© Nelon Firestop Products
© Nelon Firestop Products
Through Penetration FirestopsThrough Penetration FirestopsTopics for discussion
• What is a firestop?
• How is a firestop installed?
• How is a firestop tested?
• What is a firestop system?
© Nelon Firestop Products
What is a firestop?What is a firestop?
© Nelon Firestop Products
Firestopping is:Firestopping is:The process of restoring the hourly rating back to fire barrier walls and floors (that have lost their fire rating from penetrations, joints and other openings) using materials tested to ASTM E-814, UL1479.
ASTM - American Society for Testing and MaterialsASTM - American Society for Testing and Materials
© Nelon Firestop Products
Firestopping is:Firestopping is:
Passive Compartmentation
Prevention:
Suppression:
Containment:
The fire is not permitted to start.
The fire is extinguished after it is started. This is known asActive Suppression.
Sometimes referred to as Passive Compartmentation. The fire is prevented from progressing to another area. This is also known as“PASSIVE” fire protection.
© Nelon Firestop Products
ASTM E 119 UL 263NFPA 251
Through-PenetrationFirestops:
UL 1479ASTM E 814-83
Joint SystemsUL2079ASTM E 1966
Fire Inside
© Nelon Firestop Products
How is a firestop How is a firestop tested?tested?
© Nelon Firestop Products
ASTM E814 (UL 1479): Fire Test for Through-Penetration Firestops
• Main Criteria for Through-Penetration Firestop Systems:
– T-Rating: Max. temp. rise of 325 °F above ambient on the non-fireside
– F-Rating: Prohibits flame passage through the system for the duration of the fire test.
– L-Rating: Amount of air leakage
– Hose Stream Performance Required (UL Canada Optional)
© Nelon Firestop Products
ASTM E 119 TIME - TEMPERATURE CURVE
© Nelon Firestop Products
The through The through penetrants are penetrants are installed in the installed in the floor or wall floor or wall using various using various firestopping firestopping materials. It is materials. It is exposed to the exposed to the ASTM-E-814 ASTM-E-814 fire temperaturesfire temperatures..
© Nelon Firestop Products
When the burn is When the burn is complete, the test complete, the test assembly is lifted assembly is lifted from the furnace from the furnace and immediately and immediately prepared for the prepared for the hosestream test.hosestream test.
© Nelon Firestop Products
A hose stream test, performed in accordance with UL1479, is conducted after the fire exposure test.
© Nelon Firestop Products
Visual examination of penetrations after hose stream test. No water projection is allowed on unexposed surfaces.
© Nelon Firestop Products
Multiple metallic pipes penetrating a concrete floor. ES1399 shown. Concrete floor test also provides wall application.
© Nelon Firestop Products
Six inch diameter copper pipe penetrating a concrete floor. This test also provides up to 24” diameter steel pipe.
© Nelon Firestop Products
Typical concrete floor fire test. Shown testing copper pipe and steel pipes for 2 hour F rating.
© Nelon Firestop Products
Composite Sheet used to firestop rectangular opening in concrete wall.
© Nelon Firestop Products
Cable bundle with sleeve penetrating gypsum wall.
© Nelon Firestop Products
2-Hour, Gypsum wall test using
PVC pipes. Wrap strip and Pipe Choke used on
penetration.
© Nelon Firestop Products
What is a Firestop What is a Firestop System?System?
© Nelon Firestop Products
A firestop system is a specific construction consisting of a wall or floor assembly, a penetrating item passing through an opening in the wall or floor assembly, and the materials designed to prevent the spread of fire through the openings.
© Nelon Firestop Products
Time is the key in Fire Protection Systems. In construction of buildings, fire-rated walls
and floors of various materials have requirements of being penetrated by many
different items such as pipes, cables and HVAC ducts. These constructions require the correct through penetration (Firestop )
system to provide the fire protection needed.
© Nelon Firestop Products
The following slides depict a building and the areas within that building that might require firestopping. Joints are shown as well as through stop application even though this presentation is geared toward only through stop applications.
© Nelon Firestop Products
© Nelon Firestop Products
© Nelon Firestop Products
HEAD OF WALL J OINT
© Nelon Firestop Products
© Nelon Firestop Products
ELECTRICAL BOX INSERT
© Nelon Firestop Products
© Nelon Firestop Products
CONCRETE OR CMU WALL
© Nelon Firestop Products
CONCRETE OR CMU WALL
© Nelon Firestop Products
© Nelon Firestop Products
Firestop systems are not merely the tube of caulk bearing the UL classification symbol.
The firestop system consists of a TESTED and APPROVED method of installation which includes size of opening, maximum penetrating item number and size, depths of forming material and or sealants or firestop devices required.
© Nelon Firestop Products
Typical applications require firestop caulk, putty etc. to be Typical applications require firestop caulk, putty etc. to be installed on one side in floors and from both sides of wall installed on one side in floors and from both sides of wall applications.applications.
CONCRETE FLOORMULTIPLE METALLIC PIPE METALLIC PIPE
CMU BLOCK WALL
© Nelon Firestop Products
Approved and tested Approved and tested systems for various systems for various firestop systems are firestop systems are contained within the UL contained within the UL Fires Resistance Directory.Fires Resistance Directory.
© Nelon Firestop Products
C-AJ-1415
Example : UL System - Through Penetration
© Nelon Firestop Products
Identifying System Variables: THROUGH PENETRATION FIRESTOP SYSTEMS (XHEZ)
First Alpha Character – signifies what is being penetrated
F = Floors
W = Walls
C = Walls and Floors
© Nelon Firestop Products
Example : UL System - Through Penetration
C-AJ-1415
Floor, Wall or Combination
© Nelon Firestop Products
Identifying System Variables
THROUGH PENETRATION FIRESTOP SYSTEMS (XHEZ) Following Alpha Character(s) – wall or floor construction type A = Concrete floors 5 inch thickB = Concrete floors 5 inch thickC = Framed floorsD = Steel decks in marine vesselsE-I = Reserved for future useJ = Concrete or masonry walls 8 inch thickK = Concrete or masonry walls 8 inch thickL = Framed wallsM = Bulkheads in marine vesselsN-Z = Reserved for future use
© Nelon Firestop Products
Construction Type of Floor or Wall
C-AJ-1415
Example : UL System - Through Penetration
© Nelon Firestop Products
Identifying System Variables
THROUGH PENETRATION FIRESTOP SYSTEMS (XHEZ) Numeric Component – first digit identifies the type of penetrant, next three
are sequential system numbering 0000-0999 = No Penetrant1000-1999 = Metallic pipe, conduit or tubing2000-2999 = Plastic pipe, conduit or tubing3000-3999 = Electrical cables4000-4999 = Cable trays with electrical cables5000-5999 = Insulated pipes6000-6999 = Bus ducts 7000-7999 = HVAC ducts 8000-8999 = Mixed multiple penetrations9000-9999 = Reserved for future use
© Nelon Firestop Products
Example : UL System - Through Penetration
C-AJ-1415
Penetrant Type
© Nelon Firestop Products
C-AJ-1415
Example : UL System - Through Penetration
Individual System Number
© Nelon Firestop Products
How is a Firestop How is a Firestop Installed?Installed?
© Nelon Firestop Products
Firestop products are offered in several forms:•SealantsSealants - Typically installed using a caulk gun - Typically installed using a caulk gun
•MortarsMortars - Mixed and troweled - Mixed and troweled
•Putty Putty - Installed by hand - Installed by hand
•CoatingsCoatings - Sprayed or brushed - Sprayed or brushed
•Wrap Strip - Installed by handWrap Strip - Installed by hand
•DevicesDevices - Installed by hand - Installed by hand
© Nelon Firestop ProductsLBS+
Install Nelson Pipe Choke around the pipe on the underside of the floor or to each side of the wall. Tighten around pipe and bend tabs to lock in place.
Secure the Pipe Choke to the floor or wall using appropriate anchor into each of the anchoring tabs.
For wall assemblies, Install Nelson Pipe Choke on both sides of the wall.
Install or pack the appropriate backing material around pipe allowing for caulk fill depth.
Trowel surface smooth with wall. (Point of contact systems require a bead.)
Gun, pump or trowel Nelson firestopping sealant to required depth. (Both sides if wall)
In an empty mixing container, add the appropriate amount of water.
Trowel surface smooth with wall. Add dry Mortar and mix material by hand or power tool.
PLASTIC P IPE PENETRATION WITH PIPE CHOK E
PLASTIC P IPE PENETRATION WITH SEALANT ONLY
NELSON CMP - MORTAR
INSTALLATION PROCEDURES
© Nelon Firestop Products
LBS+
Install Nelson Pipe Choke around the pipe on the underside of the floor or to each side of the wall. Tighten around pipe and bend tabs to lock in place.
Secure the Pipe Choke to the floor or wall using appropriate anchor into each of the anchoring tabs.
For wall assemblies, Install Nelson Pipe Choke on both sides of the wall.
Install or pack the appropriate backing material around pipe allowing for caulk fill depth.
Trowel surface smooth with wall. (Point of contact systems require a bead.)
Gun, pump or trowel Nelson firestopping sealant to required depth. (Both sides if wall)
In an empty mixing container, add the appropriate amount of water.
Trowel surface smooth with wall. Add dry Mortar and mix material by hand or power tool.
PLASTIC P IPE PENETRATION WITH PIPE CHOK E
PLASTIC P IPE PENETRATION WITH SEALANT ONLY
NELSON CMP - MORTAR
INSTALLATION PROCEDURES
© Nelon Firestop Products
LBS+
Install Nelson Pipe Choke around the pipe on the underside of the floor or to each side of the wall. Tighten around pipe and bend tabs to lock in place.
Secure the Pipe Choke to the floor or wall using appropriate anchor into each of the anchoring tabs.
For wall assemblies, Install Nelson Pipe Choke on both sides of the wall.
Install or pack the appropriate backing material around pipe allowing for caulk fill depth.
Trowel surface smooth with wall. (Point of contact systems require a bead.)
Gun, pump or trowel Nelson firestopping sealant to required depth. (Both sides if wall)
In an empty mixing container, add the appropriate amount of water.
Trowel surface smooth with wall. Add dry Mortar and mix material by hand or power tool.
PLASTIC P IPE PENETRATION WITH PIPE CHOK E
PLASTIC P IPE PENETRATION WITH SEALANT ONLY
NELSON CMP - MORTAR
INSTALLATION PROCEDURES
© Nelon Firestop Products
Trowel surface smooth with wall. (Point of contact systems require a bead.)
Gun, pump or trowel Nelson firestopping sealant to required depth. (Both sides if wall)
Install or pack the appropriate backing material around pipe allowing for caulk fill depth.
Tightly bundle cables using cable ties. Install or pack the appropriate backing material around cables allowing for caulk fill depth.
Trowel surface smooth with wall. (Point of contact systems require a bead.)
Gun, pump or trowel Nelson firestopping sealant to required depth. (Both sides if wall)
If required, form and install sleeve. Install or pack the appropriate backing material around pipe allowing for caulk fill depth.
Trowel surface smooth with wall. (Point of contact systems require a bead.)
Gun, pump or trowel Nelson firestopping sealant to required depth. (Both sides if wall)
GY PSUM WALL PENETRATION - STEEL, COPPER OR EMT PIPE
CONCRETE OR CMU WALL PENETRATION - STEEL, COPPER, EMT PIPE
CONCRETE OR CMU WALL PENETRATION - CABLE BUNDLES
INSTALLATION PROCEDURES
© Nelon Firestop Products
Trowel surface smooth with wall. (Point of contact systems require a bead.)
Gun, pump or trowel Nelson firestopping sealant to required depth. (Both sides if wall)
Install or pack the appropriate backing material around pipe allowing for caulk fill depth.
Tightly bundle cables using cable ties. Install or pack the appropriate backing material around cables allowing for caulk fill depth.
Trowel surface smooth with wall. (Point of contact systems require a bead.)
Gun, pump or trowel Nelson firestopping sealant to required depth. (Both sides if wall)
If required, form and install sleeve. Install or pack the appropriate backing material around pipe allowing for caulk fill depth.
Trowel surface smooth with wall. (Point of contact systems require a bead.)
Gun, pump or trowel Nelson firestopping sealant to required depth. (Both sides if wall)
GY PSUM WALL PENETRATION - STEEL, COPPER OR EMT PIPE
CONCRETE OR CMU WALL PENETRATION - STEEL, COPPER, EMT PIPE
CONCRETE OR CMU WALL PENETRATION - CABLE BUNDLES
INSTALLATION PROCEDURES
© Nelon Firestop Products
LBS+
LBS+
LBS+
Trowel surface smooth with wall. (Point of contact systems require a bead.)
Gun, pump or trowel Nelson firestopping sealant to required depth. (Both sides if wall)
Install or pack the appropriate backing material around pipe allowing for caulk fill depth.
Tightly bundle cables using cable ties. Install or pack the appropriate backing material around cables allowing for caulk fill depth.
Trowel surface smooth with wall. (Point of contact systems require a bead.)
Gun, pump or trowel Nelson firestopping sealant to required depth. (Both sides if wall)
If required, form and install sleeve. Install or pack the appropriate backing material around pipe allowing for caulk fill depth.
Trowel surface smooth with wall. (Point of contact systems require a bead.)
Gun, pump or trowel Nelson firestopping sealant to required depth. (Both sides if wall)
GY PSUM WALL PENETRATION - STEEL, COPPER OR EMT PIPE
CONCRETE OR CMU WALL PENETRATION - STEEL, COPPER, EMT PIPE
CONCRETE OR CMU WALL PENETRATION - CABLE BUNDLES
INSTALLATION PROCEDURES
© Nelon Firestop Products
Installation of multiple metallic pipes in single opening of gypsum wall using a sealant and caulk gun.
© Nelon Firestop Products