METALITE PANEL SYSTEM - Dryvit · metalite ® panel system. ml 0.0.04. parapet detail. metal cap...

16
METALITE ® PANEL SYSTEM Prefabricated, Insulated, Metal Backed, Lightweight Exterior Wall Panels METALITE Installation Details DS112

Transcript of METALITE PANEL SYSTEM - Dryvit · metalite ® panel system. ml 0.0.04. parapet detail. metal cap...

Page 1: METALITE PANEL SYSTEM - Dryvit · metalite ® panel system. ml 0.0.04. parapet detail. metal cap flashing by others, see note 3 stiffener/connection bar metalite substrate dryvit

METALITE® PANEL SYSTEM Prefabricated, Insulated, Metal Backed, Lightweight Exterior Wall Panels

METALITE Installation Details

DS112

Page 2: METALITE PANEL SYSTEM - Dryvit · metalite ® panel system. ml 0.0.04. parapet detail. metal cap flashing by others, see note 3 stiffener/connection bar metalite substrate dryvit

Metalite® Panel System

TABLE OF CONTENTS

DETAIL NOTEPAGE

The architecture, engineering, and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this detail

and for the architecture, design, or engineering of any project. The

project design professional determines, in its sole discretion, whether

this detail or a functionally equivalent detail is best suited for the

project. Use of a functionally equivalent detail does not violate

Dryvit's warranty. This detail is subject to change without notice.

Contact Dryvit to ensure you have the most recent version.

METALITE PANEL ML 0.0.01 1

FOUNDATION DETAIL ML 0.0.02 2

HEAD/ SILL/ JAMB DETAIL ML 0.0.03 3

PARAPET DETAIL ML 0.0.04 4

WALL/ ROOF INTERSECTION ML 0.0.05 5

ROOF TERMINATION/ GRAVEL STOP ML 0.0.06 6

INSIDE CORNER ML 0.0.07 7

OUTSIDE CORNER ML 0.0.08 8

PANEL JOINTS ML 0.0.09 9

FASCIA PANEL ML 0.0.10 10

SCREEN WALL ML 0.0.11 11

BLIND PANEL ATTACHMENT OPTION ML 0.0.12 12

FASTENING PATTERN ML 0.0.13 13

COMPONENTS ML 0.0.14 14

DRYVIT MAKES NO REPRESENTATION REGARDING

CONFORMITY OF ITS SUGGESTIONS TO MODEL BUILDING

CODES, ENGINEERING CRITERIA, SPECIFIC APPLICATIONS,

OR PROJECT LOCATIONS. ALL COMPONENTS INDICATED IN

ILLUSTRATIONS, AS WELL AS OTHERS THAT MAY BE

REQUIRED FOR THE INTEGRITY OF THE SYSTEM SHALL BE

DESIGNED, DETAILED, AND ENGINEERED BY

REPRESENTATIVES OF THE ARCHITECT, OWNER, OR

CONTRACTOR TO BE IN CONFORMANCE WITH MODEL

CODES, ARCHITECTURAL, AND ENGINEERING

REQUIREMENTS PERTAINING TO SPECIFIC BUILDING

PROJECTS.

DRYVIT MAKES NO WARRANTY, EXPRESSED OR IMPLIED,

AS TO THE ARCHITECTURAL DESIGN, OR ENGINEERING, OF

PROJECTS UTILIZING DRYVIT SYSTEMS OR PRODUCTS.

THE LIABILITIES OF DRYVIT SHALL BE AS STATED IN THE

DRYVIT STANDARD WARRANTY. CONTACT DRYVIT FOR A

FULL AND COMPLETE COPY OF THIS WARRANTY.

©Dryvit Systems, Inc. 2017

©

Issued: 4/2017

Page 3: METALITE PANEL SYSTEM - Dryvit · metalite ® panel system. ml 0.0.04. parapet detail. metal cap flashing by others, see note 3 stiffener/connection bar metalite substrate dryvit

Metalite® Panel System

ML 0.0.01

Metalite Panel System

NOTE:

1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TO ABNORMALSTRESS, HIGH TRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER® MESH PRIOR TOSTANDARD OR STANDARD PLUSᵀᴹ MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

Dryvit Systems, Inc. 2017

Issued: 4/2017

The architecture, engineering, and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this detail

and for the architecture, design, or engineering of any project. The

project design professional determines, in its sole discretion, whether

this detail or a functionally equivalent detail is best suited for the

project. Use of a functionally equivalent detail does not violate

Dryvit's warranty. This detail is subject to change without notice.

Contact Dryvit to ensure you have the most recent version.

©©

DRYVIT BASE COAT

DRYVIT

REINFORCING MESH

EXPANDED

POLYSTYRENE

INSULATION BOARD

DRYVIT FINISH

METALITE SUBSTRATE

APPROVED-

METALITE FASTENER

J-CHANNEL CLOSURE

J-CHANNEL CLOSURE

APPROVED-

METALITE FASTENER

METALITE SUBSTRATE

DRYVIT BASE COAT

DRYVIT

REINFORCING MESH

EXPANDED

POLYSTYRENE

INSULATION BOARD

DRYVIT FINISH

METALITE SUBSTRATE

DRYVIT BASE COAT

DRYVIT

REINFORCING MESH

EXPANDED

POLYSTYRENE

INSULATION BOARD

DRYVIT FINISH

DRYVIT DEMANDIT SMOOTH

OR COLOR PRIME ON SURFACES

WHICH WILL RECEIVE SEALANT

DRYVIT DEMANDIT SMOOTH

OR COLOR PRIME ON SURFACES

WHICH WILL RECEIVE SEALANT

J-CHANNEL CLOSURE

TOP OF METALITE PANEL

(BOTTOM SIMILAR)

METALITE FASTENER

Page 4: METALITE PANEL SYSTEM - Dryvit · metalite ® panel system. ml 0.0.04. parapet detail. metal cap flashing by others, see note 3 stiffener/connection bar metalite substrate dryvit

Metalite® Panel System

METALITE SUBSTRATE

ML 0.0.02

Foundation Details

DRYVIT METALITE PANEL

DRYVIT COMPATIBLE SEALANT

AND CLOSED CELL BACKER

ROD BY OTHERS

DRYVIT COMPATIBLE SEALANT

AND CLOSED CELL BACKER

ROD BY OTHERS

STIFFENER/CONNECTOR BAR

ALTERNATE

3/4" MIN

(19 mm)

CONTINUOUS FLASHING AS

REQUIRED BY OTHERS

METALITE SUBSTRATE

DRYVIT METALITE PANEL

NOTE:

1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TO ABNORMALSTRESS, HIGH TRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER® MESH PRIOR TOSTANDARD OR STANDARD PLUSᵀᴹ MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

2. WIPE END OF METALITE SUBSTRATE WITH DEGREASINGAGENT PRIOR TO BASE COAT APPLICATION.

The architecture, engineering, and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this detail

and for the architecture, design, or engineering of any project. The

project design professional determines, in its sole discretion, whether

this detail or a functionally equivalent detail is best suited for the

project. Use of a functionally equivalent detail does not violate

Dryvit's warranty. This detail is subject to change without notice.

Contact Dryvit to ensure you have the most recent version.

DRYVIT DEMANDIR SMOOTH

OR COLOR PRIME ON SURFACES

WHICH WILL RECEIVE SEALANT

Dryvit Systems, Inc. 2017

Issued: 4/2017

©©

Page 5: METALITE PANEL SYSTEM - Dryvit · metalite ® panel system. ml 0.0.04. parapet detail. metal cap flashing by others, see note 3 stiffener/connection bar metalite substrate dryvit

Metalite® Panel System

ML 0.0.03

Head / Sill / Jamb Detail

NOTE:

1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TO ABNORMALSTRESS, HIGH TRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER® MESH PRIOR TOSTANDARD OR STANDARD PLUSᵀᴹ MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

2. WIPE END OF METALITE SUBSTRATE WITH DEGREASINGAGENT PRIOR TO BASE COAT APPLICATION.

3. METALITE IS NOT INTENDED TO CARRY ANY LOADS FORWINDOWS, DOORS, EQUIPMENT, ETC.

HEAD

JAMB SILL

METALITE SUBSTRATE

DRYVIT METALITE PANEL

3/4" MIN

(19 mm)

DRYVIT COMPATIBLE SEALANT

AND CLOSED CELL BACKER

ROD BY OTHERS

METALITE SUBSTRATE

DRYVIT METALITE PANEL

3/4" MIN

(19 mm)

DRYVIT COMPATIBLE

SEALANT AND CLOSED

CELL BACKER

ROD BY OTHERS

CONTINUOUS FLASHING

AS REQUIRED BY OTHERS

J-CHANNEL CLOSURE

The architecture, engineering, and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this detail

and for the architecture, design, or engineering of any project. The

project design professional determines, in its sole discretion, whether

this detail or a functionally equivalent detail is best suited for the

project. Use of a functionally equivalent detail does not violate

Dryvit's warranty. This detail is subject to change without notice.

Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. 2017

Issued: 4/2017

©©

DRYVIT COMPATIBLE SEALANT

AND CLOSED CELL BACKER

ROD BY OTHERS

3/4" MIN

(19 mm)

CONTINUOUS FLASHING AS

REQUIRED BY OTHERS

METALITE SUBSTRATE

DRYVIT METALITE PANEL

BUILDING GIRT

STIFFENER/CONNECTION BAR

J-CHANNEL CLOSURE

Page 6: METALITE PANEL SYSTEM - Dryvit · metalite ® panel system. ml 0.0.04. parapet detail. metal cap flashing by others, see note 3 stiffener/connection bar metalite substrate dryvit

Metalite® Panel System

ML 0.0.04

Parapet Detail

METAL CAP FLASHING

BY OTHERS, SEE NOTE 3

STIFFENER/CONNECTION BAR

METALITE SUBSTRATE

DRYVIT COMPATIBLE SEALANT

BY OTHERS

DRYVIT METALITE PANEL

2 1/2" MIN

(64 mm)

NOTE:

1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TO ABNORMALSTRESS, HIGH TRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER® MESH PRIOR TOSTANDARD OR STANDARD PLUSᵀᴹ MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

2. WIPE END OF METALITE SUBSTRATE WITH DEGREASINGAGENT PRIOR TO BASE COAT APPLICATION.

3. ROOF ASSEMBLY, SHEATHING AND CAP FLASHING AREINSTALLED IN THE FIELD AND NOT COMPONENTS OF THEPANEL SYSTEM.

The architecture, engineering, and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this detail

and for the architecture, design, or engineering of any project. The

project design professional determines, in its sole discretion, whether

this detail or a functionally equivalent detail is best suited for the

project. Use of a functionally equivalent detail does not violate

Dryvit's warranty. This detail is subject to change without notice.

Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. 2017

Issued: 4/2017

©©

Page 7: METALITE PANEL SYSTEM - Dryvit · metalite ® panel system. ml 0.0.04. parapet detail. metal cap flashing by others, see note 3 stiffener/connection bar metalite substrate dryvit

Metalite® Panel System

ML 0.0.05

Wall / Roof Intersection

NOTE:

1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TO ABNORMALSTRESS, HIGH TRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER® MESH PRIOR TOSTANDARD OR STANDARD PLUSᵀᴹ MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

2. WIPE END OF METALITE SUBSTRATE WITH DEGREASINGAGENT PRIOR TO BASE COAT APPLICATION.

The architecture, engineering, and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this detail

and for the architecture, design, or engineering of any project. The

project design professional determines, in its sole discretion, whether

this detail or a functionally equivalent detail is best suited for the

project. Use of a functionally equivalent detail does not violate

Dryvit's warranty. This detail is subject to change without notice.

Contact Dryvit to ensure you have the most recent version.

STIFFENER/CONNECTION BAR

METALITE SUBSTRATE

DRYVIT COMPATIBLE SEALANT

BY OTHERS

DRYVIT METALITE PANEL

2 1/2" MIN

(64 mm)

CONTINUOUS FLASHING AS

REQUIRED BY OTHERS

Dryvit Systems, Inc. 2017

Issued: 4/2017

©©

Page 8: METALITE PANEL SYSTEM - Dryvit · metalite ® panel system. ml 0.0.04. parapet detail. metal cap flashing by others, see note 3 stiffener/connection bar metalite substrate dryvit

Metalite® Panel System

ML 0.0.06

Roof Termination / Gravel Stop

METAL CAP FLASHING

BY OTHERS, SEE NOTE 3

STIFFENER/CONNECTION BAR

METALITE SUBSTRATE

DRYVIT COMPATIBLE SEALANT

BY OTHERS

DRYVIT METALITE PANEL

2 1/2" MIN

(64 mm)

J-CHANNEL CLOSURE

NOTE:

1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TO ABNORMALSTRESS, HIGH TRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER® MESH PRIOR TOSTANDARD OR STANDARD PLUSᵀᴹ MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

2. WIPE END OF METALITE SUBSTRATE WITH DEGREASINGAGENT PRIOR TO BASE COAT APPLICATION.

3. ROOF ASSEMBLY, SHEATHING AND CAP FLASHING AREINSTALLED IN THE FIELD AND NOT COMPONENTS OF THEPANEL SYSTEM.

The architecture, engineering, and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this detail

and for the architecture, design, or engineering of any project. The

project design professional determines, in its sole discretion, whether

this detail or a functionally equivalent detail is best suited for the

project. Use of a functionally equivalent detail does not violate

Dryvit's warranty. This detail is subject to change without notice.

Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. 2017

Issued: 4/2017

©©

Page 9: METALITE PANEL SYSTEM - Dryvit · metalite ® panel system. ml 0.0.04. parapet detail. metal cap flashing by others, see note 3 stiffener/connection bar metalite substrate dryvit

Metalite® Panel System

ML 0.0.07

Inside Corner

DRYVIT COMPATIBLE SEALANT

BY OTHERS

DRYVIT METALITE PANEL

3/4" MIN

(19 mm)

DRYVIT DEMANDIT® SMOOTH OR

COLOR PRIMEᵀᴹAPPLIED TO

SURFACES WHICH WILL

RECEIVE SEALANT

DRYVIT METALITE PANEL

METALITE SUBSTRATE

METALITE SUBSTRATE

NOTE:

1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TO ABNORMALSTRESS, HIGH TRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER® MESH PRIOR TOSTANDARD OR STANDARD PLUSᵀᴹ MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

2. WIPE END OF METALITE SUBSTRATE WITH DEGREASINGAGENT PRIOR TO BASE COAT APPLICATION.

3. J-CHANNEL CLOSURE AT TOP AND BOTTOM OF PANELS.

The architecture, engineering, and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this detail

and for the architecture, design, or engineering of any project. The

project design professional determines, in its sole discretion, whether

this detail or a functionally equivalent detail is best suited for the

project. Use of a functionally equivalent detail does not violate

Dryvit's warranty. This detail is subject to change without notice.

Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. 2017

Issued: 4/2017

©©

PRE-ENGINEERED CORNER

AutoCAD SHX Text
SMOOTH OR OR
Page 10: METALITE PANEL SYSTEM - Dryvit · metalite ® panel system. ml 0.0.04. parapet detail. metal cap flashing by others, see note 3 stiffener/connection bar metalite substrate dryvit

Metalite® Panel System

ML 0.0.08

Outside Corners

NOTE:

1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TO ABNORMALSTRESS, HIGH TRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER® MESH PRIOR TOSTANDARD OR STANDARD PLUSᵀᴹ MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

2. WIPE END OF METALITE SUBSTRATE WITH DEGREASINGAGENT PRIOR TO BASE COAT APPLICATION.

3. J-CHANNEL CLOSURE AT TOP AND BOTTOM OF PANELS.

The architecture, engineering, and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this detail

and for the architecture, design, or engineering of any project. The

project design professional determines, in its sole discretion, whether

this detail or a functionally equivalent detail is best suited for the

project. Use of a functionally equivalent detail does not violate

Dryvit's warranty. This detail is subject to change without notice.

Contact Dryvit to ensure you have the most recent version.

DRYVIT METALITE PANEL

3/4" MIN

(19 mm)

DRYVIT DEMANDIT® SMOOTH OR

COLOR PRIMEᵀᴹ APPLIED TO SURFACES

WHICH WILL RECEIVE SEALANT

METALITE SUBSTRATE

DRYVIT COMPATIBLE SEALANT

BY OTHERS

DRYVIT METALITE PANEL

METALITE SUBSTRATE

Dryvit Systems, Inc. 2017

Issued: 4/2017

©©

PRE-ENGINEERED CORNER

AutoCAD SHX Text
SMOOTH OR
Page 11: METALITE PANEL SYSTEM - Dryvit · metalite ® panel system. ml 0.0.04. parapet detail. metal cap flashing by others, see note 3 stiffener/connection bar metalite substrate dryvit

Metalite® Panel System

ML 0.0.09

Panel Joints

SQUARE JOINT

OVERLAPPING JOINT

NOTE:

1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TO ABNORMALSTRESS, HIGH TRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER® MESH PRIOR TOSTANDARD OR STANDARD PLUSᵀᴹ MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

2. WIPE END OF METALITE SUBSTRATE WITH DEGREASINGAGENT PRIOR TO BASE COAT APPLICATION.

3. J-CHANNEL AT DECK PERIMETER TO CREATE FRAME.

The architecture, engineering, and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this detail

and for the architecture, design, or engineering of any project. The

project design professional determines, in its sole discretion, whether

this detail or a functionally equivalent detail is best suited for the

project. Use of a functionally equivalent detail does not violate

Dryvit's warranty. This detail is subject to change without notice.

Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. 2017

Issued: 4/2017

©©

3/4" MIN

(19 mm)

DRYVIT METALITE PANEL

METALITE SUBSTRATE

METALITE SUBSTRATE

DRYVIT DEMANDIT® SMOOTH OR

COLOR PRIMEᵀᴹ APPLIED TO SURFACES

WHICH WILL RECEIVE SEALANT

DRYVIT COMPATIBLE SEALANT

BY OTHERS

AutoCAD SHX Text
SMOOTH OR OR
Page 12: METALITE PANEL SYSTEM - Dryvit · metalite ® panel system. ml 0.0.04. parapet detail. metal cap flashing by others, see note 3 stiffener/connection bar metalite substrate dryvit

Metalite® Panel System

ML 0.0.10

Fascia Panel

NOTE:

1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TO ABNORMALSTRESS, HIGH TRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER® MESH PRIOR TOSTANDARD OR STANDARD PLUSᵀᴹ MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

2. WIPE END OF METALITE SUBSTRATE WITH DEGREASINGAGENT PRIOR TO BASE COAT APPLICATION.

3. ROOF ASSEMBLY, SHEATHING, AND CAP FLASHING AREINSTALLED IN THE FIELD AND NOT COMPONENTS OF THEPANEL SYSTEM.

The architecture, engineering, and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this detail

and for the architecture, design, or engineering of any project. The

project design professional determines, in its sole discretion, whether

this detail or a functionally equivalent detail is best suited for the

project. Use of a functionally equivalent detail does not violate

Dryvit's warranty. This detail is subject to change without notice.

Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. 2017

Issued: 4/2017

©©

METAL CAP FLASHING

BY OTHERS, SEE NOTE 3

STIFFENER/CONNECTION BAR

METALITE SUBSTRATE

DRYVIT COMPATIBLE SEALANT

BY OTHERS

DRYVIT METALITE PANEL

2 1/2" MIN

(64 mm)

CONNECTING SOFFIT

PROVIDE BRACE TO

BUILDING STRUCTURE

DRYVIT COMPATIBLE SEALANT

BY OTHERS

J-CHANNEL CLOSURE

DRYVIT DEMANDIR SMOOTH

OR COLOR PRIME ON SURFACES

WHICH WILL RECEIVE SEALANT

Page 13: METALITE PANEL SYSTEM - Dryvit · metalite ® panel system. ml 0.0.04. parapet detail. metal cap flashing by others, see note 3 stiffener/connection bar metalite substrate dryvit

Metalite® Panel System

ML 0.0.11

Screen Wall

METAL CAP FLASHING

BY OTHERS

DRYVIT COMPATIBLE SEALANT

BY OTHERS

METALITE SUBSTRATE

2 1/2" MIN

(64 mm)

STEEL SUPPORT

BY OTHERS

J-CHANNEL CLOSURE

DRYVIT METALITE PANEL

STIFFENER/

CONNECTOR BAR SPACING

AND TYPE BY OTHERS

NOTE:

1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TO ABNORMALSTRESS, HIGH TRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER® MESH PRIOR TOSTANDARD OR STANDARD PLUSᵀᴹ MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

2. WIPE END OF METALITE SUBSTRATE WITH DEGREASINGAGENT PRIOR TO BASE COAT APPLICATION.

3. DRILL BOTTOM J-CHANNEL TO ALLOW FOR DRAINAGE,PAINT HOLES WITH RUST INHIBITING PAINT.

The architecture, engineering, and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this detail

and for the architecture, design, or engineering of any project. The

project design professional determines, in its sole discretion, whether

this detail or a functionally equivalent detail is best suited for the

project. Use of a functionally equivalent detail does not violate

Dryvit's warranty. This detail is subject to change without notice.

Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. 2017

Issued: 4/2017

©©

Page 14: METALITE PANEL SYSTEM - Dryvit · metalite ® panel system. ml 0.0.04. parapet detail. metal cap flashing by others, see note 3 stiffener/connection bar metalite substrate dryvit

Metalite® Panel System

ML 0.0.12

The architecture, engineering, and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this detail

and for the architecture, design, or engineering of any project. The

project design professional determines, in its sole discretion, whether

this detail or a functionally equivalent detail is best suited for the

project. Use of a functionally equivalent detail does not violate

Dryvit's warranty. This detail is subject to change without notice.

Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. 2017

Issued: 4/2017

©©

Blind Panel Attachment Option

NOTE:

1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TO ABNORMALSTRESS, HIGH TRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER® MESH PRIOR TOSTANDARD OR STANDARD PLUSᵀᴹ MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

2. WIPE END OF METALITE SUBSTRATE WITH DEGREASINGAGENT PRIOR TO BASE COAT APPLICATION.

3. J-CHANNEL AT DECK PERIMETER TO CREATE FRAME.

METALITE SUBSTRATE

DRYVIT METALITE PANEL

DRYVIT COMPATIBLE SEALANT

AND CLOSED CELL BACKER

ROD BY OTHERS

EXISTING CONCRETE

SHEAR WALL

GAUGE METAL CLIP

AND Z-CLIP

ANGLE CONNECTOR

ANGLE CONNECTOR

GAUGE METAL CLIP

AND Z-CLIP

DRYVIT METALITE PANEL

DRYVIT COMPATIBLE SEALANT

AND CLOSED CELL BACKER

ROD BY OTHERS

EXISTING CONCRETE

SHEAR WALL

METALITE SUBSTRATE

Page 15: METALITE PANEL SYSTEM - Dryvit · metalite ® panel system. ml 0.0.04. parapet detail. metal cap flashing by others, see note 3 stiffener/connection bar metalite substrate dryvit

Metalite® Panel System

ML 0.0.13

Typical Fastening Pattern

EPS

METALITE SUBSTRATE

APPROVED MECHANICAL

FASTENER, BY OTHERS

(SEE NOTE 4)

12" MIN

(305 mm)

12" MIN

(305 mm)

METALITE SUBSTRATE

APPROVED MECHANICAL

FASTENER, BY OTHERS

(SEE NOTE 4)

DRYVIT METALITE PANEL

NOTE:

1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TO ABNORMALSTRESS, HIGH TRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER® MESH PRIOR TOSTANDARD OR STANDARD PLUSᵀᴹ MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

2. OFFSET VERTICAL EPS JOINTS FOR PANEL WIDERTHAN 4'-0".

3. WIPE END OF METALITE SUBSTRATE WITH DEGREASINGAGENT PRIOR TO BASE COAT APPLICATION.

4. MECHANICAL FASTENERS SHALL BE DESIGNED FOR THESPECIFIC PROJECT LOADS AND CONDITIONS BY THE PANELFABRICATOR OR ERECTOR (SEE DS133).

The architecture, engineering, and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this detail

and for the architecture, design, or engineering of any project. The

project design professional determines, in its sole discretion, whether

this detail or a functionally equivalent detail is best suited for the

project. Use of a functionally equivalent detail does not violate

Dryvit's warranty. This detail is subject to change without notice.

Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. 2017

Issued: 4/2017

©©

Page 16: METALITE PANEL SYSTEM - Dryvit · metalite ® panel system. ml 0.0.04. parapet detail. metal cap flashing by others, see note 3 stiffener/connection bar metalite substrate dryvit

Metalite® Panel System

ML 0.0.14

Components

©Dryvit Systems, Inc. 2017

©

The architecture, engineering, and design of the project using the

Dryvit products is the responsibility of the project's design

professional. All systems must comply with local building codes and

standards. This detail is for general information and guidance only

and Dryvit specifically disclaims any liability for the use of this detail

and for the architecture, design, or engineering of any project. The

project design professional determines, in its sole discretion, whether

this detail or a functionally equivalent detail is best suited for the

project. Use of a functionally equivalent detail does not violate

Dryvit's warranty. This detail is subject to change without notice.

Contact Dryvit to ensure you have the most recent version.

J-CHANNEL

3"x1.5"x1.5"x.0598" CHANNEL

(76mm x 38mm x 38mm x 1.5mm)

STIFFENER/CONNECTOR BAR

3"x3"x.0598" ANGLE

(76mm x 76mm x 1.5mm)

METALITE SUBSTRATE

12.75"

(324 mm)

10.5"

(267 mm)

1.5"

(38 mm)

.0299" THICK

(0.75 mm)

Issued: 4/2017

NOTE:

1. LOAD/ SPAN VALUES ARE AVAILABLE FOR TECH 21CUSTOMERS.