Leakage Ratings Through Walls, Dampers, Doors,
Firestops and Joints
Richard N. Walke
Underwriters Laboratories Inc.
![Page 3: Leakage Ratings Through Walls, Dampers, Doors, Firestops and Joints Richard N. Walke Underwriters Laboratories Inc.](https://reader035.fdocuments.in/reader035/viewer/2022081519/56649ed35503460f94be3031/html5/thumbnails/3.jpg)
Topics for Discussion• Leakage Ratings for Walls,
Dampers, Doors, Firestops and Joint Systems
• Recent NFPA Code Proposals Relating to Smoke Leakage
![Page 4: Leakage Ratings Through Walls, Dampers, Doors, Firestops and Joints Richard N. Walke Underwriters Laboratories Inc.](https://reader035.fdocuments.in/reader035/viewer/2022081519/56649ed35503460f94be3031/html5/thumbnails/4.jpg)
Leakage Ratings
![Page 5: Leakage Ratings Through Walls, Dampers, Doors, Firestops and Joints Richard N. Walke Underwriters Laboratories Inc.](https://reader035.fdocuments.in/reader035/viewer/2022081519/56649ed35503460f94be3031/html5/thumbnails/5.jpg)
HVAC SmokeControl Methods
• Engineered Systems
• Static or Passive Systems
![Page 6: Leakage Ratings Through Walls, Dampers, Doors, Firestops and Joints Richard N. Walke Underwriters Laboratories Inc.](https://reader035.fdocuments.in/reader035/viewer/2022081519/56649ed35503460f94be3031/html5/thumbnails/6.jpg)
Walls – UL 263• Air Leakage Assumed to be Smoke
Tight• Standard does not Include
Leakage Ratings
![Page 7: Leakage Ratings Through Walls, Dampers, Doors, Firestops and Joints Richard N. Walke Underwriters Laboratories Inc.](https://reader035.fdocuments.in/reader035/viewer/2022081519/56649ed35503460f94be3031/html5/thumbnails/7.jpg)
Dampers – UL 555S• Air Leakage Through Interior of
Damper• Class I, II and III Performance
Levels at Elevated Temperatures• Codes focus on Class II
Performance at 250 F
![Page 8: Leakage Ratings Through Walls, Dampers, Doors, Firestops and Joints Richard N. Walke Underwriters Laboratories Inc.](https://reader035.fdocuments.in/reader035/viewer/2022081519/56649ed35503460f94be3031/html5/thumbnails/8.jpg)
Doors – UL 1784• Leakage Determined at 0.1, 0.2
and 0.3 in. WC (25, 50 and 75 Pa)• Tested at Ambient and 400 F• Results Published in cfm per sq ft
of Door Opening
![Page 9: Leakage Ratings Through Walls, Dampers, Doors, Firestops and Joints Richard N. Walke Underwriters Laboratories Inc.](https://reader035.fdocuments.in/reader035/viewer/2022081519/56649ed35503460f94be3031/html5/thumbnails/9.jpg)
Firestops – UL 1479• Leakage Determined at 0.3 in. WC
(75 Pa)• Tested at Ambient and 400 F• Results Published in cfm per sq ft
of Opening
![Page 10: Leakage Ratings Through Walls, Dampers, Doors, Firestops and Joints Richard N. Walke Underwriters Laboratories Inc.](https://reader035.fdocuments.in/reader035/viewer/2022081519/56649ed35503460f94be3031/html5/thumbnails/10.jpg)
Joints – UL 2079• Leakage Determined at 0.3 in. WC
(75 Pa)• Tested at Ambient and 400 F• Results Published in cfm per lin ft
of Opening
![Page 11: Leakage Ratings Through Walls, Dampers, Doors, Firestops and Joints Richard N. Walke Underwriters Laboratories Inc.](https://reader035.fdocuments.in/reader035/viewer/2022081519/56649ed35503460f94be3031/html5/thumbnails/11.jpg)
NFPA Code Changes
![Page 12: Leakage Ratings Through Walls, Dampers, Doors, Firestops and Joints Richard N. Walke Underwriters Laboratories Inc.](https://reader035.fdocuments.in/reader035/viewer/2022081519/56649ed35503460f94be3031/html5/thumbnails/12.jpg)
Proposed Leakage Ratings
• Requirements Covers Smoke Barriers Only
• Cumulative Leakage Limited to 0.75 cfm per sq ft of Wall for all Dampers, Doors, Through-Penetration Firestops and Joints
![Page 13: Leakage Ratings Through Walls, Dampers, Doors, Firestops and Joints Richard N. Walke Underwriters Laboratories Inc.](https://reader035.fdocuments.in/reader035/viewer/2022081519/56649ed35503460f94be3031/html5/thumbnails/13.jpg)