HVAC Flow metering

download HVAC Flow metering

of 4

Transcript of HVAC Flow metering

  • 8/7/2019 HVAC Flow metering

    1/4

    >10"

    LAMP

    W/HOO

    14"

    12"14"CT

  • 8/7/2019 HVAC Flow metering

    2/4

    Flow and Energy Measurement for Central Energy Plants

    Improved Chiller Plant Control

    Real-time Commissioning and Balancing Data

    Continuous Monitoring of Chiller Performance (KW/ton)

    Accurate flow and energy measurement provides:

    Cooling Towers

    BTU 12

    CH4-CHWR

    BTU 10

    CH3-CHWR

    BTU 8

    CH2-CHWR

    BTU 6

    CH1-CHWR

    CH-1

    FM 13

    CH4-CW

    FM 11

    CH3-CW

    FM 9

    CH2-CW

    FM 7

    CH1-CW

    FM 14

    CW MAIN

    FM 3

    CHW BYPASS

    BYPASS

    BTU 1SCHWS

    BTU 2PCHWS

    CH-2

    CH-3

    CH-4

    PRIMARY LOOP

    SECONDARY LOOP

    BTU 4

    BTU 5

    SCHWS-NORTH

    SCHWS-SOUTH

    NORTH LOOP

    SOUTH LOOP

    RETURN

    SUPPLY

    Meter ScheduleMETER

    #TAG DESCRIPTION

    FLOWMETER

    DISPLAY orBTU METER

    BTU 1 SCHWS Secondary Chilled Water Supply F-1200BTU 2 PCHWS Primary Chilled Water Supply F-1200

    FM 3 CHW BYPASS Chilled Water Bypass (decoupler) FB-1210 DB-1201

    BTU 4 SCHWS-NORTH Sec. Chilled Water Supply - North Loop F-1200

    BTU 5 SCHWS-SOUTH Sec. Chilled Water Supply - South Loop F-1200

    BTU 6 CH1-CHWR Chiller 1 - Chilled Water Return F-1200

    FM 7 CH1-CW Chiller 1 - Condenser Water F-1210

    BTU 8 CH2-CHWR Chiller 2 - Chilled Water Return F-1200

    FM 9 CH2-CW Chiller 2 - Condenser Water F-1210

    BTU 10 CH3-CHWR Chiller 3 - Chilled Water Return F-1200

    FM 11 CH3-CW Chiller 3 - Condenser Water F-1210

    BTU 12 CH4-CHWR Chiller 4 - Chilled Water Return F-1200

    FM 13 CH4-CW Chiller 4 - Condenser Water F-1210

    Condenser Water Main F-1210 D-1201

    D-1201

    D-1201

    D-1201

    D-1201

    To ensure the highest return on investment, a comprehensive metering program is essential formanaging today's complex central energy plants.

    Traditionally, energy calculations

    (if done at all) are performed within thebuilding automation system based on

    analog inputs from a flow transmitterand two temperature sensors.

    ONICON's Dual Turbine Flow Meter

    has become the recognized standardfor accurate, reliable flow measurementat a reasonable cost. However, the

    effect of using typical HVAC gradetemperature sensors with analog

    control inputs for energy calculationsis widely misunderstood, resultingin relatively high error for the

    energy calculation.

    ONICON's System-10 BTU Meterutilizes a calibrated system approach

    to provide highly accurate flow,

    temperature and energy data.Furthermore, with a serial network

    communication option, this system canactually be less expensive than

    traditional energy calculation methods.

    Contact an ONICON Representativetoday to learn more about this excitingimprovement in energy measurement.

    System-10System-10

    System-10

    System-10

    System-10

    System-10

    System-10

    System-10

    A Note on Energy Measuremenin Central Plant Environments

    POINTS LIST

    gpm, tons, ton-hrs, Tsupply, Treturn

    gpm

    gpm, flow direction

    gpm

    gpm

    gpm

    gpm

    gpm, tons, ton-hrs, Tsupply, Treturn

    gpm, tons, ton-hrs, Tsupply, Treturn

    gpm, tons, ton-hrs, Tsupply, Treturn

    gpm, tons, ton-hrs, Tsupply, Treturn

    gpm, tons, ton-hrs, Tsupply, Treturn

    gpm, tons, ton-hrs, Tsupply, Treturn

    gpm, tons, ton-hrs, Tsupply, Treturn

    CW MAINFM 140352B-1 2-1

  • 8/7/2019 HVAC Flow metering

    3/4

    FLOW

    RETURN

    SUPPLY

    POWER

    SYSTEM-10BTU METER

    Individual Chilleror Boiler

    Supply

    Sensor

    ReturnSensor

    INCORPORATED

    BTU X 10,000

    AVAILABLE OUTPUT SIGNALSTO CONTROL SYSTEM

    Serial Network Options

    BACnet

    JCI-N2LON

    Siemens-P1

    Pulse/Analog Signal Options

    Energy Total (BTU) Dry Contact

    Energy Rate (Tons) 4-20 mA

    Flow Rate (GPM) 4-20 mA

    Supply Temp (F) 4-20 mA

    Return Temp (F) 4-20 mA

    Delta-T (F) 4-20 mA

    BTU Meters with Pulse/Analog OutputsFor applications where the existing network protocol is not

    compatible with the System-10, traditional analog and pulse

    type outputs can be used. In this case, a single pulse output

    for energy total, and up to four analog outputs (for flow rate,

    energy rate and temperatures) can be provided. Each output

    for each meter must be wired to a building control system field

    panel input point (AI or BI) using a twisted pair.

    Networked Energy MetersBTU Meters configured with serial network communications

    offer simplified wiring and greatly reduced installation cost

    compared to traditional analog/pulse type outputs. The data

    provided (with a single 2-3 wire LAN connection) includes:

    energy total, energy rate, flow total, flow rate, supply

    temperature, return temperature, delta temperature.

    A Calibrated System for Energy Measurement

    Highly Accurate, Surprisingly Affordable

    24 or 120 VACInput Power

    Provides all dataon 2-3 wires}

    Typical Flow Meter Installation with Analog Output to Control System

    (BTU calculation performed by control system)

    Detail of hot tap adapterwith turbine assemblywithdrawn

    FLOW

    SystemMains

    AVAILABLE OUTPUTSIGNALS TO

    CONTROL SYSTEM

    Flow Rate (GPM)

    4-20 mA

    INCORPORATED

    Local Display of Flow, Temperatureand Energy Data

    0352C-1 2-1

  • 8/7/2019 HVAC Flow metering

    4/4

    1500 North Belcher Road, Clearwater, Florida 33765 Tel (727) 447-6140 Fax (727) 442-5699www.onicon.com E-mail: [email protected]

    0352D-1 2-1

    Energy Measurement and Flow Measurement SpecificationsFor Central Energy Plant Applications (CHW, HW, CW)

    Energy Measurement System SpecificationThe entire Energy Measurement System shall be built and calibrated by a single manufacturer, ONICON Incorporated,

    and shall consist of a flow meter, two temperature sensors, a BTU meter, temperature thermowells, and all required

    mechanical installation hardware. A certificate of NIST* traceable calibration shall be provided with each system.

    BTU Meter: Provide an ONICON System-10 BTU Meter. The BTU meter shall provide the following points both at

    the integral LCD and as outputs to the building control system: Energy Total, Energy Rate, Flow Rate, Supply

    Temperature and Return Temperature. Output signals shall be either serial network (protocol conforming to

    BACnet, LON, JCI-N2 or Siemens-P1) or via individual analog outputs. An isolated dry contact output shall be

    provided for energy total. Each BTU meter shall be factory programmed for its specific application, and shall be

    re-programmable using the front panel keypad (no special interface device or computer required).

    Temperature sensors: Temperature sensors shall be loop-powered current based (mA) sensors and shall be

    bath-calibrated and matched (NIST* traceable) for the specific temperature range for each application. The calculated

    differential temperature used in the energy calculation shall be accurate to within 0.15F (including the error from

    individual temperature sensors, sensor matching, input offsets, and calculations).

    Flow Meter: Provide an ONICON Model F-1200 Dual Turbine Flow Meter, complete with all installation hardware

    necessary to enable insertion and removal of the meter without a system shutdown. The flow meter shall be

    hand-insertable up to 400 psi. The flow meter shall have two contra-rotating axial turbines, with electronic

    impedance-based sensing and an averaging circuit to reduce measurement errors due to swirl and flow profile

    distortion. Each flow meter shall be individually wet-calibrated against a primary volumetric standard that is accurate

    to within 0.1% and traceable to NIST*. The manufacturer's certificate of calibration shall be provided with each flow

    meter. Accuracy shall be within 0.5% of rate at the calibrated velocity, within 1% of rate over a 10:1 turndown

    (3.0 to 30 ft/s) and within 2% of rate over a 50:1 turndown (from 0.4 to 20 ft/s). Output signal shall be a 0-15 V square

    wave pulse. Bi-directional meters shall be FB-1200 Series and shall include an isolated contact closure output for direc

    Flow Measurement Station Specification

    Flow Meter: Provide an ONICON Model F-1210 Dual Turbine Flow Meter complete with all installation hardware

    necessary to enable insertion and removal of the meter without a system shutdown. The flow meter shall be

    hand-insertable up to 400 psi. The flow meter shall have two contra-rotating axial turbines, with electronic

    impedance-based sensing and an averaging circuit to reduce measurement errors due to swirl and flow profile

    distortion. Each flow meter shall be individually wet-calibrated against a primary volumetric standard that is accurate

    to within 0.1% and traceable to NIST*. The manufacturer's certificate of calibration shall be provided with each flow

    meter. Accuracy shall be within 0.5% of rate at the calibrated velocity, within 1% of rate over a 10:1 turndown

    (3.0 to 30 ft/s) and within 2% of rate over a 50:1 turndown (from 0.4 to 20 ft/s). The flow meter shall include integral

    analog output(s), 4-20 mA, 0-10V, or 0-5V. Bi-directional meters shall be FB-1210 Series and shall include an isolated

    contact closure output for direction.

    Optional Flow Display: Provide a D-1200 Series Display Module for local indication of flow rate and/or total.

    For bi-directional applications, provide a DB-1200 series Display Module.

    *National Institute of Standards and Technology

    INCORPORATED