7/21/2019 J Bolt Precast Anchor Design Example http://slidepdf.com/reader/full/j-bolt-precast-anchor-design-example 1/4  ANCHOR BOLT CALCULATION EXEMPLE PER ACI318 Design a group of four headed bolts spaced as shown to support a 25,000 lb factored tension load and 7500 lb reversible factored shear load resulting from wind load. The connection is located at the base of a column in a corner of the building foundation. F’c = 4000 psi (normalweight concrete) Note: OSHA Standard 29 CFR Part 1926.755 requires that the col umn anchorage use a least four anchors and be able to sustai n a minimum eccentric gravity load of 300 lb located 18 in. from the face of the extreme outer face of the column in each direction. The load is to be applied at the top of the column. The intent is that the column be able to sustain an iron worker hanging off the side of the top of the column The solution to this example is found by assuming the size of the anchors, then checking compliance with the design provisions. Try four 3/4 in. ASTM F1554 Grade 55 headed bolts with hef = 11 in. as shown in figure. 1. This is a tension/shear interaction problem where values for both the design tensile strength and design shear strength will need to be determined. Design tensile strength is the smallest of the tensile strengths as controlled by steel, concrete breakout, pullout, and side-face blowout. Shear design strength is the smallest of the shear strengths as controlled by steel, concrete breakout, and pryout. 2. Determine the design tensile strength : Steel strength : Per Table 34-1 from ACI318, the ASTM F1554 Grade 55 headed bolt meets the Ductile Steel Element definition of D.1. 3. CULATION EXEMPLE http://www.peikko.ca/Default.aspx?id 11/3/2010

description

J-bolt Precast Design

Transcript of J Bolt Precast Anchor Design Example

Page 1: J Bolt Precast Anchor Design Example

7/21/2019 J Bolt Precast Anchor Design Example

http://slidepdf.com/reader/full/j-bolt-precast-anchor-design-example 1/4

 ANCHOR BOLT CALCULATION EXEMPLE PER ACI318

Design a group of four headed bolts spaced as shown to support a 25,000 lb factored tension load and 7500 lb reversible factored

shear load resulting from wind load. The connection is located at the base of a column in a corner of the building foundation.

F’c = 4000 psi (normalweight concrete)

Note: OSHA Standard 29 CFR Part 1926.755 requires that the column anchorage use a least four anchors and be able to sustain a

minimum eccentric gravity load of 300 lb located 18 in. from the face of the extreme outer face of the column in each direction. The

load is to be applied at the top of the column. The intent is that the column be able to sustain an iron worker hanging off the side of 

the top of the column

The solution to this example is found by assuming the size of the anchors, then checking compliance with the design

provisions. Try four 3/4 in. ASTM F1554 Grade 55 headed bolts with hef = 11 in. as shown in figure.

1.

This is a tension/shear interaction problem where values for both the design tensile strength and design shear strength will

need to be determined. Design tensile strength is the smallest of the tensile strengths as controlled by steel, concrete

breakout, pullout, and side-face blowout. Shear design strength is the smallest of the shear strengths as controlled by steel,

concrete breakout, and pryout.

2.

Determine the design tensile strength :

Steel strength :

Per Table 34-1 from ACI318, the ASTM F1554 Grade 55 headed bolt meets the Ductile Steel Element

definition of D.1.

3.

CULATION EXEMPLE http://www.peikko.ca/Default.aspx?id

11/3/2010

Page 2: J Bolt Precast Anchor Design Example

7/21/2019 J Bolt Precast Anchor Design Example

http://slidepdf.com/reader/full/j-bolt-precast-anchor-design-example 2/4

 

CULATION EXEMPLE http://www.peikko.ca/Default.aspx?id

11/3/2010

Page 3: J Bolt Precast Anchor Design Example

7/21/2019 J Bolt Precast Anchor Design Example

http://slidepdf.com/reader/full/j-bolt-precast-anchor-design-example 3/4

Page 4: J Bolt Precast Anchor Design Example

7/21/2019 J Bolt Precast Anchor Design Example

http://slidepdf.com/reader/full/j-bolt-precast-anchor-design-example 4/4

 

We will continue the study by determining shear design strength of the anchors and we will conclude by checking the interaction of 

shear and tension. These next steps will be updated soon.

 