and output modules, switching off the compressedair).

Valve terminal MPA−L with multi−pin plug connection:Information on the electrical connection of the valve terminalwith one of the multi−pin plug connections can be found in thein User’s manual, enclosed with the product.

Valve terminal MPA−L with CPX terminal:Instructions on connecting the operating voltage can befound in the CPX system manual.

Detailed instructions on connecting the CPX modules (busnode, I/O modules etc.) can be found in the relevant descrip�tions for the CPX module (see CPX system description, table�Descriptions of the CPX terminal").

Page 76: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−22 Festo P.BE−MPAL−EN en 1008NH

Load voltage supply The load voltage supply of the valves for the valve terminalMPA−L is exclusively via the multi−pin plug connection and viathe CPX terminal.

Earthing the valve terminal MPA−L

NoteEarth your valve terminal MPA−L!

· For multi−pin plug connection:Connect one of the earth connections (see Tab.�2/1) withlow impedance to the earth potential, by choosing theshortest possible line with the largest cross section.

· For CPX terminal:Connect both earth connections (see Tab.�2/1) with lowimpedance to the earth potential, by choosing theshortest possible line with the largest cross section.Observe in addition the supplementary information inthe CPX system description.

This serves to avoid interference due to electromagneticinfluences and and ensures electromagnetic compatibilityin accordance with EMC directives.

Page 77: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−23Festo P.BE−MPAL−EN en 1008NH

Valve terminal variant Earth terminals

1

MPA−L with multi−pin plug connection

2� to the left−hand end plate 1

or� to the right−hand end plate 2

1

MPA−L with CPX terminal

2 � to the left−hand end plate 1and

� to the right−hand end plate 2

Tab.�3/4: Earth connections of the valve terminal MPA−L

Page 78: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−24 Festo P.BE−MPAL−EN en 1008NH

3.6 Address assignment of the valves

Addresses are allocated in ascending order without gaps,from left to right (see the following example). A valve positionconsisting of a sub−base with electronics module, occupiesaccording to the integrated electronic module the followingnumber of addresses (see Tab.�3/5):

Electronics module Number of addresses per

Type Housing colouraddresses pervalve position:

Individual electronic module

VMPA1−EVAP−10−1 grey one address

VMPA1−EVAP−10−2 black two addresses

4 off electronic module

VMPA1−EVAP−10−1−4 grey one address (4x)

VMPA1−EVAP−10−2−4 black two addresses (4x)

Electronic module of the pneumatic supply plate

VMPA1−EVAP−20−SP black none, loopedthrough

Tab.�3/5: Available electronic module address assignment

NoteAddress assignment does not depend on whether blankingplates or valve plates are fitted.

If a valve position occupies 2 addresses, the followingapplies:

� Pilot solenoid 14 occupies the less significant ad�dress.

� Pilot solenoid coil 12 occupies the more significantaddress

Page 79: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−25Festo P.BE−MPAL−EN en 1008NH

For controlling the valves, each solenoid coil is assigned to acertain pin of the multi−pin plug socket (see Tab.�3/6).

NoteUse a uniform method of control within a multi−pin plug:Preferably, all control signals should be positive switching(0 −> 1/off −> on), otherwise all control signals negative−switching (1 −> 0/on −> off ).

Mixed mode control is not permitted!

Pin Address Valvepositionnumber

Solenoidcoil

Electronics module

12

01

0 1412

VMPA1−EVAP−10−2−4(black, for 4 MPA1 valveseach with two solenoid

34

23

1 1412

each with two solenoidcoils)

56

45

2 1412

78

67

3 1412

910

89 1)

4 14 VMPA1−EVAP−10−2−4(black, for 4 MPA1 valveseach with two solenoid

1112

1011

5 1412

each with two solenoidcoils)

1314

1213

6 1412

1516

14 1)

15 1)7

17 16 8 14 VMPA1−EVAP−10−1(grey, for an MPA1 valvewith a solenoid coil)

Page 80: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−26 Festo P.BE−MPAL−EN en 1008NH

Pin Electronics moduleSolenoidcoil

Valvepositionnumber

Address

1819

1718

9 1412

VMPA1−EVAP−10−2(black, for an MPA1 valvewith two solenoid coils)

... ... ... ... ...

25 0�V/24�V 2)

1) Address is for a solenoid coil reserved by the electronic module, not used in the current example.

2) Mixed operation is not permitted.

Tab.�3/6: Example: Address assignment of an valve terminalMPA−L with 25 pin multi−pin plug connection and10�valve positions

NoteAddresses may be shifted if the valve terminal is extended.

Page 81: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−27Festo P.BE−MPAL−EN en 1008NH

1 2 3 4

79 8

5

68

1 Addresses of the solenoid coils 14 (manual override 14)

2 Addresses of the solenoid coils 12 (manual override 12)

3 LED for solenoid coil 12

4 LED for solenoid coil 14

5 Unused/reserved valve position

6 Sub−base with VMPA1−EVAP−10−2electronic module assigned twoaddresses per valve position

7 Sub−base with VMPA1−EVAP−10−1electronic module assigned oneaddress per valve position

8 Four sub−bases with fourVMPA1−EVAP−10−2−4 electronicmodules assigned two addresses pervalve position

9 Supply plate with MPA1−EVAP−20−SPelectronic module (no addressassigned)

Fig.�3/9: Example: Address assignment for valve terminal MPA−L with multi−pin plug connection (view)

Page 82: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−28 Festo P.BE−MPAL−EN en 1008NH

3.6.1 Valve terminal MPA−L with multi−pin plug connection

For an valve terminal MPA−L with a multi−pin plug connectionthe maximum number of controllable solenoid coils is relatedto the plug type used (see Chapter.�1.3).

3.6.2 Valve terminal MPA−L with CPX terminal

Pneumatic interface The pneumatic interface of the valve terminal MPA−L createsthe mechanical and electrical connection between the CPXterminal and MPA pneumatic modules.

Display and connecting elements

The pneumatic interface has the following display and con�necting elements (Fig.�3/10):

1 Connecting plugto the MPApneumaticmodules

2 Rotary switchunder a cover cap(torque: 0.5�Nm±�10�%)

3 Inscription field

4 Fault LED (red)

5 Connecting plugto the CPXinterlinkingblocks

1

2

3

4

5

Fig.�3/10: Display and connecting elements on the pneumatic interface

Page 83: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−29Festo P.BE−MPAL−EN en 1008NH

Error LED Error messages are displayed on the one hand via the red LEDon the pneumatic interface and on the other hand transferredfrom the pneumatic interface to the CPX bus nodes. Theseerror messages to and from the pneumatic interface can beinclusively suppressed by parameterisation on the CPX ter�minal (module code: 70d).

Fault LED(red)

Procedure Status Errornumber

Error handling

off

ON

OFF

Faultless operation. � None

LED lights up

ON

OFFFault in load voltage for valvesLoad voltage for the valves (VVAL)missing or too low.

5 Apply and increase voltage

Tab.�3/7: Statuses of the error LED of the pneumatic interfaces

Configuration of the address space

From the point of view of the CPX terminal the pneumaticinterface is seen as an electrical module with a variable (configurable via the rotary switch) number of digital outputsfor the control of the attached valves

For a valve terminal MPA−L with CPX terminal a maximum of32�solenoid coils are controllable, independently of the posi �tion of the rotary switch (see Tab.�3/8).

NoteOn conversion or expansion of the valve terminal MPA−Lthe number of output addresses assigned by the pneu�matic system via the rotary switch on the pneumatic inter�face must be checked and adapted if necessary.This is not necessary if previously a sufficiently large ad�dress space for the expansion has been reserved.

Page 84: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

3. Installation

3−30 Festo P.BE−MPAL−EN en 1008NH

Rotary switch Switch position Maximumnumber of controllableSolenoid coils

0 4

1 8

2; 3 16

4; 5; 6; 7 24

8 (condition upon de�livery)

32

9 32

Tab.�3/8: Configuration of address space size

Adjustment rules for the size of the address space

� If the number of solenoid coils fitted is less than thenumber of output addresses set with the rotary switch,the superfluous addresses will be reserved for later ex�tensions (if the maximum number of valves is fitted, out�put addresses will then remain unused).

� Modifications to the configuration will not become effec�tive until the operating voltage is switched on again.

Further instructions on addressing the pneumatic modules ofthe valve terminal MPA−L with CPX terminal can be found inthe electronics manual for the module (see CPX system de�scription, table �Manuals on the CPX terminal").

Page 85: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

Commissioning

4−1Festo P.BE−MPAL−EN en 1008NH

Chapter 4

Page 86: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

4. Commissioning

4−2 Festo P.BE−MPAL−EN en 1008NH

Contents

4. Commissioning 4−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.1 General Information 4−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.1.1 Prior to commissioning 4−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.1.2 Pressure build−up in the overall supply 4−3 . . . . . . . . . . . . . . . . . . . . . .

4.2 Checking the valves and the valve/actuator combination 4−6 . . . . . . . . . . . . . . .

4.3 Mounting/removing the optional manual override cover cap 4−11 . . . . . . . . . . . .

4.4 Troubleshooting 4−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.4.1 Switching status indicator of the solenoid coils 4−13 . . . . . . . . . . . . . . .

4.4.2 Impairment of functions 4−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.4.3 Operating states of the pneumatic system 4−15 . . . . . . . . . . . . . . . . . . .

Page 87: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

4. Commissioning

4−3Festo P.BE−MPAL−EN en 1008NH

4.1 General Information

4.1.1 Prior to commissioning

· Switch off the power supply before connecting or discon�necting plug connectors (otherwise functional damage).

· Only commission a valve terminal that has been mountedand wired completely.

· Make sure that there is a sufficient supply of fresh air(cooling) for the following operating conditions: � When the maximum number of valves are fitted � When the maximum operating voltage is applied � When the solenoid coils are constantly under stress

· Note the specifications concerning the medium.

4.1.2 Pressure build−up in the overall supply

WarningIf the pressure build−up of the pilot air supply is too slowor delayed, this may cause the actuators to performsudden unexpected movements under the following condi�tions:

� When the compressed air is connected via a soft−startvalve (gradual pressure build−up) and

� If there are electric signals (e.g. after EMERGENCY STOP)

This can cause damage to the machine or system and eveninjury to persons.

· Operate the valve terminal with an external pilot air supply (3 ... 8 bar). Branch the pilot air supply before the soft−start valve (see Fig.�4/1).

Page 88: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

4. Commissioning

4−4 Festo P.BE−MPAL−EN en 1008NH

The pilot air supply must reach a pressure of 3 ... 8 bar.Otherwise it is not ensured that the valve will switch directly(see Fig.�4/1).

If the pressure is less than 3 bar, there may be a delay beforethe valve is switched, in spite of an electric signal being pres�ent. The gradual pressure build−up of the overall supply doesnot affect the actuator in that case. The actuator would reactsuddenly (e.�g. a cylinder would extend or retract suddenly ,depending on the valve function).

1

4 2

5 3

14 12

1

2

1

12/14

12/14

3

82/84

2

1 Externally supplied pilot air supply (3 to 8 bar),branched before the soft−start valve

2 Soft−start valve (slow build up in pressure of completesupply)

Fig.�4/1: Example of valve−cylinder combination with slowpressure build−up of the complete system

Page 89: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

4. Commissioning

4−5Festo P.BE−MPAL−EN en 1008NH

The table below shows the effects of gradual start−up pressurisation when there are electric signals present:

External pilotair supply

Pressure risein overall supply

Pressure rise inthe pilot airsupply (12/14)

Time when avalve reverses

Movement ofthe actuator

Branched down�stream of the soft−start valve

slowly slowly after pressurerise at (1)

fast

Branched up�stream of the soft−start valve

slowly fast before pressurerise at (1)

slowly

Tab.�4/1: Effects of slow start−up pressurisation

Page 90: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

4. Commissioning

4−6 Festo P.BE−MPAL−EN en 1008NH

4.2 Checking the valves and the valve/actuator combination

The valve terminal MPA−L should be commissioned as follows:

Commissioning variants Activity

Preliminary test of the pneuma�tic tubing connection

Test the valve−actuator combina�tion by means of the manualoverride

Complete commissioning of theoverall system

Installing and connecting theoverall system.Program control via PLC/indu�strial PC.

Tab.�4/2: Commissioning variants

Commissioning the pneumatic components by means of themanual override is described below.

Commissioning of the CPX terminal is described in the appropriate description for the CPX bus node (see CPX system description, table �Descriptions of the CPX terminal").

Page 91: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

4. Commissioning

4−7Festo P.BE−MPAL−EN en 1008NH

WarningBefore actuating the manual overrides:

Uncontrolled actuation of solenoid coils can cause theactuators to perform sudden unexpected movementswhich may cause personal injury and material damage.

· Disconnect the power supply for the solenoid coils at the relevant connections on the valve terminal MPA−L.

This prevents accidental actuation of the solenoid coils.

Before switching on the power supply:

During commissioning, manual overrides that are in theswitched state can cause actuators to perform suddenunexpected movements. These movements can cause injury to persons and damage to property.

· Make sure that all manual overrides are reset to theirinitial position.

You will thereby avoid undefined switching states of thevalves.

WarningBefore testing the valve/actuator combination:

� Make sure that nobody is in the danger zone.

NoteA valve that has been switched by an electric signal cannotbe reset by the manual override. The electric signal isdominant in this case.

· Reset the electric signal before actuating the manualoverride.

Proceed as follows:

1. Switch on the compressed air supply.

Page 92: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

4. Commissioning

4−8 Festo P.BE−MPAL−EN en 1008NH

2. Check the functioning and operation of each individualvalve/actuator combination by actuating the manual over�ride as shown in the following diagrams.

NoteIncorrect actuation of the non−detenting manual overridecan lead to malfunctioning or damage to the manual over�ride.

· Use a screwdriver (blade width max.3�mm) to actuatethe manual override.

· Operate the manual override to max. 25� N.

3. With a detenting manual override: After testing the valves,make sure that all manual overrides are in their initialpositions again.

CautionValves with manual overrides in switch position can moveactuators unintentionally during commissioning. This cancause injury to people and damage to property.

· Prior to commissioning, reset all manual overrides totheir initial positions again.

If the manual override is in the actuated state, it is notpossible to reset the valve to its neutral position with anelectric signal. The manual override is dominant in thiscase.

4. Switch off the compressed air supply after testing thevalves.

Page 93: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

4. Commissioning

4−9Festo P.BE−MPAL−EN en 1008NH

Non−detenting operation of manual override (return: automatic)

Operation Valve response

· Use a screwdriver (max. bladewidth 3 mm) to press down theplunger of the manual overrideuntil the valve switches.

Note:In the case of manual overrides without a cover cap, do not turn thepressed−down plunger as otherwisethe manual override will lock.

The pilot valve switches and sets the power valve to the switch posi�tion.

· Press and hold in the stem of the manual override.

The valve remains switched.

· Put down the screwdriver. The spring force presses the stem of the manual override back to theneutral position.Pilot valve returns to the neutral posi�tion and so too does the monostablepower valve (not for bistable valves,code�J).

Tab.�4/3: Non−locking operation of the manual override

Page 94: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

4. Commissioning

4−10 Festo P.BE−MPAL−EN en 1008NH

NoteThe detenting operation of the manual override is onlypossible if a manual override cover cap is not fitted.

Detenting operation of the manual override (return: manual)

Operation Valve response

· Use a screwdriver (max. bladewidth 3�mm) to press down theplunger of the manual overrideuntil the valve switches.

· Then turn the plunger a quarterturn in a clockwise direction.

The pilot valve switches and sets the power valve to the switch posi�tion.

· Put down the screwdriver. The valve maintains its switching position.

· Using the screwdriver rotate the stem anti−clockwise a quarterturn backwards.

· Put down the screwdriver.

The spring force presses the stem ofthe manual override back to the neu�tral position.Pilot valve returns to the neutral posi�tion and so too does the monostablepower valve (not for bistable valvescode�J).

Tab.�4/4: Detenting operation of the manual override

Page 95: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

4. Commissioning

4−11Festo P.BE−MPAL−EN en 1008NH

4.3 Mounting/removing the optional manual override cover cap

Mounting Proceed as follows:

1. Make sure that the relevant manual overrides are in anon−actuated state. If necessary set a detenting manualoverride back to the initial position (see Tab.�4/4).

2. Place the cover cap on the manual override so that thesnap hooks of the cover can grip into the recess on themanual override.

3. Clip the manual override cover caps into the recesses inthe manual overrides (see Fig.�4/2).

1 Manual overridecover caps

2 Manual override(MO)

1

2

Fig.�4/2: Mounting the MO cover caps

Page 96: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

4. Commissioning

4−12 Festo P.BE−MPAL−EN en 1008NH

NoteThe manual override cover caps serve for limiting the function of the manual override and are constructed so that they can only be removed with a great deal ofstrength. During dismantling the snap hooks of the manual override cover cap will be damaged.

Dismantling Proceed as follows:

· Use a suitable screwdriver to lift the manual overridecover caps out of the manual overrides (see Fig.�4/3).

Fig.�4/3: Dismounting the manual override cover caps

Further information can be found in the assembly instructionsenclosed with the cover caps.

Page 97: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

4. Commissioning

4−13Festo P.BE−MPAL−EN en 1008NH

4.4 Troubleshooting

4.4.1 Switching status indicator of the solenoid coils

The LEDs on the valves show the switching statuses of thesolenoid coils.

LED (yellow) Switching position of the valve

Meaning

off

Neutral position Logical 0 (signal not applied)

Switching position (normalcase)

Logical 1 (signal is present, valve has switched)

LED lights up Neutral position (error) logical 1 (signal is present, valve has not switched):� Load voltage of the valves lies below the

permitted tolerance range� Compressed air supply not OK

or� Pilot exhaust air blocked

or� Servicing required

Tab.�4/5: Meaning of the LED display

4.4.2 Impairment of functions

After switching on the compressed air supply or when subse�quently testing the individual valves, you can learn the followingabout the operating status of the pneumatic system:

Page 98: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

4. Commissioning

4−14 Festo P.BE−MPAL−EN en 1008NH

Operating status of the pneumatic system

Error handling when the compressed air supply has beenswitched off

Air escapes from ...� Common line or working

line connections· Check assembly of the tubing

Valve or pneumatic system...� Does not react as expected

� Not

· Check the installation of the tubing lines· Check the electric cables

· Bring the detenting manual override into the basic position�· After switching on again check the operating pressure (if necessary

for each pressure zone). Set operating pressure in accordance withinstructions in chapter 3.

· Servicing requiredFor valve terminals which must be operated with closed−loop regulatedexternal pilot air:· After switching on again, check the pilot pressure (if necessary,

set as a factor of the operating pressure, see chapter 3)

Tab.�4/6: Function impairment of the pneumatic system

Page 99: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

4. Commissioning

4−15Festo P.BE−MPAL−EN en 1008NH

4.4.3 Operating states of the pneumatic system

The following conditions should be fulfilled, in order that the desired pneumatic operating states listed below can beachieved:

Desired pneumaticoperating status

Requirement Description

Zero leakage � Tubing connected with care� Regulated pilot air supply

Fast reaction Sufficient pressure supply by meansof pressure supply modules

Exhaust the valve terminal MPA−Lvia all the exhaust plates or via theflat plate silencer

Trouble−free Non−return valves in common ex�haust line

This applies when several systemswith centrally ducted exhaust air areused

Two or more pressurezones

� Limiting the pressure zones bymeans of separating seals withblocked channels

� Appropriate number of pneu�matic air supply plates for supplying the different pressurezones.

Subsequent conversion possible(see Chapter 5)

Vacuum or low−pres�sure operation

Externally supplied regulated pilotair supply (3 ... 8 bar)

Vacuum/low−pressure operation notwith 3/2−way valves

EMERGENCY STOP ofpressure zones

Guaranteeing the controller functionfor the pilot air supply despite theoverall supply being switched off

The controller regulates the pilot airsupply to all the valve plates on avalve terminal MPA−L

Slow start−up afterEMERGENCY STOP

If control signals are present, the pi�lot air supply must have a pressureof 3 ... 8 bar immediately after beingswitched on

Tab.�4/7: Pneumatic operating states

Page 100: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

4. Commissioning

4−16 Festo P.BE−MPAL−EN en 1008NH

Page 101: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

Conversion and maintenance

5−1Festo P.BE−MPAL−EN en 1008NH

Chapter 5

Page 102: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

5. Conversion and maintenance

5−2 Festo P.BE−MPAL−EN en 1008NH

Contents

5. Conversion and maintenance 5−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.1 General preventive action 5−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.2 Maintaining the valve terminal MPA−L 5−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.2.1 Clean or replace flat plate silencer 5−4 . . . . . . . . . . . . . . . . . . . . . . . . . .

5.2.2 Replacing valves or cover plates 5−5 . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.3 Conversion of the MPA−L valve terminal 5−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.3.1 Tie rod system 5−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.3.2 Exchange sub−base, supply plate or extend or exchange right−hand end plate 5−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.3.3 Replace the electronic module 5−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.3.4 Conversion between ducted and unducted exhaust air 5−15 . . . . . . . . .

5.3.5 Conversion between internal and external pilot air supply 5−16 . . . . . . .

5.3.6 Converting the valve terminal MPA−L to different pressure zones 5−18 .

5.3.7 Conversion of the left−hand end plate of IP40 on IP65 cover 5−19 . . . . .

5.3.8 Conversion of the outlet direction of the multi−pin cable 5−19 . . . . . . . .

5.3.9 Conversion of the end plate between multi−pin and CPX connection 5−22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.4 Replace the pneumatic interface 5−24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 103: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

5. Conversion and maintenance

5−3Festo P.BE−MPAL−EN en 1008NH

5.1 General preventive action

WarningUncontrolled movements of the connected actuators andloose tubing can cause injury to persons and/or damageto property.

Before carrying out installation and maintenance work,switch off the following:

� Compressed air supply

� The operating and load voltage supplies.

NoteHandle all modules and components of the valve terminalMPA−L with great care. Note especially the following whenmounting components:

� Screws must be fitted exactly (prevents damage tothreads).

� Screws must be turned by hand only and fitted so thatthe self−cutting threads can be used.

� The specified torques must be observed.

� Fittings must be mounted free of offset and mechanicaltension.

� Check the seals for damage (to maintain IP�65).

� The contact surfaces must be dry and clean (sealingeffect, avoid leakage and contact errors).

Page 104: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

5. Conversion and maintenance

5−4 Festo P.BE−MPAL−EN en 1008NH

5.2 Maintaining the valve terminal MPA−L

5.2.1 Clean or replace flat plate silencer

CautionDanger of fire by easily flammable cleaning agents.· Observe the safety regulations for handling easily inflammable cleaning agents.

CautionSafety hazards· For cleaning do not use chlorinated hydrocarbons, e.�g. trichlorethylene (TR I), but petrol or petroleum.

NoteAvoiding malfunctioning:Dirt in the flat plate silencer can cause an increase in pressure in exhaust ducts (3) and (5).

· Clean the flat plate silencer if it is yellow/black or a darkcolour, or replace it by a new insert.

You can then guarantee faultless functioning of the flatplate silencer and avoid malfunctioning of the valves.

Proceed as follows:

1. Loosen the four attachment screws on the cover plate ofthe silencer and remove the cover plate and flat platesilencer from the supply plate.

2. Clean the flat plate silencer with petrol or petroleum orreplace it with a new insert.

3. Fasten the flat plate silencer only with the original screws.Tighten them to 1.4� Nm ±10�%.

Page 105: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

5. Conversion and maintenance

5−5Festo P.BE−MPAL−EN en 1008NH

5.2.2 Replacing valves or cover plates

Dismantling Proceed as follows:

· Use a screwdriver with a narrow blade to loosen thefastening screws and remove the components from thesub−bases (see Fig.�5/1).

Fig.�5/1: Dismantling valves or cover plates

Mounting Proceed as follows:

1. Check the seals for damage, especially the cord seals.

2. Replace seals if they are damaged.

3. Make sure that the cord seal between the sub−base andcomponents is in the correct position: The cord seal mustsit in the component cut−outs.

Page 106: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

5. Conversion and maintenance

5−6 Festo P.BE−MPAL−EN en 1008NH

1 Mounting screws

2 Valve or coverplate

3 Cord seal

4 Sub−base

1

2

3

4

Fig.�5/2: Mounting valve plates or cover plates

4. Place the component on the sub−base.

5. Screw the component at first slightly and then tighten to0.25�Nm ±20�%.

Page 107: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

5. Conversion and maintenance

5−7Festo P.BE−MPAL−EN en 1008NH

5.3 Conversion of the MPA−L valve terminal

You can convert the valve terminal MPA−L at a later date andadapt it to requirements by adding valve positions. The fol�lowing conversion work can be undertaken on the valve ter�minal MPA−L:

� Conversion between ducted and unducted exhaust air

� Conversion between internal or external pilot air supply

� Conversion to different pressure zones

� Adding valve positions (sub−bases)

� Adding supply plates for additional pneumatic powersupply

Shortening the The shortening of the valve terminal MPA−L by a few valvevalve terminal positions is only possible if the tie rod system is created from

individual expansion pieces (see Tab.�5/1).

Information on permitted possibilities of combining MPA−Lcomponents and accessories can be found in the Festo Cata�logue (see www.festo.com\catalogue).

5.3.1 Tie rod system

The mechanical connection between the modules of the valveterminal MPA−L is achieved via a tie rod system in the sub−bases between the two end plates.

This tie rod system is used for valve terminal MPA−Ls thatconsist of at least four VMPA1 sub−bases and supply via right−hand end plates with lateral ports or two VMPA1 sub−basesand a supply plate.

Page 108: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

5. Conversion and maintenance

5−8 Festo P.BE−MPAL−EN en 1008NH

Set up The tie rod system valve terminal MPA−L consists essentiallymainly of three parts:

� Threaded rod with lug for open−ended spanner, size�5

� Threaded sleeve with internal hexagon, size� 4

� Tie rod screw with internal hexagon, size 2.5

1 Threaded rod(graduatedlengths available)

2 Extension piece

3 Threaded sleeve

4 Tie rod screw

1 2

3 4

2

Fig.�5/3: Components of the tie rod system

Extension An extension of the valve terminal MPA−L by one of more sub−bases means that the tie rod system must be extended. Forthis extension pieces are screwed in between the threadedrod and thread sleeve. For sub−bases, 4x sub−bases andpneumatic supply plates corresponding extension pieces areavailable (see Tab.�5/1).

Page 109: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

5. Conversion and maintenance

5−9Festo P.BE−MPAL−EN en 1008NH

Product type Part number

VMPAL−ZAE−10Set for a sub−base

561139

VMPAL−ZAE−20Set for a supply plate

561141

VMPAL−ZAE−10−4Set for a 4x sub−base

570779

Tab.�5/1: Extension pieces for tie rod system

Special solutions For especially short valve terminal MPA−Ls the followingadaptations to the tie rod system are necessary (see alsoTab.�5/2):

� Valve terminals consisting of two VMPA1 sub−bases andright−hand end plate with lateral ports:Use tie rod screws for connection with left−hand end plate.

� Valve terminals consisting of three VMPA1 sub−bases andright−hand end plate with lateral ports:Use extension piece, type VMAL−ZAE−10, and tie rodscrew.

For extension of these special solutions use the correspon�ding extension pieces (see Tab.�5/1) and screw them directlybetween the tie rod screws and available components.

Page 110: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

5. Conversion and maintenance

5−10 Festo P.BE−MPAL−EN en 1008NH

Setting up the valve terminal MPA−L

Tie rod system Extension possibilities ofthe valve terminal

Standard set up

At least four sub−bases,right−hand end plate with lat�eral ports or at least twosub−bases, pneumatic sup�ply plate and right−hand endplate.

� Threaded rod� Threaded sleeve� Tie rod screw

See chapter � 5.3.2.

Special solutions

Two sub−bases, right−handend plate with lateral ports

Use only tie rod screw � One sub−base, one extensionpiece

� For extension by more thanone sub−base/supply plate theextension pieces must be re�placed by the standard setup.

Three sub−bases, right−handend plate with lateral ports

� One extension piece� One tie rod screw

For extension by one or moresub−base/supply plates the extension pieces must be replaced by the standard setup.

Tab.�5/2: Standard setup of the tie rod system and special solutions for short valve terminal MPA−Ls with extension possibilities

Page 111: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

5. Conversion and maintenance

5−11Festo P.BE−MPAL−EN en 1008NH

5.3.2 Exchange sub−base, supply plate or extend or exchange right−handend plate

You can easily adapt the valve terminal MPA−L to the require�ments of your machine or system by exchanging or adding valvepositions.

At all valve positions valves with one or two solenoid coils canbe fitted. If only one size and valves with the same number ofsolenoid coils are used the following maximum number of sub−bases (Tab.�5/3) occurs:

Valve terminal MPA−L Valve positions persub−base n1

Solenoid coils pervalve position n2

max. numberXmax

1)

MPA1 1 1 32

2 16

4 1 8

2 4

1) Maximum number of sub−bases when exclusively equipped with one size and with valves having the same number of solenoid coils

Tab.�5/3: Maximum number of sub−bases

The maximum number of controllable solenoid coils is limitedby the connection option (multi−pin plug type or CPX terminal,see Chapter� 1.3 and 1.4).For 32 controllable solenoid coils the maximum number ofsub−bases (Xmax) can be calculated as follows:

Xmax �32

�n1� n2�

Page 112: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

5. Conversion and maintenance

5−12 Festo P.BE−MPAL−EN en 1008NH

Dismantling Proceed as follows:

1. Loosen the electrical and pneumatic connections and remove the valve terminal MPA−L from its fastening surface (see Chapter� 2).

2. Place the valve terminal MPA−L on a flat working surface.

3. Undo the three screws of the tie rod on the right−hand endplate using an Allen key size 2.5 (see Fig.�5/4).

Fig.�5/4: Fittings in the right−hand end plate (here: versionswithout lateral connections)

4. Then loosen and remove the three�screws of the tie rod. The released sub−bases are now only held together by theelectrical interlinking.

5. First withdraw the components on the right from the com�ponents to be exchanged or extended.

6. If necessary withdraw the components to be exchangedand replace them.

Page 113: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

5. Conversion and maintenance

5−13Festo P.BE−MPAL−EN en 1008NH

7. For extension:Loosen the threaded sleeves from the threaded rods ofthe tie rod with an Allen key, size�4. Prevent the threadedrods from moving in the end plate by holding them withan open end spanner, size�5.

Mounting Proceed as follows:

1. Check the free cord seals on the separation points of thesub−bases for damage.

2. If necessary change the damaged cord seals.

3. Screw the extension the pieces of the tie rod between the threaded rods and threaded sleeves of the tie rod (see Fig.�5/3) and tighten them by hand.For an extension of the valve terminal MPA−L by severalcomponents the extension pieces are screwed to oneanother in a row between the threaded rod and thethreaded sleeve of the tie rod.

4. Check that all three tie rods of the valve terminal MPA−Lare the same length.

5. Tighten the three tie rods with an Allen key, size�4, in theleft−hand end plate (see Fig.�5/5, torque 1.7�Nm ±10%).

6. Place the sub−bases and if necessary the supply plates inthe desired order on the tie rod. Then fit the right−handend plate.

7. Push the three screws through the holes in the right−handend plate into the threaded sleeves of the tie rod andtighten them uniformly with a Allen key, size�2.5, handtight.Tighten the screws to a torque of 1.7�Nm ±10% and thencheck the torque on all three screws, as the torque on thescrews can change during the tightening process.

Page 114: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

5. Conversion and maintenance

5−14 Festo P.BE−MPAL−EN en 1008NH

Fig.�5/5: Connecting sub−bases by means of tie rod

8. Mount the valve terminal on the mounting surface (see Chapter 2� ).

9. Then fit the pneumatic and electrical connections (see Chapter 3).

5.3.3 Replace the electronic module

Each sub−base, 4x sub−base and supply plate is fitted with aseparate electronic module. A list of all available electronicmodules can be found in Chapter� 3.6.

To exchange an electronic module the valve terminal MPA−Lmust be partially dismantled (see Chapter� 5.3.2).

Page 115: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

5. Conversion and maintenance

5−15Festo P.BE−MPAL−EN en 1008NH

To separate the sub−base and the electronic module you require a VMPAL−LW releasing tool, use of which is describedin the enclosed assembly instructions.

CautionWhen exchanging an electronic module use only an elec�tronic module of the same type, so that undesired addressshifts and consequent incorrect switching is avoided.

CautionThe electronic module may be damaged if it is not handledcorrectly.

· Switch off the power supply before removing the elec�tronics modules.

· Do not touch any components

· Observe the handling specifications for electrostaticallysensitive devices.

· Discharge yourself before installing or removing sub−assemblies to protect the sub−assemblies from staticdischarges.

5.3.4 Conversion between ducted and unducted exhaust air

Supply plates

You can convert the valve terminal from ducted exhaust bymeans of exhaust plate to unducted exhaust air by means offlat plate silencer.

Proceed as follows to convert to unducted exhaust air:

1. Loosen the 4�attachment screws of the exhaust plate andremove the exhaust plate including the cord seal from thesupply plate.

Page 116: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

5. Conversion and maintenance

5−16 Festo P.BE−MPAL−EN en 1008NH

2. Secure the flat plate silencer and the cover plate with thefour original screws. Tighten them to 1.4�Nm ±10%.

Proceed as follows to convert to ducted exhaust air:

1. Loosen the 4�attachment screws of the co ver plate andremove the cover plate and the flat plate silencer from thesupply plate.

2. Locate the seal supplied with the exhaust plate in the slotbetween the supply plate and the exhaust plate.

3. Fasten the exhaust plate only with the four originalscrews. Tighten them to 1�Nm ±10%.

Right−hand end plate with lateral ports

Connections (3) and (5) can be fitted optionally with silencersor with connections for tubing lines.

5.3.5 Conversion between internal and external pilot air supply

NoteMixed operation of the valve terminal MPA−L with internaland external pilot air is not intended. Independently of theavailable pressure zones for various operating pressuresall solenoid coils of the valve terminal MPA−L are suppliedwith a common pilot air supply.

The pilot air supply that your valve terminal MPA−L is set forcan be determined from the position of the selector plate (seeChapter�1.5.3).

Page 117: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

5. Conversion and maintenance

5−17Festo P.BE−MPAL−EN en 1008NH

Right−hand end plate without lateral ports

Proceed as follows when converting:

1. Loosen the screws of the selector plate so that the guidebolts are released and the selector plate can be turned(see Fig.�5/6).

Fig.�5/6: Conversion of the round selector plate

2. Turn selector plate to position �Int" or �Ext" and put onthe end plate taking into account the guide bolts.

3. Tighten screw (torque 3.5�Nm ±10%).

Right−hand end plate with lateral ports

Proceed as follows when converting:

1. Unscrew the screws of the selector plate (see Fig.�5/7)and remove selector plate.

Page 118: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

5. Conversion and maintenance

5−18 Festo P.BE−MPAL−EN en 1008NH

Fig.�5/7: Conversion of the square selector plate

2. Set selector plate to the �Int" or �Ext" position on the endplate.

3. Screw in screws and tighten (torque 2.2�Nm ±10%).

5.3.6 Converting the valve terminal MPA−L to different pressure zones

For the conversion you will require at least the following components for each pressure zone:

� Sub−base with desired pressure zone separation (seeChapter�1.5.5)

� Pneumatic supply plate with exhaust plate and flat platesilencer

Page 119: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

5. Conversion and maintenance

5−19Festo P.BE−MPAL−EN en 1008NH

The procedure for the conversion of pressure zones corresponds to the exchange or extension of components, as described in Chapter� 5.3.2.

5.3.7 Conversion of the left−hand end plate of IP40 on IP65 cover

Applies only to the versions with 25−/44 pin Sub−D multi−pinplug connection.

Dismantling IP40 cover Proceed as follows:

1. Loosen and remove both locking rings on the Sub−D plug.

2. Loosen and remove the four screws of the IP40 cover.

3. Remove the IP40 cover.

Mounting of IP65 cover Proceed as follows:

1. Check that the seal is not twisted in the slot of the cover.

2. Place the cover as far as possible at right angles on themultipin sub−base, so as not to damage the contacts ofthe Sub−D plug.

3. Secure the cover to the left−hand end plate with the fourscrews provided (Torx, size�10, torque 1.2�Nm ±10%).

4. Connect the electrical cables according to the short description provided with the product.

5.3.8 Conversion of the outlet direction of the multi−pin cable

Applies only to the versions of the valve terminal MPA−L withmulti−pin connection and IP65 cover.

Page 120: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

5. Conversion and maintenance

5−20 Festo P.BE−MPAL−EN en 1008NH

Preparatory steps

1. Loosen the wires of the multi−pin cable at the rear of thevalve terminal MPA−L and all attachments of the multi−pincable up to the valve terminal.With the exception of the attachment to the Sub−D socketit must be possible to pull the multi−pin cable must fullythrough the hole in the cover during the conversion.

2. Loosen the four screws of the cover and remove the coverfrom the valve terminal.

3. Loosen the cover nut and push it back a few centimetres.

4. Loosen the cable connection on the cover and pull thistogether with the cover nut from the multi−pin cable.

5. Loosen the two screws on the internally located Sub−Dsocket in the cover, Torx size 6.

6. Pull the multi−pin cable through the opening in the cover,past the Sub−D socket and out of the cover.

Conversion to side cable outlet

When you have carried out the preparatory work proceed asfollows:

1. Using a slotted screwdriver break open the wall on theside of the cover at the circular breaking point and deburrthe breaking point.

2. Push the M20x1.5 nut provided over the multi−pin cable.

3. Guide the multi−pin cable through the hole of the desiredcable exit direction.

4. Push the cable connector and the cover nut over themulti−pin cable.

Page 121: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

5. Conversion and maintenance

5−21Festo P.BE−MPAL−EN en 1008NH

5. Secure the Sub−D socket with the two screws, Torx size 6,in the cover, by initially hand−tightening the two screwsand then loosening by a half−turn.This ensures that the multi−pin plug and socket arealigned with each other on assembly.

6. Screw the cable connector from the outside onto the internally situated M20x1.5 nut and tighten the cable connector with an open end spanner, size 24 (torque2.2�Nm ±10%).

7. Screw the cover nut onto the cable connector, hold it securely with an open end spanner, size 24, and tightenthe cover nut (torque 3�Nm ±10%).

8. Screw the locking screw M20x1.5 in the open front facehole and tighten it (torque 1.2�Nm ±10%).

9. Secure the cover to the left−hand end plate with the fourscrews provided (Torx, size�10, torque 1.2�Nm ±10%).

Conversion to straight cable outlet

When you have carried out the preparatory work proceed asfollows:

1. Loosen the locking screw M20x1.5 and remove it from thecover.

2. Place the M20x1.5 nut from the inside in the rotationprotection of the cover.

3. Insert the M20x1.5 locking screw from the outside in the side opening of the cover, secure it with the M20x1.5locking screw and screw tight the cable connector (torque3�Nm ±10%).

4. Guide the multi−pin cable through the M20x1.5 lockingscrew and out through the cover.

Page 122: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

5. Conversion and maintenance

5−22 Festo P.BE−MPAL−EN en 1008NH

5. Secure the Sub−D socket with the two screws, Torx size 6,in the cover, by initially hand−tightening the two screwsand then loosening by a half−turn.This ensures that the multi−pin plug and socket arealigned with each other on assembly.

6. Push the cable connector and the cover nut over themulti−pin cable.

7. Screw the cable connector from the outside into the coverand tighten the cable connector with an open endspanner, (size 24, torque 3�Nm ±10%).

8. Screw the cover nut onto the cable connector,and tightenthe cover nut (size 24, torque 3�Nm ±10%).

9. Secure the cover to the left−hand end plate with the fourscrews provided (Torx, size�10, torque 1.2�Nm ±10%).

5.3.9 Conversion of the end plate between multi−pin and CPX connection

Applies to the conversion between multipin sub−bases andanalogue between multipin sub−base and CPX terminal withpneumatic interface.

Dismantling Proceed as follows:

1. Loosen the electrical and pneumatic connections and re�move the valve terminal MPA−L from its fastening surface(see Chapter� 2).

2. Place the valve terminal MPA−L on a flat working surface.

3. Undo the three screws of the tie rod on the right−hand endplate using an Allen key size 2.5 (see Fig.�5/4).

4. Then loosen and remove the three�screws of the tie rod. The released sub−bases are now only held together by theelectrical interlinking.

5. Remove all components from the the left−hand end plate.

Page 123: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

5. Conversion and maintenance

5−23Festo P.BE−MPAL−EN en 1008NH

6. Loosen the threaded rods of the tie rod using and openend spanner, size�5, and unscrew these out of the left−hand end plate (see Fig.�5/8).

Fig.�5/8: Remove the threaded rods from the left−hand endplate.

Mounting Proceed as follows:

1. Replace the current multipin sub−base by the desiredmultipin sub−base and a CPX terminal with pneumaticinterface for MPA−L.

2. Rotate the threaded rods of the tie rod into the multipinsub−base and tighten with an open end spanner (size� 5,torque 1.7�Nm ±10%).

3. Carry out the remaining assembly steps in the reverseorder to dismantling.

4. Mount the valve terminal on the mounting surface (see Chapter�2).

5. Then fit the pneumatic and electrical connections (see Chapter�3).

Page 124: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

5. Conversion and maintenance

5−24 Festo P.BE−MPAL−EN en 1008NH

5.4 Replace the pneumatic interface

The valve terminal MPA−L is connected to the CPX terminal bymeans of a pneumatic interface (see Fig.�5/9). The pneumaticinterface constitutes not only the technical control interface,but also the mechanical interface between the tie rod systemsof the valve terminal MPA−L and the CPX−Terminal.

1 CPX terminal

2 Pneumaticinterface

3 Valve terminalMPA−L

1 2 3

Fig.�5/9: Valve terminal MPA−L with CPX terminal

To replace the pneumatic interface both the pneumatic andthe electrical side must be disassembled.

Dismantling Proceed as follows:

1. Loosen the electrical and pneumatic connections and remove the valve terminal MPA−L from its fastening surface (see Chapter� 2).

2. Place the valve terminal MPA−L on a flat working surface.

3. Disassemble the pneumatic side of the valve terminalMPA−L (see Chapter� 5.3.9).

Page 125: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

5. Conversion and maintenance

5−25Festo P.BE−MPAL−EN en 1008NH

4. Loosen the two tie rod screws on the left−hand end plateof the CPX terminal using an Allen key, size�3, withoutpulling them fully out.

5. With the aid of a suitable tool, e.�g. a screwdriver , removethe appropriate fastening and locking plate in the pneu�matic interface (see Fig.�5/10).Now you can separate the pneumatic interface from themodules of the CPX terminal.

1 Tie rod screw

2 Fastening plateand locking platein the pneumaticinterface

3 Screwdriver

1 2

3

1

Fig.�5/10: Dismantling on the side of the CPX terminal

Information about conversion and extension of the CPX terminal can be found in the CPX system manual type P.BE−CPX−SYS−....

Page 126: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

5. Conversion and maintenance

5−26 Festo P.BE−MPAL−EN en 1008NH

Mounting Proceed as follows:

1. Fasten the tie rod in the pneumatic interface, by placingthe fastening plate over the locking plate and pushingthese together into the groove intended for this purpose.The locking plate must lie on the side facing the pneu�matics. The hooks on the locking plate must grip into thegrooves in the fastening plate.

1 Locking plate

2 Fastening plate

3 Groove for tie rodfastening

1

23

Fig.�5/11: Mounting on the side of the CPX terminal

2. Slide the interlinking blocks together carefully and with�out tilting.Make sure that the electric plug connectors of the mani�fold sub−bases are not bent.

3. Align the CPX terminal on a flat surface so that the compo�nents are not offset. Use the bearing surface for the H−railto align the component correctly. It is easier to align if youuse an H−rail.

4. Tighten the two tie rod screws uniformly using an Allenkey, size 3, (torque 2� Nm ±0.3� Nm).

Page 127: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

5. Conversion and maintenance

5−27Festo P.BE−MPAL−EN en 1008NH

5. Mount the valve terminal on the mounting surface (seeChapter�2).

6. Then fit the pneumatic and electrical connections (seeChapter�3).

Page 128: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

5. Conversion and maintenance

5−28 Festo P.BE−MPAL−EN en 1008NH

Page 129: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

Technical appendix

A−1Festo P.BE−MPAL−EN en 1008NH

Appendix A

Page 130: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

A. Technical appendix

A−2 Festo P.BE−MPAL−EN en 1008NH

Contents

A. Technical appendix A−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.1 Technical data A−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.2 Festo accessories A−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 131: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

A. Technical appendix

A−3Festo P.BE−MPAL−EN en 1008NH

A.1 Technical data

NoteThe valves can be used at temperatures down to −5 °C. In order to prevent the condensate and the humidity fromfreezing, we recommend that you fit a dryer with whichcondensate and humidity can be removed.

General information

Permitted temperature range� Long−term storage� Operation� Medium

− 20 ... + 40 oC − 5 ... + 50 oC − 5 ... + 50 oC

Protection class to EN 60� 529 IP65 (with IP65 cover and cable fromthe Festo accessories)

Relative air humidity 90% at 40 oC

Mounting position� H−rail mounting� Wall mounting

only horizontalrequired, but: observe Tab.�A/2

Tightening torque (MA in Nm) Left−hand end plate, multipin sub−base� Printed circuit board in end plate� IP40 cover� Screw−type lock (UNC bolts)� IP65 cover� Blanking plugs, M20� Cable connector, straight/sidePneumatic supply plate� Flat plate silencer with cover� Exhaust plateSub−base� ValveRight−hand end plate� Selector plate, round� Selector plate, squareTie rod� Threaded rod/sleeve, screw

0.5 ±10%0.6 ±10%0.5 ±10%1.2 ±10%1.2 ±10%3.0 ±10% / 2.2 ±10%

1.3 ±10%1.0 ±10%

0.25 ±20%

3.5 ±10%2.2 ±10%

1.7 ±10%

Page 132: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

A. Technical appendix

A−4 Festo P.BE−MPAL−EN en 1008NH

General information

Materials� Valves and end plates� Sub−bases and supply plates� Exhaust plate� Silencer� Electronics module� Seals� Threaded rods and clamp strap� Screws

Die−cast−AL, PA6, PA6T, PBTPPA, AW−ALPA66PECuNi3Si1Mg, PBT, PA66Elastomer, NBRStainless steel, rustproofSteel, coating ZnNi

Weights (in g):� Multipin end plate� Pneumatic interface� Pneumatic supply plate (with seal, electrical

interlinking module, exhaust plate/flat platesilencer)

� Per sub−base (with seal, electronic module,electrical interlinking module)

� Per 4x sub−base (with seal, electronic module,electrical interlinking module)

� Right−hand end plate without/with lateralports

� Per valve� Per cover plate� Per pressure regulator plate

130�gapprox. 210�g87�g / 92�g

30�g (one valve position)

113�g (four valve positions)

105�g / 161�g

approx. 56�g24�g180�g

Tab.�A/1: General technical data

NoteValve terminal MPA−L with multi−pin plug connection:

� The maximum number of sub−bases that can be confi�gured corresponds to the number of addresses available(dependent on plug type, see Chapter� 1.3)

Valve terminal MPA−L with CPX terminal:

� Per valve position one or two solenoid coils and withinthe valve terminal MPA−L maximum 32 �solenoid coilscan be controlled via the CPX terminal.

Page 133: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

A. Technical appendix

A−5Festo P.BE−MPAL−EN en 1008NH

NoteFor wall mounting additional mountings may need to beinstalled (see Chapter� 2.3).

General information

Vibration and shock 4)

� Vibration

� Shock

� Continuous shock

Tested as per DIN/IEC�68/EN�60068 Par ts 2 − 6, With horizontal H−rail mounting: Severity level� 1For wall mounting: Severity level�2 2) 3)

Tested as per DIN/IEC68 / EN60068 parts 2 − 27 With horizontal H−rail mounting: Severity level� 1For wall mounting: Severity level�2 2) 3)

Tested as per DIN/IEC68 / EN60068 parts 2 − 29,For wall and H−rail mounting: Severity level 1

1) Load carrying ability specifications for vibration and shock of the CPX terminal can be found in the CPX system manual.

2) Valve terminal MPA−L with multi−pin plug connection:� up to a length of 200�mm of the v alve terminal without additional fastening� from 200�mm length of the v alve terminal every 130�mm additional mountings must be used

3) Valve terminal MPA−L with CPX terminal:� up to a length of 200�mm between the pneumatic interface and the right−hand end plate, withoutadditional mounting

� from a length of 200�mm between pneumatic interface and right−hand end plate every 130�mm additional mountings must be used

4) See following table for explanations of the severity levels.

Tab.�A/2: Load carrying ability for vibration and shock

Severity level Vibration Shock Continuous shock

1 0.15�mm Amplitude at 10�...�58 Hz; 2 g acceleration at 58�...�150 Hz

±15�g at 11�ms duration; 5 shocks in each direction

±15�g at 6�ms duration; 1000 shocks in eachdirection

2 0.35�mm Amplitude at 10�...�60 Hz; 5�g acceleration at 60�...�150�Hz

±30 g for 11�ms duration;5 shocks in each direction

Tab.�A/3: Values for vibration and shock as per DIN/IEC�68

Page 134: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

A. Technical appendix

A−6 Festo P.BE−MPAL−EN en 1008NH

Pneumatic components

Medium Compressed air, filtered (< 40 μm), lubricated(oil: VG 32) or unlubricated/vacuum, inert gases

Design Valve sub−bases with piston spool valves

Operating pressure/pilot control

Valves:� with internal pilot air supply

(branched from connection (1) ):� All valve plates on the connection (1):

� with external pilot air supply:� Valve location Ident. codes B, E, G, J and M on� connection (1):

� Valve location − Ident. codes DS, HS, KS and � NS on connection (1):

� Valve location Ident. code W at connection (2):

� Valve location Ident. code X at connection (4):

� Valve location Ident. codes D, H, i, K and N at � connection (1):

All valve plates on connection (12/14):

Pressure range

3 ... 8 bars

−0.9 ... 10 bar

−0.9 ... 8 bar

−0.9 ... 10 bar

−0.9 ... 10 bar

3 ... 10 bars

see relevant diagrams

Manual override Detenting or non−detenting

Tab.�A/4: Medium and pressure range

Page 135: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

A. Technical appendix

A−7Festo P.BE−MPAL−EN en 1008NH

1 Pressure of theexternal pilot airsupply at pilotconnection(12/14) p2 [bar]

2 Work range forvalves withexternal pilot airsupply

3 Operatingpressure at port (1) p1 [bar]

1

3

2

Fig.�A/1: Diagram: Required pilot pressure related to the operating pressure with exter�nal pilot air supply and use of valve plates with Ident. codes D, H, I, K and N

1 Pressure of theexternal pilot airsupply at pilotconnection(12/14) p2 [bar]

2 Work range forvalves withexternal pilot airsupply

3 Operatingpressure at port (1) p1 [bar]

1

3

2

Fig.�A/2: Diagram: Required pilot pressure relative to operating pressure with externalpilot air supply and using valve sub−bases with Ident. codes DS, HS, KS and NS

Page 136: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

A. Technical appendix

A−8 Festo P.BE−MPAL−EN en 1008NH

1 Pressure of theexternal pilot airsupply at pilotconnection(12/14) p2 [bar]

2 Work range forvalves withexternal pilot airsupply

3 Operatingpressure at port(1) p1 [bar]

1

3

2

Fig.�A/3: Diagram: Required pilot pressure related to the operating pressure with exter�nal pilot air and use of valve plates with Ident. codes B, E, G, J, M, W and X

Page 137: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

A. Technical appendix

A−9Festo P.BE−MPAL−EN en 1008NH

NoteThe fittings of the pneumatic ports cause a reduction in thenominal flow rate of the valves.

Pneumatic components MPA1

I.C.1) Valve Standard nominal flow rates [l/min], with QSPKG−10−6 cartridge

1 } 2 or 1 } 4 2)

2 } 3/5 or 4 } 3/5 2)

D, DSIN, NSK, KSH, HSX, WM, JBGE

2x2/2−way2x2/2−way2 x 3/2−way2 x 3/2−way2 x 3/2−way1 x 3/2 way5/2−way5/3−way valve, pressurised5/3−way valve, closed5/3−way valve, exhausted

230260300230300255360

300 (220) 3)

320240

−260300310300295360270350

240 (200) 3)

Valve switching times in [ms](Measuring method 0 −10% as per FN 942032)

On/changeover Off

D, IDSN, K, HHS, KS, NSX, WMJB, G, E

2x2/2−way2x2/2−way2 x 3/2−way2 x 3/2−way1 x 3/2 way5/2−way, monostable5/2−way double pilot valve5/3−way valves

101410141010

10/1510

201620162020−35

1) I.C. = Identificationcode of the valve sub−base2) Flow direction 1 } 4 or 4 } 3/5 not with valves having Ident. codes I, W and X.3) Values for the mid−position are quoted in brackets

Tab.�A/5: Nominal flow rates and valve switching times for MPA1

Page 138: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

A. Technical appendix

A−10 Festo P.BE−MPAL−EN en 1008NH

Electric components, general

Electromagnetic compatibility (EMC) 1)

� Interference emission� Immunity to interference 2)

See declaration of conformity è www.festo.com

Protection against electric shock(protection against direct and indirect contact asper IEC/DIN EN 60204−1)

By means of PELV power circuit(Protected Extra−Low Voltage)

1) The valve terminal MPA−L is intended for industrial usage. For residential use, measures may need to be taken to suppress interference.

2) The maximum signal cable length with valve terminal MPA−L with multi−pin plug connection is 10�m.

Tab.�A/6: Technical specifications for the electric components, general

Electric components, valve terminal MPA−L with multi−pin plug connection

Power supply� Nominal voltage DC 24� V ±10%

Current consumption at the sub−D multi−pinconnection per pin (for each solenoid coil) at 24 V � Nominal pick−up current/duration� Nominal current with current reduction

50�mA/20�ms10�mA

Tab.�A/7: Technical specifications on electric components, valve terminal MPA−L withmulti−pin plug connection

Page 139: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

A. Technical appendix

A−11Festo P.BE−MPAL−EN en 1008NH

Electric components, valve terminal MPA−L with CPX terminal

Electronic module VMPA...−FB−...Operating voltage supply for electronic compo�nents (VEL/SEN):� Nominal voltage� Max. intrinsic current consumption at 24 V

(internal electronics, all outputs logic 0)

DC 24� V ±10%13�mA

Load voltage supply for valves (VVAL)� Nominal voltage� Max. intrinsic current consumption at 24 V

(internal electronics, without valves)� Diagnostic message undervoltage VVAL, load

voltage outside function range

DC 24� V ±10%35�mA

� 17.7� V

Maximum current consumption per solenoidcoil at load voltage VVAL at 24 V� Nominal pick−up current/duration� Nominal current with current reduction

50�mA/20�ms10�mA

Tab.�A/8: Technical specifications on electric components, valve terminal MPA−L with CPX terminal

Page 140: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

A. Technical appendix

A−12 Festo P.BE−MPAL−EN en 1008NH

A.2 Festo accessories

The complete range of accessories can be found in the FestoCatalogue (see www.festo.com\catalogue).

Page 141: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

Supplementary overview of components

B−1Festo P.BE−MPAL−EN en 1008NH

Appendix B

Page 142: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

B. Supplementary overview of components

B−2 Festo P.BE−MPAL−EN en 1008NH

Contents

B. Supplementary overview of components B−1 . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.1 Overview of valve position components B−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 143: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

B. Supplementary overview of components

B−3Festo P.BE−MPAL−EN en 1008NH

B.1 Overview of valve position components

If the designations of the connections and control elementson the valve terminal differ from the logical designation of thecircuit symbols, the designations of the connections and con�trol elements are specified additionally in the circuit symbolsin brackets.

2/2−way valves

82/8412/14

4 2

1

14 12

ID code: DFunction:� Two monostable 2/2−way valves, normally

closed� Pneumatic spring return

82/8412/14

4 2

1

14 12

ID code: DSFunction:� Two monostable 2/2−way valves, normally

closed� Mechanical spring return

Page 144: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

B. Supplementary overview of components

B−4 Festo P.BE−MPAL−EN en 1008NH

2/2−way valves

82/8412/14

4 2

1

14 12

5

ID code: I, Function: 1)

� Two monostable 2/2−way valves, both valves normally closed, valve on controlside 14 reversible

� Pneumatic spring return� With dual−pressure operation:

� Supply operating pressure via connection 1� Operating pressure can be separately supplied at connection (3/5).

� Solenoid coil 14 switches the operating pressure from connection (5) to connection (4)

� Solenoid coil 12 switches the operating pressure from connection (1) to connection (2)

� With vacuum operation:� Feed operating pressure via connection (1)� Feed vacuum via connection (5)� Solenoid coil 14 switches the vacuum to connection (4)

� At connection 4 or in tubing (4) a filter is provided, so that no dirt can enter the valve.

� Solenoid coil 12 switches the operating pressure to connection (2) (e.g. for an ejector pulse in vacuum operation)

� Establish a connection using a T−piece for an ejector pulse between connections (2),(4)and the vacuum generator

1)Note: If this 2/2−way valve (Ident. code I) is also operated with other valves on the MPA−L valve terminal, then this 2/2−way valve must be operated in a separate pressure zone with a separate exhaust air channel (5).

Tab.�B/1: 2/2−way valves

Page 145: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

B. Supplementary overview of components

B−5Festo P.BE−MPAL−EN en 1008NH

3/2−way valves

82/8412/1435

4

1014

2

1

(12)

ID code: HFunction:� On control side 14, one monostable 3/2−way

valve (normally closed)� On control side 12, one monostable 3/2−way

valve (normally open)� Pneumatic spring return

82/8412/1435

4

1014

2

1

(12)

ID code: HSFunction:� On control side 14, one monostable 3/2−way

valve (normally closed)� On control side 12, one monostable 3/2−way

valve (normally open)� Mechanical spring return

82/8412/1435

4

14

2

1

12

ID code: KFunction:� Two monostable 3/2−way valves, normally

closed� Pneumatic spring return

82/8412/1435

4

14

2

1

12

ID code: KSFunction:� Two monostable 3/2−way valves, normally

closed� Mechanical spring return

Page 146: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

B. Supplementary overview of components

B−6 Festo P.BE−MPAL−EN en 1008NH

3/2−way valves

82/8412/1435

4

(14)

2

1

(12)10 10

ID code: NFunction:� Two monostable 3/2−way valves, normally

open.� Pneumatic spring return

82/8412/1435

4

(14)

2

1

(12)10 10

ID code: NSFunction:� Two monostable 3/2−way valves, normally

open.� Mechanical spring return

(82/84)(12/14)32

4(14)

14 84

20

ID code: WFunction:� 1x monostable 3/2−way valve, normally open,

external compressed air supply� Pneumatic spring return

(82/84)(12/14)3

2

4

(14)

14 84

42

ID code: XFunction:� 1x monostable 3/2−way valve, normally

closed, external compressed air supply� Pneumatic spring return

Tab.�B/2: 3/2−way valves

Page 147: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

B. Supplementary overview of components

B−7Festo P.BE−MPAL−EN en 1008NH

5/2−way valves

(12/14)35

4

14

14

2

1

12

ID code: JFunction:� A bistable 5/2−way valve

(12/14)35

4

14

14

2

1

ID code: MFunction:� One monostable 5/2−way valve� Pneumatic spring return

Tab.�B/3: 5/2−way valves

Page 148: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

B. Supplementary overview of components

B−8 Festo P.BE−MPAL−EN en 1008NH

5/3−way valves

(82/84)(12/14)5 3

1

4 2

1214

14 84 82 12

ID code: BFunction:� 5/3−way valve� Open in mid−position

(82/84)(12/14)5 3

1

4 2

1214

14 84 82 12

ID code: EFunction:� 5/3−way valve� Mid−position exhausted

(82/84)(12/14)5 3

1

4 2

1214

14 84 82 12

ID code: GFunction:� 5/3−way valve� Closed in mid−position

Tab.�B/4: 5/3−way valves

Note� In a currentless state 5/3−way valves assume the mid−position by means of spring force.

� If both solenoid coils on 5/3−way valves are energisedsimultaneously, the valve remains in the previousswitching position.

Page 149: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

B. Supplementary overview of components

B−9Festo P.BE−MPAL−EN en 1008NH

Pressure regulator plates

24

14 5 1 3 12

Pressure regulator plate for port 1 (Proportionalcontroller)ID code: PF or PAFunction:� Regulates the operating pressure in duct 1

upstream of the directional control valve

24

14 5 1 3 12

Pressure regulator plate for port 2 (B controller)ID code: PH or PCFunction:� Regulates the operating pressure in channel 2

after the directional control valve.

24

14 5 1 3 12

Pressure regulator plate for port 4 (A controller)ID code: PG or PBFunction:� Regulates the operating pressure in channel 4

after the directional control valve.

Tab.�B/5: Pressure regulator plates for regulating outputs 1, 2 and 4

Page 150: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

B. Supplementary overview of components

B−10 Festo P.BE−MPAL−EN en 1008NH

Page 151: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

Index

C−1Festo P.BE−MPAL−EN en 1008NH

Appendix C

Page 152: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

C. Index

C−2 Festo P.BE−MPAL−EN en 1008NH

Contents

C. Index C−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 153: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

C. Index

C−3Festo P.BE−MPAL−EN en 1008NH

Index

A

Abbreviations, (product−specific) XI . . . . . . . . . . . . . . . . . . .

Accessories A−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Address assignmentElectronics module 3−24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . Example 3−26 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Addresses, Valve terminal with CPX terminalConfiguration 3−29 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Rules for setting 3−30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Addresses, Valve terminal with multi−pin plug connection 1−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Air humidity, permitted A−3 . . . . . . . . . . . . . . . . . . . . . . . . . . .

Approvals VII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Avoidance of back pressure 3−7 . . . . . . . . . . . . . . . . . . . . . . .

B

Blanking plate 1−4 , 1−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dismantling/mounting 5−5 . . . . . . . . . . . . . . . . . . . . . . . . . .

C

CE marking VII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Clean, Flat plate silencer 5−4 . . . . . . . . . . . . . . . . . . . . . . . . . .

Common tubing 3−20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

ComponentsMaterials A−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Weights A−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Compressed air, Requirements A−6 . . . . . . . . . . . . . . . . . . . . .

Control elements, pneumatic 1−22 . . . . . . . . . . . . . . . . . . . . .

Page 154: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

C. Index

C−4 Festo P.BE−MPAL−EN en 1008NH

Cover cap for manual override 1−23 . . . . . . . . . . . . . . . . . . . . Dismantling/mounting 4−11 . . . . . . . . . . . . . . . . . . . . . . . . .

Cover types for multi−pin plug connection 1−7 . . . . . . . . . . . .

CPX terminalConnection via pneumatic interface 1−8 . . . . . . . . . . . . . . . Error messages on the pneumatic interface 3−29 . . . . . . . .

Current consumption A−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . .

D

DIN mounting rail 2−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Display and control elements 1−22 . . . . . . . . . . . . . . . . . . . . . Identification system 1−23 . . . . . . . . . . . . . . . . . . . . . . . . . . Manual override (MO) 1−23 . . . . . . . . . . . . . . . . . . . . . . . . . Pressure regulator 1−24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . Switching status displays for valves 1−25 . . . . . . . . . . . . . .

E

Electromagnetic compatibility A−10 . . . . . . . . . . . . . . . . . . . . .

Electronics module 3−24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dismantling/mounting 5−14 . . . . . . . . . . . . . . . . . . . . . . . . .

EMERGENCY−STOP 4−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

End plate, dismantling/mounting 5−11 . . . . . . . . . . . . . . . . . .

Error, Error LED/error messages 3−29 . . . . . . . . . . . . . . . . . . .

Exhaust 1−13 , 1−20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ducted 1−4 , 3−20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Optimisation 3−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Exhaust air, Ducted 3−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F

Flat plate silencer 1−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Clean or replace 5−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 155: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

C. Index

C−5Festo P.BE−MPAL−EN en 1008NH

H

H−rail 2−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Clamping unit 2−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Mounting/dismantling 2−4 . . . . . . . . . . . . . . . . . . . . . . . . . .

I

Identification system 1−23 . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Impairment of functions 4−13 . . . . . . . . . . . . . . . . . . . . . . . . .

Inscription label holder, Mounting/dismantling 2−13 . . . . . . .

Inscription labels 1−23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Intended use VII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

IP protection class A−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cover types 1−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

L

LEDPosition of the LEDs 1−25 . . . . . . . . . . . . . . . . . . . . . . . . . . . Switching status indicator of the solenoid coil 4−13 . . . . . .

Left−hand end plateCover type for multi−pin plug connection 1−7 . . . . . . . . . . . CPX terminal with pneumatic interface 1−8 . . . . . . . . . . . . . Multi−pin plug connection 1−5 . . . . . . . . . . . . . . . . . . . . . . .

Load voltage A−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Low−pressure operation 3−11 , 4−15 . . . . . . . . . . . . . . . . . . . . .

Page 156: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

C. Index

C−6 Festo P.BE−MPAL−EN en 1008NH

M

Manual override 1−22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Mounting/dismounting the cover cap 4−11 . . . . . . . . . . . . . Operating the non−detenting manual override 4−10 . . . . . . Operating the non−locking manual override 4−9 . . . . . . . . .

Materials A−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Medium, Requirements 3−3 , A−6 . . . . . . . . . . . . . . . . . . . . . . .

Mounting kit H−rail, 2−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Multi−pin plug connection 1−5 . . . . . . . . . . . . . . . . . . . . . . . . . Cover types 1−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ribbon cable 1−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sub−D 1−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terminal strip 1−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

N

Nominal flow rates A−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Non−return valve 3−20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Notes on the present description VIII . . . . . . . . . . . . . . . . . . .

O

OperationCompressed air preparation 3−3 . . . . . . . . . . . . . . . . . . . . . Error messages 3−29 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Operating modes 1−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Operating pressure A−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Main and additional power supply 1−10 . . . . . . . . . . . . . . .

Operating states 4−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Operating voltage A−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Optimisation, Flow rate 3−7 . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 157: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

C. Index

C−7Festo P.BE−MPAL−EN en 1008NH

P

Parametrisation, Error messages on the CPX terminal 3−29 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pictograms X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pilot air supply 1−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Branched internally/supplied externally 1−13 . . . . . . . . . . Conversion to internal/external pilot air 5−16 . . . . . . . . . . . Diagram A−7 , A−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pilot controlConversion to internal/external pilot air 5−16 . . . . . . . . . . . Diagram A−7 , A−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pressure range A−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Type of pilot control 3−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pneumatic interface 1−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connection and display components 3−28 . . . . . . . . . . . . . Error messages 3−29 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

PortsCode 3−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CPX terminal via pneumatic interface 1−8 . . . . . . . . . . . . . . Electric 1−21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pneumatic spring 1−20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Variable 3−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Power supplyLoad voltage supply for the valves A−11 . . . . . . . . . . . . . . . Operating voltage supply for the electronics A−11 . . . . . . .

Pressureregulator plate 1−16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . shut−off plate 1−16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pressure range A−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pressure regulator plate, Setting 3−10 . . . . . . . . . . . . . . . . . .

Pressure zones 1−13 , 3−8 , 4−15 , 5−18 . . . . . . . . . . . . . . . . . .

Page 158: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

C. Index

C−8 Festo P.BE−MPAL−EN en 1008NH

R

Renew, Flat plate silencer 5−4 . . . . . . . . . . . . . . . . . . . . . . . . .

Replace, Flat plate silencer 5−4 . . . . . . . . . . . . . . . . . . . . . . . .

Ribbon cable, multi−pin plug connection 1−6 . . . . . . . . . . . . .

Right−hand end platePilot air supply 1−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Selector plate 1−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Versions 1−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

S

Selector plate 1−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Separation of pressure zones 1−13 . . . . . . . . . . . . . . . . . . . . .

Service VIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Silencer 1−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Solenoid coil, Current consumption A−10 . . . . . . . . . . . . . . . .

Start−up pressurisation 4−5 . . . . . . . . . . . . . . . . . . . . . . . . . . .

Sub−base 1−4 , 1−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dismantling/mounting 5−11 . . . . . . . . . . . . . . . . . . . . . . . . .

Sub−D 1−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cover types 1−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SupplyMain and additional power supply 1−10 . . . . . . . . . . . . . . . With control air 1−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Supply plate, dismantling/mounting 5−11 . . . . . . . . . . . . . . .

Supply pressure, Internal/external pilot air supply 1−13 . . . .

Switching times A−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 159: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

C. Index

C−9Festo P.BE−MPAL−EN en 1008NH

T

Target group VIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Temperature range, Permitted A−3 . . . . . . . . . . . . . . . . . . . . .

Terminal strip, multi−pin plug connection 1−6 . . . . . . . . . . . . .

Text designations X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

The components of the valve terminalInscription labels/identification system 1−23 . . . . . . . . . . . Pressure regulator plate 1−16 . . . . . . . . . . . . . . . . . . . . . . . Sub−base 1−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Supply plate 1−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Valves 1−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Vertical stacking 1−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Tightening torques A−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Torques A−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Tubing connection 3−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Assembly 3−18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dismantling 3−19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

U

User instructions IX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 160: MPA−L valve terminal - Festo · Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34) multi−pin plug connection or for CPX−Terminal Vertical

C. Index

C−10 Festo P.BE−MPAL−EN en 1008NH

V

Vacuum operation 3−11 , 4−15 . . . . . . . . . . . . . . . . . . . . . . . . .

Valve terminalEarthing the terminal 3−22 . . . . . . . . . . . . . . . . . . . . . . . . . . With CPX terminal, Connection and display components 3−28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Supply plate 1−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Valves 1−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dismantling/mounting 5−5 . . . . . . . . . . . . . . . . . . . . . . . . . . Identification code (Ident. code) 1−9 . . . . . . . . . . . . . . . . . . Overview B−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Vertical stacking 1−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Components 1−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Label in the type code 1−16 . . . . . . . . . . . . . . . . . . . . . . . . . Pressure regulator plate 1−16 , 1−24 . . . . . . . . . . . . . . . . . .

Vibration and shock A−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

W

Wall mounting, Mounting/dismantling 2−9 . . . . . . . . . . . . . . .

Weights, Components A−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . .