HVDC grid connection of offshore wind...
-
Upload
nguyentuyen -
Category
Documents
-
view
230 -
download
5
Transcript of HVDC grid connection of offshore wind...
23-12-2009
Challenge the future
DelftUniversity ofTechnology
HVDC grid connection of offshore wind power
Ir. Arjen A. van der Meer, Electrical Sustainable Energy
2/21HVDC grid connection of offshore wind power
Contents
•Present offshore wind parks
•Grid connection
•VSC-HVDC
•Future trends
•Conclusions
3/21HVDC grid connection of offshore wind power
1st generation offshore wind parks
•Typical rating 100 – 200 MW
•Distance from the cost < 25 km
•Operation like a conventional power plant
4/21HVDC grid connection of offshore wind power
Offshore wind parks in NL
•OWEZ:
• 36 X 3 MW
• Wind park directly connected to the mainland (33 kV)
• ±12 km from the shore
•Prinses Amaliawindpark:
• 60 X 2MW
• MV/HV transformer located offshore
• Grid connection through 150 kV cable
• ±25 km from the shore
5/21HVDC grid connection of offshore wind power
Typical AC grid connection
MV strings
wind turbinesconnected at MV
onshoreMV/HV substation
offshore MV/HVsubstation (platform)
HV exportcable circuit
6/21HVDC grid connection of offshore wind power
2nd & 3rd generation wind parks
• Will have larger power rating (>500 MW)
• Will be located further from the shore (>>25 km)
• Will be clustered together
• Will show behavior like a large power plant
• In some countries, the TSOs are responsible for grid connection
7/21HVDC grid connection of offshore wind power
Limitations of AC transmission
0
250
500
750
1000
0 50 100 150 200 250 300
Cable length (km)
Cur
rent
(A)
reactive current max. active current current limit
cable is a ‘distributed capacitor’
at AC voltage, a charging current must be provided to keep voltage
thermal limit determines maximum current
maximum possible active current reduces with cable length
8/21HVDC grid connection of offshore wind power
DC transmission
• Solves most problems
• Only resistive losses, unlimited connection distance
• No reactive current compensation needed, more power per cable
• But, at the cost of
• Higher losses
• Higher investment costs
• More maintenance
9/21HVDC grid connection of offshore wind power
VSC-HVDC versus LCC-HVDC
• LCC-HVDC
• Operated through thyristors
• Dedicated for bulk power transfer
• Needs a strong grid to communitate against
• VSC-HVDC
• Operated through IGBTs
• Offers black-start capability
• Good controllability
• Feasible for systems ≤800 MW
• Smaller footprint
10/21HVDC grid connection of offshore wind power
Consequences of VSC-HVDC
• Modern wind parks are required to behave as a conventional
power plant
• VSC-HVDC creates an electrical barrier between 2 grids
• Control system now determines grid interaction
• Disadvantage: fault ride-trough behaviour
• Grid support during disturbances
11/21HVDC grid connection of offshore wind power
Low voltage ride-through
• Onshore converter has maximum current rating;
• Direct voltage quickly rises due to the power imbalance;
• Only few milliseconds are available for active power reduction;
12/21HVDC grid connection of offshore wind power
fast power reduction
• Increase of offshore frequency;
• Reduction of offshore network voltage;
• power reduction signal to wind turbines;
• Dissipation of excess energy in dynamic braking resistor
f Vac
Pref
13/21HVDC grid connection of offshore wind power
Low voltage ride-through: results
• Power reduction methods:
• Reliability is an issue
• Additional control systems needed in wind turbines
• Braking resistor: robust but expensive
14/21HVDC grid connection of offshore wind power
Grid support during disturbances
U
t0 t1 t2
U0
Umin
Un
15/21HVDC grid connection of offshore wind power
Grid support during disturbances
• Reactive current injection to support voltage restoration
• Minimize geographical impact of the fault
• Wind turbines/ VSCs are able to inject reactive power any time
• Different grid codes require different behaviour
• Common variants:
• No reactive power support
• Reactive power boosting
• Continuous voltage control
16/21HVDC grid connection of offshore wind power
Grid support: results
• Reactive current injection by VSC-HVDC improves dynamic performance
• Some support methods are more efficient than others
• Voltage support is ineffective for wind parks connected through long
AC-cables, VSC-HVDC can overcome this problem
17/21HVDC grid connection of offshore wind power
What does the future hold?
18/21HVDC grid connection of offshore wind power
Multi-terminal VSC-HVDC
• Increased need for cross-border interconnection capacity
• Utilization factor increases
• Reliability improves
• Synergies with other offshore applications
• Economic feasibility is an important prerequisite
19/21HVDC grid connection of offshore wind power
Multi-terminal DC: challenges
• Wind power dispatch amongst connection points
• Implementation into market environment
(how to earn money with the additional applications)
• Availability of DC circuit-breakers
20/21HVDC grid connection of offshore wind power
Kriegers flak
• 650 MW
• Planned between Germany,
Denmark, and Sweden
21/21HVDC grid connection of offshore wind power
Conclusions
• Next generation Wind Power Plants requires re-thinking of
connection technologies
• VSC-HVDC offers major advantages above other technologies
• VSC interface needs to fulfill grid-code compliance