HVAC Flow metering
Transcript of HVAC Flow metering
-
8/7/2019 HVAC Flow metering
1/4
>10"
LAMP
W/HOO
14"
12"14"CT
-
8/7/2019 HVAC Flow metering
2/4
Flow and Energy Measurement for Central Energy Plants
Improved Chiller Plant Control
Real-time Commissioning and Balancing Data
Continuous Monitoring of Chiller Performance (KW/ton)
Accurate flow and energy measurement provides:
Cooling Towers
BTU 12
CH4-CHWR
BTU 10
CH3-CHWR
BTU 8
CH2-CHWR
BTU 6
CH1-CHWR
CH-1
FM 13
CH4-CW
FM 11
CH3-CW
FM 9
CH2-CW
FM 7
CH1-CW
FM 14
CW MAIN
FM 3
CHW BYPASS
BYPASS
BTU 1SCHWS
BTU 2PCHWS
CH-2
CH-3
CH-4
PRIMARY LOOP
SECONDARY LOOP
BTU 4
BTU 5
SCHWS-NORTH
SCHWS-SOUTH
NORTH LOOP
SOUTH LOOP
RETURN
SUPPLY
Meter ScheduleMETER
#TAG DESCRIPTION
FLOWMETER
DISPLAY orBTU METER
BTU 1 SCHWS Secondary Chilled Water Supply F-1200BTU 2 PCHWS Primary Chilled Water Supply F-1200
FM 3 CHW BYPASS Chilled Water Bypass (decoupler) FB-1210 DB-1201
BTU 4 SCHWS-NORTH Sec. Chilled Water Supply - North Loop F-1200
BTU 5 SCHWS-SOUTH Sec. Chilled Water Supply - South Loop F-1200
BTU 6 CH1-CHWR Chiller 1 - Chilled Water Return F-1200
FM 7 CH1-CW Chiller 1 - Condenser Water F-1210
BTU 8 CH2-CHWR Chiller 2 - Chilled Water Return F-1200
FM 9 CH2-CW Chiller 2 - Condenser Water F-1210
BTU 10 CH3-CHWR Chiller 3 - Chilled Water Return F-1200
FM 11 CH3-CW Chiller 3 - Condenser Water F-1210
BTU 12 CH4-CHWR Chiller 4 - Chilled Water Return F-1200
FM 13 CH4-CW Chiller 4 - Condenser Water F-1210
Condenser Water Main F-1210 D-1201
D-1201
D-1201
D-1201
D-1201
To ensure the highest return on investment, a comprehensive metering program is essential formanaging today's complex central energy plants.
Traditionally, energy calculations
(if done at all) are performed within thebuilding automation system based on
analog inputs from a flow transmitterand two temperature sensors.
ONICON's Dual Turbine Flow Meter
has become the recognized standardfor accurate, reliable flow measurementat a reasonable cost. However, the
effect of using typical HVAC gradetemperature sensors with analog
control inputs for energy calculationsis widely misunderstood, resultingin relatively high error for the
energy calculation.
ONICON's System-10 BTU Meterutilizes a calibrated system approach
to provide highly accurate flow,
temperature and energy data.Furthermore, with a serial network
communication option, this system canactually be less expensive than
traditional energy calculation methods.
Contact an ONICON Representativetoday to learn more about this excitingimprovement in energy measurement.
System-10System-10
System-10
System-10
System-10
System-10
System-10
System-10
A Note on Energy Measuremenin Central Plant Environments
POINTS LIST
gpm, tons, ton-hrs, Tsupply, Treturn
gpm
gpm, flow direction
gpm
gpm
gpm
gpm
gpm, tons, ton-hrs, Tsupply, Treturn
gpm, tons, ton-hrs, Tsupply, Treturn
gpm, tons, ton-hrs, Tsupply, Treturn
gpm, tons, ton-hrs, Tsupply, Treturn
gpm, tons, ton-hrs, Tsupply, Treturn
gpm, tons, ton-hrs, Tsupply, Treturn
gpm, tons, ton-hrs, Tsupply, Treturn
CW MAINFM 140352B-1 2-1
-
8/7/2019 HVAC Flow metering
3/4
FLOW
RETURN
SUPPLY
POWER
SYSTEM-10BTU METER
Individual Chilleror Boiler
Supply
Sensor
ReturnSensor
INCORPORATED
BTU X 10,000
AVAILABLE OUTPUT SIGNALSTO CONTROL SYSTEM
Serial Network Options
BACnet
JCI-N2LON
Siemens-P1
Pulse/Analog Signal Options
Energy Total (BTU) Dry Contact
Energy Rate (Tons) 4-20 mA
Flow Rate (GPM) 4-20 mA
Supply Temp (F) 4-20 mA
Return Temp (F) 4-20 mA
Delta-T (F) 4-20 mA
BTU Meters with Pulse/Analog OutputsFor applications where the existing network protocol is not
compatible with the System-10, traditional analog and pulse
type outputs can be used. In this case, a single pulse output
for energy total, and up to four analog outputs (for flow rate,
energy rate and temperatures) can be provided. Each output
for each meter must be wired to a building control system field
panel input point (AI or BI) using a twisted pair.
Networked Energy MetersBTU Meters configured with serial network communications
offer simplified wiring and greatly reduced installation cost
compared to traditional analog/pulse type outputs. The data
provided (with a single 2-3 wire LAN connection) includes:
energy total, energy rate, flow total, flow rate, supply
temperature, return temperature, delta temperature.
A Calibrated System for Energy Measurement
Highly Accurate, Surprisingly Affordable
24 or 120 VACInput Power
Provides all dataon 2-3 wires}
Typical Flow Meter Installation with Analog Output to Control System
(BTU calculation performed by control system)
Detail of hot tap adapterwith turbine assemblywithdrawn
FLOW
SystemMains
AVAILABLE OUTPUTSIGNALS TO
CONTROL SYSTEM
Flow Rate (GPM)
4-20 mA
INCORPORATED
Local Display of Flow, Temperatureand Energy Data
0352C-1 2-1
-
8/7/2019 HVAC Flow metering
4/4
1500 North Belcher Road, Clearwater, Florida 33765 Tel (727) 447-6140 Fax (727) 442-5699www.onicon.com E-mail: [email protected]
0352D-1 2-1
Energy Measurement and Flow Measurement SpecificationsFor Central Energy Plant Applications (CHW, HW, CW)
Energy Measurement System SpecificationThe entire Energy Measurement System shall be built and calibrated by a single manufacturer, ONICON Incorporated,
and shall consist of a flow meter, two temperature sensors, a BTU meter, temperature thermowells, and all required
mechanical installation hardware. A certificate of NIST* traceable calibration shall be provided with each system.
BTU Meter: Provide an ONICON System-10 BTU Meter. The BTU meter shall provide the following points both at
the integral LCD and as outputs to the building control system: Energy Total, Energy Rate, Flow Rate, Supply
Temperature and Return Temperature. Output signals shall be either serial network (protocol conforming to
BACnet, LON, JCI-N2 or Siemens-P1) or via individual analog outputs. An isolated dry contact output shall be
provided for energy total. Each BTU meter shall be factory programmed for its specific application, and shall be
re-programmable using the front panel keypad (no special interface device or computer required).
Temperature sensors: Temperature sensors shall be loop-powered current based (mA) sensors and shall be
bath-calibrated and matched (NIST* traceable) for the specific temperature range for each application. The calculated
differential temperature used in the energy calculation shall be accurate to within 0.15F (including the error from
individual temperature sensors, sensor matching, input offsets, and calculations).
Flow Meter: Provide an ONICON Model F-1200 Dual Turbine Flow Meter, complete with all installation hardware
necessary to enable insertion and removal of the meter without a system shutdown. The flow meter shall be
hand-insertable up to 400 psi. The flow meter shall have two contra-rotating axial turbines, with electronic
impedance-based sensing and an averaging circuit to reduce measurement errors due to swirl and flow profile
distortion. Each flow meter shall be individually wet-calibrated against a primary volumetric standard that is accurate
to within 0.1% and traceable to NIST*. The manufacturer's certificate of calibration shall be provided with each flow
meter. Accuracy shall be within 0.5% of rate at the calibrated velocity, within 1% of rate over a 10:1 turndown
(3.0 to 30 ft/s) and within 2% of rate over a 50:1 turndown (from 0.4 to 20 ft/s). Output signal shall be a 0-15 V square
wave pulse. Bi-directional meters shall be FB-1200 Series and shall include an isolated contact closure output for direc
Flow Measurement Station Specification
Flow Meter: Provide an ONICON Model F-1210 Dual Turbine Flow Meter complete with all installation hardware
necessary to enable insertion and removal of the meter without a system shutdown. The flow meter shall be
hand-insertable up to 400 psi. The flow meter shall have two contra-rotating axial turbines, with electronic
impedance-based sensing and an averaging circuit to reduce measurement errors due to swirl and flow profile
distortion. Each flow meter shall be individually wet-calibrated against a primary volumetric standard that is accurate
to within 0.1% and traceable to NIST*. The manufacturer's certificate of calibration shall be provided with each flow
meter. Accuracy shall be within 0.5% of rate at the calibrated velocity, within 1% of rate over a 10:1 turndown
(3.0 to 30 ft/s) and within 2% of rate over a 50:1 turndown (from 0.4 to 20 ft/s). The flow meter shall include integral
analog output(s), 4-20 mA, 0-10V, or 0-5V. Bi-directional meters shall be FB-1210 Series and shall include an isolated
contact closure output for direction.
Optional Flow Display: Provide a D-1200 Series Display Module for local indication of flow rate and/or total.
For bi-directional applications, provide a DB-1200 series Display Module.
*National Institute of Standards and Technology
INCORPORATED