Limited Service Electric Fire Pump Controller...GPL 1. ViZiTouch V2 operator interface 2. Exterior...

4
Standard Features ViZiTouch V2 operator interface NEMA 2 enclosure Available in single phase Pressure and event recorder Voltage and amperage display Rotary type main disconnect switch complete with door interlock Surge arrestor Wall mounting lugs Start and stop pushbuttons Circuit breaker (150% - 250% of FLC) Phase reversal indication Remote start / deluge valve start provision Pressure transducer Alarm contacts for remote indication Emergency manual start handle Available with automatic power transfer switch Model GPL Limited Service Electric Fire Pump Controller LISTEN DEVELOP LEAD 2018-2019 Model GPL Limited Service Electric Fire Pump Controller Model GPL+ GLU Limited Service Electric Fire Pump Controller with Automatic Power Transfer Switch Limitations Across the line starting only Horsepower rating of maximum 30hp Can only be installed where acceptable by the authority having jurisdiction Not accepted in FM insured property

Transcript of Limited Service Electric Fire Pump Controller...GPL 1. ViZiTouch V2 operator interface 2. Exterior...

Page 1: Limited Service Electric Fire Pump Controller...GPL 1. ViZiTouch V2 operator interface 2. Exterior USB Port (Interior USB port also supplied) 3. Emergency start 2 4 3 5 1 7 6 4. Key

Tornatech Inc, Montreal, Quebec, Canada

LISTEN DEVELOP LEAD

Standard Features• ViZiTouch V2 operator interface• NEMA 2 enclosure• Available in single phase• Pressure and event recorder• Voltage and amperage display• Rotary type main disconnect switch complete with door interlock• Surge arrestor• Wall mounting lugs• Start and stop pushbuttons• Circuit breaker (150% - 250% of FLC)• Phase reversal indication• Remote start / deluge valve start provision• Pressure transducer• Alarm contacts for remote indication• Emergency manual start handle• Available with automatic power transfer switch

Model GPLLimited Service Electric Fire Pump Controller

LISTEN DEVELOP LEAD

2018-2019

Model GPL Limited ServiceElectric Fire Pump Controller

Model GPL+ GLU Limited ServiceElectric Fire Pump Controller

with Automatic Power Transfer Switch

Limitations• Across the line starting only• Horsepower rating of maximum 30hp• Can only be installed where acceptable by the authority having jurisdiction• Not accepted in FM insured property

Page 2: Limited Service Electric Fire Pump Controller...GPL 1. ViZiTouch V2 operator interface 2. Exterior USB Port (Interior USB port also supplied) 3. Emergency start 2 4 3 5 1 7 6 4. Key

— G

PL

1. ViZiTouch V2 operator interface2. Exterior USB Port

(Interior USB port also supplied)3. Emergency start

2

4

3

5

1

7

6

4. Key lock5. Remote alarm contacts with removable terminals6. Surge arrestor7. Transfer switch

Page 3: Limited Service Electric Fire Pump Controller...GPL 1. ViZiTouch V2 operator interface 2. Exterior USB Port (Interior USB port also supplied) 3. Emergency start 2 4 3 5 1 7 6 4. Key

— G

PL

ViZiTouch V2 Operator Interface

HOME SCREEN

Electric Fire Pump Controller

0

300

System

Home 26C13:34:102016.Dec.01

Pressure actuated Non automatic controller Automatic shutdown

L2

L3

L1480 V 480 V

480 V

23.4A

23.4A

23.4A

90

150

70PSI

0

300

System

Home 26C13:34:102016.Dec.01

Pressure actuated Non automatic controller Automatic shutdown

L2

L3

L1480 V 480 V

480 V

23.4A

23.4A

23.4A

90

150

70PSI

VIZITOUCH V2 MAJOR FEATURES INCLUDE:

• Touch screen operation with 7” color display and intuitive graphics

• Multi-language• Upgradable software• Password protected

ConfigHome 26C14:34:282016.Dec.01

Pressure

Periodic test

Advanced

PSI

PT1

Duration (min)

14:09:552016.Dec.01

Cut-in

Cut-out 150

100

Monday

Week. Test

Auto. Shutdown (m)

Date and time

RUN TEST

User login

Duration (min) 10

Duration (min) 10

30

5

7

Max. Pres. 300

2

EventsHistory 26°C14:34:282016.Dec.01

2016.12.01

2016.12.01 Under Voltage: ACTIVE

Under Voltage INACTIVE

2016.12.01 Alarms Reset

2016.12.01

2016.12.01

2016.12.01

2016.12.01

2016.12.01

2016.12.01

2016.12.01

14:28:23

14:28:52

14:28:09

14:09:55

14:11:22

14:03:11

14:08:46

14:03:03

14:12:06

14:28:08 ACB in OFF or Tripped: INACTIVE

Alternate is Tripped/Open: INACTIVE

Control Voltage not Healthy: ACTIVE

Generator: Started

Motor: Started in Automatic

Loss of Power: ACTIVE

Pump On Demand: INACTIVE

ServiceHome 26C14:33:062016.Dec.01

Last service date

Commissionning date

Service interval

Nameplate Information

Jockey pump cut-in

Live view

Jockey pump cut-out

Complete service

Next service due

2016.12.01 14:28:52

2016.12.01 14:28:52

1 year

130

2016.12.01 14:28:52

110

[email protected]

+ 65 6795 8114+ 65 6795 7823

ASIA

+ 32 (0) 1084 4001EUROPE

+ 1 800 363 8448+ 514 334 0523

AMERICAS

+ 971 (0)4 887 0615MIDDLE EAST

Pressure CurvesHistory 26°C14:37:172016.Dec.01

150

120

90

60

30

0

2016.02.2314:24:05

2016.02.2314:25:05

1m 5m 20m 1h 2h 3h 4h 5h 6h 12h 1d 2d 3d 4d 5d 6d 1w 2w

StatisticsFirst Service StatisticsStatistics 26C14:34:282016.Dec.01

First Service Statistics

From

2016.12.01Since

2016.12.01

14:28:09

20

0-00-08-57

14:08:46

99.1 PSI

61-04-08-27On Time

Motor

Start Count

Last Started On

Pressure

Minimum

On Time

SETTINGS

HISTORY/STATISTICS

EVENTS

SERVICE

PUMP CURVES PRESSURE CURVES

ON-SCREEN MENU

Home

Alarm

Configuration

History

Service

Manual

Languages

Pump CurvesHistory 26°C14:37:172016.Dec.01

P

90

68

45

23

01075538 1613 2150 Q 2016.02.23

14:25:05

PMS 295 PMS 361 Noir

®

Home 53C06:45:342016.Dec.01

Non pressure actuated Automatic controller Automatic shutdown

N2

N3

N1

A2

A3

A1

480 V 480 V

480 V

0 V0 V

0 V

480 V 480 V

480 V

23.4A

23.4A

23.4A

MANUAL

0

300

System

70PSI

90110

Electric Fire Pump Controllerwith Automatic Transfer Switch

Page 4: Limited Service Electric Fire Pump Controller...GPL 1. ViZiTouch V2 operator interface 2. Exterior USB Port (Interior USB port also supplied) 3. Emergency start 2 4 3 5 1 7 6 4. Key

GPL-SBRO-004-E Rev.0.1

AMERICAS

Tornatech Inc.

Head Office

Laval, Quebec, Canada

Tel: + 1 514 334 0523

Toll free: + 1 800 363 8448

MIDDLE EAST

Tornatech FZE

Dubai, United Arab Emirates

Tel: + 971 (0)4 887 0615

ASIA

Tornatech Pte Ltd.

Singapore

Tel: + 65 6795 8114

Tel: + 65 6795 7823

EUROPE

Tornatech Europe SPRL

Wavre, Belgium

Tel: + 32 (0) 10 84 40 01

Withstand Rating (short circuit current)

208V to 240V - 1ph - 50/60HZ

Normal Power Section Alternate Power Section

Standard 65, 000A

Optional n/a

SHORT CIRCUIT WITHSTAND RATING

THREE PHASE - SHORT CIRCUIT WITHSTAND RATING

HP / VOLTAGE / DIMENSIONS / WEIGHTS

Withstand Rating

(short circuit current)

208V to 240V - 1ph - 50/60HZ 380V to 480V - 3ph - 60HZ 600V - 3ph - 60HZ

Normal Power Section

Alternate Power Section

Normal Power Section

Alternate Power Section

Normal Power Section

Alternate Power Section

Standard 65, 000A 25, 000A 18, 000A

Optional n/a 65, 000A 25, 000A

208V to 240V - 1ph - 50/60HZ

380V to 600V - 3ph - 60HZ GPL GPL + GPU

HP Range (kW) Dimension in inches (mm)

Approx. Shipping Weight in Lbs (Kg)

Dimension in inches (mm)

Approx. Shipping Weight in Lbs (Kg)

5 - 15 (3.7 - 11) 5 - 30 (3.7 - 22)20”w x 24”h x 8”d(508 x 610 x 203)

100(48)

40”w x 24”h x 8”d(1016 x 610 x 203)

250(114)

HOW TO ORDER: GPL - V / HP / Ph / Hz / Options

Ex.: GPA - 208 / 30 / 3 / 60 / Options